Danfoss Icon Programmable Data sheet

Data Sheet
Danfoss Icon™ Programmable
Room Thermostats, 230 V
Description
Danfoss Icon™ Programmable 088U1020 Danfoss Icon™ Programmable 088U1025
Ordering
Danfoss Icon™ is a range of flush and surface mounted room thermostats for hydronic floor heating applications.
Danfoss Icon™ Programmable is mains powered and can be used as a stand-alone thermostat or in combination with Wiring Center.
The thermostat uses a triac output and can control up to 5 thermal actuators.
The user can choose between 7 pre-defined heat­ing schedules. A schedule can be temporarily overrided by using the three mode keys.
The thermostat can also operature without sched­uling (constant room temperature setpoint).
The thermostat uses forecast (adaptive learning).
The thermostat uses a “touch on glass” interface with a shine through display. The display is “OFF” in normal operation.
Product Version Size For junction box Code no.
Features:
• Accurate PWM-control;
• Compatible with 3’rd party wall frames;
• Shine through display with mode keys;
• 7 pre-defined schedules and forecast;
• Range limitation via user menu;
• Neutral design and simple user interface;
• Frost protection setting;
• Can be used with 230V NC or NO actuators;
• Can be optimized for different heatsources via service menu;
• Valve exercise feature;
• Can be used in systems with cooling;
• Has input for global setback;
• Can be used with floor sensor (optional);
• Very high UV-resistance.
© Danfoss | FEC | 2021.06
Danfoss Icon™ Programmable In-wall 80 × 80 mm Euro, Ø 68 mm 088U1020
Danfoss Icon™ Programmable In-wall 86 × 86 mm Square, 70 × 70 mm 088U1021
Danfoss Icon™ Programmable In-wall 88 × 88 mm Swiss type 088U1022
Danfoss Icon™ Programmable On-wall 86 × 86 mm N.A. 088U1025
AI189586480138en-000301 | 1
Data Sheet Danfoss Icon™ Programmable Room Thermostats, 230 V
Accessories
Technical specifications
Product Code no.
Danfoss Icon™ 230V Wiring Center, 8 channels, up to 14 outputs 088U1040
Danfoss Icon™ 230V Wiring Center, 8 channels, up to 14 outputs, CH 088U1041
Danfoss Icon™ 230V Wiring Center, 8 channels, up to 14 outputs, NP 088U1042
Danfoss Icon™ Floor Sensor 47 kΩ, 3 m, IP 67 088U1110
Typ e Electronic thermostat with touch user interface
User interface Capacitive touch and shine through display
User interface features
Display type Hybrid: red single LED’s and custom segment
Display features Switches OFF after 10 sec. with no interaction
Real time clock
Automatic daylight saving time Standard, can be turned off
Heating schedules
Temperature setting range 5 °C to 35 °C (frost protection setting = 5 °C)
Heating icon, arrow up/down, confirm key, back key, Home, Away, Night, Settings
Yes, std. Gregorian calendar. 8 hrs. running reserve (new product) down to 1,5 hrs. running reserve in year 10 after installation.
7 × pre-defined schedules (P0-P6) 5/2 days (weekdays and weekends)
Ambient temperature, storage −20 °C to +60 °C
Ambient temperature, used in application 0 °C to 40 °C
Controller, type Adjustable Pulse Width Modulation
Change over, cooling Yes, via 230 V input terminal
Global setback/Away Yes, via 230 V input terminal
Max. continuous load (output) < 50 mA / 10 W (= 5 pcs. Danfoss TWA actuators)
Max. inrush current (actuator) 3 A ≤ 100 ms
Power consumption 0,2 W
Power supply (excl. actuators) 220-240 V, 50/60 Hz
Sensor, room NTC 47 kΩ
Sensor, floor (optional) NTC 47 kΩ, 3 m, IP 68
Shell material
IP and Protection class IP: 21 Protection class: II
ErP class
Approval CE, RoHS, WEEE
Colour White RAL9010 / Dark Grey RAL7024
Dimensions, in-wall versions
Dimensions, on-wall version 86 × 86 × 25 mm (088U1025)
White parts: PC ASA Grey parts: PC, 10% glass
(2%)
80 × 80 × 11 mm (088U1020) 86 × 86 × 11 mm (088U1021) 88 × 88 × 13 mm (088U1022)
2 | © Danfoss | FEC | 2021.06
AI189586480138en-000301
Data Sheet Danfoss Icon™ Programmable Room Thermostats, 230 V
220-240V
N
NN
NN
220-240V
N
Application examples
Wiring without Wiring Center, neutral wire from main installation
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LN
Load
L
IP21
T30
Max. load: 10W/50mA
TC
088N3454 v000
Min. 3G1.5 cable to thermostat (not counting Protective earth)
M
Max. 5 actuators, type NC or NO, 230V Max. 10 W / Max. 50 mA continuous load Max. 3 A inrush current 100 ms
L
50-60 Hz
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LN
Load
L
IP21
T30
Max. load: 10W/50mA
TC
088N3452 v000
50-60 Hz
Wiring with Wiring Center
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LNNNTC
Min. 3G1.5 cable to thermostat (not counting Protective Earth)
1)
Note! Wiring Centers only support NC actuators, and do not support cooling change-over or global setback .
Min. 4G1.5 cable to thermostat (not counting Protective earth)
M
Max. 5 actuators, type NC or NO, 230V Max. 10 W / Max. 50 mA continuous load Max. 3 A inrush current 100 ms
L
IP21
Max. load: 10W/50mA
Load
L
T30
088N3452 v000
LN
LOAD
Wiring Center
088U1040 088 U10 41 088U1042
1)
Max. 5 actuators, type NC, 230V
Max. 10 W / Max. 50 mA continuous load
Max. 3 A inrush current 100 ms
© Danfoss | FEC | 2021.06
AI189586480138en-000301 | 3
Data Sheet Danfoss Icon™ Programmable Room Thermostats, 230 V
220-240V
N
220-240V
N
220-240V
N
Application examples
How to set thermostats to cooling mode from external device
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LNNNTC
Load
L
IP21
T30
Max. load: 10W/50mA
M
088N3452 v000
S
L
50-60 Hz
How to set thermostats to Away (global standby) from external device
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LNNNTC
Load
L
IP21
T30
Max. load: 10W/50mA
M
088N3452 v000
S
L
50-60 Hz
S: Can be mechanical switch
Summer / Winter or relay ac ti­vated by external device.
Use the same phase which supplies the thermostat.
The thermostat/room re mains in cooling mode as long as the phase is live onto the terminal.
Note! Switch not delivered by Danfoss.
S: Can be mechanical switch
Home / Away or relay acti­vated by external device.
Use the same phase which supplies the thermostat.
The thermostat/room re mains in Away mode as long as the phase is live onto the terminal.
Note! Switch not delivered by Danfoss.
4 | © Danfoss | FEC | 2021.06
How to install a floor sensor
Danfoss A/S 6430 Nordborg Denmark
Icon™ Programmable
LNNNTC
Load
L
IP21
T30
Max. load: 10W/50mA
M
L
50-60 Hz
Note! Use Danfoss 47 KΩ NTC sensor, code no.: 088U1110 Always route e xternal sensors in a suitable electrical pipe!
088N3452 v000
1. 2. 3. 4.
AI189586480138en-000301
Dimensions
60
60
60
60
47
71
71
80
51
51
23
11
Danfoss Icon™ Programmable 088U1020
80 80
47
23
11
Danfoss Icon™ Programmable 088U1021
47
71
71
86
88
80
86
© Danfoss | FEC | 2021.06
23
51
Danfoss Icon™ Programmable 088U1022 (incl. Feller EDIZIOdue frame and adapter)
75
13
86
25
Danfoss Icon™ Programmable 088U1025
AI189586480138en-000301 | 5
88
86