Danfoss EV250B Data sheet

Data Sheet
Solenoid valve Type EV250B
Assisted lift operated 2/2-way valve program is use in closed circuits with low dierential pressure
EV250B with assisted lift can operate from zero and up to 10 bar dierential pressure.
This 2/2-way valve program is especially to use in closed circuits with low dierential pressure, but demanding moderate ow rates.
Valve body in dezincication resistant brass for ensuring a long life even in connection with aggressive steam media.
Features and versions:
• For water, oil, compressed air and similar neutral media
• Clip on coil
• Ambient temperature: Up to 80 °C
• Coil enclosure: Up to IP67
• The valve can be used for rough vacuum
• Water hammer damped
AI236986441319en-001001
Features
EV250B
Body material
DZR Brass
DN [mm]
10 - 22
Connection
G'' - G1''
Sealing material
EPDM, FKM
Function
NC, NO
Kv [m3/h]
2.5 - 7
Dierential pressure range [bar]
0 - 10
Temperature range [°C]
-30 - 140
Solenoid valve, type EV250B
1 Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.06 AI236986441319en-001001 | 2
1
2
3
4
5
6
7
8
9
123456789
Coil
Armature
Closing spring
Valve plate
Pilot orice
Diaphragm
Main orice
Equalizing orice
Assisted lift
Solenoid valve, type EV250B
2 Functions
2.1 Function NC
Coil voltage disconnected (closed):
When the supply voltage to the coil (1) is disconnected, the valve plate (4) is pressed down against the pilot orice (5) by the closing spring (3). The pressure across the diaphragm (6) is built up via the equalizing orice (8). The diaphragm closes the main orice (7) as soon as the pressure across the diaphragm is equivalent to the inlet pressure below, due to the larger diameter of the upper side and/or the tension of the closing spring (3). The valve will be closed as long as the voltage to the coil is disconnected.
Coil voltage connected (open):
When voltage is applied to the coil, the armature (2) and the valve plate (4) are lifted clear of the pilot orice (5).
If there is a dierential pressure across the valve, the pressure above the diaphragm (6) drops as the pilot orice is larger than the equalizing orice. Therefore the diaphragm is lifted clear of the main orice (7). If there is no dierential pressure across the valve, the armature (2) draws the diaphragm (6) clear of the main orice (7) using the assisted lift (9). The valve will be open for as long as there is voltage to the coil.
2.2 Function NO
Coil voltage disconnected (valve is open):
When the supply voltage to the coil (1) is disconnected, the valve plate (7) are lifted clear of the pilot orice (9) if there is a dierential pressure across the valve. The pressure above the diaphragm (10) drops as the pilot orice is larger than the equalizing orice. Therefor the diaphragm is lifted clear of the main orice (12). If there is no dierential pressure across the valve, the opening spring (5) draws the diaphragm (10) clear of the main orice (12) using the assisted lift (8). The valve will be open for as long as there is no voltage to the coil.
Coil voltage connected (valve is closed):
When the supply voltage to the coil (1) is connected, the armature (3) will compress the opening spring (5) and the closing spring will push the spindle (4)/ valve plate down against the pilot orice (9). The pressure across the diaphragm (10) is built up via the equalising orice (11). The diaphragm closes the main orice (12) as soon as the pressure across the diaphragm is equivalent to the inlet pressure below, due to the larger diameter of the upper side and / or the tension of the closing spring (2). The valve will be closed as long as coil voltage is connected.
© Danfoss | Climate Solutions | 2021.06 AI236986441319en-001001 | 3
1
2
3
4
5
6
7
8
9
11
10
12
123456789101112Coil
Closing spring
Armature
Spindle
Opening spring
Armature stop
Valve plate
Assisted lift
Pilot orice
Diaphragm
Equalising orice
Main orice
Solenoid valve, type EV250B
© Danfoss | Climate Solutions | 2021.06 AI236986441319en-001001 | 4