Danfoss GEO 250 Data sheet

Technical Paper
Geothermal Heating Surface GEO 250
Description
Heating / Cooling Capacity
Technical Data
The geothermal surface has two functions:
• Winter: preheating the outdoor air to protect the system from icing up.
• Summer: cooling the outdoor air to freshen up the inlet air.
The effect to be achieved with the geothermal surface depends on a number of variables, e.g.
• type of soil
• height of subsoil water
• laying depth of ground pipe
• how the soil is surrounding the ground pipe
The following example describes guidelines for laying ground pipe with brine (Antifreeze).
Width 600 mm
Height 335 mm
Depth 250 mm
Weight 6.3 kg
Duct system connector Ø 250 mm
Power consumption 3-10 W
Electrical connection 230 V, 50 Hz
The only power consumption required for this solution is for the circulation pump. The surface is supplied fully assembled, incl. automation, two temperature sensors for duct fit­ting and the required cables. Plug’n’play installation - the system recognises and configures the surface automatically on connection. The surface is fitted in the duct system on the outdoor side.
Prerequisites for ground pipe
• min. depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 m
• center distance . . . . . . . . . . . . . . . . . . . . . . . . . . .1 m
• length for a2/w2 unit. . . . . . . . . . . . . . . . 120-150 m
• length for a3 unit . . . . . . . . . . . . . . . . . . . 160-200 m
Under conditions as mentioned, an output of approx. 15W/m2 = 15W/m is to be expected (rule of thumb).