Danfoss Flow and Difference Pressure Optimize Guide Fact sheet

0 (0)
Danfoss Flow and Difference Pressure Optimize Guide Fact sheet

Technical Paper

Flow and Difference Pressure Optimize Guide

Introduction

Between 80 and 90 % of all buildings in Northern

In 2-pipe heating systems a correct dimensioning

 

Europe have heating systems with little or no

and adjustment of the valves is a prerequisition

 

hydronic balancing.

for achieving optimal energy consumption and

 

The results are:

high user comfort.

 

• Discomfort due to underor overheating

By spending a few minutes on studying this

 

• Discomfort due to noise problems

paper you will be ready to use RA-DV Dynamic

 

• High energy costs

Valves™.

Balancing a

The purpose of balancing a heating system is to

heating system

optimize the flow and get as good a heat con-

 

sumption as possible.

 

To achieve this we have to make sure that the

 

right amount of water is distributed to the

 

radiators, as well as the pump pressure or setting

 

of the differential pressure regulator is correct.

 

Balancing - installation - performance

 

1. Exact calculation of the heating output,

 

or

 

2. Estimation of the Heating output:

 

• Get drawings with room sizes in m2 of all flats.

 

If drawings are not available a laser range

 

finder can be used for measuring the areas.

 

• Select the heat loss.

 

• Calculate the flow.

 

• Determine preset values for​ each radiator

 

valve according to the calculated flow. Find

 

the selected preset in the Presetting table (see

 

next page).

 

• Decide together with the property owner or

 

caretaker limitations and the current room

 

temperature. Consider the need for thermo-

 

stats with remote sensor.

 

• All radiator valves must be preset.

 

• Fill with water and bleed the system.

Fig. 1: Pressure and flow changes

Fig 2: Comfort with hydronic balancing

VFGWG102

© Danfoss

05/2014

1

Technical Paper

Flow and Difference Pressure Optimize Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tables

1. Heat loss (empirical values)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Year of

until

 

1959-

1969-

1974-

1978-

1984-

1995-

from

 

construction

1958

 

1968

1973

1977

1983

1994

2001

2002

 

Single family house

180 W/m2

 

170 W/m2

150 W/m2

115 W/m2

95 W/m2

75 W/m2

60 W/m2

40 W/m2

 

Townhouse:

 

 

 

 

 

 

 

 

 

 

- at the end

160 W/m2

 

150 W/m2

130 W/m2

110 W/m2

90 W/m2

70 W/m2

55 W/m2

35 W/m2

 

- in the middle

140 W/m2

 

130 W/m2

120 W/m2

100 W/m2

85 W/m2

65 W/m2

50 W/m2

30 W/m2

 

Multi family house:

 

 

 

 

 

 

 

 

 

 

- up to 8 floors

130 W/m2

 

120 W/m2

110 W/m2

75 W/m2

65 W/m2

60 W/m2

45 W/m2

33 W/m2

 

- more than 8 floors

120 W/m2

 

110 W/m2

100 W/m2

70 W/m2

60 W/m2

55 W/m2

40 W/m2

33 W/m2

2. Difference flow and return temperature

Typical values (K)

∆t (K) Heat source

10-15 Heat pump

15-20 Low temperature boiler

20-25 Condensing boiler

25-40 District energy, indirect

3. Presetting

RAW

RA2000

living/TWA

Presetting

 

 

 

 

15

20

25

1

 

 

 

 

20

25

30

2

 

 

 

 

30

30

35

3

 

 

 

 

40

40

45

4

 

 

 

 

50

50

60

5

 

 

 

 

70

75

80

6

 

 

 

 

90

95

100

7

 

 

 

 

110

125

135

N

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

Building type

 

 

 

 

 

 

Multi family house

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Year of construction

 

 

 

 

 

1984

 

 

 

 

 

 

 

 

 

 

 

 

 

Room size

 

 

 

 

 

 

 

40 m2

 

 

Number of radiators in the room

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Heat effect needed

 

 

 

 

55 W/m2 (according to table 1)

 

Difference flow (ΔT) needed

 

 

 

20° C (according to table 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Formula:

=

 

(W/m2) x m2 x 0.86

= ..... l/h

=

55 x 40 x 0.86

= 94.6 l/h

 

 

∆t (K)

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Presetting should be 7 (according to table 3, with RA2000).

Presetting of more radiators in the room

Two radiators in the room of same size should be preset to:

94.6

= 47.3 l/h = presetting 5 (with RA2000)

2

 

Are the radiators of different sizes, the presetting should be calculated according to each radiator’s area coverage.

Further calculation possibilities concerning the radiator performance as well as the heat loss offers the Danfoss Heating App and the DanBasicSoftware.

Note!

Corner rooms, rooms with ceiling towards the outside and without heated floors, walls and concrete deck directly on soil requires slightly more effect from the radiator to provide the same comfort as in other rooms (raise the presetting with 0.5 compared with a normal room).

2

VFGWG102

© Danfoss

05/2014

Loading...
+ 2 hidden pages