Data sheet Flow Insert
for manifold radiators
Application
Technical data
Spare parts
Materials
Max. pressure Max. water
Valve type Code No. kv (2.0)1) k
temp.
Working Different.2) Test
RA-FN 013G4220 0.63 1.60 10 0.3 16 120
1)
The kv-value indicates the water flow (Q) in m3/h at a pressure drop (∆p) across the valve of 1 bar;
1)
vs
kv = Q: √ ∆p. The kv-value is stated according to EN 215, at XP = 2K i.e. the valve is closed at 2°C higher
room temperature.
The kvs-value states the flow Q at a maximum lift, i.e. at fully open valve.
2)
The maximum differential pressure specified is the maximum pressure at which the valves give satisfac-
tory regulation. As with any device which imposes a pressure drop in the system, noise may occur under
certain flow/pressure conditions. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
Product Code No.
Gland seal (Pack of 10 pcs)
(Pack of
013G0290
Spindle Ms
O-rings EPDM
Valve cone NBR
Pressure pin Chrome-plated steel
Valve body Ms 58, Ni-coated
DKCD VDTVX102 © Danfoss 2/2009 1
Data sheet Flow Insert for manifold radiators
Capacities
Dimensions
The flow insert is designed for radiators using
steel, copper and alu valve garnitures as shown.