Danfoss FJVR 10, FJVR 15 Data sheet

Data Sheet
Return Temperature Limiter Type FJVR - Sensor and Valve Body
Application
System
Data and Ordering
The return limiter type FJVR automatically con­trols the return temperature from radiators, con­vectors and floor heating pipes.
In ventilation systems FJVR ensures a certain min­imal circulation in the pipe system up to the heat exchanger.
Sensors
Type Colour Setting range Code no.
FJVR Return Temperature Limiter
Valve bodies
Valve bodies
FJVR 10, angle FJVR 10, straight 003L1010 FJVR 15, angle FJVR 15, straight 0.90 003L1014
Connections
Inlet
Outlet
Rp ³/₈
R ³/₈
Rp ¹/₂
R ¹/₂
2)
kvs
1)
Working
0.39 10 bar 1 bar 16 bar 120 °C
0.68 003L1013
Setting can be limited and locked. FJVR valve bodies are nickel-plated.
White RAL 9010 10 - 50 ˚C 003L1040 White RAL 9010 10 - 80 ˚C 003L1070
Chrome 10 - 50 ˚C 003L1072
Max. pressure
Different.
3)
Test
Max. water
temp.
Code no.
003L1009
1)
Outlet connection is prepared for Danfoss compression fittings.
2)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (Δp) across the valve of 1 bar.
3)
The max. differential pressure indicates the limit for an optimal valve performance. To ensure quiet op­eration it is recommended to choose a pump which provides the correct pressure to circulate the re­quired flow of water. In most systems a differential pressure of 0.1-0.3 bar is sufficient. The differential pressure may be reduced by using Danfoss differential pressure controls.
Danfoss Heating Solutions VDTGO502 © Danfoss 06/2013 1
1 2 3 4 5 6 7 8 9
10 20 30 40 45 50 60 65 70 80 ˚C
1 2 3 4 5 6 7 8
10 20 30 40 45 50 ˚C
1 2 3 4
Data Sheet Return Temperature Limiter Type FJVR - Sensor and Valve Body
Spare parts
Product Code no. Gland seal (10 pcs.) 013G0290
Design
Mounting
The return temperature limiter includes a ther­mo-static element type FJVR and a valve body type FJVR 10. The element and the valve body are ordered sep­arately. The gland of the valve can be exchanged without draining down system.
Materials in contact with water
1. Sensor
2. Bellows
3. Setting handle
4. Spring
5. Pressure pin
6. Gland seal
7. Valve top
8. Valve cone
9. Valve body
Valve body and other metal
Ms 58
parts Pressure pin in gland seal Chrome steel O-ring EPDM Valve cone NBR
Straight valve Angle valve
Setting
FJVR is mounted in the radiator outlet. The valve and sensor can be fitted in any position as long as flow direction is observed.
FJVR 003L1070
During construction, the heat can be controlled by turning the slotted screw in the valve cap, pri­or to fitting the element.
FJVR 003L1040 / 003L1072
Frost protection setting = 10 °C
2 VDTGO502 © Danfoss 06/2013 Danfoss Heating Solutions