Danfoss EV251B Data sheet

Data Sheet
Solenoid valve Type EV251B
Compact servo operated with assisted lift for general purpose
EV251B with assisted lift is especially suitable for applications such as closed systems with low and uctuating pressure conditions or open systems with dierential pressure down to 0 bar.
EV251B valves are supplied complete, including coil and plug.
Features and versions
• Clip on coil
• Ambient temperature: Up to 80 °C
• Coil enclosure: IP65
AI236986442833en-000901
Features
EV251B
Body material
Brass
DN [mm]
10-22
Connection
G3/8'' - G1''
Sealing material
NBR
Function
NC
Kv [m3/h]
1.5-3.5
Dierential pressure range [bar]
0-10
Temperature range [°C]
-10-90
Solenoid valve, type EV251B
1 Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.06 AI236986442833en-000901 | 2
1
234567899.1
9.2
Coil
Armature
Closing spring
Valve plate
Pilot orice
Diaphragm
Main orice
Equalizing orice
Assist
Assist spring
Assist connector
Solenoid valve, type EV251B
2 Function
2.1 Function NC
Coil voltage disconnected (closed)
When the supply voltage to the coil (1) is disconnected, the valve plate (4), is pressed down against the pilot orice (5), by the closing spring (3). The pressure across the diaphragm (6), is built up via the equalizing orice (8). The diaphragm closes the main orice (7), when the pressure above the diaphragm exceeds the inlet pressure below due to the larger diameter of the upper side and the compression of the closing spring (3). The valve will be closed for as long as the voltage to the coil is disconnected.
Coil voltage connected (open)
When the voltage is applied to the coil, the armature (2), and the valve plate (4), are lifted clear of the pilot orice (5). If there is a dierential pressure across the valve, the pressure across the diaphragm (6), drops because the pilot orice is larger than the equalizing orice. This causes the diaphragm to be lifted clear of the main orice (7). If there is no dierential pressure across the valve, the armature (2) draws the diaphragm (6) clear of the main orice (7), using the assist spring (9.1) and assist connector (9.2). The valve will be open for as long as there is voltage to the coil.
Figure 1: Function NC
© Danfoss | Climate Solutions | 2021.06 AI236986442833en-000901 | 3