Technical data
Danfoss recommends the installation of the Heat Cartridge
027R9788
Kit ICAD 600 / ICAD 900 on ICM motor operated valves in the following applications:
When the media temperature through the ICM valve is lower than –30oC (–22oF).
When the ICM valve is installed outdoor and the media temperature through the ICM valve is lower than –10oC (14oF).
When the ICM is installed indoor, with relative humidity higher than 90%, and when the media temperature though the ICM valve is lower than –10oC (14oF).
2.5 mm Hexagon key
Heat cartridge holder
Heat conduction compound
Voltage
24 V d.c / 24 V a.c
Load
1.5 A / 30 W
Cable
The Heat Cartridge is delivered with 1 m (39 in.) cable. 3 × 0.5 mm2 (3 × 20 AWG).
• Brown and Blue: 24 V d.c (polarity unimportant), 24 V a.c
• Yellow/Green: Ground/Earth
1C
1B
027R9788
2.5 mm Hexagon key
Heat cartridge
ICAD
Code numbers
Heat Cartridge Kit ICAD 600 for ICM 20 ICM 25 ICM 32
Heat Cartridge Kit ICAD 900 for ICM 40 ICM 50
1
ICM 65
027H1200 027H1205 027H1210
027H1201 027H1206 027H1211
Heat Cartridge Kit
Code number
027H1209
027H1219
The Heat Cartidge Kit contains:
• Heat cartidge
• Heat cartidge holder
• Heat conduction compound
© Danfoss A/S (MWA), 2015-01 DKRCI.PI.HT0.E4.02 / 520H2195 1
ICAD
2.5 mm Hexagon key
2 3
Installation
Mechanical installation
General procedure for installing the Heat Cartridge Kit ICAD 600 / ICAD 900 on all sizes of ICM valves:
Please Note:
The Heat Cartridge Kit ICAD 600 / ICAD 900 must be installed before the ICAD 600/900 actuator is mounted on the ICM valve.
• Check that the three socket set screws on the ICAD actuator are counter clockwise fully unscrewed and removed with a 2.5 mm Hexagon key (see g. 2).
• Check that the two socket set screws on the heat cartridge holder are counter clockwise fully unscrewed with a 2.5 mm Hexagon key (see g. 1).
• Apply heat conductive compound to:
• the heat cartridge (marked 1A in g. 1)
• into both ends of the holes for heat cartridge, on the heat cartridge holder (marked 1B in g. 1)
• on the inner surface of the heat cartridge holder (marked 1C in g. 1)
2 DKRCI.PI.HT0.E4.02 / 520H2195 © Danfoss A/S (MWA), 2015-01
• Insert the heat cartridge into the smallest hole of the heat cartridge holder (see g. 1).
• Fasten the heat cartridge with the socket set screw using a
2.5 mm Hexagon key.
• Insert the ICAD into the hole of the heat cartridge holder. (g. 2)
• Install the heat cartridge holder on the ICAD actuator. Position the heat cartridge holder in a center position as shown in g. 3
• Fasten the heat cartridge holder using a 2.5 mm Hexagon key.
• Reinstall the three socket set screws on the ICAD actuator.
• Please consult the ICAD instruction (DKRCI.PI.HV0.A) regarding the mounting of ICAD actuators on ICM motor operated valves.
Electrical installation
Please Note: Do not connect supply voltage before the heat cartridge is inserted into the hole of the the heat cartridge holder - then