Data Sheet
Flow Indicator - Measuring Device for Flow and
Pressure
Description
Application
The flow indicator is a new simple measuring device for measuring flow and pressure in heating,
cooling and domestic hot water systems.
The flow indicator consists of a differential pressure gauge and a slide ruler, which enables the
pressure to be calculated into flow.
Find the presetting
Given: LENOTM MSV-BD 15, desired flow 500l/h
Desired: Presetting
The slide ruler has been developed for Danfoss
balancing valves.
The slide rulers can also help determine the presetting of balancing valves.
▪
Move 1st ruler to the desired flow
e.g. 500 l/h or 10 kW.
▪
▪
nd
Move 2
ferential pressure (∆p), e.g. 0.1 bar.
Presetting can be read where the
scale of LENOTM MSV-BD 15 is
crossing the red line, in this example presetting = 4.
ruler to the desired dif-
Danfoss Heating Solutions VDE2D202 © Danfoss 06/2013 1
Data Sheet Flow Indicator - Measuring Device for Flow and Pressure
Determine the flow
Find out the dimension of the installed LENOTM MSV-BD valve and read the actual presetting (here DN 15
and presetting 4).
▪
▪
▪
▪
▪
▪
st
Move 1
ruler to read presetting =
4
Read differential pressure on man-
ometer, e.g. 0.07 bar.
nd
Move 2
ruler to 0.07 bar, and
read flow = 400 l/h
To balance 500 l/h, change the
presetting or regulate the differential pressure.
Move 1st ruler to 500 l/h, and read
new presetting = 4.5
Or adjust the differential pressure
at the pump.
Ordering
The flow indicator can be used for manual balancing valves and partner valves for ASV:
▪
Leno
ASV-I
▪
ASV-BD
▪
USV-I
▪
MSV-F2
▪
TM
Flow indicator suit case
Contents
Max static
pressure
Differential pres-
sure
Differential pressure gauge & slide ruler.
2 pcs. of quick coupling sockets G1/4" with push in fitting nipple.
Blue measuring hose (1.5 meter/6 x 1mm).
10 bar 0-1 bar 003L8310
Red measuring hose (1.5 meter/6 x 1mm).
2 pcs. of measuring needles with ball valve and push in fitting
elbows.
Code no.
Accessories
Type Code no.
2 pcs. of quick coupling sockets G1/4" with
003L8315
push in fitting nipple
Measuring hoses, 2x1.5m 003L8261
2 VDE2D202 © Danfoss 06/2013 Danfoss Heating Solutions
Data Sheet Flow Indicator - Measuring Device for Flow and Pressure
Type Code no.
Measuring needle with ball valve and push in
fitting elbows
Strap 003L8324
Slide ruler (LENOTM MSV-BD/B and ASV-BD)
Slide ruler (USV-I and ASV-I) 003L8321
Slide ruler (MSV-F2) 003L8320
003L8319
003L8262
Technical Data
How to Measure
Item Value
Pressure range 0-1 bar
Max static pressure 10 bar
Reliability, linearity and hysteresis error 2.5%
Medium temperature -5 to 150°C
Calibration When pointer in wrong posi-
tion
Measure the differential pressure
1) 2) 3)
Make sure bypass is open Fit connectors onto the hoses Fit hoses to MSV-BD
4) 5) 6)
Fit hoses to manometer
Danfoss Heating Solutions VDE2D202 © Danfoss 06/2013 3
Open ball valves, first blue then
red
Close bypass and read pressure
and process with flow indicator