Danfoss HRM032, HRM038, HRM040, HRM042, HRM045 Instructions For Use Manual

...
H SERIES COMPRESSORS
Operating limits
HRM/HLM/HCM  HRP/HLP/HCP  HRH/HLH/HLJ/HCJ
Model variation T (R22 / R407C / R410A)
70
65
60
55
50
45
40
35
C o n d. T e m p . (° C )
30
25
20
-30 -25 -20 -15 -10 -5 0 5 10 15
Ev a p . T e m p . ( °C )
HRM/HLM/HCM  HRP/HLP/HCP  HRH/HLH/HLJ/HCJ
Model variation U (R22 / R410A)
70
65
60
55
50
45
40
35
C o n d. T e m p . (° C )
30
25
20
-30 -25 -20 -15 -10 -5 0 5 10 15
70
65
60
55
50
45
40
35
C o n d. T e m p . (° C )
30
25
20
-30 -25 -20 -15 -10 -5 0 5 10 15
Ev a p . T e m p . ( °C )
HHP (R407C)
SH 5K
SH 10K
Ev a p . T e m p . ( °C )
SH 11K
SH 30K
INSTRUCTIONS
A: Model number B: Technical number C: Serial Number D: Manufacturing year E: Internal protection F: Supply voltage range G: Run capacitor H: Locked rotor current
Maximum operating current
I: Lubricant type and nominal charge J: Approved Refrigerant
Installation and servicing of the
compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
Electrical connections
Quick connect spade terminals
P terminal box type
C T₁
S
T₂
R
T₃
Ring connect screw terminals
C terminal box type
push
push
push
A
400
B
C
D E
Single phase
C
S
Line
R
KA
PM
Run Capacitor
KS
T1T3T2
HPs
DGT
2
L1 L3 L2
C
S
Line
R
Three phase (Wiring diagram with pump-down cycle)
CONTROL CIRCUIT
F1F1
KM
KA KA
A1
A3
KS
180 s
A2
TH
LP
KS
KM
KA
LLSV KS
PSC wiring
Run Capacitor
CSR wiring
5
Potential Relay
1
Start Capacitor
Q1
KM
M
F
G H
I
J
The compressor must only be used for its designed purpose(s) and within its scope of application (refer to «ope­rating limits»). Consult Application guidelines and datasheet available from cc.danfoss.com
Never operate compressor without terminal box cover in place and secured.
The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble bolts, plugs, fittings, etc... unless all pressure has been relieved
Under all circumstances, the EN378 (or other applicable local safety regulation) requi­rements must be fulfilled. Wear protective goggles and work gloves.
The compressor must be handled with caution in the vertical position (maximum offset from the vertical : 15°).
from the compressor.
1 – Introduction
These instructions pertain to the Performer® HRM/ HLM/HCM  HRP/HLP/HCP/HHP  HRH/HLH/HLJ/ HCJ scroll compressors used for HVAC systems. They provide necessary information regarding safety and proper usage of this product.
2 – Handling and storage
• Handle the compressor with care. Use the dedicated handles in the packaging. Use the compressor lifting
1 2
lug and use appropriate and safe lifting equipment.
• Store and transport the compressor in an upright position.
• Store the compressor between -35°C and 70°C /
-31°F and 158°F.
• Don’t expose the compressor and the packaging to rain or corrosive atmosphere.
3 – Safety measures before assembly
Never use the compressor in a flammable atmosphere.
• Mount the compressor on a horizontal flat sur­face with less than 7° slope.
• Verify that the power supply corresponds to the compressor motor characteristics (see nameplate).
• When installing a compressor model HRP / HLP / HCP / HHP - HRH / HLH /HLJ / HCJ, use equipment specifically reserved for HFC refrigerants which was never used for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade cop­per tubes and silver alloy brazing material.
FRCC.PI.006.A2.22 © Danfoss Commercial Compressors 04/10 FRCC.PI.006.A2.22 © Danfoss Commercial Compressors 04/10
Instructions
• Use clean and dehydrated system components.
• The piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations.
• The compressor must always be mounted with the rubber grommets supplied with the compressor.
4 – Assembly
• Slowly release the nitrogen holding charge through discharge and suction ports.
• Connect the compressor to the system as soon as possi­ble to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
• Braze with great care using state-of-the-art techni­que and vent piping with nitrogen gas flow.
• Connect the required safety and control devices. When the schrader port, if any, is used for this, re­move the internal valve.
• For parallel assemblies of the compressors in ver­sion C8, contact Danfoss.
5 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosion.
• Do not use leak detection dye.
• Perform a leak detection test on the complete system.
• The low side test pressure must not exceed 31 bar /450 psi.
• When a leak is discovered, repair the leak and re­peat the leak detection.
6 – Vacuum dehydration
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP & HP sides.
• Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
• Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
7 – Electrical connections
• Switch off and isolate the main power supply.
• All electrical components must be selected as per local standards and compressor requirements.
• Refer to page 1 for electrical connections details.For three phase applications, the terminals are labeled T1, T2, and T3. For single-phase applications the terminals are labeled C (common), S (start), and R (run).
• Danfoss scroll compressors will only compress gas while rotating counter-clockwise (when viewed from the compressor top). Since single-phase motors will start and run in only one direction, reverse rotation is not a major consideration. Three-phase motors, howe­ver, will start and run in either direction, depending on the phase angles of the supplied power. Care must be taken during installation to ensure that the compres­sor operates in the correct direction.
• Use ø 4.8 mm / #10 - 32 screws and ¼” ring terminals for the power connection with ring connect screw ter­minal (C type). Fasten with 3 Nm torque.
• Use ø 6.3 mm tabs for quick connect spade termi­nals (P type).
• Use a self tapping screw to connect the compres­sor to earth.
8 – Filling the system
• Keep the compressor switched off.
• Keep the refrigerant charge below the indicated charge limits if possible. Above this limit; protect the compressor against liquid flood-back with a
pump-down cycle or suction line accumulator.
• Never leave the filling cylinder connected to the circuit.
Compressor models
HRM032-034-038-040-042-045-047
HRP034-038-040-042-045-047
HHP015-019-021-026
HRH031-032-034-036-038-040
HRM048-051-054-058-060 /
HLM068-072-075-078-081
HRP048-051-054-058-060 /
HLP068-072-075-081
HHP030-038-045
HRH044-049-051-054-056 /
HLH061-068 - HLJ072-083
HCM094-109-120
HCJ090-105-120
Refrigerant
charge limit
3.6 kg / 8 lb
5.4 kg / 12 lb
7.2 kg / 16 lbHCP094-109-120
9 – Verification before commissioning
Use safety devices such as safety pressure switch and mechanical relief valve in compliance with both generally and locally applicable regu­lations and safety standards. Ensure that they are operational and properly set.
Check that the settings of high-pressure swit­ches don’t exceed the maximum service pressure of any system component.
• A low-pressure switch is recommended to avoid
low pressure operation.
Minimum setting for R22 Minimum setting for R407C Minimum setting for R410A 2.5 bar (absolute) / 36 psia
1.5 bar (absolute) / 22 psia
• Verify that all electrical connections are properly faste-
ned and in compliance with local regulations.
• When a crankcase heater is required, it must be
energized at least 24 hours before initial start-up and start-up after prolonged shutdown.
10 – Start-up
• Never start the compressor when no refrigerant is
charged.
• Do not provide any power to the compresor
unless suction and discharge service valves are open, if installed.
• Energize the compressor. It must start promptly.
If the compressor does not start, check wiring conformity and voltage on terminals.
• Eventual reverse rotation can be detected by following
phenomena; the excessive noise, no pressure differen­tial between suction and discharge, and line warming rather than immediate cooling. A service technician should be present at initial start-up to verify that sup­ply power is properly phased and that the compressor is rotating in the correct direction. H-series Scroll com­pressors are designed to operate for a maximum of 150 hours in reverse, but as a reverse rotation situation can go unnoticed for longer periods, phase monitors are recommended. For compressors HLM078, HLP081, HLJ083 and larger, phase monitors are required for all applications. Danfoss recommends phase protection for residential compressors.
• If the internal overload protector trips out, it must cool
down to 60°C / 140°F to reset. Depending on ambient temperature, this may take up to several hours.
11 – Check with running compressor
Check current draw and voltage. Measurement of amps and volts during running conditions must be taken at other points in the power supply, not in the compressor electrical box.
• Check suction superheat to reduce risk of slugging.
H series
• Observe the oil level in the sight glass (if provi­ded) for about 60 minutes to ensure proper oil return to the compressor.
• Respect the operating limits.
• Check all tubes for abnormal vibration. Move­ments in excess of 1.5 mm / 0.06 in require cor­rective measures such as tube brackets.
• When needed, additional refrigerant in liquid phase may be added in the low-pressure side as far as pos­sible from the compressor. The compressor must be operating during this process.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out a general installation inspection regarding cleanli­ness, noise and leak detection.
• Record type and amount of refrigerant charge as well as operating conditions as a reference for fu­ture inspections.
12 – Maintenance
Internal pressure and surface temperature are dangerous and may cause permanent injury. Main­tenance operators and installers require appropria­te skills and tools. Tubing temperature may exceed 100°C / 212°F and can cause severe burns.
Ensure that periodic service inspections to en­sure system reliability and as required by local re­gulations are performed. To prevent system related compressor problems, fol­lowing periodic maintenance is recommended:
• Verify that safety devices are operational and pro-
perly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Confirm that the system is operating in a way
consistent with previous maintenance records and ambient conditions.
• Check that all electrical connections are still ade-
quately fastened.
• Keep the compressor clean and verify the absen-
ce of rust and oxidation on the compressor shell, tubes and electrical connections.
• Acid / moisture content in system and oil should
be checked regularly.
13 - Warranty
Always transmit the model number and serial number with any claim filed regarding this product. The product warranty may be void in following cases:
• Absence of nameplate.
• External modifications; in particular, drilling, wel-
ding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the com-
pressor.
• Use of a refrigerant or lubricant not approved by
Danfoss.
• Any deviation from recommended instructions per-
taining to installation, application or maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted
with the warranty claim.
14 – Disposal
Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.
Loading...
+ 2 hidden pages