Danfoss ICAD 600, ICAD 900 Installation guide

Installation Guide

Heat Cartridge Kit

ICAD 600 / ICAD 900 for ICM

<![if ! IE]>

<![endif]>027R9788

Technical data

 

 

 

 

 

 

 

 

Danfoss recommends the installation of the Heat Cartridge

Voltage

 

 

Kit ICAD 600 / ICAD 900 on ICM motor operated valves in

24 V d.c / 24 V a.c

 

 

the following applications:

 

Load

 

 

 

 

 

 

When the media temperature through the ICM valve is lower

1.5 A / 30 W

 

 

Cable

 

 

than –30oC (–22oF).

 

 

 

When the ICM valve is installed outdoor and the media

 

The Heat Cartridge is delivered with 1 m (39 in.) cable.

 

 

3 ×0.5 mm2 (3 × 20 AWG).

 

temperature through the ICM valve is lower than –10oC (14oF).

• Brown and Blue:

24 V d.c (polarity unimportant), 24 V a.c

 

When the ICM is installed indoor, with relative humidity higher

 

• Yellow/Green:

Ground/Earth

 

than 90%, and when the media temperature though the ICM

 

 

 

valve is lower than –10oC (14oF).

 

 

 

 

2.5 mm Hexagon key

Heat cartridge holder

 

1C

Heat conduction compound

1B

2.5 mm Hexagon key

1A

Heat cartridge

 

 

ICAD

Heat Cartridge Kit

The Heat Cartidge Kit contains:

 

 

Code numbers

Code number

Heat cartidge

 

 

 

 

Heat cartidge holder

 

Heat Cartridge Kit ICAD 600 for

027H1200

 

 

 

Heat conduction compound

 

ICM 20

027H1209

 

ICM 25

027H1205

 

 

 

027H1210

 

 

 

 

ICM 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Cartridge Kit ICAD 900 for

027H1201

 

 

 

 

ICM 40

 

 

 

 

027H1206

027H1219

 

 

 

ICM 50

 

 

1

027H1211

 

 

 

ICM 65

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>027R9788

© Danfoss A/S (MWA), 2015-01

DKRCI.PI.HT0.E4.02 / 520H2195

1

Danfoss ICAD 600, ICAD 900 Installation guide

ICAD

2.5 mm Hexagon key

2

3

Installation

Mechanical installation

General procedure for installing the Heat Cartridge Kit ICAD 600 / ICAD 900 on all sizes of ICM valves:

Please Note:

The Heat Cartridge Kit ICAD 600 / ICAD 900 must be installed before the ICAD 600/900 actuator is mounted on the ICM valve.

Check that the three socket set screws on the ICAD actuator are counter clockwise fully unscrewed and removed with a 2.5 mm Hexagon key (see fig. 2).

Check that the two socket set screws on the heat cartridge holder are counter clockwise fully unscrewed with a 2.5 mm Hexagon key (see fig. 1).

Apply heat conductive compound to:

the heat cartridge (marked 1A in fig. 1)

into both ends of the holes for heat cartridge, on the heat cartridge holder (marked 1B in fig. 1)

on the inner surface of the heat cartridge holder (marked 1C in fig. 1)

Insert the heat cartridge into the smallest hole of the heat cartridge holder (see fig. 1).

Fasten the heat cartridge with the socket set screw using a 2.5 mm Hexagon key.

Insert the ICAD into the hole of the heat cartridge holder. (fig. 2)

Install the heat cartridge holder on the ICAD actuator. Position the heat cartridge holder in a center position as shown in fig. 3

Fasten the heat cartridge holder using a 2.5 mm Hexagon key.

Reinstall the three socket set screws on the ICAD actuator.

Please consult the ICAD instruction (DKRCI.PI.HV0.A) regarding the mounting of ICAD actuators on ICM motor operated valves.

Electrical installation

Please Note:

Do not connect supply voltage before the heat cartridge is inserted into the hole of the the heat cartridge holder - then connect 24 V d.c/a.c

2

DKRCI.PI.HT0.E4.02 / 520H2195

© Danfoss A/S (MWA), 2015-01