Danfoss H 228/328 Fact sheet

Fact sheet
H 228/328
District heating substation for large properties
FEATURES AND BENEFITS
• District heating substation for indirect heat­ing
• Connection pipes for DHW cylinder
• Equipped with A-labelled low-energy pump
• Pipes and heat exchanger in stainless steel
• Minimized risk of lime scale and bacteria for­mation
• The substation is very service-friendly due to practical piping and assembly with nuts and gaskets
• Excellent operating economy
Application
The H 228/328 is made in a compact design and is especially suitable for supply of heat­ing for large properties and apartment hous­es. The substation is suitable for two pipe systems. The substation features a plate heat exchan­ger for the heating circuit and it is prepared for connection to a domestic hot water cy­linder. The H 228/328 is available in two basic vari­ants, - one variant with Danfoss ECL 210 or 310 and motorized control valve for control of the heating circuit and another variant with Danfoss ECL 210 or 310 and motorized control valves for control of both the heating circuit as well as the DHW cylinder circuit. The H 228/328 variants offer capacities ran­ging from 44 to 170 kW heating and 13 to 100 kW domestic hot water. Please contact our sales department and together we shall find the optimum solution for your exact re­quirements.
Construction
The H 228/328 is supplied with a brazed plate heat exchanger for heating, electronic actuator()s and valve(s), safety valves, pump, shut-off valves, mano- and thermometers, strainers, sensor pockets, differential pres­sure controller as well as connection pipes for DHW cylinder. Actuator(s) and pump(s) are electrically wired from factory and sup­plied with CEE plug for connection to 220 V.
The electronic control ECL 310 is prepared for WebAccess, which enables remote con
-trol and remote monitoring via the internet/ intranet. The substations are delivered preassem-bled, electrically wired internally and the electro­nic control is tested for function and preset from factory. The substation can be supplied with fitting piece for heat meter in the district heating supply and return pipe (to be speci­fied when ordering).
Design
The H 228/328 is designed for wall-moun­ting and during the construction much im­portance has been attached to a clear and user-friendly placement of all components. The H 228/328 is built on a frame of galva­nized iron and offers variable connection possibilities, as connection of pipes can be established both in the top or in the bottom (standard) of the substation. The H 228/328 can be supplied with a white-lacquered steel cover with door, which enables easy access for meter reading and service purposes.
Connection pipes for domestic hot water cylinder (DHW)
As standard the H 228/328 is supplied with primary connection pipes for DHW cylinder, with or without motorized control valve and electronic control of the cylinder circuit.
Heat exchanger for DHW heating
The heat exchanger used in the H 228/328 is a brazed, highly efficient Danfoss plate heat exchanger, which has been tested and ap­proved according to the PED-directive.
Reading and setting
All thermometers are placed so they are easy to read. Components, which can be adjust­ed, are easily accessible.
Service og maintenance
The substation is very service-friendly due to practical piping and assembly with nuts and gaskets. It is mounted on the wall and as all pipes are placed in pipe bracket distance, it is possible to establish a nice piping.
www.danfoss.com
CIRCUIT DIAGRAM – EXAMPLE - H 228 / 328 WITH ECL 310, A266
P, M and S refer to the Danfoss ECL instruction manual
Cylinder Supply
Cylinder Return
DH Supply
DH Return
Design specifications:
Nominal pressure (prim/sec): PN 16 / PN 10 Max. supply temperature.: 120 °C Min. ΔP: 0,75 bar incl. differential pressure controller (alternatively 0,5 bar)
Weight: Max . 90 kg
1 Plate heat exchanger HE 4 Differential pressure controller 5 Strainer 6 Non-return valve 7 Ball valve 8 Pump HE 9 Connection for pump (circ.) 11 Safety valve, HE 13 Thermometer 14 Manometer w/shut-off valve
HE Supply
HE Return
15 Manometer 17 Air valve 19 Drain valve/connection for expansion vessel 23 Sensor pocket for heat meter (optional) 24 Fitting piece for heat meter (optional) 25 Controller Danfoss ECL310/A266 26 Outdoor sensor 27 Sensor forward/return 28 Sensor, DHW 29 Actuator 2 30 Valve 2 31 Actuator 1 32 Valve 1
Connections:
1. DH supply 4. HE return
2. DH return 5. Cylinder supply
3. HE supply 6. Cylinder return
Connections sizes:
DH, HE: G 1“ or 5/4” (int. thread) Cylinder: G 1“ or 5/4” (int. thread)
Colour (cover): White RAL 9010
Electrical supply: 220 V AC
Dimensions (mm):
Without cover: H 1350 x W
max. 917 x D 380
With cover: H 1350 x W 1030 x D 420
CAPACITY, WEIGHT AND DIMENSIONS
Heating and DHW capacity examples
Contact your local Danfoss sales representative for capacity examples
HEATING: CAPACITY EXAMPLES
© Danfoss | DHS-SRMT/ PL | 2018 . 04
VL.IE.M2.02
Loading...