Danfoss Flow and Difference Pressure Optimize Guide Fact sheet

Technical Paper
Flow and Dierence Pressure Optimize Guide
Introduction
Balancing a heating system
Between 80 and 90 % of all buildings in Northern Europe have heating systems with little or no hydronic balancing. The results are:
• Discomfort due to under- or overheating
• Discomfort due to noise problems
• High energy costs
The purpose of balancing a heating system is to optimize the ow and get as good a heat con­sumption as possible. To achieve this we have to make sure that the right amount of water is distributed to the radiators, as well as the pump pressure or setting of the dierential pressure regulator is correct.
Balancing - installation - performance
1. Exact calculation of the heating output,
or
2. Estimation of the Heating output:
• Get drawings with room sizes in m2 of all ats. If drawings are not available a laser range nder can be used for measuring the areas.
• Select the heat loss.
• Calculate the ow.
• Determine preset values for each radiator valve according to the calculated ow. Find the selected preset in the Presetting table (see next page).
• Decide together with the property owner or caretaker limitations and the current room temperature. Consider the need for thermo­stats with remote sensor.
• All radiator valves must be preset.
• Fill with water and bleed the system.
In 2-pipe heating systems a correct dimensioning and adjustment of the valves is a prerequisition for achieving optimal energy consumption and high user comfort. By spending a few minutes on studying this paper you will be ready to use RA-DV Dynamic
Valve s™.
Fig. 1: Pressure and ow changes
Fig 2: Comfort with hydronic balancing
VFGWG102 © Danfoss 05/2014
1
Technical Paper Flow and Dierence Pressure Optimize Guide
Tables
1. Heat loss (empirical values)
Yea r of construction
Single family house 180 W/m2170 W/ m2150 W/m2115 W/m295 W/m275 W/m260 W/m240 W/m
Townhouse:
- at the end
- in the middle
Multi family house:
- up to 8 oors
- more than 8 oors
2. Dierence ow and return temperature
Typical values (K)
∆t (K) Heat source
10 -15 Heat pump
15-20 Low temperature boiler
20 -25 Condensing boiler
25-40 District energy, indirect
until 1958
160 W/m 140 W/m
130 W/m 120 W/m
2
150 W/m
2
130 W/m
2
120 W/m
2
110 W/m
1959-
1968
2
130 W/m
2
120 W/m
2
110 W/m
2
100 W/m
1969-
1973
2
110 W/m
2
100 W/m
2
75 W/m
2
70 W/m
1974 -
1977
2
2
2
2
1978 -
1983
90 W/m 85 W/m
65 W/m 60 W/m
2
2
2
2
1984-
1994
70 W/m 65 W/m
60 W/m 55 W/m
3. Presetting
RAW RA2000 living/TWA
15 20 25 1
20 25 30 2
30 30 35 3
40 40 45 4
50 50 60 5
2
2
2
2
1995-
2001
55 W/m 50 W/m
45 W/m 40 W/m
from 2002
2
35 W/m
2
30 W/m
2
33 W/m
2
33 W/m
Presetting
70 75 80 6
90 95 100 7
110 125 135 N
2
2
2
2
2
Example
Building type Multi family house
Year of construction 1984
Room size 40 m
2
Number of radiators in the room 1
Heat eect needed 55 W/m2 (according to table 1)
Dierence ow (ΔT) needed 20° C (according to table 2)
Formula:
(W/m2) x m2 x 0.86
=
∆t (K)
= ..... l/h
55 x 40 x 0.86
=
20
Presetting should be 7 (according to table 3, with RA2000).
Presetting of more radiators in the room
Two radiators in the room of same size should be preset to:
94.6 = 4 7. 3 l /h = presetting 5 (with RA2000)
2
Are the radiators of dierent sizes, the presetting should be calculated according to each radiator’s area coverage.
Further calculation possibilities concerning the radiator performance as well as the heat loss oers the Danfoss Heating App and the DanBasic­Software.
Note! Corner rooms, rooms with ceiling towards the outside and without heated oors, walls and concrete deck directly on soil requires slightly more eect from the radiator to provide the same comfort as in other rooms (raise the presetting with 0.5 compared with a normal room).
= 94.6 l/h
2
VFGWG102 © Danfoss 05/2014
Loading...
+ 2 hidden pages