Danfoss GEO 250 Data sheet

Danfoss GEO 250 Data sheet

Technical Paper

Geothermal Heating Surface GEO 250

Description

Heating / Cooling

Capacity

Technical Data

The geothermal surface has two functions:

Winter: preheating the outdoor air to protect the system from icing up.

Summer: cooling the outdoor air to freshen up the inlet air.

The typical air supply temperature will be 14-16°C, depending on the outdoor temperature, soil conditions for the brine circuit, etc.

The geothermal surface is connected to a buried ground pipe in which brine (antifreeze) is circulated.

The effect to be achieved with the geothermal surface depends on a number of variables, e.g.

type of soil

height of subsoil water

laying depth of ground pipe

how the soil is surrounding the ground pipe

The following example describes guidelines for laying ground pipe with brine (Antifreeze).

The only power consumption required for this solution is for the circulation pump.

The surface is supplied fully assembled, incl. automation, two temperature sensors for duct fitting and the required cables.

Plug’n’play installation - the system recognises and configures the surface automatically on connection.

The surface is fitted in the duct system on the outdoor side.

Prerequisites for ground pipe

 

 

 

 

 

 

 

min. depth . . . . . . . .

.

.

.

.

.

.

. 1.5 m

center distance . . . . . .

.

.

.

.

.

.

. .1 m

length for a2/w2 unit . . . .

.

.

.

 

. 120-150 m

length for a3 unit . . . . .

.

.

.

.

160-200 m

Under conditions as mentioned, an output of approx. 15W/m2 = 15W/m is to be expected (rule of thumb).

Width

600 mm

 

 

Height

335 mm

 

 

Depth

250 mm

 

 

Weight

6.3 kg

 

 

Duct system connector

Ø 250 mm

 

 

Power consumption

3-10 W

 

 

Electrical connection

230 V, 50 Hz

 

 

Ordering

Code no . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

089F0354

VFFKB102

© Danfoss

10/2010