Danfoss FIA 15-200 Installation guide

Danfoss FIA 15-200 Installation guide

Installation guide

Strainer

FIA 15-200 with butt weld F connection

<![if ! IE]>

<![endif]>148R9618

Installation

 

 

Note:

 

At delivery the strainer housing is not equipped with strainer

 

element or accessories.

 

Remarque :

 

Le corps du filtre est livré sans élément et sans accessoire.

<![if ! IE]>

<![endif]>Danfoss 148H115_06-2014

FIA 15-200

1

2

Maintenance

Filter bag

Flow direction

Sac filtrant

Direction du flux

Max. torque / Couple max.

 

 

Nm

LB-ft

DN 15-20

21

15

DN 25-32-40-50

44

32

DN 65

74

54

DN 80

44

32

DN 100

75

53

DN 125-150

183

135

DN 200-300

370

272

3

4

<![if ! IE]>

<![endif]>148R9618

D

© Danfoss | DCS (MWA) | 2015.05

DKRCI.PI.FN1.D3.ML / 520H8311

1

ENGLISH

Refrigerants

Applicable to HCFC, HFC, R717 (Ammonia), R744 (CO2) and all flammable refrigerants.

The strainer is only recommended for use in closed circuits. For further information please contact your local Danfoss sales office.

Pressure and temperature range

–60/+150°C (–76/+302°F)

FIA:

52 bar g (754 psi g) (DN 15 - DN 125) 25 bar g (362 psi g) (DN 150 - DN 200).

Please see the technical brochure (DKRCI.PD.F00.A) for a more detailed description of the pressure and

temperature range.

Installation

Note:

At delivery the strainer housing is not equipped with strainer element or accessories

The strainer must be installed with the top cover downwards, and the flow must be directed towards the top cover as indicated by the arrow on the strainer housing (fig. 1). The strainer element must be inserted after welding.

The strainer housing is designed to withstand a high internal pressure. However, the piping system should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. It must be ensured that the strainer is protected from pressure transients like “liquid hammer” in the system.

Recommended flow direction

The strainer must be installed with the flow towards the top cover as indicated by the arrow on the side of the valve body (fig.

1). Flow in the opposite direction is not acceptable.

Welding

To prevent damage to the gasket between the strainer housing and top cover, the top cover should be removed before welding and protect it from dirt and moisture (fig. 2).

Only materials and welding methods, compatible with the strainer housing material, must be welded to the strainer housing.

Clean the strainer housing internally to remove welding debris at completion of welding and before the strainer is reassembled.

Removing the top cover can be omitted provided that:

The temperature in the area between the strainer body and top cover during welding does not exceed +150°C/+302°F.

This temperature depends on the welding method as well as on any cooling of the strainer housing during the welding itself.

(Cooling can be ensured by, for example, wrapping a wet cloth around the strainer body.) Make sure that no dirt, welding debris etc. get into the strainer during the welding procedure.

The strainer housing must be free from stresses (external loads) after installation.

Strainers must not be mounted in systems where the outlet side of the strainer is open to atmosphere. The outlet side of the strainer must always be connected to the system or properly capped off, for example with a welded-on end plate.

Assembly

Remove welding debris and any dirt from pipes and strainer housing before assembly. Check that the strainer element has the right size before it is inserted in the top cover and check that the gasket is undamaged.

Place the strainer element (pos. D) from underneath. The element has a slight force fit into the housing, no gaskets or O-rings are used.

If magnet inserts have been chosen as accessory, fit those on the top cover before replacing the cover.

Tightening

Tighten the top cover with a torque wrench, to the values indicated in the table (fig. 3).

Please note that the table (fig. 3) containing maximum torque must be adhered to and never exceeded.

If the drain valve has been chosen as accessory, the drain plug should be replaced by the drain valve.

Colours and identification

The FIA strainers are painted with a red oxide primer in the factory. Precise identification of the strainer is made via

the ID plate on the top cover, as well as by the stamping on the strainer housing. The external surface of the strainer housing must be prevented against corrosion with a suitable protective coating after installation and assembly.

Be sure to protect the ID plate when repainting the strainer.

Maintenance

Mounting of accessory: Filter bag (fig. 4)

A 50µ filter bag (pos. E), especially for commissioning of the plant, can replace the normal strainer element.

Mount the filter bag (held in place by the filter holder) and be sure to place the filter bag correctly in the strainer as shown in fig. 4.

The flow must go into the filter bag cavity and out or else the bag will not function properly.

Dismantling the strainer (fig. 3)

Before servicing the strainers, isolate it from the system and remove all refrigerant by evacuation to zero pressure. Check for refrigerant pressure before unscrewing and removal of the top cover.

The strainer element must be removed without any use of tools

Cleaning

Clean the strainer element using an appropriate solvent by flushing and brushing. The use of strong acids cannot be recommended. The strainer element must be wiped or blown dry before inspection. If the element is damaged or the sediments cannot be removed, the strainer element must be replaced.

Assembly

Remove any dirt from the housing before the strainer is assembled.

Replacement of gasket

Change the gasket for the top cover (pos. C) and drain plug.

Check that the strainer element is correctly placed before remounting the top cover and bolts (pos. A).

Tightening (fig. 3)

Tighten the top cover bolts (pos. A) with a torque wrench according to the table in fig. 3

Use only original Danfoss parts (including gaskets) for replacement. Materials of new parts are certified for the relevant refrigerant.

In cases of doubt, please contact your local Danfoss sales office.

2

DKRCI.PI.FN1.D3.ML / 520H8311

© Danfoss | DCS (MWA) | 2015.05

Loading...
+ 2 hidden pages