Danfoss FLX 17 Pro Installation Manual

www.danfoss.com/solar
SOLAR INVERTERS
Installation Guide
FLX Series
MAKING MODERN LIVING POSSIBLE
Safety Message Types
The following symbols are used in this document:
DANGER
Indicates a potentially hazardous situation which could result in death.
WARNING
Indicates a potentially hazardous situation which could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations which may result in damage to equipment or property.
General Safety
All persons installing and servicing inverters must be:
Trained and experienced in general safety rules for work on electrical equipment.
Familiar with local requirements, rules and regulations for the installation.
NOTICE
Before installation Check for damage to equipment and packaging. If in doubt, contact the supplier before commencing instal­lation.
CAUTION
Installation For optimum safety, follow the steps described in this document. Keep in mind that the inverter has 2 voltage carrying sides; the PV input and the AC grid.
WARNING
Disconnecting the inverter Before starting work on the inverter, switch off AC at the mains switch and PV using the PV load switch. Ensure that the device cannot be unintentionally reconnected. Use a voltage tester to ensure that the unit is discon­nected and voltage free. The inverter can still be charged with very high voltage at hazardous levels even when it is disconnected from AC grid and solar modules. Wait at least 8 minutes following disconnection from grid and PV panels before proceeding.
For safe disconnection of DC current, turn off the PV load switch (1).
Safety and Conformity
L00410568-02_02 / Rev. date: 2013-12-10
CAUTION
Maintenance and modification Only authorised personnel are permitted to modify the inverter. To ensure personal safety, use only original spare parts available from the supplier. If non-original spare parts are used, compliance with CE guidelines in respect of electrical safety, EMC and machine safety is not guaranteed. The temperature of the cooling racks and components inside the inverter can exceed 70 ºC. Observe the danger of burn injury.
DC voltages up to 1000 V are present in a PV system even when the inverter is disconnected from the AC grid. Faults or inappropriate use may lead to electric arcing.
WARNING
PV modules generate voltage when exposed to light.
WARNING
Do not work on the inverter while disconnecting DC and AC.
The short-circuit current of the photovoltaic panels is only slightly higher than the maximum operating current and depends on the level of solar irradiation.
Conformity
Go to the download area at www.danfoss.com/solar, Approvals and Certifications, for information.
See also 5 Technical Data.
CE marking - This symbol certifies the conformity of
the equipment with the requirements of the
applicable EC directives
Safety and Conformity
L00410568-02_02 / Rev. date: 2013-12-10
Contents
1 Introduction
3
1.1 Purpose of the Manual
3
1.2 Software Version
3
1.3 Spare Parts
4
1.4 Unpacking
4
1.5 Identification of Inverter
4
1.6 Installation Sequence
4
1.7 Return and Disposal
4
1.7.1 Return 5
1.7.2 Disposal 5
1.8 Overview of Installation Area
6
2 Installation
7
2.1 Environment and Clearances
7
2.2 Mounting the Mounting Plate
8
2.3 Mounting the Inverter
9
2.4 Removing the Inverter
10
2.5 Access to the Installation Area
10
2.6 AC Grid Connection
11
2.7 RS-485 or Ethernet Connections
12
2.8 Options
12
2.9 Closure
12
2.10 PV Connection
13
2.10.1 Protection Rating for PV Modules 14
3 Initial Setup and Start
15
3.1 User Interface
15
3.1.1 Operation Modes 15
3.1.2 Security Level 15
3.1.3 Preparation for Master Inverter
16
3.1.4 Manual PV Configuration 16
3.2 Display
16
3.2.1 Initial Setup via Display
17
3.2.2 Turn PV Load Switch On 20
3.2.3 Start-up 20
3.2.4 Autotest Procedure
20
3.3 Web Interface
20
3.3.1 Prepare for Setup 20
3.3.3 Setup Wizard 21
3.3.4 Web Interface 27
Contents
L00410568-02_02 / Rev. date: 2013-12-10 1
3.3.5 Plant, Group and Inverter Views 28
3.3.6 Autotest Procedure 29
4 Service
30
4.1 Troubleshooting
30
4.2 Maintenance
33
5 Technical Data
34
5.1 Specifications
34
5.1.1 Inverter Specifications 34
5.2 Derating Limits
38
5.3 Conformity
38
5.4 Installation Conditions
39
5.5 Cable Specifications
40
5.6 Torque Specifications
42
5.7 Mains Circuit Specifications
43
5.8 Auxiliary Interface Specifications
43
5.9 RS-485 and Ethernet Connections
44
Contents
2 L00410568-02_02 / Rev. date: 2013-12-10
1Introduction
1.1 Purpose of the Manual
The Installation Guide provides information required to install and commission the FLX series inverter.
Additional resources available:
User Guide, for information required in monitoring and setup of the inverter, via the display or web interface.
Design Guide, for information required for planning use of the inverter in a diversity of solar energy applications.
CLX GM Quick Guide, for information required to install and set up power management of the FLX Pro inverter using the CLX GM device.
CLX Home Installation Manual, or CLX Home GM, CLX Standard, CLX Standard GM Quick Guide, for
information required to install and set up monitoring of the FLX inverter.
Sensor Interface Option Installation Guide, for installation and commissioning of the sensor interface option.
GSM Option Kit Installation Guide, for information required to install a GSM option, and set up data upload or messaging from the inverter.
PLA Option Guide, for information required to install and set up PLA option for connecting radio ripple control receiver to the inverter.
Fan Installation Instruction, for information required to replace a fan.
These documents are available from the download area at www.danfoss.com/solar, or from the supplier of the solar inverter.
Illustration 1.1 FLX Series Inverter
The FLX series inverters feature:
IP65 enclosure
PV load switch
Sunclix connectors for PV input
Manual access via the display, for configuration and monitoring of the inverter.
Ancillary service functionalities. Refer to the FLX Series Design Guide for details.
Access via web interface, for configuration and monitoring of the inverter.
1.2 Software Version
This manual is applicable for inverter software 2.05 and onwards. To see the software version, via the display or web interface (inverter level), go to [Status → Inverter → Serial no. and SW ver. → Inverter].
NOTICE
Software version at manual release is 2.05. Information about current software version is available at www.danfoss.com/solar.
Introduction
L00410568-02_02 / Rev. date: 2013-12-10 3
1 1
1.3 Spare Parts
Contact Danfoss for information about spare parts, part numbers, and ordering.
1.4 Unpacking
Contents:
Inverter
Mounting plate
Accessories bag, containing: 3 mounting screws, 2 cable glands, 2 rubber cups, 1 earthing screw, and 1 security label for France.
4 to 6 Sunclix mating parts depending on the number of MPPT for FLX Pro 5-17.
Installation guide, booklet format
Quick guide, poster format
The following items are not supplied:
Security screws, M5 x 8-12, optional (not available as product from Danfoss)
1.5 Identification of Inverter
Illustration 1.2 Product Label
The product label on the side of the inverter shows:
Inverter type
Important specifications
Serial number, located under the bar code, for inverter identification.
1.6 Installation Sequence
1. Pay special attention to 1.1 Safety Message Types.
2. Install the inverter according to 2.1 Environment and Clearances, 2.2 Mounting the Mounting Plate and 2.3 Mounting the Inverter.
3. Open the inverter according to 2.5 Access to the Installation Area.
4. Install AC according to 2.6 AC Grid Connection.
5. Install RS-485 or Ethernet, if used, according to
2.7 RS-485 or Ethernet Connections.
6. Install options, if any, according to the installation guide supplied with the option.
7. Close the inverter according to 2.5 Access to the Installation Area.
8. Install PV according to 2.10 PV Connection.
9. Turn on AC at the mains switch.
10. Set language, master mode, time, date, installed PV power, country, and grid code:
For setup via the web interface, refer to
3.3 Web Interface.
For setup via the display, refer to
3.2 Display.
11. Turn on PV by turning on the PV load switch. Refer to 2.10.1 Connection of PV.
12. Verify the installation by comparing with the autodetection result in the display, as described in 2.10 PV Connection.
13. The inverter is now in operation.
For installation and setup of multiple FLX Pro inverters in master-follower configuration:
Perform steps 2–9 and 11 for each inverter.
Perform step 10 on the inverter planned as master.
Perform step 12.
1.7 Return and Disposal
When replacing an inverter, it can either be returned to your distributor, to Danfoss directly, or disposed of according to local and national regulations. Danfoss is committed to its policy of environmental responsibility, and therefore appeals to end users who are disposing of inverters to follow local environmental legislation and to seek safe, responsible means of disposal.
Introduction
4 L00410568-02_02 / Rev. date: 2013-12-10
1
1.7.1 Return
For return to Danfoss, the inverter should always be in its original packaging or equivalent packaging. If the product is returned as a result of inverter failure, contact your Danfoss inverter supplier. For return shipment and details, contact Danfoss hotline.
1.7.2 Disposal
In case of end of service life, the inverter can be returned to your distributor, to Danfoss directly, or disposed of in the respective country. The shipping to the distributor or Danfoss is paid by the sender. Recycling and disposal of the inverter must be done according to the rules and regulations applicable in the country of disposal. All the inverter packaging material is recyclable.
Introduction
L00410568-02_02 / Rev. date: 2013-12-10 5
1 1
1.8 Overview of Installation Area
PELV (Safe to touch)
1 RS-485 interface
2 Option slot A (can be used for GSM option, optional sensor interface, or PLA option)
3 Ethernet interface
4 Option slot A (can be used for GSM option, optional sensor interface, or PLA option)
Live Part
5 PV connection area
6 Communication board
7AC terminal
Other
8 Security screw position
9PV load switch
10 Security screw position
Illustration 1.3 Overview of Installation Area
Introduction
6 L00410568-02_02 / Rev. date: 2013-12-10
1
2 Installation
2.1 Environment and Clearances
Illustration 2.1 Avoid Constant Stream of Water
Illustration 2.2 Avoid Direct Sunlight
Illustration 2.3 Ensure Adequate Air Flow
Illustration 2.4 Ensure Adequate Air Flow
Illustration 2.5 Mount on Non-flammable Surface
Illustration 2.6 Mount Upright on Vertical Surface. Tilt of up to
10 degrees is permitted
Illustration 2.7 Prevent Dust and Ammonia Gases
NOTICE
When planning the installation site, ensure that inverter product and warning labels remain visible. For details, refer to 5 Technical Data.
Installation
L00410568-02_02 / Rev. date: 2013-12-10 7
2
2
2.2 Mounting the Mounting Plate
Illustration 2.8 Safe Clearances
NOTICE
Ensure 620 mm base clearance for adequate airflow.
Installation
8 L00410568-02_02 / Rev. date: 2013-12-10
2
Illustration 2.9 Mounting Plate
NOTICE
Use of the mounting plate delivered with the inverter is mandatory.
Mount the mounting plate:
Mount in the defined environment.
Use screws and rawl plugs that can safely carry the weight of the inverter.
Ensure that the mounting plate is correctly aligned.
Observe safe clearances when installing one or more inverters, to ensure adequate airflow. Clearances are specified in Illustration 2.8 and the mounting plate label.
Mounting multiple inverters in a single row is recommended. Contact the supplier for guidelines, when mounting inverters in more than one row.
Ensure adequate clearance at the front, for service access to the inverter.
.
Illustration 2.10 Mounting the Mounting Plate
2.3 Mounting the Inverter
CAUTION
For safe handling of the inverter, 2 people must carry the unit, or a suitable transport trolley must be used. Wear safety boots.
Procedure:
1. Lift the inverter. Locate the slots on the side of the mounting plate.
Illustration 2.11 Position the Inverter
Installation
L00410568-02_02 / Rev. date: 2013-12-10 9
2
2
2. On the inverter, position the side screws against the mounting plate slots.
3. Push the inverter as shown so the side screws slide into the 2 lower slots, then the 2 upper slots. See Illustration 2.12 and Illustration 2.13.
Illustration 2.12 Slide into Slots
Illustration 2.13 Detail of Sliding into Slot
4. Check that the 4 side screws sit securely in the mounting plate slots.
5. Release the inverter.
Anti-theft Protection (Optional)
To protect the inverter against theft, fasten as follows:
1. Use 2 security screws, M5 x 8-12 (not supplied).
2. Insert screws through the pre-drilled anti-theft holes (see Illustration 1.3), through the mounting plate to the wall.
3. Tighten screws.
2.4 Removing the Inverter
Procedure:
1. Perform removal in the reverse order of mounting.
2. Lift the inverter. 2 people must carry the unit.
3. With a firm grip at the base of the inverter, lift and slide the inverter out of the mounting plate slots.
4. Lift the inverter free of the mounting plate.
2.5 Access to the Installation Area
CAUTION
Observe ESD safety regulations. Discharge any electro­static charge by touching the grounded enclosure, before handling any electronic component.
Procedure:
1. To open the cover, loosen the 2 lower front screws using a TX 20 screwdriver. The screws cannot fall out.
2. Lift the cover 180 degrees. A magnet holds the cover open.
3. To close the cover, lower it into place and fasten the 2 front screws.
Illustration 2.14 Loosen Front Screws and Lift Cover
Installation
10 L00410568-02_02 / Rev. date: 2013-12-10
2
2.6 AC Grid Connection
Illustration 2.15 Installation Area
Illustration 2.16 AC Cable Wire Strip
On the AC cable, strip insulation on all 5 wires. The PE wire must be longer than the mains and neutral wires. See Illustration 2.16.
Illustration 2.17 AC Connection Area
L1, L2, L3 3 mains wires
NNeutral wire
PE1 Primary protective earth
PE2 Secondary protective earth
1. Verify that the inverter rating matches the grid.
2. Ensure that main circuit breaker is released, and take precautions to prevent reconnection.
3. Open the front cover.
4. Insert the cable through the AC gland to the terminal blocks.
5. Connect the 3 mains wires (L1, L2, L3), the neutral wire (N) and the protective earth wire (PE) to the terminal block with the respective markings.
6. Optional: Make an extra PE connection at the secondary PE earthing points.
7. All wires must be properly fastened with the correct torque. See 5.6 Torque Specifications.
CAUTION
Check that all wiring is correct. Connecting a phase wire to the neutral terminal may permanently damage the inverter.
NOTICE
Tighten all screws and glands thoroughly.
Installation
L00410568-02_02 / Rev. date: 2013-12-10 11
2
2
NOTICE
This product may generate DC current exceeding 6 mA, into the external grounded PE wire. Where a residual current-operated protective (RCD) or monitoring (RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of Type B is allowed on the supply side of this product. When applying an RCD it must have a 300 mA sensitivity to avoid tripping. IT systems are not supported.
NOTICE
For fuse and RCD information, refer to 5 Technical Data.
2.7 RS-485 or Ethernet Connections
Before connecting RS-485 or Ethernet cables, refer to requirements in 5.9 RS-485 and Ethernet Connections.
Procedure:
1. Do not remove the RJ-45 connector.
2. Guide the cables through the base of the inverter via cable glands. See Illustration 2.18.
3. Plug into the RS-485 or Ethernet connector.
4. Fasten cables with cable ties to ensure a durable connection over time. See Illustration 2.19.
Illustration 2.18 Guide Through Cable Glands
Illustration 2.19 Fasten with Cable Ties
NOTICE
Tighten all screws and glands thoroughly.
2.8 Options
To install options, refer to the respective option installation guide.
NOTICE
Tighten all screws and glands thoroughly.
2.9 Closure
1. Close the cover of the inverter installation area. Fasten the 2 front screws.
2. Turn on AC power.
Installation
12 L00410568-02_02 / Rev. date: 2013-12-10
2
2.10 PV Connection
WARNING
PV modules generate voltage when exposed to light. Do NOT connect PV to earth.
Illustration 2.20 Do Not Connect PV to Earth
Use a suitable voltmeter that can measure up to 1000 V DC.
1. Mount Sunclix connectors (not supplied) on the PV cables, according to Illustration 2.21.
2. Verify the polarity and maximum voltage of the PV arrays by measuring the PV open-circuit voltage. See Illustration 2.21.
The PV open-circuit voltage must not exceed 1000 V DC. The inverter is protected against reversed polarity and will not generate power until the polarity is correct. Reversed polarity damages neither the inverter nor the connectors.
Illustration 2.21 Correct Polarity: Mounting Sunclix Connector
on Cable
1. Measure the DC voltage between the positive terminal of the PV array and earth (or the green/ yellow PE cable).
The voltage measured should approximate zero. If the voltage is constant and not zero, there is an insulation failure somewhere in the PV array.
2. Locate and fix the failure before continuing.
3. Repeat this procedure for all arrays. Uneven distri­bution of input power on the PV inputs is permitted, if:
The individual input is not overloaded. The maximum permissible load per input is 8000 W.
The maximum short-circuit current of the PV modules at STC (Standard Test Conditions) does not exceed 13.5 A per input.
Installation
L00410568-02_02 / Rev. date: 2013-12-10 13
2
2
CAUTION
PV installation Unused PV inputs may not be short-circuited.
Illustration 2.22 DC Connection Area
1. On the inverter turn the PV load switch into off position.
2. Connect the PV cables using Sunclix connectors. Ensure correct polarity, see Illustration 2.21.
Attach Sunclix mating part to PV cable.
Connect to each PV input in the PV connection area with a 'click'.
Illustration 2.23 Connect to PV Input
2.10.1 Protection Rating for PV Modules
The inverter must only be operated with PV modules of protection class II, compliant to IEC 61730, application class A. Module voltage rating must be more than 480 V (typical module voltage rating is 1000 V). This does not prevent the use of strings with lower operating voltage. Only connect PV modules to the inverter. Other energy sources are not allowed.
Installation
14 L00410568-02_02 / Rev. date: 2013-12-10
2
3 Initial Setup and Start
3.1 User Interface
The user interface comprises:
Local display. Enables manual setup of the inverter.
Web interface. Enables access to multiple inverters via Ethernet.
Choose an interface to set up and start the inverter, either via
Display
3.2 Display
3.2.1 Initial Setup via Display
or
Web interface
3.3 Web Interface
3.3.4 Web Interface
Do not touch the other interface during the setup and start-up processes.
For access and menu information, refer to the FLX Series User Guide.
3.1.1 Operation Modes
The inverter has 4 operation modes, indicated by LEDs. For more information on the LEDs, refer to the FLX Series User Guide.
Off grid (LEDs off) When no power has been delivered to the AC grid for more than 10 minutes, the inverter disconnects from the grid and shuts down. 'Off grid - standby' is the default night mode. 'Off grid - sleep' is the night mode for lowest energy consumption.
Off grid - standby mode (LEDs off)
The inverter is disconnected from grid. User and communication interfaces remain powered for communication purposes.
Off grid - sleep mode (LEDs off)
The inverter is disconnected from grid. User, communication, and option interfaces are powered down.
Connecting (Green LED flashing) The inverter starts up when the PV input voltage reaches 250 V. The inverter performs a series of internal self-tests, including PV autodetection and measurement of the
resistance between the PV arrays and earth. Meanwhile, it also monitors the grid parameters. When the grid parameters have been within the specifications for the required amount of time (depends on grid code), the inverter starts to energise the grid.
On grid (Green LED on) The inverter is connected to the grid and energises the grid. The inverter disconnects when:
it detects abnormal grid conditions (dependent on grid code), or
an internal event occurs, or
insufficient PV power is available (no power is supplied to the grid for 10 minutes).
The inverter then enters connecting mode or off grid mode.
Fail Safe (Red LED flashing) If the inverter detects an error in its circuits during the self­test (in connecting mode) or during operation, the inverter goes into fail safe mode, disconnecting from grid. The inverter will remain in fail safe mode until power has been absent for a minimum of 10 minutes, or the inverter has been shut down completely (AC+PV).
3.1.2 Security Level
3 predefined security levels filter user access to menus and options.
Security levels:
Level [0]: General access. No password is required.
Level [1]: Installer or service technician. Password access required.
Level [2]: Installer or service technician. Password extended access required.
Throughout the manual, a [0], [1] or [2] inserted after the menu item indicates the minimum security level required for access.
When logged on to the web interface as Admin, access is at security level [0].
Access to levels [1] and [2] requires a service logon, comprising a user ID and a password.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 15
3
3
The service logon provides direct access to a specific security level for the duration of the current day.
Obtain the service logon from Danfoss.
Enter the logon via the display, or the web interface logon dialog.
When the service task is complete, log off at [SetupSecurity].
The inverter automatically logs the user off after 10 minutes of inactivity.
Security levels are similar on the display and the web interface. A security level grants access to all menu items at the same level as well as all menu items of a lower security level.
3.1.3 Preparation for Master Inverter
The master mode feature allows 1 inverter to be appointed as master inverter for the inverter network. The master inverter accesses the other inverters in the network, enabling:
Settings and data replication to the rest of the network, enabling easy commissioning and data management.
Control of power at plant level (control of ancillary services).
Data retrieval from the network, for graphical display on the web interface, upload to a data warehouse, or export to a PC.
Before enabling master mode, ensure that the following requirements are met:
No other master inverters are present in the network.
Ethernet connection from PC to inverter RJ-45 interface, using a patch cable (network cable cat5e, crossed or straight through). See 2.7 RS-485 or Ethernet Connections.
Installed sensor interface option, with sensors installed, when sensor data are required.
Location closest to the router, in a daisy chain network topology.
After enabling master mode, perform a network scan to verify that all follower inverters are connected to the master inverter. To initiate the scan, go to [Setup Inverter detailsMaster mode → Network].
3.1.4 Manual PV Configuration
Set up the inverter for manual PV configuration:
Via the display, security level 1, at [Setup → Setup detailsPV configuration].
Via the web interface, security level 0, at [Inverter level: SetupSetup detailsPV configuration].
When the inverter is set to manual PV configuration, the autodetection is subsequently overridden.
To set the configuration manually via the display:
1. Turn on AC to start the inverter.
2. Obtain the installer password from the distributor. Go to [Setup → Security → Password], and enter the password.
3.
Press [Back]. Use the arrows to navigate to [Setup Setup detailsPV configuration].
4.
Select manual PV configuration mode, at: [Setup Setup detailsPV configurationMode: Manual].
5. Set up the PV input configuration to match the wiring, at: [Setup Setup details PV configu­ration].
PV input 1: Individual, Parallel or Off
PV input 2: Individual, Parallel or Off
PV input 3: Individual, Parallel or Off
3.2 Display
NOTICE
The display activates up to 10 seconds after power up.
The integrated display on the inverter front gives the user access to information about the PV system and the inverter.
The display has 2 modes:
1.
Normal: The display is in use.
2.
Power saving: After 10 minutes of display inactivity the back light of the display turns off to save power. Reactivate the display by pressing any key.
Initial Setup and Start
16 L00410568-02_02 / Rev. date: 2013-12-10
3
Illustration 3.1 Overview of Display Buttons and Functionality
Key Function LED
F1
View 1/View 2 - Screen
When keys F1-F4 are
selected, the LED above
the key will light up
F2
Status Menu
F3
Production Log Menu
F4
Setup Menu
Home
Return to View Screen
OK
Enter/select
Arrow up
A step up/increase value
Arrow
Down
A step down/decrease
value
Arrow Right
Moves cursor right
Arrow Left
Moves cursor left
Back
Return/de-select
On - Green
LED
On/flashing = On grid/
Connecting
Alarm - Red
LED
Flashing = Fail safe
The inverter is
configured as master.
This icon appears in the
top right corner.
The inverter is a
follower, connected to a
master. This icon
appears in the top right
corner.
Table 3.1 Overview of Display Buttons and Functionality
NOTICE
The contrast level of the display can be altered by pressing the arrow up/down button while holding down the F1 button.
The menu structure is divided into 4 main sections:
1.
View - presents a short list of information, read only.
2.
Status - shows inverter parameter readings, read only.
3.
Log - shows logged data.
4.
Setup - shows configurable parameters, read/ write.
See the following sections for more detailed information.
3.2.1 Initial Setup via Display
The inverter is shipped with a predefined set of settings for different grids. All grid-specific limits are stored in the inverter and must be selected at installation. It is always possible to see the applied grid limits in the display. After installation, check all cables and then close the inverter. Turn on AC at the mains switch. IP address can be found in the display during commis­sioning.
When prompted by the display select language. This selection has no influence on the operating parameters of the inverter and is not a grid code selection.
Illustration 3.2 Select Language
The language is set to English at initial start-up. To change this setting press the [OK] button. Press [
] to scroll down
through the languages. Select language by pressing [OK].
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 17
3
3
NOTICE
To use the default language (English) simply press the [OK] button twice to select and accept.
Illustration 3.3 Master Mode
To enable master mode go to the Inverter details menu [SetupInverter detailsMaster mode] and set master mode to Enabled.
Illustration 3.4 Set Time
Set time as prompted by the display. Press [OK] to select number. Press [
] to scroll up through the numbers. Select by pressing [OK]. The clock is 24-hour format. The inverter accounts for daylight saving automatically.
NOTICE
Set the time and date accurately. The inverter uses this information for logging. If an incorrect time/date is accidentally set, correct it immediately in the set date and time menu [SetupInverter detailsSet date and time].
Illustration 3.5 Set Date
Set date as prompted by the display. Press [OK] to select. Press [
] to scroll up through the numbers. Select by
pressing [OK].
Illustration 3.6 Installed PV Power
Enter the amount of installed PV power for each of the PV inputs. When a group of PV inputs are connected in
Initial Setup and Start
18 L00410568-02_02 / Rev. date: 2013-12-10
3
parallel, enter average installed PV power for each PV input, as shown in the examples.
PV String Configuration
Enter this value for
“Installed PV power”
Example 1: PV1, PV2 and PV3 are each set
to individual mode.
Nominal PV power installed:
PV 1: 6000 W PV 1: 6000 W
PV 2: 6000 W PV 2: 6000 W
PV 3: 3000 W PV 3: 3000 W
Example 2: PV1 and PV2 are set to
parallel mode and have a total of 10 kW
PV power installed. PV3 is set to
individual mode and has nominal 4 kW
PV power.
PV 1: 5000 W
PV 2: 5000 W
PV 3: 4000 W
Example 3: PV1 and PV2 are set to
parallel mode and have a total of 11 kW
PV power installed. PV3 is set to [Off] and has no PV installed.
PV 1: 5500 W
PV 2: 5500 W
PV 3: 0 W
Table 3.2 Examples of Installed PV Power
The display will now show ‘Select country’. The setting is ‘undefined’ at initial start-up. Press [] to scroll down through the list of settings. To select the desired setting, press [OK].
Illustration 3.7 Select Country
Illustration 3.8 Select Grid Code
The display will now show ‘Select grid code’. The grid code is set to ‘undefined’ at initial start-up. To select the grid code, press [OK]. Press [
] to scroll down through the list. Select the grid code for the installation by pressing [OK]. It is very important to choose the correct grid code.
Illustration 3.9 Confirm Grid Code Selection
To confirm, select the grid code again and press [OK]. The settings for the chosen grid code have now been activated.
WARNING
Correct selection of grid code is essential to comply with local and national standards.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 19
3
3
NOTICE
If the 2 grid code selections do not match, they will be cancelled and it will be necessary to repeat this step. If an incorrect grid code is accidentally accepted at the first selection, simply accept the “Grid: Undefined” in the confirm grid code screen. This cancels the grid code selection and enables a new selection.
NOTICE
Access on security level 2 is granted for 5 hours after setup completion. Logout must be performed before leaving the site. If an incorrect grid code is selected twice, it can be changed within the 5 hours. Access on a higher level is possible by locking the configuration and logging on again using a 24-hour password. Only authorised personnel is allowed to configure the inverter. Changes will be logged and Danfoss accepts no liability for damage caused by changing the inverter configuration.
3.2.2 Turn PV Load Switch On
Illustration 3.10 Turn the PV Load Switch On
3.2.3 Start-up
The inverter starts automatically if sufficient solar irradiation is available. The start-up will take a few minutes. During this period, the inverter performs a self-test.
NOTICE
The inverter is protected against reversed polarity. The inverter does not generate power until any reversed polarity is corrected.
3.2.4 Autotest Procedure
For certain grid codes, an automatic test of the inverter can be initialised by activating the inverter autotest procedure:
Via the display, go to [Setup Autotest] and press [OK].
3.3 Web Interface
These instructions describe the web interface, which facilitates remote access to the inverter. Refer to the download area at www.danfoss.com/solar for the newest instructions.
For all text entries, the software supports characters compatible with Unicode.
For inverter name, no spaces are permitted.
For plant, group and inverter name, only the following characters are supported:
Letters abcdefghijklmnopqrstuvwxyz
Capital letters ABCDEFGHIJKLMNOPQRSTUVWXYZ
Numbers 0123456789
Special
characters
- _.
3.3.1 Prepare for Setup
Ensure that the following items are ready before commencing setup:
Master inverter is designated and prepared, see
3.1.3 Preparation for Master Inverter.
Ethernet connection from PC to inverter is established, see also 2.7 RS-485 or Ethernet Connections.
3.3.2 Initial Setup via Web Interface
CAUTION
Change the Web Server logon and password of the master inverter immediately for optimal security when connecting to the Internet. To change the password go to [SetupWeb ServerAdmin].
Setup Sequence
1. Ensure that the master inverter is designated and prepared, see 3.1.3 Preparation for Master Inverter.
2. On the PC, wait until Windows reports limited connectivity (if no DHCP is present). Open the Internet browser and ensure that pop-ups are enabled.
3. Type 1 of the following options in the address field:
Initial Setup and Start
20 L00410568-02_02 / Rev. date: 2013-12-10
3
For Windows XP and older Windows versions: http://invertername, where 'invertername' is the final 10 digits of the serial number.
For Windows 7 and newer Windows versions: http://IP address. The IP address can be found in the display.
It is not possible to use the installation wizard with Windows 7 and 8.
Find the serial number marked on the product label on the side of the inverter enclosure. See Illustration 1.2.
1. The web interface logon dialog opens.
2. Type 'admin' in the user and password fields, and click ‘Log in’.
3. At initial logon the inverter runs a setup wizard.
3.3.3 Setup Wizard
Step 1 of 8: Display language
Select display language.
The default language is English.
NOTICE
This selection defines the language in the display, not the grid code.
Illustration 3.11 Step 1 of 8: Display Language
To change the language setting later, go to [Setup Setup Details].
Step 2 of 8: Master setting
To set up a master inverter, click on ‘Set as master’.
A scan runs to identify inverters in the network.
A pop-up window shows the inverters successfully identified.
Click [OK] to confirm that the correct number of inverters has been found.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 21
3
3
Illustration 3.12 Step 2 of 8: Master Setting
To change this setting later, go to [Inverter level: Setup Inverter details].
Step 3 of 8: Time and date
Enter:
Time in 24-hour format
Date
Time zone
Accuracy is important, because date and time are used for logging purposes. Adjustment for daylight savings is automatic.
Illustration 3.13 Step 3 of 8: Time and Date
To change these settings later, go to [Inverter level: Setup Set date and time].
Step 4 of 8: Installed power
For each PV input, enter installed PV power.
The installed PV power values are used to calculate performance ratio. For more information refer to the FLX Series Design Guide.
Initial Setup and Start
22 L00410568-02_02 / Rev. date: 2013-12-10
3
CAUTION
Incorrect setting can have serious consequences for production efficiency.
Illustration 3.14 Step 4 of 8: Installed Power
To change the installed power, go to [Inverter level: Setup Calibration, PV Array].
Step 5 of 8: Country of Installation
Select the setting to match the location of the installation.
CAUTION
Correct selection is essential to comply with local and national standards.
Illustration 3.15 Step 5 of 8: Country of Installation
Step 6 of 8: Grid code
Select the grid code to match the location of the installation.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 23
3
3
The default setting is [undefined].
Select the grid code again, to confirm.
The setting is activated immediately.
CAUTION
Correct selection is essential to comply with local and national standards.
Illustration 3.16 Step 6 of 8: Grid Code
NOTICE
If the initial and confirmation settings are different,
grid code selection is cancelled, and
the wizard recommences step 5.
If initial and confirmation settings match, but are incorrect, contact service.
Step 7 of 8: Replication
This step is available for a master inverter with followers connected. To replicate the settings from steps 1–6 to other inverters in the same network:
Select inverters.
Click [Replicate].
Initial Setup and Start
24 L00410568-02_02 / Rev. date: 2013-12-10
3
NOTICE
When the PV configuration, installed PV power and PV array area of follower inverters in the network differ from that of the master, do not replicate. Set up the follower inverters individually.
Illustration 3.17 Step 7 of 8: Replication
Step 8 of 8: Inverter start-up
The wizard displays an overview of the setup configuration. Click on [Finish] to start up the inverter. Start-up will commence when solar irradiation is sufficient. The start-up sequence, including self-test, takes a few minutes.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 25
3
3
Illustration 3.18 Step 8 of 8: Inverter start-up
To change the setup later, access the inverter via the web interface or the display, at inverter level.
To change the name of the inverter, go to [Inverter level: Setup Inverter details].
To enable master mode, go to [Inverter level: Setup Inverter details].
Initial Setup and Start
26 L00410568-02_02 / Rev. date: 2013-12-10
3
3.3.4 Web Interface
The web interface overview is structured as follows.
Illustration 3.19 Overview
1.
Plant name: Displays the current plant name:
Click on the plant name to display the plant view.
Change the plant name at [Setup Plant details].
2.
Group menu: Displays groups of inverters:
Inverters join group 1 by default.
Click on a group name to display the group view, and a list of inverters in the group.
Change the group name via [Setup Inverter details] in the inverter view.
3.
Group members: Displays the inverter names in the group currently selected. The default inverter name is based on the serial number.
Click on an inverter name to display the inverter view.
Change the name of the inverter via [SetupInverter details] in the inverter view.
4.
Main menu: This menu corresponds to the inverter display main menu.
5.
Submenu: The submenu corresponds to the main menu item currently selected. All submenu items belonging to a particular main menu item are displayed here.
6.
Content area: The main menu and submenus of the web interface are identical to the menus in the inverter display. The submenu content displayed here corresponds to the submenu selected: [Overview]. On some pages, a horizontal menu is provided for improved readability.
7.
Footer: Options in the footer bar:
Language: Opens a pop-up window.
Click on the country flag to change the language of the web interface to the desired language for the active session.
Contact: Opens a pop-up window,
which displays Danfoss contact information.
Logout: Opens the login/logout dialog
box.
Security level: Displays the current
security level as explained in the section Security Levels.
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 27
3
3
NOTICE
The content of the main menu changes depending on which view is currently selected: the plant, a group of inverters, or an individual inverter.
3.3.5 Plant, Group and Inverter Views
The overview screens for plant view, group view, and inverter view display the same overall status information.
Illustration 3.20 Overall Plant Status
Initial Setup and Start
28 L00410568-02_02 / Rev. date: 2013-12-10
3
Item Unit View Description
Plant and
Group
Inverter
Overall plant status - x
Red: Plant PR <50%, or:
Any inverter in the network
- in fail safe mode, or
- missing from the scan list, no contact with the master
Yellow: Any inverter in the network
- with PR <70%, or
- in Connecting or Off grid mode
Green: Plant PR ≥70%, and
- all inverters with PR ≥70%, and
- all inverters in On grid mode
x
Red: Inverter PR <50%, or inverter has an error
Yellow: Inverter PR between 51% and 70%, or inverter in Connecting
mode
Green: No errors, and
- inverter PR ≥70%, and
- inverter in On grid mode
Current production kW x x Real time energy production level
Yield today kWh x x Cumulative yield for the day
Total revenue Euro x x Cumulative revenue earned since initial startup
Total CO
2
saving kg x x Cumulative CO2 saved since initial startup
Performance ratio % x x Real time performance ratio
Total yield kWh x x Cumulative yield since initial startup
Power limit adjustment % x Maximum power limit as % of nominal inverter AC output rating
Table 3.3 Information Displayed in Plant View, Overview Screen
NOTICE
To calculate performance ratio PR, an irradiation sensor is required, see [SetupCalibration].
3.3.6 Autotest Procedure
For certain grid codes, an automatic test of the inverter can be initialised by activating the inverter autotest procedure:
Via the web interface, go to [Inverter level: Setup Setup details Autotest] and click on [Start Test].
Initial Setup and Start
L00410568-02_02 / Rev. date: 2013-12-10 29
3
3
4Service
4.1 Troubleshooting
This guide provides tables showing messages appearing in the inverter display, known as events. The tables contain descriptions as well as which actions to take, when an event arises. For the full event list, refer to the FLX Series
User Guide.
To view events, go to the Log menu and enter the Eventlog menu. The latest event registered by the inverter, as well as a list of the 20 most recent events, is shown
here. When the inverter enters the On grid mode, the most recent event is cleared and is shown as 0. The event code is made up of 2 elements: the group classifier and the event ID. The group classifier describes the general type of the event, while the event ID is used to identify the specific event. Table 4.1 is an overview of how the tables of inverter events are constructed and how to use them.
Event Type
-
ID Status message Description Action DNO Hotline PV
201 Tpower_high. The internal temperature of the
inverter is too high.
Check the inverter is not covered and that the
ventilation duct is not blocked. If not, call installer.
-x -
Table 4.1 How to Read the Event Tables
Event Type
Indicates whether the event relates to grid, PV, internal or fail safe issues.
ID
The specific event ID.
Display
Text shown in display.
Description
Description of the event.
Action
Description of which action to take prior to contacting any other parties.
DNO
If the prescribed action has not identified the malfunction, contact the DNO for further assistance.
Hotline
If the prescribed action has not identified the malfunction, contact the inverter hotline for further assistance.
PV
If the prescribed action has not identified the malfunction, contact the PV supplier for further assistance.
Grid-related Events
ID Status
message
Description Action DNO Hotline PV
1–6 Grid voltage too low. Call the installer and inform about the grid-phase voltage.
Check voltage and AC installation, if the voltage is zero
check the fuses.
x- -
7–9 Grid voltage average over 10
minutes too high.
Call the installer and inform about the grid-phase voltage.
Check that the installation is correct according to the instal-
lation guide. If so, then increase the mean voltage limit according to section Functional Safety.
x- -
10–15 Grid voltage too high.
Call the installer and inform about the grid-phase voltage.
Check voltage and AC installation.
x- -
16–18 The inverter has detected a
voltage peak on the grid.
x- -
19–24 Grid frequency too low or too
high.
Call the installer and inform about the grid frequency.. x - -
25–27 Loss of mains, Phase-to-phase
voltages too low.
Call the installer and inform about the voltage on all three
phases.
Check the phase-to-phase voltages and the AC installation.
x- -
28–30 Loss of mains, ROCOF out of
range.
If the event reoccurs several times each day, contact the
DNO.
x- -
31–33 DC grid current too high. For occurrence several times daily, contact installer.
Installer: Perform on-site grid analysis.
-x -
Service
30 L00410568-02_02 / Rev. date: 2013-12-10
4
ID Status
message
Description Action DNO Hotline PV
34–37 Residual Current Monitoring Unit
(RCMU) has measured an
excessive current.
Turn both DC and AC off and wait until the display turns
off. Then turn on DC and AC and observe if the event
reoccurs. If the event reoccurs, call the installer.
Installer: Visual inspection of all PV cables and modules.
-x -
40 AC grid notOKThe AC grid has been out of
range for more than 10 minutes
(frequency and/or voltage).
Call the installer and inform about Frequency, SW version
and Grid code setting
Installer: Check the AC installation.
x- -
41–43 The inverter has detected that
grid voltage was below a certain
level.
If this event is reported several times each day, contact the
installer.
Installer: Perform on-site grid analysis.
47 PLA below
threshold
The inverter disconnects from
grid if PLA is below 3% of
nominal power.
Contact the DNO and obtain status on active power
reduction (PLA).
x- -
48–53 Grid
frequency
too low or
too high
Call the installer and inform about the grid frequency.
Check the AC installation.
x- -
54–56 DC grid current too high (stage
2).
For occurrence several times daily, contact installer.
Installer: Perform on-site grid analysis.
x- -
246 A grid event was detected and
inverter was stopped by the
redundant safety circuit.
A grid event was detected and inverter was stopped by the
redundant safety circuit. Check the event log. If the majority
of entries are of type 246, call the service department. Otherwise wait 24 hours and check again.
-x -
Table 4.2 Grid-related Events
PV-related Events
ID Status
message
Description Action DNO Hotline PV
100-102 PV negative Input current is negative, polarity
incorrect.
Call the installer.
Installer: Check polarity, if correct, call service.
-- x
103-105 PV current is
too high/ waiting.
Too many PV modules connected in
parallel. Should only appear on newly installed systems.
Call the installer.
Installer: Check no. of strings in parallel and current ratings. Has the current limit been
exceeded? Has the inverter derated on PV
current? Reconnect strings in parallel, possibly install a second inverter.
-x x
112-114 PV config fault Call the installer.
Installer: Call service.
-- x
115 PV ISO too low The resistance between ground and
PV is too low for the inverter to start
up. This will force the inverter to make
a new measurement after 10 minutes
have passed.
Make a visual inspection of all PV cables and
modules for correct installation according to
the installation guide. The event could indicate
that the PE connection is missing.
-x x
116-118 PV wrong polarity Call the installer.
Installer: Call service.
-x x
121-123,
125
PV ISO low PV1, PV2, PV3, multiple
(related to 115)
Call the installer.
Installer: Call service.
-x x
258 PV voltage too
high/waiting
PV voltage is too high. Check that installation and layout correspond
to recommendations in the manuals.
-x x
Table 4.3 PV-related Events
Service
L00410568-02_02 / Rev. date: 2013-12-10 31
4
4
Internal Events
ID Status
message
Description Action DNO Hotline PV
201–208 The internal temperature of the
inverter is too high.
Check the inverter is not covered and that the
ventilation duct is not blocked. If not, call the
installer.
-x -
209, 210 Voltage on DC bus is too high. Reset the inverter by disconnecting DC and AC,
using the switches. If the event is repeated, call
the installer. Installer: Check the maximum PV voltage using the display
to see if it is above the limits.
-x -
211 Fan rpm low Fan speed is too low. Is the inverter fan blocked?
Yes: Clean the fan, No: Call the installer.
-x -
212 DC bus
balance
timeout
Inverter unable to balance DC bus. Call the installer.
Installer: Call service.
-x -
213–215 Internal error Voltage measured
before and after the relay differs by
more than 20 V.
Call the installer.
Installer: Call service.
-x -
216–221 Current measured on AC side is too
high.
Call the installer.
Installer: Call service.
-x -
224 RCMU over
range
A wire is broken in the RCMU. Call the installer.
Installer: If self-test does not complete
successfully, call service partner.
-x -
225–240 Failure in Memory/ EEPROM. Restart the inverter. If event persists, call the
installer. Installer: Call service.
-x -
241, 242,
249
Internal communication error. - x -
243, 244 Internal error. -x -
247 FSP plausi-
bility fault
A plausibility fault has occurred in
the functional safety processor.
Check event log for other grid events (1-55) and
follow the instructions for these events. If the
event persists, call the installer.
-x -
248, 251 Self test failed
FSP fail safe
The self-test has failed. - x -
252-254 Current measured on AC side is too
high.
Call the installer.
Installer: Call service.
-x -
255–257 Islanding protection trip. Call the installer.
Installer: Call service.
-x -
260 The resistance between ground and
PV is too low for the inverter to start
up. This will force the inverter to
make a new measurement after 10
minutes have passed.
Call the installer.
Installer: Call service.
-x -
261-262 PV current measurements failed. Call the installer.
Installer: Call service.
-x x
Table 4.4 Internal Events
Service
32 L00410568-02_02 / Rev. date: 2013-12-10
4
Events Caused by the Self-test
ID Description Action DNO Hotline PV
264-271 Measurement circuit test failed. Restart the inverter. If event persists, call the installer.
Installer: Call service.
-x -
352 RCMU self-test failed. Call the installer.
Installer: Call service.
-x -
353 Current sensor test failed. -x -
356-363 Transistor and relay test failed, or inverter
relay has failed (contact assumed welded).
-x -
364 Neutral connection is damaged or missing. Call the installer. Installer: Check AC installation for failures
on neutral connection. Call service.
-x -
365 Earth wire failed. Call the installer.
Installer: Call service.
-x -
Table 4.5 Events Caused by the Self-test
4.2 Maintenance
Normally, the inverter needs no maintenance or calibration.
Ensure that the heat sink at the rear of the inverter is not covered.
Clean the contacts of the PV load switch once per year. Clean by cycling the switch to on and off positions 10 times. The PV load switch is located at the base of the inverter.
For correct operation and long service life, ensure free air circulation
-
around the heat sink at the top and side of the inverter where the air exhausts, and
-
to the fan at the inverter base.
To clear obstructions, clean using pressurised air, a soft cloth, or a brush.
WARNING
Temperature of the heat sink can exceed 70 °C.
Service
L00410568-02_02 / Rev. date: 2013-12-10 33
4
4
5 Technical Data
5.1 Specifications
5.1.1 Inverter Specifications
Nomen­clature
Parameter
FLX series
56789
AC
|S| Rated apparent
power
5 kVA 6 kVA 7 kVA 8 kVA 9 kVA
P
ac,r
Rated active power
1)
5 kW 6 kW 7 kW 8 kW 9 kW
Active power at
cos(phi)=0.95
4.75 kW 5.7 kW 6.65 kW 7.6 kW 8.55 kW
Active power at
cos(phi)=0.90
4.5 kW 5.4 kW 6.3 kW 7.2 kW 8.1 kW
Reactive power
range
0 - 3.0 kVAr 0 - 3.6 kVAr 0 - 4.2 kVAr 0 - 4.8 kVAr 0 - 5.4 kVAr
V
ac,r
Nominal AC voltage
(AC voltage range)
3P+N+PE - 230/400 V (+/- 20 %)
Rated current AC 3 x 7.2 A 3 x 8.7 A 3 x 10.1 A 3 x 11.6 A 3 x 13 A
I
acmax
Max. current AC
3 x 7.5 A 3 x 9.0 A 3 x 10.6 A 3 x 12.1 A 3 x 13.6 A
AC current distortion
(THD at nominal output power, %)
-----
Inrush current 9.5 A / 10 ms
cosphi
ac,r
Power factor at
100% load
>0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
Standby
consumption
2.7 W
f
r
Nominal grid
frequency (range)
50 (
±
5 Hz)
DC
Max. PV input power
per MPPT
5.2 kW 6.2 kW 7.2 kW 8 kW
Nominal power DC 5.2 kW 6.2 kW 7.2 kW 8.3 kW 9.3 kW
V
dc,r
Nominal voltage DC
715 V
V
dcmin
/
V
mppmin
-
V
mppmax
MPP voltage - active
tracking
2)
/ rated
power
3)
220/250 - 800 V 220/260 - 800 V 220/300 - 800 V 220/345-800 V 220/390 - 800 V
MPP efficiency, static 99.9%
MPP efficiency,
dynamic
99.7%
V
dcmax
Max. DC voltage
1000 V
V
dcstart
Turn on voltage DC
250 V
V
dcmin
Turn off voltage DC
220 V
I
dcmax
Max. MPP current
12 A per PV input
Technical Data
34 L00410568-02_02 / Rev. date: 2013-12-10
5
Nomen­clature
Parameter
FLX series
56789
Max. short-circuit
current DC (at STC) 13.5 A per PV input
Min. on grid power 20 W
Efficiency
Max. efficiency - 97.8% - 97.9% -
Euro efficiency, V at
dc,r
- 96.5% - 97.0% -
Other
Dimensions (H, W,
D), inverter / incl. packaging
667 x 500 x 233 mm / 774 x 570 x 356 mm
Mounting
recommendation
Mounting plate
Weight, inverter /
incl. packaging
38 kg / 44 kg
Acoustic noise level
4
-
MPP trackers 2
Operation
temperature range
-25..60 °C
Nom. temperature
range
-25..45 °C
Storage temperature
-25..60 °C
Overload operation Change of operating point
Overvoltage
categories
Grid: OVC III
PV: OVC II
Table 5.1 Specifications
1)
At rated grid voltage (V
ac,r
), Cos(phi)=1.
2)
To utilise the full range, asymmetrical layouts must be considered
including start-up voltage for at least 1 string. Achieving nominal
power will depend on configuration.
3)
At symmetric input configuration.
4)
SPL (Sound Pressure Level) at 1 m under normal operating
conditions. Measured at 25 °C.
Nomen­clature
Parameter
FLX series
10 12.5 15 17
AC
|S| Rated apparent
power
10 kVA 12.5 kVA 15 kVA 17 kVA
P
ac,r
Rated active power
1)
10 kW 12.5 kW 15 kW 17k W
Active power at
cos(phi)=0.95
9.5 kW 11.9 kW 14.3 kW 16.2 kW
Active power at
cos(phi)=0.90
9.0 kW 11.3 kW 13.5 kW 15.3 kW
Reactive power
range
0 - 6.0 kVAr 0-7.5 kVAr 0-9.0 kVAr 0-10.2 kVAr
V
ac,r
Nominal AC voltage
(AC voltage range)
3P+N+PE - 230/400 V (+/- 20 %)
Rated current AC 3 x 14.5 A 3 x 18.2 A 3 x 21.7 A 3 x 24.7 A
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 35
5
5
Nomen­clature
Parameter
FLX series
10 12.5 15 17
I
acmax
Max. current AC
3 x 15.1 A 3 x 18.8 A 3 x 22.6 A 3 x 25.6 A
AC current distortion
(THD at nominal
output power, %)
-<2 %
Inrush current 0.5 A / 10 ms
cosphi
ac,r
Power factor at
100% load
>0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
Standby
consumption
2.7 W
f
r
Nominal grid
frequency (range)
50 (
±
5 Hz)
DC
Max. PV input power
per MPPT
8 kW
Nominal power DC 10.4 kW 12.9 kW 15.5 kW 17.6 kW
V
dc,r
Nominal voltage DC
715 V
V
dcmin
/
V
mppmin
-
V
mppmax
MPP voltage - active
tracking
2)
/ rated
power
3)
220/430 - 800 V 220/360 - 800 V 220/430 - 800 V 220/485 - 800 V
MPP efficiency, static 99.9%
MPP efficiency,
dynamic
99.7%
V
dcmax
Max. DC voltage
1000 V
V
dcstart
Turn on voltage DC
250 V
V
dcmin
Turn off voltage DC
220 V
I
dcmax
Max. MPP current
12 A per PV input
Max. short-circuit
current DC (at STC) 13.5 A per PV input
Min. on grid power 20 W
Efficiency
Max. efficiency 98%
Euro efficiency, V at
dc,r
97.0% 97.3% 97.4% 97.4%
Other
Dimensions (H, W,
D), inverter / incl.
packaging
667 x 500 x 233 mm / 774 x 570 x 356 mm
Mounting
recommendation
Mounting plate
Weight, inverter /
incl. packaging
38 kg / 44 kg 39 kg / 45 kg
Acoustic noise level
4
-55 dB(A)
MPP trackers 2 3
Operation
temperature range
-25..60 °C
Nom. temperature
range
-25..45 °C
Technical Data
36 L00410568-02_02 / Rev. date: 2013-12-10
5
Nomen­clature
Parameter
FLX series
10 12.5 15 17
Storage temperature
-25..60 °C
Overload operation Change of operating point
Overvoltage
categories
Grid: OVC III
PV: OVC II
Table 5.2 Specifications
1)
At rated grid voltage (V
ac,r
), Cos(phi)=1.
2)
To utilise the full range, asymmetrical layouts must be considered
including start-up voltage for at least 1 string. Achieving nominal
power will depend on configuration.
3)
At symmetric input configuration.
4)
SPL (Sound Pressure Level) at 1 m under normal operating
conditions. Measured at 25 °C.
Parameter FLX series
Connector type Sunclix
Parallel mode Yes
Interface Ethernet (Web interface), RS-485
Options GSM Option Kit, Sensor Interface Option, PLA Option
PV Sweep Yes
Overload operation Change of operating point
Grid supportive functionality Fault ride-through
Active power control
5)
Integrated, or via external device
Reactive power control
5)
Yes
DC short-circuit protection Yes
Table 5.3 Inverter Features and Functionalities
5)
Remote control via external device.
Parameter FLX series
Electrical
Safety (protective class) Class I (grounded)
PELV on the communi-
cation and control card
Class II
Overvoltage categories Grid: OVC III
PV: OVC II
Functional
Islanding detection - loss
of mains
Disconnection
3-phase monitoring
ROCOF
Voltage magnitude Disconnection, included
Frequency Disconnection, included
DC content of AC current Disconnection, included
Insulation resistance Connection prevented, included
RCMU - Type B Disconnection, included
Table 5.4 Safety Specifications
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 37
5
5
5.2 Derating Limits
To ensure that the inverters can produce the rated power, measurement inaccuracies are taken into account when enforcing the derating limits stated in Table 5.5.
(Limit = rated value + tolerance).
FLX series
5 6 7 8 9 10 12.5 15 17
Grid current, per phase 7.5 A 9.0 A 10.6 A 12.1 A 13.6 A 15.1 A 18.8 A 22.6 A 25.6 A
Grid power, total 5150 W 6180 W 7210 W 8240 W 9270 W 10300 W 12875 W 15450 W 17510 W
Table 5.5 Derating Limits
5.3 Conformity
FLX series
International
Standards
5 6 7 8 9 10 12.5 15 17
Directive LVD 2006/95/EC
Directive EMC 2004/108/EC
Safety IEC 62109-1/IEC 62109-2
Integrated PV load switch VDE 0100-712
Functional Safety IEC 62109-2
EMC immunity
EN 61000-6-1
EN 61000-6-2
EMC emission
EN 61000-6-3
EN 61000-6-4
Utility interference EN 61000-3-2/-3 EN 61000-3-11/-12
CE Yes
Utility characteristics
IEC 61727
EN 50160
S0 Energy Meter (option) EN62053-31 Annex D
Table 5.6 International Standards Compliance
Technical Data
38 L00410568-02_02 / Rev. date: 2013-12-10
5
5.4 Installation Conditions
Parameter Specification
Temperature
25 °C - +60 °C (for temperature derating see the FLX Series Design Guide.)
Relative humidity 95 % (non-condensing)
Pollution degree PD2
Environmental class according to IEC IEC60721-3-3
3K6/3B3/3S3/3M2
Air quality - general ISA S71.04-1985
Level G2 (at 75% RH)
Air quality - coastal, heavy industrial and agricultural zones Must be measured and classified acc. to ISA S71.04-1985
Vibration 1G
Observe product ingress protection class IP65
Max. operating altitude 2000 m above sea level.
PELV protection is effective up to 2000 m above sea level only.
Installation Avoid constant stream of water.
Avoid direct sunlight.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
The FLX inverter is an outdoor unit.
Table 5.7 Conditions for Installation
Parameter Condition Specification
Mounting plate Hole diameter 30 x 9 mm
Alignment
Perpendicular
±
5° all angles
Table 5.8 Mounting Plate Specifications
5.4.1 France UTE Requirements
NOTICE
In France, observe the UTE C 15-712-1 and NF C 15–100 requirements.
For installation in France, apply warning label to front of inverter.
Illustration 5.1 Warning Label
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 39
5
5
5.5 Cable Specifications
NOTICE
Avoid power loss in cables greater than 1% of the nominal inverter rating by following the values stated in the tables and illustrations.
NOTICE
Table states only cable lengths less than 100 m.
Specification FLX series
AC cable maximum
length [m]
AC cable size 5 6 7 8 9 10 12.5 15 17
2.5 mm
2
43 m 36 m 31 m 27 m 24 m 21 m
1) 1) 1)
4 mm
2
69 m 57 m 49 m 43 m 38 m 34 m 27 m
2) 2)
6 mm
2
86 m 74 m 64 m 57 m 52 m 41 m 34 m 30 m
10 mm
2
95 m 86 m 69 m 57 m 51 m
16 mm
2
92 m 81 m
AC cable type 5-wire copper cable
AC cable outer diameter 18-25 mm
AC cable insulation strip Strip 16 mm length of insulation from all 5 wires
PE cable diameter Equal to or greater than diameter of AC phase cables
Table 5.9 AC Cable Specifications
1)
Using cable with a diameter less than 4 mm2 is not recommended.
2)
Using cable with a diameter less than 6 mm2 is not recommended.
Specification FLX series
DC cable type
Min. 1000 V, 13.5 A
DC cable length
DC cable size 4 mm
2
- 4.8 Ω /km
< 200 m*
DC cable size 6 mm
2
- 3.4 Ω /km
200-300 m*
Mating connector Sunclix PV-CM-S 2,5-6(+) / PV-CM-S 2,5-6(-)
Table 5.10 DC Cable Specifications
* The distance between inverter and PV array and back, plus the
cumulative length of the cables used for PV array installation.
Consider also the following when choosing cable type and cross-sectional area:
Ambient temperature
Layout type (inside wall, under ground, free air etc.)
UV resistance
Technical Data
40 L00410568-02_02 / Rev. date: 2013-12-10
5
Illustration 5.2 FLX Series 5, Cable Losses [%] versus Cable
Length [m]
Illustration 5.3 FLX Series 6, Cable Losses [%] versus Cable
Length [m]
Illustration 5.4 FLX Series 7, Cable Losses [%] versus Cable
Length [m]
Illustration 5.5 FLX Series 8, Cable Losses [%] versus Cable
Length [m]
Illustration 5.6 FLX Series 9, Cable Losses [%] versus Cable
Length [m]
Illustration 5.7 FLX Series 10, Cable Losses [%] versus Cable
Length [m]
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 41
5
5
Illustration 5.8 FLX Series 12.5, Cable Losses [%] versus Cable
Length [m]
Illustration 5.9 FLX Series 15, Cable Losses [%] versus Cable
Length [m]
Illustration 5.10 FLX Series 17, Cable Losses [%] versus Cable
Length [m]
5.6 Torque Specifications
Illustration 5.11 Overview of Inverter with Torque Indications
1
Parameter Tool Tightening Torque
1M16 cable gland
body
Wrench 19 mm 3.75 Nm
M16 cable gland,
compression nut
Wrench 19 mm 2.5 Nm
2M25 cable gland
body
Wrench 27 mm 7.5 Nm
M25 cable gland,
compression nut
Wrench 27 mm 5.0 Nm
3 Front screw Torx TX 20 1.5 Nm
Table 5.11 Nm Specifications 1
Technical Data
42 L00410568-02_02 / Rev. date: 2013-12-10
5
Illustration 5.12 Overview of Inverter with Torque Indications
2
Parameter Tool Tightening Torque
1M32 cable gland
body
Wrench 42 mm 7.5 Nm
2M32 cable gland,
compression nut
Wrench 42 mm 5.0 Nm
3Terminals on AC
terminal block
Pozidriv PZ2 or
Straight slot 1.0 x
5.5 mm
2.0 - 4.0 Nm
4 PE Torx TX 20 or
Straight slot 1.0 x
5.5 mm
2.2 Nm
Table 5.12 Nm Specifications 2
5.7 Mains Circuit Specifications
FLX series
5 6 7 8 9 10 12.5 15 17
Maximum inverter current, I
acmax
7.5 A 9 A 10.6 A 12.1 A 13.6 A 15.1 A 18.8 A 22.6 A 25.6 A
Recommended blow fuse type gL/gG
*)
10 A 13 A 13 A 13 A 16 A 16 A 20 A 25 A 32 A
Recommended automatic fuse type B or C
*)
16 A 16 A 16 A 20 A 20 A 20 A 25 A 25 A 32 A
Table 5.13 Mains Circuit Specifications
*)
Always choose fuses according to national regulations.
5.8 Auxiliary Interface Specifications
Interface Parameter Parameter Details Specification
RS-485 and Ethernet Cable
Cable jacket diameter (
)
2x5-7 mm
Cable type Shielded Twisted Pair (STP CAT 5e or
SFTP CAT 5e)
2)
Cable characteristic impedance 100 Ω – 120
RJ-45 connectors:
2pcs RJ-45 for RS-485
2pcs RJ-45 for Ethernet
Wire gauge 24-26 AWG (depending on mating
metallic RJ-45 plug)
Cable shield termination Via metallic RJ-45 plug
Galvanic interface insulation Yes, 500 Vrms
Direct contact protection Double/Reinforced insulation Yes
Short-circuit protection Yes
RS-485 only Cable Max. cable length 1000 m
Max. number of inverter
nodes
63
Ethernet only Communication Network topology Star and daisy chain
Cable Max. cable length between
inverters
100 m
Max. number of inverters
100
1)
Table 5.14 Auxiliary Interface Specifications
1)
Max. number of inverters are 100. If GSM modem is used for portal
upload, the number of inverters in a network is limited to 50.
2)
For outdoor use, we recommend outdoor burial type cable (if
buried in the ground) for both Ethernet and RS-485.
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 43
5
5
Illustration 5.13 Auxiliary Interfaces
5.9 RS-485 and Ethernet Connections
RS-485
Terminate the RS-485 communication bus at both ends.
Termination is automatic when no RJ-45 plug is inserted into the socket. The absence of a mating connector enables both termination and bias.
In rare cases, bias is unwanted, but termination is required. To terminate the RS-485 bus, mount a 100 Ω termination resistor into an RJ-45 field mountable connector. Then insert the connector (with resistor) into the unused RJ-45 connector.
The RS-485 address of the inverter is unique, and defined at the factory.
Illustration 5.14 RJ-45 Pinout Detail for RS-485
1.
GND
2. GND
3.
RX/TX A (-)
4. BIAS L
5. BIAS H
6.
RX/TX B (+)
7. Not connected
8. Not connected
Bold = Compulsory, Cat5 cable contains all 8 wires.
For Ethernet: 10Base-TX and 100Base-TX auto cross-over.
Technical Data
44 L00410568-02_02 / Rev. date: 2013-12-10
5
Illustration 5.15 RJ-45 Pinout Detail for Ethernet
Pinout
Ethernet
Colour Standard
Cat 5
T-568A
Cat 5
T-568B
1. RX+ Green/white Orange/white
2. RX Green Orange
3. TX+ Orange/white Green/white
4. Blue Blue
5. Blue/white Blue/white
6. TX- Orange Green
7. Brown/white Brown/white
8. Brown Brown
5.9.1 Network Topology
The inverter has 2 Ethernet RJ-45 connectors enabling the connection of several inverters in a line topology as an alternative to the typical star topology. The 2 ports are similar and may be used interchangeably. For RS-485, only linear daisy chain connections can be used.
NOTICE
Ring topology is not permitted.
Illustration 5.16 Network Topology
1Linear Daisy Chain
2Star Topology
3 Ring Topology (not permitted)
(4) (Ethernet Switch)
NOTICE
The 2 network types cannot be mixed. The inverters can only be connected in networks which are either solely RS-485 or solely Ethernet.
NOTICE
Ethernet is recommended for faster communication. RS-485 is required when a weblogger or datalogger is connected to the inverter.
Technical Data
L00410568-02_02 / Rev. date: 2013-12-10 45
5
5
Danfoss Solar Inverters A/S
Nordborgvej 81 DK-6430 Nordborg Denmark Tel: +45 7488 1300 Fax: +45 7488 1301 E-mail: solar-inverters@danfoss.com www.danfoss.com/solar
Rev. date 2013-12-10 Lit. No. L00410568-02_02
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Loading...