Data sheet
FVR, FVR-D Strainers
Description
FVR |
FVR-D |
FV strainer is used in heating and hotwaterservice systems to protect the fittings. The strainer filter traps foreign matters in the pipe water like welding beads, swarf, sand, etc.FV must be fitted in the system flow to protect the fittings from external foreign matters. FV must also be fitted ahead of sensitive components like meters, pumps,control valves to protect against internal foreign matters.
Features:
•Replaceable filter
•Version with draining ball valve (FVR-D)
Main data:
•DN 10-50
•kVS 3,0-32 m3/h
•PN 25
•Temperature:
FVR: |
−20 … 130 °C |
FVR-D: |
−15 … 130 °C |
•Medium: Circulation water / glycolic water up to 50 %
•Min. storage and transport temperature: −40 °C
•Threaded connection
Ordering |
DN |
kVS |
FVR |
FVR-D |
|
Picture |
|||||
(mm) |
(m3/h) |
Code No. |
Code No. |
||
|
10 |
3,0 |
065B8234 |
- |
|
|
15 |
4,0 |
065B8235 |
065B8241 |
|
|
20 |
8,0 |
065B8236 |
065B8242 |
|
|
25 |
10 |
065B8237 |
065B8243 |
|
|
32 |
15 |
065B8238 |
065B8244 |
|
|
40 |
21 |
065B8239 |
065B8245 |
|
|
50 |
32 |
065B8240 |
065B8246 |
Spare parts - Screen
Picture |
DN |
FVR, FVR-D |
|
(mm) |
Code no. |
||
|
|||
|
10 |
065B8247 |
|
|
15 |
||
|
|
||
|
20 |
065B8248 |
|
|
25 |
065B8249 |
|
|
32 |
065B8250 |
|
|
40 |
065B8251 |
|
|
50 |
065B8252 |
Accessories - Ball valve
Picture |
DN |
FVR-D |
|
(mm) |
Code no. |
||
|
|||
|
10 |
|
|
|
15 |
|
|
|
20 |
|
|
|
25 |
065B8254 |
|
|
32 |
|
|
|
40 |
|
|
|
50 |
|
© Danfoss | 2020.10 |
AI138786466020en-010301 | 1 |
Data sheet |
FVR, FVR-D Strainers |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ordering |
|
|
|
|
|
|
|
|
|
|
|
Nominal diameter |
DN |
10 |
15 |
20 |
|
25 |
|
32 |
40 |
50 |
|
|
Value kVS |
m3/h |
3,0 |
4,0 |
8,0 |
|
10 |
|
15 |
21 |
32 |
|
Nominal pressure |
PN |
|
|
|
25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
Medium |
|
|
Circulation water, glycolic water up to 50 % |
|
||||||
|
|
|
|
|
|
|
|
|
|
||
|
Medium pH |
|
|
|
|
Min. 7, Max. 10 |
|
|
|
||
|
Medium temperature |
°C |
|
|
FVR: −20 … 130 °C |
|
|
||||
|
|
|
FVR-D: −15 … 130 °C |
|
|
||||||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Mesh size |
µm |
|
|
|
500 |
|
|
|
|
|
|
Number of meshes |
n/cm2 |
|
|
|
50 |
|
|
|
|
|
|
Connection |
|
|
|
Internal thread Rp |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Materials |
|
|
|
|
|
|
|
|
|
|
|
Body (strainer) |
|
|
|
Dezincification free brass |
|
|
||||
|
|
|
|
|
|
|
|
||||
|
Plug (strainer) |
|
|
|
Dezincification free brass |
|
|
||||
|
Screen |
|
|
|
|
Stainless steel |
|
|
|
||
|
O-ring |
|
|
|
|
|
EPDM |
|
|
|
|
|
Body (ball valve) |
|
|
|
|
|
Brass |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Applications
Installation positions |
The medium flow direction must correspond to |
|
an arrow on the strainer body. |
|
Strainers are to be installed in horizontal |
|
position |
|
with mesh bonet directed downwards. Vertical |
|
position is also allowed (be aware - when |
|
medium flows upwards strainer retains all |
|
foreign particles but is not able to collect them). |
|
Sufficient space to pull out the mesh for |
|
replacement and cleaning must be ensured. |
2 | AI138786466020en-010301 |
© Danfoss | 2020.10 |