Danfoss ECL Comfort 310 Data sheet

Data sheet
ECL Comfort 310 controller,
Designed in Denmark
Remote Control Units ECA 30 / 31 and Application keys
Description
ECL Comfort 310 controller series
ECL 310
The ECL Comfort 310 is an electronic weather compensated temperature controller in the ECL Comfort controller family for use in district heating, central heating and cooling systems. Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. Up to 4 circuits can be controlled.
The weather compensation function in the ECL Comfort controllers measures the outdoor temperature and controls the flow temperature to the heating system accordingly. The weather compensated heating system increases the comfort level and saves energy.
The ECL Comfort 310 controller is configured with a selected application by means of an ECL Application Key.
The web-based ECL Portal communicates with the ECL Comfort 310 for an effective and easy-to­use turnkey SCADA (Supervisor y Control And Data Acquisition) tool for all users, service personnel and at commissioning. Service level can be increased and/or service costs reduced. The heating and/or cooling installation is made accessible from virtually anywhere at any time via laptops or Smartphones which increases service level and reduces response time to alarms.
The ECL Tool software for ECL Comfort 310 offers possibilities for an alternative remote control in relation to ECL Portal and OPC server software.
ECL Comfort 310 is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application Key (Plug-and-Play) and user-friendly operation.
Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power.
The ECL Comfort 310 is easily operated by means of a dial (multi-functional knob) or a Remote Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language.
The ECL Comfort 310 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output.
6 Pt 1000 temperature sensors can be connected. In addition, 4 inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analogue input (0 – 10 V) or digital input.
Depending on application, one of the internal extension modules ECA 32 or ECA 35 (inserted into the controller’s base part) can give additional input and output signals.
© Danfoss | 2020.01
AI155886473192en-000602| 1
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Description (continued) The enclosure is designed for mounting on wall
and DIN rail. A variant ECL Comfort 310B (without display and dial) is available. It can be used for mounting inside a panel and is operated by means of the RCU ECA 30 / 31 which can be placed in front of the panel.
The ECL Comfort 310 can work as a stand-alone controller and communicate with up to two RCUs and an extension module ECA 32 or ECA 35 with additional inputs / outputs.
The ECL Comfort 310 can also work with up to 2 x RCUs, ECA 32 / 35 and other ECL Comfort 210 / 296 / 310 controllers via the ECL 485 communication bus.
Ethernet connec tion is integrated in the controller. Furthermore, Modbus communication to SCADA systems (Supervisory Control and Data Acquisition) and M-bus communication to heat meters are integrated.
ECL Application Key and applications:
Different ECL Application Keys make it easy for the ECL Comfort 310 hardware to run different applications. The ECL Comfort 310 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (basic application sketches are shown in the display), languages, factory settings and firmware.
Remote Control Unit (RCU):
The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL Comfort 310. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted pair cable for communication and power supply (ECL 485 communication bus).
The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substitutin g the built-in temperature sensor.
Furthermore, the ECA 31 has a built-in relative humidity sensor and the signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master/ slave system).
The ECL Application Keys, series A2xx can b e used in ECL Comfort 210, ECL Comfort 296 and ECL Comfort 310. Most of the A2xx application keys give extended functionalities when used in ECL Comfort 310, such as additional temperature sensors and M-bus communication. The ECL Application Keys, series 3xx can be used in ECL Comfort 310 only.
The application parameters are stored in the controller and are not affected by power break. The relevant ECL Application Keys for the ECL Comfort 210 / 296 / 310 controller can be found in the ordering section.
2 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Application keys, overview, sub-types included
ECL Comfort 210 / 296 ECL Comfort 310
Key
A214 A214.1, A214.2, A214.3, A214.4, A214.5,
A214.6
A217 A217.1, A217. 2, A 217.3 A217.1, A217. 2, A 217.3
A230 A230.1, A230.2, A230.3, A230.4 A230.1 *, A230.2 *, A230.3 *, A230.4 *
A231 A231.1, A 231.2 A231.1, A231.2
A232 A232.1 A2 32 .1
A237 A 2 37.1, A237. 2 A237.1, A2 37.2
A247 A 247.1, A247. 2, A3 47.3 A247.1, A 247. 2, A247. 3
A260 A26 0.1 A26 0.1
A266 A266.1, A266.2, A266.9, A266.10 A266.1 *, A266.2 **, A266.9 *, A266.10 *
A275 A275.1, A275.2, A275.3 A275.1, A275.2, A275.3
A319 A319.1, A319.2
A333 A333.1, A333.2, A333.3
A361 A361.1, A 361.2
A362 A3 62.1
A367 A 367.1, A367. 2
A368 A368.1, A368.2, A368.3, A368.4, A368.5,
A376 A376.1, A376.2, A376.3 *, A376.9, A376.10
A377 A 377.1, A377.2, A377.3
A390 A390.1, A390.2 *, A390.3, A390.11 *, A390.12 *,
A214.1, A214. 2, A214.3, A214 .4, A214. 5, A214.6 A314.1, A314.2, A314.3, A314.4, A314.5, A314.6, A314.7, A314.9
A317.1, A317. 2
A331.1, A331. 2
A332.1, A332.2, A332.3, A332.4
A337.1, A 337. 2
A347.1, A3 47.2, A 3 47. 3
A375.1, A375.2, A375.3, A375.4, A375.5
A368.6
A390.13 *
* When used in ECL 310 + ECA 32 / 35, 0 - 10 Volt controlled actuators can be used alternatively.
** When used in ECL 310 + ECA 32 / 35 a 0 - 10 Volt controlled actuator can, alternatively, be used for the heating circuit.
This is an overview of currently available application keys for the ECL Comfort controllers. Not all keys are for sale in your country. Please contact your local Danfoss sales company.
AI155886473192en-000602
© Danfoss | 2020.01 | 3
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Application examples All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve and so
on) are wired to the ECL Comfort ECL 210 / 296 / 310.
All applications from ECL Comfort 210 / 296 can run in ECL Comfort 310. Extra functions and communication facilities are enabled.
A214.1, ex. a: Cooling application, duct temperature based on room temperature.
S1
ECL 210 / 296 / 310
A1
M2
S5
X3
P2
F1
S3
S8S8S8
A214.2, ex. a: Heating application, heating temperature based on duct temperature.
S1
ECL 210 / 296 / 310
A1
S4
Danfoss
87H2113.13
Danfoss
87H2118.12
P2
S3
X3
S6
S7
S5
M1
F1
S4
S8S8S8
4 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A214.3, ex. a: Heating application, duct temperature based on room temperature.
S1
ECL 210 / 296 / 310
A1
M1
X3
S5
P2
S6
S7
F1
S3
S8S8S8
A214.5, ex. a: Heating / cooling application, duct temperature based on room temperature.
S4
Danfoss
87H2120.12
S1
P2
X3
ECL 210 / 296 / 310
M1
S5
S6
S7
A1
F1
M2
S8S8S8
S3
S4
Danfoss
87H2124.12
AI155886473192en-000602
© Danfoss | 2020.01 | 5
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A314.1, ex. a: Ventilation system with heating, passive cooling (outside air) and constant duct temperature control. Analogue controlled passive cooling stage (M2).
S1
P2
M2
A
ECL 310
+ ECA 32
S3
X3
S6
A1
M1
S5
F1
S7
A314.1, ex. b: Ventilation system with heating, cooling and duct temperature control. Analogue controlled cooling stage (M2).
S1
ECL 310
+ ECA 32
A1
S4
S8S8S8
S2
S2
Danfoss
87H2133.12
Danfoss
87H2128.12
P2
S3
X3
S6
S7
S5
M1
F1
M2
A
S4
S8S8S8
6 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A314.2, ex. b: Ventilation system with heating, cooling and room temperature control. Analogue controlled cooling stage (M2).
S1
X3
ECL 310
+ ECA 32
M1
S5
A1
M2
A
S2
P2
S6
S7
F1
S8S8S8
S3
S4
A314.3, ex. a: Ventilation system with heating and room temperature control. Speed controlled fan.
S1
ECL 310
S2
+ ECA 32
A1
Danfoss
87H2135.12
Danfoss
87H2131.12
S10
P2
X3
S6
S7
M1
S5
F1 / V1
S3
S4
S8S8S8
AI155886473192en-000602
© Danfoss | 2020.01 | 7
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A217.1, ex. a: DHW tank charging application.
A217.1, ex. b: DHW tank heating application.
S1
ECL 210 / 296 / 310
S2
M1
S5
A217.2, ex. a: DHW tank charging with preheating circuit.
S1
S2 S3
S3
P1
ECL 210 / 296 / 310
S4
A1
A1
S6
S6
S8
P3
Danfoss
87H2068.13
Danfoss
87H2071.13
8 | © Danfoss | 2020.01
M1
S5
P1
A
S8
B
P2
P3
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A217.3, ex. a: DHW heating.
A217.3, ex. c: DHW heating on demand (flow switch). With or without circulation.
A230.1, ex. a: Indirectly connected heating system. Wind compensation as option.
AI155886473192en-000602
© Danfoss | 2020.01 | 9
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A230.2, ex. a: Indirectly connected cooling system (district cooling).
A230.3: Indirectly connected heating system. Compensation for too high relative humidity (measured by ECA 31). Wind compensation as option.
10 | © Danfoss | 2020.01
A230.4: Indirectly connected heating system. Static pressure measurement / alarm. Monitoring of DHW - and DHW circulation return temperatures.
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A231.2: Indirectly connected heating system with 2-pump control and refill water function.
A331.2, ex. a: Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control.
AI155886473192en-000602
A232.1, ex. a: Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature.
© Danfoss | 2020.01 | 11
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A332.1, ex. a: Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature. Optional return temperature limitation.
A332.2, ex. a: Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew point temperature. Optional return temperature limitations.
A332.3: Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew point temperature. Optional return temperature limitations. Advanced instantaneous DHW temperature control.
12 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A332.4: Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature. External override of heating / cooling mode. Optional return temperature limitation.
ECL 310
A1
S8
S7
S9
DanfossS187H1496.10
S6
M1
S3
X3
X2
S10
A237.1 / A337.1, ex. a: Indirectly connected heating and DHW system.
S2
P1
S5
M2
AI155886473192en-000602
A237.2 / A337.2, ex. a: Indirectly connected heating and DHW charging system.
© Danfoss | 2020.01 | 13
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A247.1, ex. a: Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority.
A247.2, ex. a: Indirectly connected heating and DHW tank charging system with preheating circuit. Parallel mode or DHW priority.
14 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A247.3, ex. a: Indirectly connected heating and advanced DHW tank charging system with preheating circuit. Parallel mode or DHW priority.
A347.1, ex. a: Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority.
S1
M2
M1
S5
S2
S3
S4
ECL 310
B
A1
P1
S6
S8
P2
S7
A
P3
Danfoss
87H2057.11
AI155886473192en-000602
© Danfoss | 2020.01 | 15
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A347.2, ex. a: Indirectly connected heating and DHW tank charging system with preheating circuit. Parallel mode or DHW priority.
A260.1, ex. a: Two heating systems.
16 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A260.1, ex. d: Two heating systems. Circuit 2 is a sub-circuit of circuit 1.
A266.1, ex. a: Heating and direct DHW heating system. Parallel mode or DHW priority.
AI155886473192en-000602
© Danfoss | 2020.01 | 17
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A266.2, ex. a: Heating and direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand (flow switch).
A266.9, ex. a: Heating and direct DHW heating system. Pressure monitoring / alarm. Universal alarm input. Parallel mode or DHW priority.
18 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A266.10, ex. a: Heating and direct DHW heating system. Pressure monitoring / alarm. Universal alarm input. Parallel mode or DHW priority. S7 is pulse based flow or energy meter for related limitation.
A275.1, ex. a: Heating system with 1-stage boiler.
S1
S3
S5
B1
ECL 210 / 296 / 310
P1
Danfoss
A1
S7
*
87H2163.13
1
AI155886473192en-000602
© Danfoss | 2020.01 | 19
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A275.2, ex. a: Heating system with 1-stage boiler and DHW tank.
S1
ECL 210 / 296 / 310
A1
S3
P1
S5
*
B1
P3
A275.3, ex. a: Heating system with 1-stage boiler, mixing circuit and DHW tank.
S6
S7
Danfoss
87H2165.12
1
2
S1
ECL 210 / 296 / 310
Danfoss
87H2169.13
M2
S4
P4
S2
S3
P1
S5
B1
P3
*
S6
S8
2
S7
1
3
20 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A375.1, ex. a: Up to 8 x boiler ON / OFF control for a heating circuit.
S1
S3
B1 B8
S5
ECL 310
+ ECA 32
P1
A1
S7
*
A375.2, ex. a: Up to 8 x boiler ON / OFF control for a heating circuit and a DHW circuit. Optional DHW priority.
S1
S3
ECL 310
+ ECA 32
A1
S7
Danfoss
87H2182.10
Danfoss
87H2188.10
B1 B8
P1
S5
*
S6
P4
P3
AI155886473192en-000602
© Danfoss | 2020.01 | 21
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A375.3, ex. a: Up to 8 x boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit (3). Optional DHW priority.
S1
S3
B1 B8
S5
ECL 310
+ ECA 32
M2
A1
S4
P4
S2
P1
*
S6
P3
A375.4, ex. a: Heating system with 1-stage boiler ON / OFF controlled or 0 - 10 Volt controlled. Pressure monitoring / alarm.
Danfoss
87H2189.10
S8
S7
S1
B1
V1
S3
S5
S9
P1
ECL 310
+ ECA 32
*
A1
S7
Danfoss
87H1544.10
1
22 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A
A
A
A
A
A
A
A
A375.5, ex. a: Heating system with 1-stage boiler ON / OFF controlled or 0 - 10 Volt controlled. Mixing circuit for second heating circuit. DHW tank heating. Pressure monitoring / alarm.
S1
S3
S5
B1
V1
Burner control overview:
ECL 310
Danfoss
M2
+ ECA 32
S4
A1
S8
P4
87H1545.10
2
S2
S9
P1
*
S7
1
S6
3
P5
P3
275.1
275.2
275.3
375.1
375.2
375.3
375.4
375.5
ECL 310ECL 210
R2 R2 R3 R4 R5
1
1
1
1
1
1
3 4
1
1
1
1
Triac 6
Triac 5
7
2
2
7
R7 R8 R9 R10
5
8
3
3
8
ECA 32
6
7
821
4
5
6
4
5
6
R2-R10 = relay nos. in ECL / ECA 32
A319.1: Indirectly connected charging system with 2 temperature sensors in buffer. Heating system connected directly to buffer. Pump P3 speed controlled in relation to differential pressure S9.
Danfoss
87H2185.11
AI155886473192en-000602
© Danfoss | 2020.01 | 23
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A319.2: Indirectly connected charging system with 2 temperature sensors in buffer. Heating system connected to buffer via mixing valve. Pump P3 speed controlled in relation to differential pressure S9.
A333.1, ex. a: Heating system with control of 1 or 2 circulation pumps. Refill water function with control of 1 or 2 pumps. Pressure measurements in the system.
24 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A333.2, ex. a: Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.
A333.3, ex. a: Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Control valve M1 is 0 ­10 V controlled. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.
AI155886473192en-000602
© Danfoss | 2020.01 | 25
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A361.2, ex. a: 2 x heating systems with two-pump control and refill water function. Supply temperature dependent flow temperature control.
A362.1, ex. a: Cascade control of heat exchangers. Indirectly connected system with 2 x HEX, each managed by means of a 0 - 10 Volt controlled motorized control valve (MCV). Each HEX circuit has its own circulation pump. Cascade control can manage up to 6 heat exchangers by using additional ECL 310.
S1
V1
S5
V2
S6
ECL 310
+ ECA 32
S3
S4
S9
S10
A1
P1
P2
S8
S7
O1
O2
S15
S16
S2
V3 (0 - 10 V)
87H1754.10
Danfoss
26 | © Danfoss | 2020.01
Other solutions, such as 3-point controlled actuators for control valves or a combination 0 - 10 V / 3-point, are possible.
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A367.1, ex. a: System with 2 heating circuits and secondarily connected DHW tank with internal heat exchanger. Optional DHW priority.
S1
M2
M1
S4
S2
S3
S5
ECL 310
A1
P5
P1
S6
S8
P2
A367.2, ex. a: System with 2 heating circuits and secondarily connected DHW tank charging system. Optional DHW priority.
P3
Danfoss
S9
S7
87H2073.11
S1
S4
M2
S2
P1
S3
M1
S5
ECL 310
P5
P2
Danfoss
A1
S9
P4
S6
S8
87H2078.11
(S7)
(S7)
P3
AI155886473192en-000602
© Danfoss | 2020.01 | 27
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A368.2, ex. a: Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps.
A368.4, ex. a: Heating system with two-pump control and refill water function with 1 or 2 pumps. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps. Pressure measurements in the systems.
28 | © Danfoss | 2020.01
A368 has in total 6 subtypes with differences in temperature / pressure measurements and refill / circulation pump control.
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A376.1, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority.
S1
ECL 310
A1
S3
P2
M2
S5
S9
P3
M3
S10
S4
M1
S6
P1
A376.2, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand (flow switch).
Danfoss
87H2097.11
S2
1
S7
2
3
S1
M2
S5
M3
S10
S7
M1
S6
ECL 310
Danfoss
A1
S3
P2
S9
P3
S4
87H2099.11
(S2)
1
(S2)
2
3
S8
P1
AI155886473192en-000602
© Danfoss | 2020.01 | 29
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A376.3, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Control valves M1, M2 and M3 are 0 - 10 V controlled.
S1
M2
S5
A
M3
S10
A
M1
S6
A
ECL 310
Danfoss
+ ECA 32
S3
P2
S9
P3
S4
A1
87H2101.11
S2
1
S7
2
3
P1
A376.9, ex. a: Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Pressure measurements and temperature monitoring in the system.
30 | © Danfoss | 2020.01
A376.10 is like A376.9, but S11 and S12 are pressure sensors.
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A377.1, ex. a: Two heating circuits and one DHW tank charging system. Parallel mode or DHW priority.
S1
ECL 310
Danfoss
87H2139.12
A1
S4
P5
M3
S2
S3
P2
M2
S5
S9
M1
S10
P1
S7
S6
A
S8
B
P4
P3
A377.2, ex. a: Two heating circuits and one DHW tank charging system. Control of the DHW heating temperature. Parallel mode or DHW priority.
S1
S4
M3
S2
S3
M2
S5
ECL 310
Danfoss
A1
P5
P2
M1
S9
P1
S10
S6
A
P3
S8
B
P4
87H2141.12
AI155886473192en-000602
© Danfoss | 2020.01 | 31
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A390.1, ex. a: 3 x indirectly connected heating circuits.
A390.2, ex. a: 3 x indirectly connected heating circuits; Actuators for control valves are controlled by 0 - 10 Volt signal.
32 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A390.3, ex. a: 3 x indirectly connected cooling circuits. Cooling to rooms can be based on Air Handling Units (AHU).
A390.11, ex. a: Three independent heating circuits. The heating circuits are indirectly con nected. DHW charging circuit 4 is com bined with circuit 1. Optional DHW priority.
AI155886473192en-000602
© Danfoss | 2020.01 | 33
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A390.12, ex. a: Two indirectly connected heating cir cuits. One advanced DHW charging cir cuit. Optional DHW priority.
S1
M3
S2
M2
S5
S9
M1
S10
P1
ECL 310
Danfoss
A1
S4
P5
S3
P2
S7
B
P4
S6
A
S8
P3
87H2139.12
A390.13, ex. a: Two indirectly connected heating cir cuits and one DHW charging circuit. Always DHW charging priority.
34 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Ordering Controller, base parts and accessories:
Typ e Designation Code no.
ECL Comfort 310 Universal hardware - 230 V a.c.
ECL Comfort 310 Universal hardware - 24 V a.c.
ECL Comfort 310B Universal hardware - 230 V a.c.
ECL Comfort 310 base part For mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted
Base part is not included. Installation guide (no text) is included.
Base part is not included. Installation guide (no text) is included.
Without display and dial. Requires a Remote Control Unit. Base part is not included. Installation guide (no text) is included.
in an ECL Comfor t 310 base part (for future upgrade). Installation guide (no text) and cable inlet accessories is included.
Remote Control Units and accessories
Typ e Designation Code no.
ECA 30 Remote Control Unit with an integrated room temperature sensor and
ECA 31 Remote Control Unit with an integrated room temperature sensor and a
ECA 30 / 31 frame kit for mounting in panel front
ECA 32 Internal extension module with 6 inputs (Pt 1000 / analog / digital). 3 x
ECA 35 Internal extension module with 2 inputs (P t 1000 / analog / digital). 3 x
possibility for connecting an external Pt 1000 room temperature sensor. Base part for mounting on wall included. Installation guide (no text) is included.
humidity sensor. Possibility for connecting an external Pt 1000 room temperature sensor. Used for dedicated applications. Base par t for mounting on wall included. Installation guide (no text) is included.
For mounting in a panel cut-out. Format 144 × 96 mm, actual cut-out 139 × 93 mm. Installation guide (no text) is included.
analog (0 - 10 Volt) outputs. 4 x relay outputs. To be placed in the ECL 310 base part. See separate data sheet.
analog (0 - 10 Volt) outputs and 4 x PWM outputs. 4 x relay outputs. To be placed in the ECL 310 base part. See separate data sheet.
087H304 0
087H304 4
087H3050
087H3230
087H3200
087H3201
087H3236
087H3202
087H3205
Accessories:
Typ e Designation Code no.
ECA 99 230 V a.c. to 24 V a.c. transformer (35 VA) 08 7B115 6
AI155886473192en-000602
© Danfoss | 2020.01 | 35
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys
Typ e Application type description Controller output
A214
A217
A230
A231
A232
A237
A247
A260
• Temperature cont rol (heating / cool ing) of ventilation sy stems. Duct / ro om temperature control. Return temperature limitation. Flow / power limitation. Fire and frost protection as well as alarm function.
• The A214 applicatio n key contains applic ations related to ECL Com fort 310 for increased functionalities (control of rotating heat-exchanger).
• Advanced tem perature control o f DHW (Domestic H ot Water) circuit with/ without storage charging system. Circulation pump control. Return temperature limitation. Frost protection and alarm function.
• The A217 application key co ntains applicat ions related to ECL Comf ort 296 / 310 for increased functionalities (M-bus).
• (A230.1) Weather compensated flow temperature control of heating systems. Circulation pump control. Room temperature control and sliding return temp erature limita tion. Flow / power lim itation. Wind com pensation, frost protection and alarm function.
• (A230.2) Flow temperature control of cooling systems. Compensation for outdoor and room temperatures. Return temperature limitation.
• (A230.3) Weather compensated control of flow temperature in a heating circuit. Room temperature compensation. Compensation for too high relative humidity. Sliding return temperature limitation. Power / flow limitation. Compensation for wind. Alarm function related to flow temperature.
Monitoring of temperatures in self-acting temperature controlled DHW
circuit.
• (A230.4) Weather compensated control of flow temperature in a heating circuit. Room temperature compensation. Sliding return temperature limitation. Power / flow limitation. Alarm function related to flow temperature and static pressure.
Monitoring of temperatures in self-acting temperature controlled DHW
circuit.
• The A230 application key works in ECL Comfort 296 / 310 for increased functionalities (M-bus).
• The A230 application key works in ECL Comfort 310, including EC A 32, for 0 - 10 Volt control of actuator for control valve.
• Weather compensated flow temperature control of heating systems. 2-pump control for circulation and refill water function. Sliding return temperature limitation. Frost protection and alarm function.
• The A231 applic ation key contains app lications relate d to ECL Comfort 310 for increased functionalities (2 pumps for refill water and M-bus).
• Weather compensated flow temperature control of heating / cooling circuit(s). Automati c change-ove r between hea ting and cooling. Ci rculation pump control. Dew point (cooling mode only) and surface temperature compensation.
• The A232 appli cation key contains a pplications rel ated to ECL Comfort 310 for increased functionalities (return temperature limitation and separated control of heating and cooling circuits).
• Weather compensated flow temperature control of heating systems. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Temperature control of secondar ily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circu it in connectio n with primarily con nected stora ge tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function.
• The A237 appli cation key contains ap plications rel ated to ECL Comfort 29 6 / 310 for increased functionalities (M-bus).
• Weather compensated flow temperature control of heating systems. Circulation pump control. Sliding return temperature limitation. Flow / power limitation. Temperature control of DHW circuit with storage tank charging system. DHW circulation pump control through the storage tank or the heat-exchanger. Frost protection and alarm function.
• The A247 applicat ion key contains app lications relate d to ECL Comfort 310 for increased functionalities (room temperature sensor and M-bus).
• Weather compensated flow temperature control of heating systems. Circulation pump control, room temperature control and sliding return temperat ure limitation fo r two independ ent heating circuit s. Flow / power limitation, frost protection and alarm function.
• The A260 application key works in ECL Comfort 296 / 310 for increased functionalities (M-bus).
signals
2 x 3-point, 2 x 2-point 087 H3811
1 x 3-point, 3 x 2-point 087H38 07
1 x 3-point, 2 x 2-point 087H3802
1 x 3-point, 3 x 2-point 087H3805
1 x 3-point, 3 x 2-point 08 7H38 12
1 x 3-point, 3 x 2-point 087H3806
2 x 3-point, 3 x 2-point 087H3808
2 x 3-point, 2 x 2-point 087H3801
Code no.
36 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Typ e Application type description Controller output
A266
A275 • Weather compensated flow temperature control of 1-stage boiler based
A319 • Weather compensated control of flow temperature in a heating circuit or
A333 • Weather compensated flow temperature control of a heating system.
A361 • Weather compensated flow temperature control of 2 heating circuits.
A362 • Weather compensated control of flow temperature in a heating circuit or
A367 • Weather compensated flow temperature control of 2 heating circuits.
A368 • Weather compensated flow temp erature control of a heating circuit.
A376 • Weather compensated flow temperature control of 2 heating circuits.
• Weather compensated flow temperature control of heating systems. Circulation pump control, room temperature control and sliding return temperature limitation.
• Temperature control of DHW circuit with DHW circulation. Return temperature limitation, sliding DHW priority, frost protection and alarm function. Optional control of DHW heating based on DHW demand.
• The A266 application key works in ECL Comfort 310 for increased functionalities (M-bus).
• The A266 application key work s in ECL Comfort 310, including ECA 32, for 0 - 10 Volt control of actuators for control valves; exception: A266.2, DHW circuit
heating systems. One direct heating circuit and one mixing circuit. Circulation pumps control, room temperature control and sliding return temperature limitation.
• Temperature control of DHW storage tank with internal heat exchanger. Frost protection and alarm function.
• The A275 applica tion key contains app lications relate d to ECL Comfort 310 for increased functionalities (multiple boiler stages).
• The A375 application key (subtypes A375.4 and A375.5) works in ECL Comfort 310, includ ing ECA 32, for 0 - 10 Volt control of bo iler temperatu re.
combined h eating / DHW circuit s based on an advan ced buffer tempe rature control. Charging pump is speed controlled, based on 0 - 10 Volt or PWM (Pulse Width Modulated) signal. Discharging of buffer is avoided according to built-in lo gic. Differenti al pressure can be ma intained by means o f speed controlled circulation pump (0 - 10 Volt or PWM).
Optional sliding return temperature limitation. Relay output present for buffer heating demand; override signal for remote setting of desired flow temperature. Alarm functions are related to flow and buffer temperatures.
ON / OFF and spe ed control of 1 or 2 circulation pumps and sliding return temperat ure limitation. Fl ow / power limitatio n. Frost protect ion and alarm function. ON / OFF and speed control of 1 or 2 refill water pumps. Refill water storage control. Pressure release function. Pressure and temperature monitoring. Frost protection and alarm function.
Supply temperature dependent flow temperature control. 2-pump control for circulation. Sliding return temperature limitation. Flow / power limitaion. Refill water function. Frost protection and alarm function.
combined heating / DHW circuits, based on ad vanced cascade control of 2 heat exchangers (HEX). Control valve characteristics are taken into consideration and flow in unused HEX circuit can be stopped.
Optional sliding return temperature limitation. Scheduled shift for inversed cascade (HEX-1 - HEX-2 and HEX-2 - HEX-1) can be set. Override inputs for
start o f HEX-1 and HEX-2 are avail able. M-Bus bas ed signal can be used f or flow / energy limitation.
Up to 6 heat excha ngers can be cas cade controlled b y 1, 2 or 3 ECL Comfo rt
310 control lers, each equipped with the application key A362; the ECL controllers are interconnected by means of the ECL 485 Bus.
Alarm functions are related to flow and flow temperatures.
Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation.
• Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional O N / OFF control of the DHW circ uit in connection w ith primarily connected storage tank with internal heat exchanger.
DHW circulation pump control. Frost protection and alarm function.
Supply temperature dependent flow temperature control. 2-pump control for circulat ion. Sliding ret urn temperature l imitation. Flow / p ower limitation Flow / power limitation and refill water function.
• Temperature control of a DHW circuit with DHW circulation, return
temperature limitation and sliding DHW priorit y. Frost protection and alarm function.
Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation.
• Temperature control of a DHW circuit with DHW circulation, return temperat ure limitation an d sliding DHW prior ity. Optional cont rol of DHW heating based on DHW demand. Frost protection and alarm function.
signals
2 x 3-point, 2 x 2-point 087H380 0
1 x 3-point, 4 x 2-point 087H3814
1 or 2 x 3-point, 4 x 2-point, 2 x 0 - 10 Volt PWM
1 x 3-point, 7 x 2-point* or 1 x 0 - 10 V control*, 7 x 2-point*
2 x 3-point, 7 x 2-point* 087H3804
2 x 3-point, 2 x 0 - 10 Volt, 3 x 2-point
2 x 3-point, 5 x 2-point 08 7H3813
2 x 3-point, 5 x 2-point 087H3803
3 x 3-point, 5 x 2-point or 3 x 0 - 10 V control*, 5 x 2-point
Code no.
087H3847
087 H3818
087H3845
087H3810
AI155886473192en-000602
* ECA 32 module needed
© Danfoss | 2020.01 | 37
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Typ e Application type description Controller output
A377
A390 • Weather compensated control of flow tem perature in up to three heating
• Weather compensated flow temperature control of 2 heating circuits. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation.
• Temperature cont rol of DHW circuit with sto rage tank charging system or storage tank with internal heat exchanger. DHW circulation pump control. Optional DHW heating temperature control. Frost protection and alarm function.
circuits. Room temperature compensation and sliding return temperature limitatio n. Heating circuits wo rk independent in pa rallel or circuit 2 and 3 after circuit 1.
Control of flow temperature in up to three cooling circuits. Room temperature compensa tion and return temperature limitation.
Cooling cir cuits work indep endent in paralle l or circuit 2 and 3 af ter circuit
1.
Temperature control of DHW tank charging circuit. Control of DHW heating
temperature. Return temperature limitation. DHW priority possibility.
Alarm functions related to flow temperatures. Optional co ntrol of motorized cont rol valves by means of anal og signal, 0
- 10 volt, (3 x heating circuits only).
signals
3 x 3-point, 5 x 2-point 08 7H3817
3 x 3-point, 3 x 0 - 10 Volt, 5 x 2-point
Code no.
087H3815
Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 installation guide and 1 set of multi-lingual user guides.
Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C):
Typ e Designation Code No.
ESMT Outdoor temperature sensor 08 4N1012
ESM-10 Room temperature sensor 087 B116 4
ESM -11 Pipe surface temperature sensor 087 B1165
ES MB-12 Universal temperature sensor 087 B118 4
ESMC Pipe surface temperature sensor incl. 2 m cable 087N0011
ESMU -100 Immersion sensor, 100 mm, copper 087 B118 0
ESM U-250 Immersion sensor, 250 mm, copper 0 87B 1181
ESMU -100 Immersion sensor, 100 mm, stainless steel 087B1182
ESM U-250 Immersion sensor, 250 mm, stainless steel 0 87B 1183
Typical ordering, types:
Reference, additional products / software:
Accessories and spare par ts:
Pocket Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180) 0 87 B119 0
Pocket Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181) 087 B1191
Pocket Immersion, stainless steel 100 mm, for ESMB-12, (087B1184) 087 B1192
Pocket Immersion, stainless steel 250 mm, for ESMB-12, (087B1184) 087B1193
ECL Comfort Controller Base part Appl. key Remote Control Unit Temperature sensors Actuators /
ECL 310, 230 V a.c. ECL 310 B, 230 V a.c. ECL 310, 24 V a.c.
ECL Portal Access to the ECL Comfort 310 via a web browser.
ECL Tool Sof tware for laptop. Connect ECL Comfort 210 / 296 /
OPC server For ECL Comfort 310 (Modbus or TCP Ethernet
for ECL 310 A2xx
A3xx
After having arranged an account, access to the ECL Comfort 310 can also be done via a Smar t phone.
310 directly to laptop for e.g. parameter lists, commissioning reports.
connection).
ECA 30 ECA 31
ESMT (outdoor) ESM-11 (pipe surface) ESMC (pipe surface) ESMU (immersion) ESM-10 (roo m) ESMB-12 (universal)
See separate data sheet
Download from Internet
See separate data sheet and download from Internet
valves
see dedicated literature
38 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Operation
A
B
The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters. The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-func tional knob (B)).
Examples of favorite displays:
The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL Comfort 310 with dial and backlighted display.
AI155886473192en-000602
© Danfoss | 2020.01 | 39
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Functions General functions:
• The ECL Comfort 310 has all the required functions of a modern electronic temperature controller for heating and DHW applications.
• The controller can be used as master or slave in systems with master / slave ECL Comfort 210 / 310 controllers.
• The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required.
• The ECL Comfort 310 contains, besides the standard functions, log and alarm functions.
• The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule.
• Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking.
• Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode.
• The ECL Comfort 310 can receive pulses from a heat or flow meter to limit the power or the flow. Alternatively, the data can come from heat or flow meter via the M-bus connection.
• In many applications analogue input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller.
• Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal.
• The control parameters, propor tional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control).
• Motorized control valves in some applications can be controlled with a 0 - 10 V signal.
• Several applications fulfil the demand for refill water function and / or 2-pump control.
• Some applications can speed control circulation pumps by means of 0 - 10 Volt or PWM signal.
Heating functions:
• The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set.
• In some application sub-types (for example A337, A347, A367, A375 and A377) the desired flow temperature can be set by means of a voltage in the range 0 - 10 volt.
• The return temperature limitation can work in relation to the outdoor temperature or be a fixed value.
• The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures.
• Based on the room temperature the ECL Comfor t 310 can correct the desired flow temperature in order to increase the comfort level.
• The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating).
• The ramping function makes a smooth cut-in of the heating valuable (district heating installations).
• The boost function makes a powerful cut-in of the heating (boiler based installations).
• The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking.
• The saving function gives two possibilities:
· reduced flow temperature with fixed reduction or reduction in relation to outdoor temperature (the lower the outdoor temperature, the less the reduction),
· heating off, still with active frost protection.
DHW functions:
• The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the application A217, A266, A368 and A376. However, Auto Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS.
• The anti- bacteria function can follow a sche dule program.
• The heating circuit can have sliding DHW priorit y.
Communication The ECL Comfort 310 has:
ECL 485 bus, non-galvanic isolated, for closed communication between master, slave and RCUs.
RS 485 bus, galvanic isolated, for Modbus communication to SCADA systems.
M-bus, non-galvanic isolated, for M-bus communication with meters.
USB, type B, for ECL Tool (software for PC).
Ethernet, RJ 45, for TCP / IP communication to Internet (ECL Portal)
40 | © Danfoss | 2020.01
Master / slave connections
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Languages
Menu languages are selectable among approx. 22 languages. See “Language list”.
General data ECL Comfort controller and RCU data:
ECL Comfort 310 / 310B ECA 30 / 31
Ambient temperature 0 - 55 °C
Storage and transportation temperature -40 - 70 °C
Installation Installation must be avoided if there is a risk for condensation (dew)
Mounting To be mounted on a vertical wall and
Connections Terminals in base part Terminals in base part
Number of inputs 8 in total:
Temperature sensor type Pt 1000 (1000 ohm at 0 °C), IEC 751B
Digital input 12 V pull-up possible
Analog input 0 - 10 V, resolution 9 bits -
Pulse input, frequency range (selected applications)
Weight 0.46 / 0.42 kg 0 .14 kg
Display (ECL Comfort 310 and ECA 30 / 31 only)
Setting (ECL Comfort 310 and ECA 30 / 31 only)
Setting (ECL Comfort 310 B) ECA 30 / 31
Data logging Up to 10 days for 14 parameters
Min. backup time for time and date 72 hours -
Backup of settings and data Flash memor y Flash memory
Grade of enclosure IP 41 IP 20
-marking in accordance with the
standards
Temperature control Complies with EN 60730
*) Configured at application upload.
turned horizontally or on a DIN rail (35 mm)
6 temperature sensors 4*) Pt 1000 sensor, digital, analogue or pulse
Range: -60 – 150 °C
Activation of a digital input must be done with a potential free switch / contact.
For monitoring: 0.01 - 200 Hz For limitation: Minimum 1 Hz (recommended) and regular pulses for having a stable control.
Graphical monochrome with backlight 128 × 96 dots Display mode: Black background, white text
Dial with intuitive push and turn function
EMC (ElectroMagnetic Compatibility Directive) LVD (Low Voltage Directive) RoHS (Restriction of Hazardous Substances Directive)
Furthermore, English is always uploaded in parallel to the selected language.
To be mounted on a ver tical wall and turned horizontally or in a panel cut-out
-
Alternative to built-in room temperature sensor: P t 10 00 (1000 ohm at 0 °C), IEC 751B
-
-
AI155886473192en-000602
ECL application key:
Storage type Flash memory
Segmentation Part 1: Application data, not changeable
Part 2: Factory settings, not changeable Part 3: Updating SW for the ECL Comfort controller, not changeable Part 4: User settings, changeable
Applications A2xx keys work in ECL Comfort 210 and ECL Comfort 310
A3xx keys work in ECL Comfor t 310 only
Lock function If not inser ted in the ECL Comfort controller, all set tings can be seen, but not
changed
Menu languages Menu languages are selectable among approx. 22 languages. See “Language list”.
© Danfoss | 2020.01 | 41
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL 485 communication bus data:
Purpose Only for internal connec tions between ECL Comfort 210 / 296 /
Connection Terminals in base part
Cable type Shielded cable, 2 x twisted pair,
Max. total cable length (bus cable + sensor cables) 200 m in total (inclusive sensor cables)
Max. number of ECL slaves connected Units with unigue address (1 - 9): 9
Max. number of Remote Control Units connected 2
Data sent from master Date
Data sent from addressed slave controller Desired flow temperature from each circuit
Data sent from ECA 30 / 31
310 and ECA 30 / 31. (Danfoss proprietary bus)
Non-galvanic isolated
Min. cross section: 0,22 mm (AWG 24). Examples: LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5
Units with address “0”: 5
Time Outdoor temperature Desired room temperature DHW-priority signal
Actual and desired room temperature
Function selector mode
(ECA 31) Relative humidit y
Modbus communication data:
Purpose For SCADA system
Connection Terminals 34 and 35 in base part. Modbus reference (terminal
Protocol Modbus RTU
Cable type Shielded cable, 2 x twisted pair + Signal GND.
Max. bus cable length 1200 m (dependent on cable t ype and installation).
Communication speed Half duplex.
Serial mode 8 data bit, even parity and 1 stop bit.
Network According to the standard Modbus Serial Line Implementation
36) must be connected. Galvanic isolated (500 V ).
Min. cross section: 0,22 mm2 (AWG 24). Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)
9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit/s
Guide V1.0.
M-bus communication data:
Purpose Connection to heat meters, max. 5 heat meters
Connection Terminals 37 and 38 in base par t.
M-Bus master according to DS / EN 1434-3: 1997
Cable type 2 x 0,8 mm2
Max. cable length 50 m
Baud rate 300 baud (adjustable)
Update time 60 s (adjustable)
Gateway function Allows the ECL Portal to read energy meters directly
Supported heat meters Infocal 6 and many other marks and types.
Transmitted heat meter data Heat meter type dependent:
Recommendations: Danfoss recommends 230 V a.c. supplied heat meters
Non-galvanic isolated
Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)
Information about other heat meters on request
• Primary flow temperature
• Primary return temperature
• Actual flow / accumulated flow
• Actual heat / power
• Accumulated heat energy
USB communication data:
USB CDC (Communication Device Class) For service purposes
Modbus over USB Similar to the serial Modbus, but with relaxed timing
Connection, cable type Standard USB cable (USB A ----- --- USB B)
(Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM port)
42 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Ethernet communication (Modbus / TCP) data:
Purpose For SCADA system
Connection RJ45 female connector
Protocol Modbus / TCP
Cable type Standard Ethernet cable (CAT 5)
Max. Bus cable length According to Ethernet standard
Auto cross-over detection Enabled
Default Ethernet address (IP address) 192.16 8.1.100
Port number 502 (Modbus / TCP por t)
Number of connections 1
Security Must be provided by Ethernet infrastructure
A port: USB (type B female plug) B port: Ethernet (RJ45, female plug) C port: ECL Application Key
Language list
Comparison with ECL Comfort 210 / 296
Bulgarian Estonian Latvian Slovak
Croatian Finnish Lithuanian Slovenian
Czech French Polish Spanish
Danish German Romanian Swedish
Dutch Hungarian Russian
English Italian Serbian
The selected language + English is uploaded at application upload.
ECL Comfort 310 ECL Comfort 210 ECL Comfort 296
M-bus communication Ye s No Yes
Modbus connection Yes, galvanic isolated Yes, non-galvanic isolated Yes, galvanic isolated
Ethernet Yes, RJ45 connection, Modbus /
Inputs 10 8 8
Relay outputs 6 4 4
Valve actuator outputs 3 x 3-point 2 x 3-point 2 x 3-point
Extension of inputs / outputs Yes, ECA 32, placed in base part.
Application keys A2xx and A3x x A2xx A2xx
Front dimensions (W x H, mm)
Supply voltage 230 V and 24 V 230 V 230 V
TCP. For SCADA solutions and ECL Portal
• 6 inputs
• 2 pulse inputs
• 3 analogue outputs (0 - 10 V)
• 4 relays Alternative, ECA 35:
• 2 inputs
• 2 pulse inputs
• 3 analogue outputs (0 - 10 V)
• 4 PWM outputs
• 4 relays
220 x 110 220 x 110 144 x 96
No Yes, RJ45 connec tion,
Modbus / TCP. For SCADA solutions and ECL Portal
No No
AI155886473192en-000602
© Danfoss | 2020.01 | 43
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - 230 V a.c.
ECL Comfort 310 wiring example
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Max. load on relay outputs 4(2) A - 230 V a.c. (4 A for ohmic load,
Max. load on triac outputs for actuators 0.2 A - 230 V a.c.
2 A for inductive load)
Wiring - 24 V a.c.
ECL Comfort 310 wiring example
Do not connect 230 V a.c. powered components to a 24 V a.c. power supplied controller directly. Use auxiliary relays (K) to separate 230 V a.c. from 24 V a.c.
Supply voltage 24 V a.c. - 50 Hz
Voltage range 21.6 to 26.4 V a.c. (IEC 60038)
Power consumption 5 VA
Max. load on relay output 4(2) A - 24 V a.c. (4 A for ohmic load,
2 A for inductive load)
Max. load on triac outputs for actuators 1 A - 24 V a.c.
44 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - input
Wiring - ECA 30 / 31 Remote Control Unit
Base part
Dimensions
Wiring of ECL Comfort 310 / 310B and ECA 30 / 31
Supply voltage From ECL 485 communication bus
Power consumption 1 VA
External room temperature sensor Pt 100 0 (ESM-10), substitutes the built-in room temperature
sensor
ECA 31 only Contains humidity sensor, used for special applications
ECL Comfort 310 base part (can be used for ECL Comfort 210 too).
AI155886473192en-000602
ECL Comfort 310
© Danfoss | 2020.01 | 45
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Comfort 310B
ECA 30 / 31 cut-out for mounting in panel front
ECA 30 / 31
ECA 32
A frame (code no. 087H3236) is placed in the cut­out (139 × 93 mm) in which the ECA 30 / 31 is placed.
46 | © Danfoss | 2020.01
AI155886473192en-000602
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Tender text: Electronic controller for heating and domestic hot water applications
1a
Electronic weather compensator for flow temperature control in heating and domestic hot water installations. Turn-push-dial, backlighted graphic display and menu-based operation in local languages. The controller can operate multiple application uploaded by means of application software keys.
1b
• Heat curve setting in 6 coordinates or as slope.
• Flow temperature limitations.
• Room temperature compensation and Comfort / Saving periods according to week schedule.
• Holiday schedule.
• Return temperature limitation as a fixed value (DHW) or in relation to outdoor temperature (heating).
• Pumps controlled in relation to heat demand and frost protection.
• Alarm functions and log pictures for all sensors.
• Manuel override of the individual outputs.
• Communication: M-bus (up to 5 meters), Modbus, Ethernet (e.g. internet connection to ECL Portal), ECL 485 (internal data bus).
• Connection for commissioning / service via PC
• 6 temperature sensor (Pt 1000) inputs.
• 4 application related and configured inputs.
• 6 relay outputs
• 3 pairs of electronic output for noiseless operation of the motorized control valve.
Remote control unit ECA 30 / 31:
• Turn-push-dial, backlighted graphic display
• Integrated room temperature sensor
• Integrated humidity sensor (ECA 31 only)
Extension module ECA 32 enables:
• Additional 6 configurable inputs
• 2 pulse counters
• 4 relay outputs
• 3 analogue outputs
Extension module ECA 35 enables:
• Additional 2 configurable inputs
• 2 pulse counters
• 4 relay outputs
• 3 analogue outputs
• 4 PWM outputs
1c
Main data:
• Supply voltage, 230 V a.c., 50 Hz: ECL 310 and ECL 310 B
• Supply voltage, 24 V a.c., 50 Hz: ECL 310
• Power consumption: max. 5 VA
• Ambient temperature: 0 – 55 °C
• Storage temperature: -40 – 70 °C
2
Product characteristics:
• Protection class: IP 41
• DIN rail adaptor integrated
• Dimension (inclusive base part) L*W*H, 220*110*80 mm
• Ordering code no.: ECL Comfort 310, 230 V: 087H3040
• Ordering code no.: ECL Comfort 310B, 230 V: 087H3050
• Ordering code no.: ECL Comfort 310, 24 V: 087H3044
• Ordering code no.: Base part for ECL Comfort 310 / 310B: 087H3230
• Ordering code no.: ECA 30: 087H3200
• Ordering code no.: ECA 31: 087H3201
• Ordering code no.: ECA 32: 087H3202
• Ordering code no.: ECA 35: 087H3205
• Ordering code no. for application key depends on preferred application
AI155886473192en-000602
© Danfoss | 2020.01 | 47
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Additional documentation for ECL Comfort 310, modules and accessories is available on http://heating.danfoss.com/ or http://store.danfoss.com/