Remote Control Units ECA 30 / 31 and Application keys
Description
ECL Comfort 310 controller
series
ECL 310
The ECL Comfort 310 is an electronic weather
compensated temperature controller in the ECL
Comfort controller family for use in district
heating, central heating and cooling systems.
Energy savings can be achieved by correct control
of the flow temperature in heating and cooling
systems. Up to 4 circuits can be controlled.
The weather compensation function in the ECL
Comfort controllers measures the outdoor
temperature and controls the flow temperature
to the heating system accordingly. The weather
compensated heating system increases the
comfort level and saves energy.
The ECL Comfort 310 controller is configured with
a selected application by means of an ECL
Application Key.
The web-based ECL Portal communicates with
the ECL Comfort 310 for an effective and easy-touse turnkey SCADA (Supervisor y Control And Data
Acquisition) tool for all users, service personnel
and at commissioning. Service level can be
increased and/or service costs reduced. The
heating and/or cooling installation is made
accessible from virtually anywhere at any time via
laptops or Smartphones which increases service
level and reduces response time to alarms.
The ECL Tool software for ECL Comfort 310 offers
possibilities for an alternative remote control in
relation to ECL Portal and OPC server software.
ECL Comfort 310 is designed for comfortable
temperatures, optimum energy consumption,
easy installation by means of the ECL Application
Key (Plug-and-Play) and user-friendly operation.
Improved energy savings are facilitated by
weather compensation, adjustment of
temperature according to schedule, optimization
as well as limitation of return temperature, flow
and power.
The ECL Comfort 310 is easily operated by means
of a dial (multi-functional knob) or a Remote
Control Unit (RCU). The dial and the backlighted
display guide the user through the text menus in
the selected language.
The ECL Comfort 310 controller has electronic
output for motorized valve control, relay output
for circulation pump / changeover valve control
among others, as well as alarm output.
6 Pt 1000 temperature sensors can be connected.
In addition, 4 inputs are configured when
uploading the application. The configuration can
be Pt 1000 temperature sensor input, analogue
input (0 – 10 V) or digital input.
Depending on application, one of the internal
extension modules ECA 32 or ECA 35 (inserted into
the controller’s base part) can give additional input
and output signals.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Description (continued)The enclosure is designed for mounting on wall
and DIN rail. A variant ECL Comfort 310B (without
display and dial) is available. It can be used for
mounting inside a panel and is operated by means
of the RCU ECA 30 / 31 which can be placed in
front of the panel.
The ECL Comfort 310 can work as a stand-alone
controller and communicate with up to two RCUs
and an extension module ECA 32 or ECA 35 with
additional inputs / outputs.
The ECL Comfort 310 can also work with up to 2 x
RCUs, ECA 32 / 35 and other ECL Comfort 210 / 296
/ 310 controllers via the ECL 485 communication
bus.
Ethernet connec tion is integrated in the controller.
Furthermore, Modbus communication to SCADA
systems (Supervisory Control and Data
Acquisition) and M-bus communication to heat
meters are integrated.
ECL Application Key
and applications:
Different ECL Application Keys make it easy for
the ECL Comfort 310 hardware to run different
applications. The ECL Comfort 310 controller is
loaded with the desired application by means of
the ECL Application Key, which contains
information about applications (basic application
sketches are shown in the display), languages,
factory settings and firmware.
Remote Control Unit (RCU):
The RCUs ECA 30 and ECA 31 are used for room
temperature control and override of the ECL
Comfort 310. The display has backlight. The RCUs
are connected to the ECL Comfort controllers by
means of 2 × twisted pair cable for communication
and power supply (ECL 485 communication bus).
The ECA 30 / 31 has a built-in room temperature
sensor. An external room temperature sensor can
be connected substitutin g the built-in temperature
sensor.
Furthermore, the ECA 31 has a built-in relative
humidity sensor and the signal is used in relevant
applications. It is possible to connect up to 2 RCUs
on the ECL 485 communication bus. One RCU can
monitor max. 10 ECL Comfort controllers (master/
slave system).
The ECL Application Keys, series A2xx can b e used
in ECL Comfort 210, ECL Comfort 296 and ECL
Comfort 310. Most of the A2xx application keys
give extended functionalities when used in ECL
Comfort 310, such as additional temperature
sensors and M-bus communication.
The ECL Application Keys, series 3xx can be used
in ECL Comfort 310 only.
The application parameters are stored in the
controller and are not affected by power break.
The relevant ECL Application Keys for the ECL
Comfort 210 / 296 / 310 controller can be found
in the ordering section.
*
When used in ECL 310 + ECA 32 / 35, 0 - 10 Volt controlled actuators can be used alternatively.
**
When used in ECL 310 + ECA 32 / 35 a 0 - 10 Volt controlled actuator can, alternatively, be used for the
heating circuit.
This is an overview of currently available application keys for the ECL Comfort controllers.
Not all keys are for sale in your country. Please contact your local Danfoss sales company.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A332.1, ex. a:
Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and
dew point temperature. Optional return temperature limitation.
A332.2, ex. a:
Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew
point temperature. Optional return temperature limitations.
A332.3:
Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew
point temperature. Optional return temperature limitations. Advanced instantaneous DHW
temperature control.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A332.4:
Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and
dew point temperature. External override of heating / cooling mode. Optional return temperature
limitation.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A266.10, ex. a:
Heating and direct DHW heating system. Pressure monitoring / alarm. Universal alarm input. Parallel
mode or DHW priority. S7 is pulse based flow or energy meter for related limitation.
A275.1, ex. a:
Heating system with 1-stage boiler.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A
A
A
A
A
A
A
A
A375.5, ex. a:
Heating system with 1-stage boiler ON / OFF controlled or 0 - 10 Volt controlled. Mixing circuit for
second heating circuit. DHW tank heating. Pressure monitoring / alarm.
S1
S3
S5
B1
V1
Burner control overview:
ECL 310
Danfoss
M2
+ ECA 32
S4
A1
S8
P4
87H1545.10
2
S2
S9
P1
*
S7
1
S6
3
P5
P3
275.1
275.2
275.3
375.1
375.2
375.3
375.4
375.5
ECL 310ECL 210
R2R2R3R4R5
1
1
1
1
1
1
34
1
1
1
1
Triac 6
Triac 5
7
2
2
7
R7R8R9R10
5
8
3
3
8
ECA 32
6
7
821
4
5
6
4
5
6
R2-R10 = relay nos. in ECL / ECA 32
A319.1:
Indirectly connected charging system with 2 temperature sensors in buffer. Heating system
connected directly to buffer. Pump P3 speed controlled in relation to differential pressure S9.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A319.2:
Indirectly connected charging system with 2 temperature sensors in buffer. Heating system
connected to buffer via mixing valve.
Pump P3 speed controlled in relation to differential pressure S9.
A333.1, ex. a:
Heating system with control of 1 or 2 circulation pumps. Refill water function with control of 1 or 2
pumps. Pressure measurements in the system.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A333.2, ex. a:
Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Refill water function
with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank.
Pressure measurements in the system.
A333.3, ex. a:
Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Control valve M1 is 0 10 V controlled. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control
of refill water storage tank. Pressure measurements in the system.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A361.2, ex. a:
2 x heating systems with two-pump control and refill water function. Supply temperature
dependent flow temperature control.
A362.1, ex. a:
Cascade control of heat exchangers.
Indirectly connected system with 2 x HEX, each managed by means of a 0 - 10 Volt controlled
motorized control valve (MCV). Each HEX circuit has its own circulation pump.
Cascade control can manage up to 6 heat exchangers by using additional ECL 310.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A368.2, ex. a:
Heating system with two-pump control and refill water function. Supply temperature dependent
flow temperature control. DHW heating system with control of 1 or 2 circulation pumps.
A368.4, ex. a:
Heating system with two-pump control and refill water function with 1 or 2 pumps. Supply
temperature dependent flow temperature control. DHW heating system with control of 1 or 2
circulation pumps. Pressure measurements in the systems.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A376.3, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Control
valves M1, M2 and M3 are 0 - 10 V controlled.
S1
M2
S5
A
M3
S10
A
M1
S6
A
ECL 310
Danfoss
+ ECA 32
S3
P2
S9
P3
S4
A1
87H2101.11
S2
1
S7
2
3
P1
A376.9, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Pressure
measurements and temperature monitoring in the system.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A390.3, ex. a:
3 x indirectly connected cooling circuits. Cooling to rooms can be based on Air Handling Units
(AHU).
A390.11, ex. a:
Three independent heating circuits. The heating circuits are indirectly con nected. DHW charging
circuit 4 is com bined with circuit 1.
Optional DHW priority.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
OrderingController, base parts and accessories:
Typ e Designation Code no.
ECL Comfort 310 Universal hardware - 230 V a.c.
ECL Comfort 310 Universal hardware - 24 V a.c.
ECL Comfort 310BUniversal hardware - 230 V a.c.
ECL Comfort 310 base partFor mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted
Base part is not included. Installation guide (no text) is included.
Base part is not included. Installation guide (no text) is included.
Without display and dial. Requires a Remote Control Unit.
Base part is not included. Installation guide (no text) is included.
in an ECL Comfor t 310 base part (for future upgrade). Installation guide (no
text) and cable inlet accessories is included.
Remote Control Units and accessories
Typ e Designation Code no.
ECA 30Remote Control Unit with an integrated room temperature sensor and
ECA 31Remote Control Unit with an integrated room temperature sensor and a
ECA 30 / 31 frame kit for
mounting in panel front
ECA 32Internal extension module with 6 inputs (Pt 1000 / analog / digital). 3 x
ECA 35Internal extension module with 2 inputs (P t 1000 / analog / digital). 3 x
possibility for connecting an external Pt 1000 room temperature sensor.
Base part for mounting on wall included. Installation guide (no text) is
included.
humidity sensor. Possibility for connecting an external Pt 1000 room
temperature sensor. Used for dedicated applications. Base par t for mounting
on wall included. Installation guide (no text) is included.
For mounting in a panel cut-out.
Format 144 × 96 mm, actual cut-out 139 × 93 mm. Installation guide (no text)
is included.
analog (0 - 10 Volt) outputs. 4 x relay outputs. To be placed in the ECL 310
base part. See separate data sheet.
analog (0 - 10 Volt) outputs and 4 x PWM outputs. 4 x relay outputs. To be
placed in the ECL 310 base part. See separate data sheet.
087H304 0
087H304 4
087H3050
087H3230
087H3200
087H3201
087H3236
087H3202
087H3205
Accessories:
Typ e Designation Code no.
ECA 99 230 V a.c. to 24 V a.c. transformer (35 VA) 08 7B115 6
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys
Typ eApplication type description Controller output
A214
A217
A230
A231
A232
A237
A247
A260
• Temperature cont rol (heating / cool ing) of ventilation sy stems. Duct / ro om
temperature control. Return temperature limitation. Flow / power
limitation. Fire and frost protection as well as alarm function.
• The A214 applicatio n key contains applic ations related to ECL Com fort 310
for increased functionalities (control of rotating heat-exchanger).
• Advanced tem perature control o f DHW (Domestic H ot Water) circuit with/
without storage charging system. Circulation pump control. Return
temperature limitation. Frost protection and alarm function.
• The A217 application key co ntains applicat ions related to ECL Comf ort 296
/ 310 for increased functionalities (M-bus).
• (A230.1) Weather compensated flow temperature control of heating
systems. Circulation pump control. Room temperature control and sliding
return temp erature limita tion. Flow / power lim itation. Wind com pensation,
frost protection and alarm function.
• (A230.2) Flow temperature control of cooling systems. Compensation for
outdoor and room temperatures. Return temperature limitation.
• (A230.3) Weather compensated control of flow temperature in a heating
circuit. Room temperature compensation. Compensation for too high
relative humidity. Sliding return temperature limitation. Power / flow
limitation. Compensation for wind. Alarm function related to flow
temperature.
Monitoring of temperatures in self-acting temperature controlled DHW
circuit.
• (A230.4) Weather compensated control of flow temperature in a heating
circuit. Room temperature compensation. Sliding return temperature
limitation. Power / flow limitation. Alarm function related to flow
temperature and static pressure.
Monitoring of temperatures in self-acting temperature controlled DHW
circuit.
• The A230 application key works in ECL Comfort 296 / 310 for increased
functionalities (M-bus).
• The A230 application key works in ECL Comfort 310, including EC A 32, for
0 - 10 Volt control of actuator for control valve.
• Weather compensated flow temperature control of heating systems.
2-pump control for circulation and refill water function. Sliding return
temperature limitation. Frost protection and alarm function.
• The A231 applic ation key contains app lications relate d to ECL Comfort 310
for increased functionalities (2 pumps for refill water and M-bus).
• Weather compensated flow temperature control of heating / cooling
circuit(s). Automati c change-ove r between hea ting and cooling. Ci rculation
pump control. Dew point (cooling mode only) and surface temperature
compensation.
• The A232 appli cation key contains a pplications rel ated to ECL Comfort 310
for increased functionalities (return temperature limitation and separated
control of heating and cooling circuits).
• Weather compensated flow temperature control of heating systems.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation. Temperature control of
secondar ily connected DHW circuit with storage tank charging system or
storage tank with internal heat exchanger. Optional ON / OFF control of
the DHW circu it in connectio n with primarily con nected stora ge tank with
internal heat exchanger. DHW circulation pump control. Frost protection
and alarm function.
• The A237 appli cation key contains ap plications rel ated to ECL Comfort 29 6
/ 310 for increased functionalities (M-bus).
• Weather compensated flow temperature control of heating systems.
Circulation pump control. Sliding return temperature limitation. Flow /
power limitation. Temperature control of DHW circuit with storage tank
charging system. DHW circulation pump control through the storage tank
or the heat-exchanger. Frost protection and alarm function.
• The A247 applicat ion key contains app lications relate d to ECL Comfort 310
for increased functionalities (room temperature sensor and M-bus).
• Weather compensated flow temperature control of heating systems.
Circulation pump control, room temperature control and sliding return
temperat ure limitation fo r two independ ent heating circuit s. Flow / power
limitation, frost protection and alarm function.
• The A260 application key works in ECL Comfort 296 / 310 for increased
functionalities (M-bus).
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Typ eApplication type description Controller output
A266
A275• Weather compensated flow temperature control of 1-stage boiler based
A319• Weather compensated control of flow temperature in a heating circuit or
A333• Weather compensated flow temperature control of a heating system.
A361• Weather compensated flow temperature control of 2 heating circuits.
A362• Weather compensated control of flow temperature in a heating circuit or
A367• Weather compensated flow temperature control of 2 heating circuits.
A368• Weather compensated flow temp erature control of a heating circuit.
A376• Weather compensated flow temperature control of 2 heating circuits.
• Weather compensated flow temperature control of heating systems.
Circulation pump control, room temperature control and sliding return
temperature limitation.
• Temperature control of DHW circuit with DHW circulation. Return
temperature limitation, sliding DHW priority, frost protection and alarm
function. Optional control of DHW heating based on DHW demand.
• The A266 application key works in ECL Comfort 310 for increased
functionalities (M-bus).
• The A266 application key work s in ECL Comfort 310, including ECA 32, for
0 - 10 Volt control of actuators for control valves; exception: A266.2, DHW
circuit
heating systems. One direct heating circuit and one mixing circuit.
Circulation pumps control, room temperature control and sliding return
temperature limitation.
• Temperature control of DHW storage tank with internal heat exchanger.
Frost protection and alarm function.
• The A275 applica tion key contains app lications relate d to ECL Comfort 310
for increased functionalities (multiple boiler stages).
• The A375 application key (subtypes A375.4 and A375.5) works in ECL
Comfort 310, includ ing ECA 32, for 0 - 10 Volt control of bo iler temperatu re.
combined h eating / DHW circuit s based on an advan ced buffer tempe rature
control. Charging pump is speed controlled, based on 0 - 10 Volt or PWM
(Pulse Width Modulated) signal. Discharging of buffer is avoided according
to built-in lo gic. Differenti al pressure can be ma intained by means o f speed
controlled circulation pump (0 - 10 Volt or PWM).
Optional sliding return temperature limitation.
Relay output present for buffer heating demand; override signal for remote
setting of desired flow temperature.
Alarm functions are related to flow and buffer temperatures.
ON / OFF and spe ed control of 1 or 2 circulation pumps and sliding return
temperat ure limitation. Fl ow / power limitatio n. Frost protect ion and alarm
function. ON / OFF and speed control of 1 or 2 refill water pumps.
Refill water storage control. Pressure release function. Pressure and
temperature monitoring. Frost protection and alarm function.
Supply temperature dependent flow temperature control. 2-pump control
for circulation. Sliding return temperature limitation. Flow / power
limitaion. Refill water function. Frost protection and alarm function.
combined heating / DHW circuits, based on ad vanced cascade control of
2 heat exchangers (HEX). Control valve characteristics are taken into
consideration and flow in unused HEX circuit can be stopped.
Optional sliding return temperature limitation. Scheduled shift for inversed
cascade (HEX-1 - HEX-2 and HEX-2 - HEX-1) can be set. Override inputs for
start o f HEX-1 and HEX-2 are avail able. M-Bus bas ed signal can be used f or
flow / energy limitation.
Up to 6 heat excha ngers can be cas cade controlled b y 1, 2 or 3 ECL Comfo rt
310 control lers, each equipped with the application key A362; the ECL
controllers are interconnected by means of the ECL 485 Bus.
Alarm functions are related to flow and flow temperatures.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation.
• Temperature control of secondarily connected DHW circuit with storage
tank charging system or storage tank with internal heat exchanger.
Optional O N / OFF control of the DHW circ uit in connection w ith primarily
connected storage tank with internal heat exchanger.
DHW circulation pump control. Frost protection and alarm function.
Supply temperature dependent flow temperature control. 2-pump control
for circulat ion. Sliding ret urn temperature l imitation. Flow / p ower limitation
Flow / power limitation and refill water function.
• Temperature control of a DHW circuit with DHW circulation, return
temperature limitation and sliding DHW priorit y. Frost protection and
alarm function.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation.
• Temperature control of a DHW circuit with DHW circulation, return
temperat ure limitation an d sliding DHW prior ity. Optional cont rol of DHW
heating based on DHW demand. Frost protection and alarm function.
signals
2 x 3-point, 2 x 2-point087H380 0
1 x 3-point, 4 x 2-point087H3814
1 or 2 x 3-point, 4 x
2-point, 2 x 0 - 10 Volt
PWM
1 x 3-point, 7 x 2-point*
or
1 x 0 - 10 V control*, 7 x
2-point*
2 x 3-point, 7 x 2-point*087H3804
2 x 3-point, 2 x 0 - 10
Volt, 3 x 2-point
2 x 3-point, 5 x 2-point08 7H3813
2 x 3-point, 5 x 2-point087H3803
3 x 3-point, 5 x 2-point
or
3 x 0 - 10 V control*, 5 x
2-point
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Typ eApplication type description Controller output
A377
A390• Weather compensated control of flow tem perature in up to three heating
• Weather compensated flow temperature control of 2 heating circuits.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation.
• Temperature cont rol of DHW circuit with sto rage tank charging system or
storage tank with internal heat exchanger. DHW circulation pump control.
Optional DHW heating temperature control. Frost protection and alarm
function.
circuits. Room temperature compensation and sliding return temperature
limitatio n. Heating circuits wo rk independent in pa rallel or circuit 2 and 3
after circuit 1.
Control of flow temperature in up to three cooling circuits.
Room temperature compensa tion and return temperature limitation.
Cooling cir cuits work indep endent in paralle l or circuit 2 and 3 af ter circuit
1.
Temperature control of DHW tank charging circuit. Control of DHW heating
temperature. Return temperature limitation. DHW priority possibility.
Alarm functions related to flow temperatures.
Optional co ntrol of motorized cont rol valves by means of anal og signal, 0
- 10 volt, (3 x heating circuits only).
signals
3 x 3-point, 5 x 2-point08 7H3817
3 x 3-point, 3 x 0 - 10
Volt, 5 x 2-point
Code no.
087H3815
Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 installation guide and 1
set of multi-lingual user guides.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Operation
A
B
The graphical monochrome display (A) shows all
temperature values as well as status information
and is used for the setting of control parameters.
The display has backlight. Different favorite
displays can be selected. Navigation, browsing
and selecting the current item in the menus is
done by means of the dial (multi-func tional knob
(B)).
Examples of favorite displays:
The RCUs ECA 30 / 31 are used for remote setting
and override of ECL Comfort controller. By means
of the built-in room temperature sensor, the flow
temperature can be corrected to keep a constant
room temperature at comfort or saving
temperature. The ECA 30 / 31 is operated as an
ECL Comfort 310 with dial and backlighted display.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
FunctionsGeneral functions:
• The ECL Comfort 310 has all the required
functions of a modern electronic temperature
controller for heating and DHW applications.
• The controller can be used as master or slave in
systems with master / slave ECL Comfort 210 /
310 controllers.
• The ECL Application Key contains the application
software for flexible configuration. Furthermore,
an update of the controller software is done
automatically, if required.
• The ECL Comfort 310 contains, besides the
standard functions, log and alarm functions.
• The built-in Real Time Clock gives automatic
summer / winter time changeover, week and
holiday schedule.
• Motor protection, which ensures stable control
and a long life of the motorized control valve, is
available for most of the applications. In periods
without heat demand, the motorized control
valve is exercised to avoid blocking.
• Scheduled control (Comfort and Saving mode)
is based on a week program. A holiday program
gives the possibility to select days with comfort
or saving mode.
• The ECL Comfort 310 can receive pulses from a
heat or flow meter to limit the power or the flow.
Alternatively, the data can come from heat or
flow meter via the M-bus connection.
• In many applications analogue input (0 – 10 V)
is configured for pressure measuring among
others. The scaling is set in the controller.
• Some applications are configured to handle
digital input. This function can be used to have
an external switch to run comfort or saving
mode or react on a flow switch signal.
• The control parameters, propor tional band (Xp),
integration time (Tn), running time of the
motorized control valve and neutral zone (Nz)
can be set individually for each output (3-point
control).
• Motorized control valves in some applications
can be controlled with a 0 - 10 V signal.
• Several applications fulfil the demand for refill
water function and / or 2-pump control.
• Some applications can speed control circulation
pumps by means of 0 - 10 Volt or PWM signal.
Heating functions:
• The heat curve (relationship between outdoor
temperature and desired flow temperature) is
set by means of 6 coordinate points or a slope
value. Max. / min. limitation of the desired flow
temperature can be set.
• In some application sub-types (for example
A337, A347, A367, A375 and A377) the desired
flow temperature can be set by means of a
voltage in the range 0 - 10 volt.
• The return temperature limitation can work in
relation to the outdoor temperature or be a fixed
value.
• The heating cut-out function can switch OFF the
heating and stop the circulation pump at high
outdoor temperatures.
• Based on the room temperature the ECL Comfor t
310 can correct the desired flow temperature in
order to increase the comfort level.
• The optimizer function ensures heating in the
desired periods (the lower outdoor temperature,
the earlier cut-in of the heating).
• The ramping function makes a smooth cut-in of
the heating valuable (district heating
installations).
• The boost function makes a powerful cut-in of
the heating (boiler based installations).
• The circulation pump is controlled in relation to
heat demand and frost protection. In periods
without heat demand, the circulation pump is
exercised to avoid blocking.
• The saving function gives two possibilities:
· reduced flow temperature with fixed
reduction or reduction in relation to outdoor
temperature (the lower the outdoor
temperature, the less the reduction),
· heating off, still with active frost protection.
DHW functions:
• The Auto Tuning function with automatic setting
of control parameters for constant DHW
temperature is integrated in the application
A217, A266, A368 and A376. However, Auto
Tuning is only applicable with valves that are
approved for Auto Tuning, i.e. the Danfoss types
VB 2 and VM 2 with split characteristic as well as
logarithmic valves such as VF and VFS.
• The anti- bacteria function can follow a sche dule
program.
• The heating circuit can have sliding DHW priorit y.
CommunicationThe ECL Comfort 310 has:
• ECL 485 bus, non-galvanic isolated, for closed
communication between master, slave and
RCUs.
• RS 485 bus, galvanic isolated, for Modbus
communication to SCADA systems.
• M-bus, non-galvanic isolated, for M-bus
communication with meters.
• USB, type B, for ECL Tool (software for PC).
• Ethernet, RJ 45, for TCP / IP communication
to Internet (ECL Portal)
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - 230 V a.c.
ECL Comfort 310 wiring example
Supply voltage230 V a.c. - 50 Hz
Voltage range207 to 244 V a.c. (IEC 60038)
Power consumption5 VA
Max. load on relay outputs4(2) A - 230 V a.c. (4 A for ohmic load,
Max. load on triac outputs for actuators0.2 A - 230 V a.c.
2 A for inductive load)
Wiring - 24 V a.c.
ECL Comfort 310 wiring example
Do not connect 230 V a.c. powered components to a 24 V a.c. power supplied controller directly.
Use auxiliary relays (K) to separate 230 V a.c. from 24 V a.c.
Supply voltage24 V a.c. - 50 Hz
Voltage range21.6 to 26.4 V a.c. (IEC 60038)
Power consumption5 VA
Max. load on relay output4(2) A - 24 V a.c. (4 A for ohmic load,
2 A for inductive load)
Max. load on triac outputs for actuators1 A - 24 V a.c.
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Tender text:Electronic controller for heating and domestic hot water applications
1a
Electronic weather compensator for flow temperature control in heating and domestic hot water
installations.
Turn-push-dial, backlighted graphic display and menu-based operation in local languages.
The controller can operate multiple application uploaded by means of application software keys.
1b
• Heat curve setting in 6 coordinates or as slope.
• Flow temperature limitations.
• Room temperature compensation and Comfort / Saving periods according to week schedule.
• Holiday schedule.
• Return temperature limitation as a fixed value (DHW) or in relation to outdoor temperature
(heating).
• Pumps controlled in relation to heat demand and frost protection.
• Alarm functions and log pictures for all sensors.
• Manuel override of the individual outputs.
• Communication: M-bus (up to 5 meters), Modbus, Ethernet (e.g. internet connection to ECL Portal),
ECL 485 (internal data bus).
• Connection for commissioning / service via PC
• 6 temperature sensor (Pt 1000) inputs.
• 4 application related and configured inputs.
• 6 relay outputs
• 3 pairs of electronic output for noiseless operation of the motorized control valve.
Remote control unit ECA 30 / 31:
• Turn-push-dial, backlighted graphic display
• Integrated room temperature sensor
• Integrated humidity sensor (ECA 31 only)
Extension module ECA 32 enables:
• Additional 6 configurable inputs
• 2 pulse counters
• 4 relay outputs
• 3 analogue outputs
Extension module ECA 35 enables:
• Additional 2 configurable inputs
• 2 pulse counters
• 4 relay outputs
• 3 analogue outputs
• 4 PWM outputs
1c
Main data:
• Supply voltage, 230 V a.c., 50 Hz: ECL 310 and ECL 310 B
• Supply voltage, 24 V a.c., 50 Hz: ECL 310
• Power consumption: max. 5 VA
• Ambient temperature: 0 – 55 °C
• Storage temperature: -40 – 70 °C
2
Product characteristics:
• Protection class: IP 41
• DIN rail adaptor integrated
• Dimension (inclusive base part) L*W*H, 220*110*80 mm