Danfoss IP21/Type 1 Conversion Kit Installation Instructions Manual

The instructions provide information about installing the IP21/
Type 1 conversion kit in VLT
®
AutomationDrive FC 360,
enclosure sizes J6 and J7.
Only Danfoss authorized, qualied personnel is allowed to repair this equipment. The personnel must be familiar with the instructions and safety measures described in the
VLT
®
AutomationDrive FC 360 Service Guide.
Items Supplied
IP21 top cover
NEMA conduit box
NEMA base cover
Screws and washers, M4x7 (8 pieces)
Description Ordering number
IP21/Type 1 Conversion Kit, J6 132B0376
IP21/Type 1 Conversion Kit, J7 132B0377
Tab le 1. 1 Order ing N um bers
Tools Required
T20 screwdriver
Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are
o.
Fail ure to wai t the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The minimum waiting time is specied in Tab l e 1. 2.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Volt age [V ]
Power range [kW
(hp)]
Minimum waiting time
(minutes)
380–480 30–75 (45–100) 15
Tab le 1. 2 Disch arge Time
Installation Instructions
IP21/Type 1 Conversion Kit Enclosure Sizes J6 & J7
VLT
®
AutomationDrive FC 360
Danfoss A/S © 12/2015 All rights reser ved. MI06V102
Installation
1. Mount the top cover on the top of the frequency converter.
2. Fasten with 4 screws, 2 screws on each side.
3. Tighten the screws to 1.5 Nm (13.3 in-lb).
1Top cover
Illustration 1.1 Mounting the Top Cover
4. Mount the conduit box on the bottom of the frequency converter.
5. Fasten with 2 screws, 1 screw on each side.
6. Tighten the screws to 1.5 Nm (13.3 in-lb).
1Conduit box
Illustration 1.2 Mounting the Conduit Box
7. Mount the conduit cover on the bottom of the frequency converter.
8. Fasten with 2 screws, 1 screw on each side.
9. Tighten the screws to 1.5 Nm (13.3 in-lb).
1Conduit cover
Illustration 1.3 Mounting the Conduit Cover
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.