Danfoss ECL Comfort 296 controller Data sheet

Data sheet
ECL Comfort 296 controller,
Designed in Denmark
Remote Control Units ECA 30 / 31 and Application Keys
Description
ECL Comfort 296 controller series
ECL Comfort 296 controller:
The ECL Comfort 296 is an electronic weather compensated temperature controller in the ECL Comfort controller family for use in district heating, central heating, cooling and ventilation systems.
Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. The controller has 2 control circuits and one additional thermostatic function.
The weather compensation function in the ECL Comfort controllers measures the outdoor temperature and controls the flow temperature to the heating system accordingly. In case it is available it also controls the domestic hotwater installation.
The weather compensated heating system increases the comfort level and saves energy.
The ECL Comfort 296 controller is configured with a selected application by means of an ECL Application Key.
The web-based ECL Portal communicates with the ECL Comfort 296 controller for an effective and easy-to-use turnkey SCADA (Supervisory Control And Data Acquisition) tool for all users, service personnel and at commissioning. Service level can b e increased and/or service costs reduced. The heating and/or cooling installation is made accessible from vir tually anywhere at any time via i.e. laptops or Smartphones which increases service level and reduces response time to alarms.
The ECL Tool software for ECL Comfort 296 controller offers possibilities for an alternative remote control in relation to the ECL Portal and OPC server software.
The ECL Comfort 296 controller is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application Key (Plug-and-Play) and user­friendly operation.
Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power.
The ECL Comfort 296 controller is easily operated by means of a dial (multi-functional knob) or a Remote Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language.
The ECL Comfort 296 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output.
Six Pt 1000 temperature se nsors can be connected. In addition, two inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analogue input (0 – 10 V) or digital input.
© Danfoss | 2020.01
AI183286470028en-000403| 1
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Description (continued)
The enclosure is designed for panel mounting, on a wall and DIN rail.
The ECL Comfort 296 can work as a stand-alone controller and communicate with up to two RCUs.
The ECL Comfort 296 can also work with other ECL Comfort 296 / 210 / 310 controllers via the ECL 485 communication bus.
Ethernet connec tion is integrated in the controller. Furthermore, Modbus communication to SCADA systems (Supervisory Control And Data Acquisition) and M-bus communication to heat meters are integrated.
ECL Application Key and applications:
Different ECL Application Keys make it easy for the ECL Comfort 296 hardware to run different applications. The ECL Comfort 296 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (basic application sketches are shown in the display), languages, factory settings and firmware.
The ECL Application Keys, series A2xx can be used in the ECL Comfort 296.
Remote Control Unit (RCU):
The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL Comfort 296. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted p air cable for communication and power supply (ECL 485 communication bus).
The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substituting the built-in temperature sensor.
Furthermore, the ECA 31 has a built-in humidity sensor and the relative humidity signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master / slave system).
ECL 296 controls 3-point based actuators:
If need for control of 0 - 10 Volt based actuators, the ECL 310 and extension module ECA 32 or ECA 35 is recommended for dedicated applications. Here the 0 - 10 Volt signal comes from the extension module.
The application parameters are stored in the controller and are not affected by power break. The relevant ECL Application Keys for the ECL Comfort 296 controller can be found in the ordering section.
In addition to the above selected application keys can run and log a temperature / time controlled floor (screed) drying process for floor heating applications.
2 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Application keys, overview
Key Subtypes usable in ECL Comfort 296:
A214 A214.1, A214.2, A 214. 3, A214.4, A214. 5, A214.6
A217 A217.1, A 217. 2 , A 217. 3
A230 A230.1 *, A230.2 *, A230.3 *, A230.4 *
A231 A231.1, A231. 2
A232 A232.1
A237 A 237.1, A 237. 2
A247 A247.1, A 247. 2, A247. 3
A260 A260.1
A266 A266.1 *, A266.2 **, A266.9 *, A266.10 *
A267 DEA267.1
A275 A275.1, A275.2, A275.3
* When used in ECL 310 + ECA 32 / 35, 0 - 10 Volt controlled actuators can be used alternatively.
** When used in ECL 310 + ECA 32 / 35 a 0 - 10 Volt controlled actuator can, alternatively, be used for the heating circuit.
This is an overview of currently available application keys which can work in the ECL Comfort 296. The application keys can work in ECL Comfort 210 / 310 too. Not all keys are marketed in all countries. Please contact your local Danfoss sales company.
AI183286470028en-000403
© Danfoss | 2020.01 | 3
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Application examples All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve) are
wired to the ECL Comfort controller.
A217.1: DHW tank charging application
A230.1: Indirectly connected heating system. Wind compensation as option
A230.2: Indirectly connected cooling system (district cooling)
4 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
A230.3: Indirectly connected heating system. Compensation for too high Relative Humidity (measured by ECA 31). Wind compensation as option.
A230.4: Indirectly connected heating system. Static pressure measurement / alarm. Monitoring of DHW ­and DHW circulation return temperatures.
AI183286470028en-000403
A231. 2: Indirectly connected heating system with 2-pump control and refill water function.
© Danfoss | 2020.01 | 5
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
A237.1: Typical heating and DHW system (district heating)
A247.1: Typical heating and DHW storage tank system (district heating)
6 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
A260.1: Typical heating system (district heating)
A266.1: Typical heating and DHW system (district heating). Remote Control Unit ECA 30 replaces a room temperature sensor.
AI183286470028en-000403
© Danfoss | 2020.01 | 7
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
A275. 3: Boiler-based heating system
S1
ECL 210 / 296 / 310
Danfoss
87H2169.13
M2
S4
P4
S2
S3
P1
S5
B1
P3
*
S6
S8
2
S7
1
3
8 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Ordering Controller, base parts and accessories:
Typ e Designation Code no.
ECL Comfort 296 Universal hardware - 230 V a.c. For mounting on base part or in panel
ECL Comfort 296 base part For mounting on wall or DIN rail (35 mm). Installation guide (no text) is
Panel mounting kit Set of connectors for panel mounted ECL Comfort 296. Installation guide (no
Remote Control Units and accessories:
Typ e Designation Code no.
ECA 30 Remote Control Unit with an integrated temperature sensor and possibility
ECA 31 Remote Control Unit with an integrated temperature sensor and a humidity
ECA 30 / 31 frame kit for mounting in panel front
ECL Application Keys for ECL 210, 296 and 310
Typ e Application type description Controller output
A214* Constant temperature control (heating / cooling) of ventilation systems. 2 x 3-point, 2 x 2-point 087H3 811
A217* Advanced temperature control of DHW (domestic hot-water) circuit with /
without storage charging system.
A230 • Weather compensated or constant flow temperature control of heating
systems with sliding return temperature limitation and with / without wind compensation.
• Weather compensated or constant flow temperature control of district cooling based systems.
• Weather compensated flow temperature control of boiler based heating systems and minimum boiler temperature.
• Since 1st quarter of 2016, the application key contains floor (screed) drying program.
A231* Weather compensated flow temperature control with twin-pump control
for circulation and make-up water.
A232* Weather compensated flow temperature control in combined heating and
cooling systems, typically floor systems. The slab temperature can be limited. In addition, the dew point temperature will limit the flow temperature at cooling (temperature and humidity are measured by ECA
31).
A237* Weather compensated flow temperature control of systems with sliding
return temperature limitation. Constant temperature control of secondarily connected DHW circuits with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connec tion with primarily connected storage tank with internal heat exchanger. Since 1st quarter of 2016, the application key contains floor (screed) drying program.
A247* Weather compensated flow temperature control of systems with sliding
return temperature limitation. Constant temperature control of DHW circuits with storage tank charging system. Since 1st quarter of 2016, the application key contains floor (screed) drying program.
cut-out. Base part and panel mounting kit are not included. Installation guide (no text) is included.
included.
text) is included.
for connec ting an external Pt 1000 temperature sensor. Base part for mounting on wall included.
sensor. Possibility for connecting an external Pt 100 0 temperature sensor. Base part for mounting on wall included.
For mounting in a cut-out. Format 144 × 96 mm, actual cut-out 139 × 93 mm.
087H3000
087H3240
087H3242
087H3200
087H3201
087H3236
Code no.
signals
1 x 3-point, 3 x 2-point 087H3807
1 x 3-point, 2 x 2-point 087H3802
1 x 3-point, 4 x 2-point 087H3805
1 x 3-point, 3 x 2-point 087H3 812
1 x 3-point, 3 x 2-point 087H3806
2 x 3-point, 3 x 2-point 087H3808
AI183286470028en-000403
*: Application key also contains subtypes for ECL Comfort 310.
Each of the above-mentioned code nos. comprises: ECL Application key, installation guide and user guides.
© Danfoss | 2020.01 | 9
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
ECL Application Keys for ECL 210, 296 and 310 (continued):
Typ e Application type description Controller output
A260 Weather compensated flow temperature control of heating systems with
sliding return temperature limitation for two independent heating circuits. Since 1st quarter of 2016, the application key contains floor (screed) drying program.
A266 Weather compensated flow temperature control of heating systems with
sliding return temperature limitation. Constant temperature control of DHW circuits with flow system. Since 1st quarter of 2016, the application key contains floor (screed) drying program.
A267 DE Weather compensated flow temperature control of 2 heating circuits.
• Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger.
• Optional ON / OFF control of the DHW circuit in connec tion with primarily connected storage tank with internal heat exchanger.
• DHW circulation pump control. Frost protection and alarm function
• Since 1st quarter of 2016, the application key contains floor (screed) drying program.
A275* Boiler controller with constant temperature control of DHW circuit and
weather compensated flow temperature control of a mixed and an unmixed heating circuit.
*: Application key also contains subtypes for ECL 310.
Each of the above-mentioned code nos. comprises: ECL application key, installation guide and user guides.
signals
2 x 3-point, 2 x 2-point 087H38 01
2 x 3-point, 4 x 2-point 087H3800
2 x 3-point, 4 x 2-point
1 x 3-point, 3 x 2-point 087H3814
Code no.
087H3828
Typical ordering, types:
Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C):
Typ e Designation Code No.
ESMT Outdoor temperature sensor 08 4N1012
ESM-10 Room temperature sensor 087 B116 4
ESM -11 Surface temperature sensor 087 B116 5
ES MB-12 Universal temperature sensor 087 B118 4
ESMC Surface temperature sensor incl. 2 m cable 087N0011
ESMU -100 Immersion sensor, 100 mm, copper 087 B118 0
ESM U-250 Immersion sensor, 250 mm, copper 087 B1181
ESMU -100 Immersion sensor, 100 mm, stainless steel 087B1182
ESM U-250 Immersion sensor, 250 mm, stainless steel 087 B118 3
Accessories and spare parts:
Pocket Immersion, stainless steel 100 mm, for ESMU -100, Cu (087B1180) 0 87B 1190
Pocket Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181) 087 B1191
Pocket Immersion, stainless steel 100 mm, for ESMB -12, (087B1184) 087 B119 2
Pocket Immersion, stainless steel 250 mm, for ESMB-12, (087B1184) 087B1193
ECL Comfort Controller Mounting Appl. key Optional:
ECL Comfort 296 Base part
or Panel kit
A2xx ECA 30
Remote Control Unit
ECA 31
Temperature sensors Ac tuators /
ESMT (outdoor) ESM-11 (pipe surface) ESMC (pipe surface) ESMU (immersion) ESM-10 (r oom) ESMB-12 (universal)
valves
see dedicated literature
Reference, additional products / software:
10 | © Danfoss | 2020.01
ECL Portal Internet-based communication. Access to the ECL
Comfort 296 via a web browser. After having arranged an account, access to the ECL Comfort 296 can also be done via a smar tphone.
ECL To ol Software for PC or laptop. Connect the ECL Comfor t
296 directly to a PC or laptop for e.g. parameter lists, commissioning reports.
OPC server Software for communication between SCADA system
and ECL Comfor t 296 (Modbus or TCP Ethernet connection).
See separate data sheet
Download from Internet
See separate data sheet and download from Internet
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Operation
A: Display B: Dial C: Slot for ECL Tool connection D: Slot for application key E: Front door, transparent
The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters. The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-func tional knob (B)). A transparent front door covers the display and slots for application key and ECL Tool connection.
Examples of favorite displays:
The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL Comfort 296 with dial and backlighted display.
AI183286470028en-000403
© Danfoss | 2020.01 | 11
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Functions General functions:
• The ECL Comfort 296 has all the required functions of a modern electronic temperature controller for heating, cooling and DHW applications.
• The controller can be used as master or slave in systems with master / slave ECL Comfort 296 / 210 /310 controllers.
• The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required.
• The ECL Comfort 296 contains, besides the standard functions, log and alarm functions.
• The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule.
• Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking.
• Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode.
• If applicable in the application key the ECL Comfort 296 can receive pulses from a heat or flow meter to limit the power or the flow. Alternatively, the data can come from heat or flow meter via the M-bus connection.
• In many applications analogue input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller.
• Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal.
• The control parameters, proportional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control).
• Dedicated applications fulfil the demand for refill water function and / or 2-pump control.
Heating functions:
• The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set.
• The return temperature limitation can work in relation to the outdoor temperature or be a set value.
• The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures.
• Based on the room temperature the ECL Comfort 296 can correct the desired flow temperature in order to increase the comfort level.
• The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating).
• The ramping function makes a smooth cut-in of the heating valuable (district heating installations).
• The boost function makes a powerful cut-in of the heating (boiler based installations).
• The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking.
• The saving function gives two possibilities:
· reduced flow temperature with set reduction or reduction in relation to outdoor temperature (the lower the outdoor temperature, the less the reduction),
· heating off, still with active frost protection.
DHW functions:
• The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the applications A217 and A266. However, Auto Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS.
• The anti-bacteria function can follow a week schedule.
• The DHW circuit can have full or sliding priority.
Communication The ECL Comfort 296 has:
• ECL 485 bus, non -g alvanic isolated, f or closed
communication between master, slave and RCUs.
• RS 485 bus, galvanic isolated, for Modbus communication.
• M-bus, non-galvanic isolated, for M-bus communication with meters.
• USB, type B, for ECL Tool (software for PC / laptop).
• Ethernet, RJ 45, for TCP/IP communication to Internet (ECL Portal) and SCADA systems.
Languages Most application keys contain up to 22
languages. See language list.
12 | © Danfoss | 2020.01
Master (M) / slave (S) connections
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
General data ECL Comfort controller and RCU data:
ECL Comfort 296 ECA 30 / 31
Ambient temperature 0 - 45 °C
Storage and transportation temperature -20 - 70 °C
Installation Installation must be avoided if there is a risk for condensation (dew)
Mounting To be mounted on a vertical wall and
Connections Terminals in base part Terminals in base part
Number of inputs 8 in total:
Temperature sensor type Pt 1000 (1000 ohm at 0 °C), IEC 751B
Digital input 12 V pull-up possible
Analog input 0 - 10 V, resolution 9 bits -
Pulse input, frequency range (selected applications)
Weight 0.41 kg (ECL 296)
Display (ECL Comfort 296 and ECA 30 /
31)
Setting (ECL Comfort 296 and ECA 30 /
31)
Data logging Up to 10 days for 14 parameters
Min. backup time for time and date 72 hours -
Backup of settings and data Flash memor y Flash memor y
Grade of enclosure IP 40 when mounted according to
-marking in accordance with the
standards
Temperature control Complies with EN 60730
*) Configured at application upload.
turned horizontally, on DIN rail (35 mm) or in a panel cut-out (138 x 92 mm)
6 Pt 1000 temperature sensors. 2*) Pt 1000 temperature sensors, 0 - 10 V, pulse and digital.
Range: -60 – 150 °C
Activation of a digital input must be done with a potential free switch / contact.
For monitoring: 0.01 - 200 Hz For limitation: Minimum 1 Hz (recommended) and regular pulses for having a stable control.
0.21 kg (base par t)
Graphical monochrome with backlight 128 × 96 dots Display mode: Black background, white text
Dial with intuitive push and turn function
instructions
EMC (ElectroMagnetic Compatibility Directive) LVD (Low Voltage Directive) RoHS (Restriction of Hazardous Substances Directive)
To be mounted on a ver tical wall and turned horizontally, or in a panel cut-out (138 x 92 mm)
-
Alternative to built-in room temperature sensor : Pt 1000 (1000 ohm at 0 °C), IEC 751B
-
-
0.14 kg
IP 20 when mounted according to instructions
ECL application key:
Storage type Flash memory
Segmentation Part 1: Application data, not changeable
Applications A2xx keys work in ECL Comfort 210, 296 and 310
Lock function If not inserted in the ECL Comfort controller, all settings can be seen, but not
Menu languages Menu languages are selectable among approx. 22 languages. See “Language list”.
Part 2: Factory set tings, not changeable Part 3: Updating SW for the ECL Comfort controller, not changeable Part 4: User settings, changeable
A3xx keys work in ECL Comfort 310 only
changed
AI183286470028en-000403
© Danfoss | 2020.01 | 13
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
ECL 485 communication bus data:
Purpose Only for internal connections between ECL Comfor t 210 / 296 /
Connection Terminals in base part
Cable type Shielded cable, 2 x twisted pair,
Max. total cable length (bus cable + sensor cables) 200 m in total (inclusive sensor cables)
Max. number of ECL slaves connected Units with unigue address (1 - 9): 9
Max. number of Remote Control Units connec ted 2
Data sent from master Date
Data sent from addressed slave controller Desired flow temperature from each circuit
Data sent from ECA 30 / 31
310 and ECA 30 / 31. (Danfoss proprietary bus)
Non-galvanic isolated
Min. cross section: 0,22 mm (AWG 24). Examples: LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5
Units with address “0”: 5
Time Outdoor temperature Desired room temperature DHW-priority signal
Actual and desired room temperature
Function selector mode
(ECA 31) Relative humidit y
Modbus communication data:
Purpose For SCADA system
Connection Terminals 34 and 35 in base part. Modbus reference (terminal
Protocol Modbus RTU
Cable type Shielded cable, 2 x twisted pair + Signal GND.
Max. bus cable length 1200 m (dependent on cable type and installation).
Communication speed Half duplex.
Serial mode 8 data bit, even parity and 1 stop bit.
Network According to the standard Modbus Serial Line Implementation
36, S. Gnd) must be connected. Galvanic isolated (500 V).
Min. cross section: 0,22 mm2 (AWG 24). Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)
9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit /s
Guide V1.0.
M-bus communication data:
Purpose Connection to heat meters, max. 5 heat meters
Connection Terminals 37 and 38 in base par t.
M-Bus master according to DS / EN 1434-3: 1997
Cable type 2 x 0,8 mm2
Max. cable length 50 m
Baud rate 300 baud (adjustable)
Update time 60 s (adjustable)
Gateway function Allows the ECL Portal to read energy meters directly
Supported heat meters Infocal 6 and many other marks and t ypes.
Transmitted heat meter data Heat meter type dependent:
Recommendations: Danfoss recommends 230 V a.c. supplied heat meters
Non-galvanic isolated
Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)
Information about other heat meters on request
• Primary flow temperature
• Primary return temperature
• Actual flow / accumulated flow
• Actual heat / power
• Accumulated heat energy
USB communication data:
USB CDC (Communication Device Class) For service purposes
Modbus over USB Similar to the serial Modbus, but with relaxed timing
Connection, cable type Standard USB cable (USB A - ------- USB B)
(Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM por t)
14 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Ethernet communication (Modbus / TCP) data:
Purpose For Internet (ECL Portal) and SCADA
Connection RJ45 female connector
Protocol Modbus / TCP
Cable type Standard Ethernet cable (CAT 5)
Max. Bus cable length According to Ethernet standard
Auto cross-over detec tion Enabled
Default Ethernet address (IP address) 192.168 .1.100
Port number 502 (Modbus / TCP por t)
Number of connections 1
Security Must be provided by Ethernet infrastructure
A-B-C port
Language list
Comparison with ECL Comfort 310 / 210
A port: USB (type B female plug) B port: Ethernet (RJ45, female plug) C port: ECL application key
Bulgarian Estonian Latvian Slovak
Croatian Finnish Lithuanian Slovenian
Czech French Polish Spanish
Danish German Romanian Swedish
Dutch Hungarian Russian
English Italian Serbian
The selected language + English is uploaded at application upload.
ECL Comfort 296 ECL Comfort 310 ECL Comfort 210
M-bus communication Ye s Yes No
Modbus connection Yes, galvanic isolated Yes, galvanic isolated Yes, non- galvanic isolated
Ethernet Yes, RJ45 connection,
Inputs 8 10 8
Relay outputs 4 6 4
Valve actuator outputs 2 x 3-point 3 x 3-point 2 x 3-point
Extension of inputs / outputs No Yes, ECA 32, placed in base part.
Application keys A2xx A2xx and A3xx A2xx
Front dimensions (W x H, mm)
Supply voltage 230 V 230 V and 24 V 230 V
Modbus / TCP. For SCADA solutions and ECL Portal
144 x 96 220 x 110 220 x 110
Yes, RJ45 connection, Modbus / TCP. For SCADA solutions and ECL Portal
• 6 inputs
• 2 pulse inputs
• 3 analogue outputs (0 - 10 V)
• 4 relays
No
No
AI183286470028en-000403
© Danfoss | 2020.01 | 15
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Wiring - 230 V a.c.
ECL Comfort 296 wiring example: Application A266.1
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Max. load on relay outputs 4(2) A - 230 V a.c. (4 A for ohmic load,
Max. load on triac outputs for actuators 0.2 A - 230 V a.c.
2 A for inductive load)
16 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Wiring - input
Wiring - ECA 30 / 31 Remote Control Unit
Base part
Wiring of ECL Comfort 296 and ECA 30 / 31
Supply voltage From ECL 485 communication bus
Power consumption 1 VA
External room temperature sensor Pt 1000 (ESM-10), substitutes the built-in room temperature
sensor
ECA 31 only Contains humidity sensor, used for special applications
ECL Comfort 296 base part with pre-wirings
AI183286470028en-000403
© Danfoss | 2020.01 | 17
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Dimensions ECL Comfort 296
Dimensions including the base part. Depth of base part: 38 mm
Cut-out in panel for mounting
Dimensions ECA 30 / 31
Panel kit for mounting, code no. 087H3242 The panel plate thickness A must not exceed
5 mm.
18 | © Danfoss | 2020.01
AI183286470028en-000403
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
ECA 30 / 31 cut-out for mounting in panel front
Tender text Electronic controller for heating and domestic hot water applications
A frame (code no. 087H3236) is placed in the cut-out (139 × 93 mm) in which the ECA 30 / 31 is placed.
1a
Electronic weather compensator for flow temperature control in heating, domestic hot water and ventilation installations. Turn-push dial, backlighted graphic display and menu-based operation in local languages. The controller can operate multiple applications uploaded by means of application software keys.
1b
• Heat curve setting in 6 coordinates or as slope.
• Flow temperature limitations.
• Room temperature compensation and comfort / saving periods according to week schedule.
• Holiday schedule.
• Return temperature limitation as a set value (DHW) or in relation to outdoor temperature (heating).
• Pumps controlled in relation to heat demand and frost protection.
• Alarm functions and log pictures for all sensors.
• Manuel override of the individual outputs.
• Communication: M-bus (up to 5 meters), Modbus, Ethernet (e.g. internet connection to ECL Portal), ECL 485 (internal data bus).
• Connection for commissioning / service via PC
• 6 temperature sensor (Pt 1000) inputs.
• 2 application related and configured inputs.
• 4 relay outputs.
• 2 pairs of electronic output for noiseless operation of the motorized control valve.
AI183286470028en-000403
Remote control unit ECA 30 / 31:
• Turn-push-dial, backlighted graphic display
• Integrated room temperature sensor
• Integrated humidity sensor (ECA 31 only)
1c
Main data:
• Supply voltage, 230 V a.c., 50 Hz
• Power consumption: max. 5 VA
• Ambient temperature: 0 – 45 °C
• Storage temperature: -20 – 70 °C
2
Product characteristics:
• Protection class: IP 40
• DIN rail adaptor integrated in base part
• Dimension (inclusive base part) L * W * H, 144 * 96 * 88 mm
• Ordering code no.: ECL Comfort 296, 230 V: 087H3000
• Ordering code no.: Base part for ECL Comfort 296: 087H3240
• Ordering code no.: ECA 30: 087H3200
• Ordering code no.: ECA 31: 087H3201
• Ordering code no. for application key depends on preferred application
© Danfoss | 2020.01 | 19
ECL Comfort 296 controller, Remote Control Units ECA 30 / 31 and Application Keys
Additional documentation for ECL Comfort 296, modules and accessories is available on http://heating.danfoss.com/ or http://store.danfoss.com/