Danfoss Icon 230V Wiring Center Data sheet

Danfoss Icon 230V Wiring Center Data sheet

Data Sheet

Danfoss Icon™ 230V Wiring Center

Description

Danfoss Icon™ 230V Wiring Center is a connection box for use in hydronic floor heating using 230V thermostats and actuators.

The Icon™ 230V Wiring Center can connect up to 14 thermal actuators from up to 8 room thermostats. It is provided with 230V Live circulation pump output and a voltage-free relays for controlling a boiler. The relays are activated when one or more thermostats require heat.

The Wiring Center also supports away and cooling mode which can be controlled by a 230 V signal as well as LED’s to indicate when outputs are active.

Mounting is made easy due to a simple layout of the terminals and clear marking on the screw terminals. Mounting can be done by using screws.

Ordering

 

 

 

Product

Type of plug

Code number

 

 

 

 

 

 

Danfoss Icon™ 230V Wiring Center, 8 ch.

F

088U1040

 

 

 

 

 

Danfoss Icon™ 230V Wiring Center, 8 ch., CH

J

088U1041

 

 

 

 

 

Danfoss Icon™ 230V Wiring Center, 8 ch., NP

088U1042

 

 

 

 

© Danfoss | FEC | 2020.12

AI364356068139en-000101 | 1

Data Sheet

Danfoss Icon™ 230V Wiring Center

 

Technical data

 

 

Max. number of thermostats

8

 

 

 

 

 

Max number of actuators

14

 

 

 

 

Supported actuator types

Normally closed (NC)

 

 

 

 

Internal fuse

3 A

 

 

 

 

Conforms with diectives

LVD, EMC, RoHs, WEEE

 

 

 

 

Supply voltage

220-240 V AC

 

 

 

 

Supply frequency

50/60 Hz

 

 

 

 

Output voltage, actuators

230 V AC

 

 

 

 

Ambient temp. range, operation

0 °C to 50 °C

 

 

 

 

Storage temp. range

−20 °C to +60 °C

 

 

 

 

Output relay, pump

230 V Max. 100 W

 

 

 

 

Output relay, boiler

Voltage-free Max. 2 A

 

 

 

 

Output cooling

230 V when active

 

 

 

 

Output Setback

230 V when active

 

 

 

 

Input Cooling

External switch input (230 V rating)

 

 

 

 

Input setback

External switch input (230 V rating)

 

 

 

 

Rated impulse voltage

4 kV

 

 

 

 

Temperature for ball pressure test

75 °C

 

 

 

 

Control pollution degree

Pollution degree 2

 

 

 

 

Disposal instructions

As electronic waste

 

 

 

2 | © Danfoss | FEC | 2020.12

AI364356068139en-000101