
OperatingGuide
ECLComfort210/296/310,applicationA217/A317
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................11
2.3Mounting...........................................................12
2.4Placingthetemperaturesensors................................16
2.5Electricalconnections.............................................18
2.6InsertingtheECLApplicationKey..............................27
2.7Checklist............................................................34
2.8Navigation,ECLApplicationKeyA217/A317................35
3.0Dailyuse.........................................................41
3.1Howtonavigate...................................................41
3.2Understandingthecontrollerdisplay..........................42
3.3Ageneraloverview:Whatdothesymbolsmean?...........44
3.4Monitoringtemperaturesandsystem
components........................................................45
3.5Influenceoverview................................................46
3.6Manualcontrol.....................................................47
3.7Schedule............................................................48
4.0Settingsoverview............................................49
5.0Settings...........................................................51
5.1IntroductiontoSettings..........................................51
5.2Tanktemperature..................................................52
5.3Flowtemperature..................................................56
5.4Returnlimit.........................................................57
5.5Flow/powerlimit.................................................62
5.6Controlparameters................................................65
5.7Application.........................................................71
5.8Anti-bacteria........................................................78
5.9Alarm................................................................80
5.10Alarmoverview....................................................83
6.0Commoncontrollersettings..............................84
6.1Introductionto‘Commoncontrollersettings’................84
6.2Time&Date.........................................................85
6.3Holiday..............................................................86
6.4Inputoverview.....................................................88
6.5Log...................................................................89
6.6Outputoverride....................................................90
6.7Keyfunctions.......................................................91
6.8System...............................................................93
7.0Miscellaneous................................................100
7.1Severalcontrollersinthesamesystem......................100
7.2Frequentlyaskedquestions....................................103
7.3Definitions........................................................105
7.4Type(ID6001),overview.......................................109
7.5Automatic/manualupdateoffirmware.....................110
7.6ParameterIDoverview..........................................111
©Danfoss|2021.04AQ055186460331en-010501|1

OperatingGuideECLComfort210/296/310,applicationA217/A317
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA217
(ordercodeno.087H3807).
TheA217Keycontainstwosetsofapplications:oneset(A217.1/
A217.2/A217.3)andanotherset(A317.1/A317.2).
Thefunctionscanberealizedin:
ECLComfort210(A217)forsimplesolutionsor
ECLComfort310(A217/A317)foradvancedsolutions,e.g.M-bus,
ModbusandEthernet(Internet)communication.
TheapplicationsA217/A317complywithECLComfortcontrollers
210/310asofsoftwareversion1.11(visibleatstart-upofthe
controllerandin‘Commoncontrollersettings’in‘System’).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/or
http://store.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
2|©Danfoss|2021.04
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
•Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
Circuit1Parameterno.
2
Circuit2Parameterno.
174
AQ055186460331en-010501
©Danfoss|2021.04|3

OperatingGuideECLComfort210/296/310,applicationA217/A317
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot
bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back
schemefortherecyclingofelectricalandelectronic
equipment.
•Disposeoftheproductthroughchannelsprovided
forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws
andregulations.
4|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.0Installation
2.1Beforeyoustart
Thetwoapplications,A217.1/A317.1arealmostidentical.
However,A317.1hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.1/A317.1areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
Theheating/chargingtemperaturesensorS3isthemost
importantsensor.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheating/chargingpump(P1)is
switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain
theheating/chargingtemperatureatS3.Thistemperatureis
typically5–10degreeshigherthanthedesiredDHWtemperature.
Amax.valuecanbeset.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperature,theDHWheating/chargingpump(P1)
isswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperatureandthelowertemperature(atS8)getshigher
thanthecut-outtemperature,theDHWheating/chargingpump
(P1)isswitchedOFF.Thepost-runtimecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
TypicalA217.1./A317.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
Chargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWchargingpump(DHWheatingpump)
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensateforthe
heatlossintheDHWcirculationpipe.Furthermore,afterDHW
tankcharging,thecirculationtemperature(atS3)iscontrolled
accordingtothedesiredDHWtemperature.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
AQ055186460331en-010501
©Danfoss|2021.04|5

OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationA217.1(usedinECLComfort210)/A317.1(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWchargingtemperature.
A217.1/A317.1examplea:
A217.1/A317.1exampleb:
A217.1/A317.1examplec:
A217.1/A317.1exampled:
A217.1/A317.1examplee:
6|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Thetwoapplications,A217.2/A317.2arealmostidentical.
However,A317.2hassomeextrafunctionswhicharedescribed
separately.
TheapplicationsA217.2/A317.2areveryflexible.Thesearethe
basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS6).
TheDHWheatingtemperaturesensorS3andthecharging
temperaturesensorS4arethemostimportantsensors.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired
DHWtemperature,theDHWheatingpump(P1)isswitchedON.The
motorizedcontrolvalve(M1)iscontrolledinordertomaintainthe
DHWheatingtemperatureatS3.TheDHWheatingtemperatureis
determinedbythedesiredDHWchargingtemperatureatS4.
WhentheDHWheatingtemperatureisreached,theDHWcharging
pumpP2isswitchedON.
IftheDHWchargingtemperatureatS4cannotbereached,the
ECLcontrollergraduallyincreasesthedesiredDHWheating
temperatureatS3inordertoobtainthechargingtemperature.
Amax.valuecanbeset.
TheDHWchargingtemperatureatS4istypically5–10degrees
higherthanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S6):
IfthemeasuredDHWtemperature(S6)getshigherthanthedesired
DHWtemperature,theDHWheatingpump(P1)andtheDHW
chargingpump(P2)areswitchedOFF .Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8):
IfthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperatureandthelowertemperature(atS8)gets
higherthanthecut-outtemperature,theDHWheatingpump(P1)
andtheDHWchargingpump(P2)areswitchedOFF .Thepost-run
timecanbeset.
TypicalA217.2./A317.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWheatingtemperaturesensor
S4
DHWchargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWheatingpump
P2
DHWchargingpump
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
InchargingapplicationstheDHWcirculationcanbethrough
theDHWtank(connectionA)orthroughtheheat-exchanger
(connectionB).
ThesolutionwithconnectionAresultsinclosingofthemotorized
controlvalveaftertheDHWtankchargingprocedure.
ThesolutionwithconnectionBisusedtocompensatefortheheat
lossintheDHWcirculationpipe.
Furthermore,afterDHWtankcharging,thecirculationtemperature
(atS4)iscontrolledaccordingtothedesiredDHWtemperature.
AQ055186460331en-010501
©Danfoss|2021.04|7

OperatingGuideECLComfort210/296/310,applicationA217/A317
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe
adjusted(typicallytoalowervalue),thusresultinginagradual
closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional
band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe
circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
ApplicationA217.2(usedinECLComfort210)/A317.2(usedin
ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto
controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased
onpulsesignalsandinECLComfort310basedonM-bussignal)
canlimitthefloworenergytoasetmaximum.
A217.2/A317.2examplea:
A217.2/A317.2exampleb:
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6)
canbeactivatediftheactualflowtemperatureatS3differsfrom
thedesiredDHWheatingtemperature.
8|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
TheapplicationA217.3isveryflexible.Thesearethebasic
principles:
DomesticHotWater(DHW),examplea:
Bymeansofaweekschedulee(upto3‘Comfort’periods/day),the
DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesforthedesiredDHWtemperatureatS3).The
DHWtemperaturesensorS3isthemostimportantsensor.
IfthemeasuredDHWtemperature(S3)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue)thusresultinginagradualclosingofthe
motorizedcontrolvalve,i.e.thereturntemperaturewilldecrease.
Thecirculationpump,P1,iscontrolledbymeansofaseparateweek
schedule(upto3‘Comfort’periods/day).
IfasupplytemperaturesensorS2isconnected,theproportional
bandXpisadaptedtotheactualsupplytemperatureinorderto
avoidcontrolinstability.
TypicalA217.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWsupplytemperaturesensor
S5Returntemperaturesensor
S8
(Flowswitch—examplesb,c,d)
P1
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
AQ055186460331en-010501
©Danfoss|2021.04|9

OperatingGuideECLComfort210/296/310,applicationA217/A317
A217.3examplea:
Exampleb:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Anidletemperature
forthesupplytemperature(atS2)canbemaintainedtominimize
theheat-uptimefortheDHW.
Examplec:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW
ondemand(DHWtapping/DHWdraw-off).Thetemperatureat
S3ismaintainedduringthecomforttimesofthecirculationpump
P1.Anidletemperatureforthesupplytemperature(atS2)canbe
maintainedtominimizetheheat-uptimefortheDHW.
Exampled:
TheDHWtankisdirectlyheated.Thesettingofthereturn
temperaturelimitation(atS5)canavoidatoohighflowinthe
heatingcoil.Anidletemperatureforthesupplytemperature(at
S2)canbemaintainedtominimizetheheat-uptimefortheDHW.
A217.3exampleb:
A217.3examplec:
A217.3exampled:
10|©Danfoss|2021.04
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
AQ055186460331en-010501
©Danfoss|2021.04|11

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
•onawall
•onaDINrail(35mm)
ECLComfort296canbemounted
•inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
12|©Danfoss|2021.04
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
AQ055186460331en-010501
©Danfoss|2021.04|13

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
•Mountingonawall,ECA30/31
•Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
14|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
AQ055186460331en-010501
©Danfoss|2021.04|15

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
16|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ055186460331en-010501
©Danfoss|2021.04|17

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage,
relaycontactsandtriacoutputsdonothavemutualsafetydistanceof
minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic
separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis
recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby
meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
18|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ055186460331en-010501
©Danfoss|2021.04|19

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic
relay)terminals
4(2)A/24Va.c.
(4Aforohmicload,2Afor
inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
20|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.3Electricalconnections,safetythermostats,230Va.c.or24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing:
Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe
motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the
motorizedcontrolvalveisclosedgradually.Atahighertemperature
(theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve
closesthevalveimmediately.
AQ055186460331en-010501
©Danfoss|2021.04|21

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
sensorandinputconnections.
A217/A317:
Sensor
S1
Description
Outdoortemperature
sensor*(optional)
S2
Supplytemperaturesensor
(optional)
S3
DHWheating/charging
temperaturesensor**
(A217.1/A317.1)
DHWheatingtemperature
sensor**(A217.2/A317.2)
DHWtemperaturesensor**
(A217.3)
S4
DHWchargingtemperature
sensor**(A217.2/A317.2
only)
S5Returntemperaturesensor
(optional)
S6
DHWtanktemperature
sensor,upper***
S7
Flow/heatmeter(pulse
signalandECL210only)
S8
DHWtanktemperature
sensor,lower(A217.1/
A217.2/A317.1/A317.2).
Flowswitch(A217.3)
ECL310only:
Notused
ECL310only:
Notused
Recommendedtype
ESMT
ESM-11/ESMB/
ESMC/ESMU
ESM-11/ESMB/
ESMC/ESMU
ESM-11/ESMB/
ESMC/ESMU
ESM-11/ESMB/
ESMC/ESMU
ESMB/
ESMU
ESMB/
ESMU
*
Usedforfrostprotectionpurposes.Iftheoutdoor
temperaturesensorisnotconnectedorthecableis
short-circuited,thecontrollerassumesthattheoutdoor
temperatureis0(zero)°C.
**
DHWcharging/heatingtemperaturesensormustalwaysbe
connectedinordertohavethedesiredfunctionality.Ifthe
sensorisnotconnectedorthecableisshort-circuited,the
motorizedcontrolvalvecloses(safetyfunction).
***
Thissensorisusedifonlyonetanktemperaturesensoris
required.
22|©Danfoss|2021.04
Wirecrosssectionforsensorconnections:Min.0.4mm².
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Connectionofvoltagesignal(0–10V)forexternalcontrolof
desiredflowtemperature
Connectionofflowmeter
SeetheInstallationGuide(deliveredwiththeapplicationkey).
AQ055186460331en-010501
©Danfoss|2021.04|23

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.5Electricalconnections,ECA30/31
Terminal
ECL
Terminal
ECA30/31
30
31
4
1
322
333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature
sensor*
Type
(recomm.)
Cable2x
twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL
Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A
progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible
toconnectanECA30/31toeachcircuit.Theelectricalconnections
aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller
ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage:
‘Applicationreq.newerECA’:
Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact
yourDanfosssalesoffice.
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
24|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave
systemsviatheinternalECL485communicationbus(2xtwisted
paircable).
TheECL485communicationbusisnotcompatiblewiththeECL
businECLComfort110,200,300and301!
Someapplicationsdonotcontainfunctionsrelatedtoactualroom
temperature.TheconnectedECA30/31willonlyfunctionasremote
control.
Terminal
Description
Type
(recomm.)
30
Commonterminal
+12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/
slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x
twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike
this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe
master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections
ECLComfort296:GalvanicisolatedModbusconnections
ECLComfort310:GalvanicisolatedModbusconnections
AQ055186460331en-010501
MaximumrecommendedlengthoftheECL485bus:
200-81m=119m
©Danfoss|2021.04|25

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented
ECLComfort296:Onboard,non-galvanicisolated.Max.cable
length50m.
ECLComfort310:Onboard,non-galvanicisolated.Max.cable
length50m.
26|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.6InsertingtheECLApplicationKey
2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
•theapplicationanditssubtypes,
•currentlyavailablelanguages,
•factorysettings:e.g.schedules,desiredtemperatures,
limitationvaluesetc.Itisalwayspossibletorecoverthefactory
settings,
•memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight
beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired
DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display
brightnessetc.
AQ055186460331en-010501
ECLComfort296
©Danfoss|2021.04|27

OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
•Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about
thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;for20minutes
settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
28|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationKey:Situation1
Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed.
InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266
Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross"
isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm
Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date'
Turnandpushthedialtoselectand
change'Hours' ,'Minutes','Date',
'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’
Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer
andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure
AorBistakingplace:
A
TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey
toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B
TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot
containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
AQ055186460331en-010501
OnlyfactorysettingsfromtheECLApplicationKeywill
becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory
settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill
becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings)
willbecopiedtothecontroller.
©Danfoss|2021.04|29

OperatingGuideECLComfort210/296/310,applicationA217/A317
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory
settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2
Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the
currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
30|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationKey:Situation3
Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
•forsaving(backup)ofspecialuserandsystemsettings
•whenanotherECLComfortcontrollerofthesametype(210,
296or310)mustbeconfiguredwiththesameapplicationbut
user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ .
‘ECL’or‘KEY’willbeindicated.Choose
’ECL’orKEY’
Pushthedialrepeatedlytochoose
copydirection
Choose‘Systemsettings’or‘User
settings’
Pushthedialrepeatedlytochoose
‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’
TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser
settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
*
‘ECL’:
‘KEY’:
**
‘NO’:
‘YES’:
AQ055186460331en-010501
DatawillbecopiedfromtheApplicationKeytothe
ECLController.
DatawillbecopiedfromtheECLControllertothe
ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied
totheApplicationKeyortotheECLComfortcontroller.
Specialsettings(differingfromthefactorysettings)will
becopiedtotheApplicationKeyortotheECLComfort
controller.IfYEScannotbechosen,therearenospecial
settingstobecopied.
©Danfoss|2021.04|31

OperatingGuideECLComfort210/296/310,applicationA217/A317
Language
Atapplicationupload,alanguagemustbeselected.*
IfanotherlanguagethanEnglishisselected,theselectedlanguage
ANDEnglishwillbeuploadedintotheECLcontroller.
ThismakesserviceeasyforEnglishspeakingservicepeople,just
becausetheEnglishlanguagemenuscanbevisiblebychanging
theactualsetlanguageintoEnglish.
(Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe
erased.UserandSystemsettingscanbesavedontheapplication
keybeforeerasing.
Afternewuploadwithpreferredlanguage,theexistingUserand
Systemsettingscanbeuploaded.
*)
(ECLComfort310,24Volt)Iflanguagecannotbeselected,the
powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck
andadjustallorsomeofthebasicsettings.Thenewsettingscan
bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave
beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe
ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation
1:Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3:
Acopyofthecontrollerssettingsisneededforconfiguringanother
controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin
thecontroller.IftheKeyisremoved,itisnotpossibletochange
settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon
theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto
anothercontrollerprovidedthatthetwocontrollersarefromthesame
series(210or310).
Furthermore,whentheECLComfortcontrollerhasbeenuploaded
withanapplicationkey,minimumversion2.44,itispossibletoupload
personalsettingsfromapplicationkeys,minimumversion2.14.
32|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
The“Keyoverview”doesnotinform—throughECA30/31—about
thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;for20minutes
settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
AQ055186460331en-010501
©Danfoss|2021.04|33

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.7Checklist
IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected:
230V:Live=terminal9andNeutral=terminal10
24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour
requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled
components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
34|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
2.8Navigation,ECLApplicationKeyA217/A317
Navigation,applicationA217.1/A317.1(*A217.1only,**A317.1only)
Home
IDno.
MENU
ScheduleSelectable
Schedulecirc.PSelectable
Settings
HolidaySelectable
Alarm
Influenceoverview
Tanktemperature
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
DigitalS9**
Alarmoverview
Des.DHWT
11193Chargedifference
11195
11194
11152
11030
11035
11036
11037
11111
11112
11113
11109
11115
11114
11174
11185
11186
11187
11189
11055
11054
11041
11500
11076
11093
11141
11142
11147
11148
11149
11150
11636
11637
DHW,circuit1
Function
Startdifference
Stopdifference
Max.chargeT
Limit
Infl.-max.
Infl.-min.
Adapt.time
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse*
Motorpr.
Xpactual
Tn
Mrun
Nz
Min.act.time
Circ.Ppriority
Cont.Tcontrol
DHWPpost-run
SenddesiredT
Circ.PfrostT
Frostpr.T
Ext.input
Ext.mode
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Alarmvalue
Alarmtime-out
Returnlim.
Flow/powerlim.
Holiday
Ext.override
Anti-bacteria
SCADAoverride
AQ055186460331en-010501
©Danfoss|2021.04|35

OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.1/A317.1,Commoncontrollersettings(*A317.1only)
Home
MENU
Time&Date
Scheduleoutput*Selectable
Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
SupplyTLogtoday
DHWflow&des.
DHWreturnT&lim.Log2days
TankTup.&des.Log4days
TankTup.&low.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet
M-busconfig
EnergyMeters
Display
Communication
Language
IDno.
60058
60059
38
2048
2150
2151
2050
Commoncontrollersettings
Function
Selectable
SupplyT
DHWflowT
DHWreturnT
TankupperT
TanklowerT
S9status*
Logyesterday
M1,P1,P3,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
Selectable
Selectable
Backlight
Contrast
Modbusaddr.
ECL485addr.
Servicepin
Ext.reset
Language
36|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.2/A317.2(*A217.2only,**A317.2only)
Home
IDno.
MENU
ScheduleSelectable
Schedulecirc.PSelectable
Settings
HolidaySelectable
Alarm
Influenceoverview
Tanktemperature
11193Chargedifference
11195
11194
11152
11068
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
DigitalS9**
Alarmoverview
Des.DHWT
11030
11035
11036
11037
11111
11112
11113
11109
11115
11114
11174
11185
11186
11187
11189
11055
11054
11041
11042
11500
11076
11093
11141
11142
11147
11148
11149
11150
11136
11137
DHW,circuit1
Function
Startdifference
Stopdifference
Max.chargeT
FlowTadapttime
Limit
Infl.-max.
Infl.-min.
Adapt.time
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse*
Motorpr.
Xpactual
Tn
Mrun
Nz
Min.act.time
Circ.Ppriority
Cont.Tcontrol
DHWPpost-run
Char.Ppost-run
SenddesiredT
Circ.PfrostT
Frostpr.T
Ext.input
Ext.mode
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Alarmvalue
Alarmtime-out
Returnlim.
Flow/powerlim.
Holiday
Ext.override
Anti-bacteria
SCADAoverride
AQ055186460331en-010501
©Danfoss|2021.04|37

OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.2/A317.2,Commoncontrollersettings(*A217.2only,**A317.2only)
Home
MENU
Time&Date
Scheduleoutput**Selectable
Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
SupplyTLogtoday
DHWflow&des.
ChargeTLog2days
DHWreturnT&lim.Log4days
TankTup.&des.
TankTup.&low.
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension
Ethernet
M-busconfig
EnergyMeters
Display
Communication
Language
IDno.
60058
60059
38
2048
2150
2151
2050
Commoncontrollersettings
Function
Selectable
SupplyT
DHWflowT
ChargeT*
DHWreturnT
TankupperT
TanklowerT
S9status**
Logyesterday
M1,P1,P2,P3,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
Selectable
Selectable
Backlight
Contrast
Modbusaddr.
ECL485addr.
Servicepin
Ext.reset
Language
38|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.3
Home
IDno.
MENU
ScheduleSelectable
Schedulecirc.PSelectable
Settings
HolidaySelectable
Alarm
Influenceoverview
Flowtemperature
11178Temp.max.
11177
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
Alarmoverview
Des.DHWT
11030
11035
11036
11037
11085
11111
11112
11113
11109
11115
11114
11173
11174
11185
11186
11187
11189
11097
11096
11094
11095
11500
11022
11023
11076
11040
11093
11141
11142
11147
11148
11149
11150
11150
DHW,circuit1
Function
Temp.min.
Limit
Infl.-max.
Infl.-min.
Adapt.time
Priority
Limit
Adapt.time
Filterconstant
Inputtype
Units
Pulse
Autotuning
Motorpr.
Xpactual
Tn
Mrun
Nz
Min.act.time
SupplyT(idle)
Tn(idle)
Opentime
Closetime
SenddesiredT
Pexercise
Mexercise
Circ.PfrostT
Ppost-run
Frostpr.T
Ext.input
Ext.mode
Upperdifference
Lowerdifference
Delay
Lowesttemp.
Lowesttemp.
2:Temp.monitor.
Returnlim.
Flow/powerlim.
Holiday
Ext.override
Anti-bacteria
SCADAoffset
AQ055186460331en-010501
©Danfoss|2021.04|39

OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.3,Commoncontrollersettings
Home
MENU
Time&Date
Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
OutdoorTLogtoday
DHWflow&des.
DHWreturnT&lim.Log2days
SupplyTLog4days
NewapplicationEraseapplication
Application
FactorysettingSystemsettings
Copy
Keyoverview
Extension(ECL310only)
Ethernet(ECL310only)Selectable
Portalconfig(ECL310only)
M-busconfig(ECL310only)
EnergyMeters(ECL310only)Selectable
Rawinputoverview
Alarm
Display
Communication
Language
Function
Selectable
OutdoorT
DHWflowT
DHWreturnT
SupplyT
Flowswitch
Logyesterday
M1,P1,A1
Usersettings
Gotofactory
To
Systemsettings
Usersettings
Startcopying
Codeno.
Hardware
Software
Buildno.
Serialno.
MAC
Productionweek
ECLportal
Portalstatus
Portalinfo
Selectable
Selectable
32:Temp.monitor.
60058
Backlight
60059
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Band
2150
Servicepin
2151
Ext.reset
2050
Language
40|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.0Dailyuse
3.1Howtonavigate
Younavigateinthecontrollerbyturningthedialleftorrightto
thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the
fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay(
youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One
heatingcircuit()andonedomestichot-water(DHW)circuit().
Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare
locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ055186460331en-010501
©Danfoss|2021.04|41

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.2Understandingthecontrollerdisplay
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault
display.Thefavoritedisplaywillgiveyouaquickoverviewofthe
temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill
reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay
selector(
turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
DHWcircuit
Overviewdisplay1informsabout:
actualDHWtemperature,controllermode,desiredDHW
temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout:
stateofthecontrolledcomponents,actualDHWtemperature,
(desiredDHWtemperature),controllermode,returntemperature
(limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW
circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter
alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe
nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith
Influenceindication:
42|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe
overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW
temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled
operationandincomfortmode.
Examples:
50
55
OverviewofsettingrangeandsettingsforDHWmodes:
Factorysetting
Frostprotection*
Mode
Comfort
Saving
Settingrange
10...150°C50°C
10...150°C10°C
5...40°C10°C
*relatedtodesiredflowtemperature
AQ055186460331en-010501
©Danfoss|2021.04|43

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.3Ageneraloverview:Whatdothesymbolsmean?
Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor
connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+)
Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses
Actuator,analoguecontrol
signal
Pump/fanspeed
DamperON
Circuit
Controlled
component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin
thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
44|©Danfoss|2021.04
DamperOFF
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.4Monitoringtemperaturesandsystemcomponents
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview
oftheactualand(desired)temperaturesaswellastheactualstate
ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
--
(30)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures
isthe'Inputoverview'whichisvisibleinthecommoncontroller
settings(howtoenterthecommoncontrollersettings,see
‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured
actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
AQ055186460331en-010501
©Danfoss|2021.04|45

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Themenugivesanoverviewoftheinfluencesonthedesired
flowtemperature.Itdiffersfromapplicationtoapplicationwhich
parametersarelisted.Itcanbehelpfulinaservicesituationto
explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor
moreparameters,itisindicatedbyasmalllinewitharrow-down,
arrow-upordouble-arrow:
Arrow-down:
Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up:
Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow:
Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline:
Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor
'Roomlim. ' .Thismeansthattheactualroomtemperatureis
higherthanthedesiredroomtemperaturewhichagainresultsina
decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
46|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.6Manualcontrol
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich
thesymbolsforthecontrolledcomponents(valve,pumpetc.)are
visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe
desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe
installation.Thecontrolledcomponents,valve,pumpetc.,canbe
controlledforcorrectfunction.
AQ055186460331en-010501
Whenmanualcontrolisselectedforonecircuit,itisautomatically
selectedforallcircuits!
Manualcontrolof0–10voltcontrolledactuator:
Theactuatorsymbolhasavalue(in%)whichcanbechanged.The%
valueiscorrespondingtoavoltageintherange0–10volt.
©Danfoss|2021.04|47

OperatingGuideECLComfort210/296/310,applicationA217/A317
3.7Schedule
3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.Insomeapplications,however,theremightbemore
thanoneschedule.Additionalschedulescanbefoundin‘Common
controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof
yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose:
Choose'MENU'inanyoftheoverview
displays
Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays
(inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort
periodbysettingstartandstoptimestothesamevalue.
48|©Danfoss|2021.04
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto
'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
4.0Settingsoverview
Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” .
ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Actual(actualfloworpower)
Xpactual
Day
Starttime
Duration
DesiredT
Pexercise(pumpexercise)
Mexercise(valveexercise)
Limit(returntemp.limitation)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
DHWPpost-run(DHWpump,post-run)
Char.Ppost-run(DHWchargingpump,post-run)
Cont.Tcontrol
Circ.Ppriority
FlowTadapttime(Flowtemperature,adaptationtime)
Circ.PfrostT
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Opentime
Closetime
Tn(idle)
SupplyT(idle)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Max.chargeT(maximumheating/chargingtemperature)
Autotuning
1x022
1x023
1x03059
1x03559
1x03660
1x03761
1x040
1x041
1x04272
1x05472
1x05572
1x06852
1x07672
1x08561
1x09373
1x09466
1x09566
1x09667
1x09767
1x10962
1x111
1x11263
1x11363
1x114
1x115
1x141
1x142
1x147
1x14880
1x14981
1x15081
1x15252
1x17367
Factorysettingsincircuit(s)
1
63
68
78
78
79
79
71
71
71
71
63
64
64
73
74
80
AQ055186460331en-010501
©Danfoss|2021.04|49

OperatingGuideECLComfort210/296/310,applicationA217/A317
SettingIDPage
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Chargedifference
Stopdifference
Startdifference
SenddesiredT
Alarmvalue
Alarmtime-out
1x174
1x177
1x17856
1x18569
1x18669
1x18769
1x18970
1x19352
1x19453
1x195
1x50076
1x63681
1x63782
Factorysettingsincircuit(s)
1
68
56
54
50|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.0Settings
5.1IntroductiontoSettings
Descriptionsofsettings(parameter'sfunctions)aredividedinto
groupsasusedintheECLComfort210/296/310controller's
menustructure.Examples:"Flowtemperature" ,"Roomlimit"and
soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto
theparameter'sIDnumbers.Youmightcomeacrossdifferences
betweentheorderinthisOperatingGuideandtheECLComfort
210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication
subtypes.Thismeansthatyoumightnotseetherelatedparameter
intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof
thisOperatingGuide,whereparameter'ssettingrangesandfactory
settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit
…)covermultiplesubtypes.
AQ055186460331en-010501
©Danfoss|2021.04|51

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.2Tanktemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Tanktemperature
FlowTadapttime(Flowtemperature,adaptationtime)
Settheadaptationtime(inseconds)forthedesiredtemperatureinthe
primarycircuit,basedonthedesiredchargingtemperature.
TheECLComfortcontrollergraduallyincreasesthedesiredflowtemperature
intheprimarycircuitinordertomaintainthedesiredchargingtemperature.
1x068
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureintheprimarycircuitis
notadaptedtothedesiredchargingtemperature.
Low
Theadaptationisquick.
value:
High
Theadaptationisslow.
value:
MENU>Settings>Tanktemperature
Max.chargeT(maximumheating/chargingtemperature)
Setthemax.heating/chargingtemperaturefortheDHW.
1x152
SeeAppendix“ParameterIDoverview”
Value:Setthetemperature.
Thedesiredheating/chargingtemperaturecannotbehigherthanthe
settemperaturein'Max.chargeT’ .
NOTE:
ThedesiredDHWtemperaturewillbereducedif"Max.chargeT"is
lowerthan(DesiredDHWtemp.+Chargedifference).
Example:
DesiredDHWtemp.=
Chargedifference=
Max.chargeT=
50°C
10K
55°C
52|©Danfoss|2021.04
Result:
DesiredDHWtemp.willbereducedto45°C.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Chargedifference
SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill
resultintheDHWheating(charging)temperature.
SeeAppendix“ParameterIDoverview”
Value:
NumberofdegreestobeaddedtothedesiredDHW
temperaturetoobtaintheDHWheating(charging)
temperature.
1x193
=
X
#1#
#2#
#3#
#4#
#5#
ThedesiredDHWtemperatureisrelatedtothetanktemperature
sensor.
Iftwotanktemperaturesensorsareinstalled,therelationistothe
uppertanktemperaturesensor.
Time
=
Chargingdifference(ID1x193)
=
DesiredDHWtemperature
=
Startdifference(ID1x195)
=
ActualDHWtemperature
=
DHWheating/chargingactivity
AQ055186460331en-010501
©Danfoss|2021.04|53

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Stopdifference
OneDHWtanktemperaturesensor:
SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill
stoptheDHWheating(charging).
TwoDHWtanktemperaturesensors:
SetthenumberofdegreesaboveorbelowthedesiredDHWtemperature,
butmeasuredbythelowertanktemperaturesensorthatwillstoptheDHW
heating(charging).
SeeAppendix“ParameterIDoverview”
–50...50:
Setthenumberofdegrees.
OneDHWtanktemperaturesensor(examplewithpositive‘Stop
difference’value):
1x194
Temp.
Stopdifference
DesiredDHWtemp.
Time
DHWheating
OneDHWtanktemperaturesensor(examplewithnegative‘Stop
difference’value):
Temp.
Stopdifference
DesiredDHWtemp.
Time
DHWheating
TwoDHWtanktemperaturesensors,upperandlower
Temp.
UpperDHWtemp.sensor
Stopdifference
DesiredDHWtemp.
LowerDHWtemp.sensor
Time
DHWheating
54|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Startdifference
SetthenumberofdegreesbelowthedesiredDHWtemperaturethatwill
starttheDHWheating(charging).
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofdegrees.
1x195
=
X
#1#
#2#
#3#
#4#
#5#
Example:
DesiredDHWtemp.:
Startdifference:
Result:
TheDHWheatingstartswhenthetemperaturemeasuredbythetank
temperaturesensor(upper)islowerthan52°C.
Time
=
Chargingdifference(ID1x193)
=
DesiredDHWtemperature
=
Startdifference(ID1x195)
=
ActualDHWtemperature
=
DHWheating/chargingactivity
55°C
-3K
AQ055186460331en-010501
©Danfoss|2021.04|55

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.3Flowtemperature
TheECLComfort210/296/310controlstheDHWtemperature
accordingtothedesiredflowtemperatureforexampleunderthe
influenceofthereturntemperature.
ThedesiredDHWtemperatureissetintheoverviewdisplay.
ActualDHWtemp.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow
temperaturewillnotbelowerthanthissetting.Adjustthefactory
setting,ifrequired.
DesiredDHW
temp.
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor
'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn
temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired
temperaturewillnotbehigherthanthissetting.Adjustthefactory
setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
56|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.4Returnlimit
Thereturntemperaturelimitationisbasedontheoutdoor
temperature.Typicallyindistrictheatingsystemsahigherreturn
temperatureisacceptedatadecreaseinoutdoortemperature.The
relationshipbetweenthereturntemperaturelimitsandoutdoor
temperatureissetintwocoordinates.
Theoutdoortemperaturecoordinatesaresetin'HighToutX1'
and'LowToutX2' .Thereturntemperaturecoordinatesaresetin
'HighlimitY2'and'LowlimitY1' .
Thecontrollerautomaticallychangesthedesiredflowtemperature
toobtainanacceptablereturntemperaturewhenthereturn
temperaturefallsbeloworgetshigherthanthecalculatedlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor)
respondsquicklytodeviationsandI('Adapt.time')responds
slowerandovertimeremovesthesmalloffsetsbetweenthe
desiredandactualvalues.Thisisdonebychangingthedesired
flowtemperature.
X
Y
#X1#
#X2#
#Y1#
#Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant
temperaturevalue.
Thecontrollerautomaticallychangesthedesiredflowtemperature
toobtainanacceptablereturntemperaturewhenthereturn
temperaturefallsbeloworgetshigherthanthesetlimit.
ThislimitationisbasedonaPIregulationwhereP('Infl.'factor)
respondsquicklytodeviationsandI('Adapt.time')responds
slowerandovertimeremovesthesmalloffsetsbetweenthe
desiredandactualvalues.Thisisdonebychangingthedesired
flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay.
Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X
#1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp.
Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp.
Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis
ariskofunstablecontrol.
AQ055186460331en-010501
©Danfoss|2021.04|57

OperatingGuideECLComfort210/296/310,applicationA217/A317
Example,maximumreturntemperaturelimitation;
returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
58|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Example,minimumreturntemperaturelimitation;
returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe
setvalue,thecontrollerautomaticallychangesthedesiredflow/
ducttemperaturetoobtainanacceptablereturntemperature.The
influenceissetin'Infl.-max. 'and'Infl.-min.' .
AQ055186460331en-010501
©Danfoss|2021.04|59

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe
returntemperatureishigherthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn
temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn
temperaturegetshigherthanthecalculatedlimit.
1x035
=
X
#1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp.
Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp.
Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis
ariskofunstablecontrol.
Example
Thereturnlimitisactiveabove50°C.
Theinfluenceissetto-2.0.
Theactualreturntemperatureis2degreestoohigh.
Result:
Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto
avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn
temperatureisacceptable(seealso'Infl.-min. ').
60|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe
returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn
temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn
temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn
temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt.
time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value:
Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C.
Theinfluenceissetto-3.0.
Theactualreturntemperatureis2degreestoolow.
Result:
Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower
returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo
lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature
withmax.8K.
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset
min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled.
Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication:
Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication:
Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum
limited,when"Priorityforreturntemperature"(ID1x085)isset
toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe
minimumlimited,when"Priorityforreturntemperature"
(ID1x085)issettoON.
AQ055186460331en-010501
©Danfoss|2021.04|61

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.5Flow/powerlimit
Dependingoncontrollertype,theflow/powerlimitisbasedon
differentinputtypes:
ECLKey
application
A2xx
A3xx
AfloworenergymetercanbeconnectedtotheECLcontrollerin
ordertolimitthefloworconsumedpower.Thesignalfromthe
floworenergymetercanbebasedonpulseorM-bussignal.
Whentheflow/powergetshigherthanthesetlimit,thecontroller
graduallyreducesthedesiredDHWtemperaturetoobtainan
acceptablemax.floworpowerconsumption.
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL
controllerinordertolimitthefloworconsumedpower.
Whentheflow/powergetshigherthanthesetlimit,thecontroller
graduallyreducesthedesiredflowtemperaturetoobtainan
acceptablemax.floworpowerconsumption.
ECLComfort210
ECLComfort310
controller
PulsesignalPulsesignal
NotpossibleM-bussignal
controller
Flow/power
limitation
Desiredflow
temp.
Limit
Time
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
62|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5:
EM1-
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy
meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe
actualoutdoortemperature.
Inotherapplicationsthevalueisaselectablelimitationvalue.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
1x111
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired
limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt.
time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value:
Major
Thedesiredtemperatureisadaptedslowly.
value:
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
AQ055186460331en-010501
©Danfoss|2021.04|63

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured
value.
Thehigherthevalue,themoredampening.
Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value:
Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Pulse
Setthevalueofthepulsesfromtheflow/energymeter.
SeeAppendix“ParameterIDoverview”
OFF:
1...9999:
Noinput.
Pulsevalue.
1x113
Example:
1x114
Onepulsecanrepresentanumberoflitres(fromaflowmeter)
oranumberofkWh(fromaenergymeter).
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue.
Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl.
ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh
orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed
asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare
expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units':
ml,l/h
l,l/h
ml,m³/h
l,m³/h
Wh,kW
kWh,kW
kWh,MW
MWh,MW
MWh,GW
GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h
10
Eachpulserepresents10litresandtheflowisexpressedascubic
meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt)
1
Eachpulserepresents1kiloWatthourandthepoweris
expressedinkiloWatt.
64|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.6Controlparameters
Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point
controlsignal.
Valvecontrol:
Themotorizedcontrolvalveisopenedgraduallywhentheflow
temperatureislowerthanthedesiredflowtemperatureandvice
versa.
Thewaterflowthroughthecontrolvalveismanagedbymeans
ofanelectricactuator.Thecombination"actuator"and"control
valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin
thiswaygraduallyincreaseordecreasetheflowinordertochange
thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator:
Theelectricactuatorcontainsareversiblegear-motor.Electric
"open"and"close"signalscomefromtheelectronicoutputsofthe
ECLComfortcontrollerinordertomanagethecontrolvalve.The
signalsareintheECLComfortcontrollerexpressedas"Arrow-up"
(open)and"Arrow-down"(close)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe
desiredflowtemperature,shortopen-signalscomefromtheECL
Comfortcontrollerinordertograduallyincreasetheflow.Bythis,
theflowtemperaturewillalignwiththedesiredtemperature.
Oppositely,whentheflowtemperatureishigherthanthedesired
flowtemperature,shortclose-signalscomefromtheECLComfort
controllerinordertograduallyreducetheflow.Again,theflow
temperaturealignswiththedesiredtemperature.
Neitheropen-signalsnorclose-signalswillcomeaslongastheflow
temperaturecorrespondstothedesiredtemperature.
AQ055186460331en-010501
©Danfoss|2021.04|65

OperatingGuideECLComfort210/296/310,applicationA217/A317
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator.
InsidetheABVanelectricheatcoilwillheatathermostaticelement
whenanelectricsignalisapplied.Whenheatingthethermostatic
elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO
(normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve
closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL
Comfortcontrollerinordertomanagethecontrolvalve.When
open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas
"Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe
desiredflowtemperature,relativelylongopen-signalscomefrom
theECLComfortcontrollerinordertoincreasetheflow.Bythis,
theflowtemperaturewillovertimebealignedwiththedesired
temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired
flowtemperature,relativelyshortopen-signalscomefromtheECL
Comfortcontrollerinordertoreducetheflow.Again,theflow
temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique
designedalgorithmandisbasedonthePWMprinciple(Pulse
WidthModulation),wherethedurationofthepulsedetermines
themanagementofthecontrolvalve.Thepulsesarerepeated
each10sec.
Aslongastheflowtemperaturecorrespondstothedesired
temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Opentime
The‘Opentime’istheforcedtime(inseconds)thatittakestoopenthe
motorizedcontrolvalvewhenaDHWdraw-off(tapping)isdetected(the
flowswitchisactivated).Thisfunctioncompensatesforthedelaybeforethe
flowtemperaturesensormeasuresachangeintemperature.
1x094
SeeAppendix“ParameterIDoverview”
66|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Closetime
The‘Closetime’istheforcedtime(inseconds)thatittakestoclosethe
motorizedcontrolvalvewhenaDHWdraw-off(tapping)isstopped(the
flowswitchisdeactivated).Thisfunctioncompensatesforthedelaybefore
theflowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Tn(idle)
WhennoDHWdraw-off(tapping)isdetected(theflowswitchisdeactivated),
thetemperatureismaintainedatalowlevel(savingtemperature).The
integrationtime‘Tn(idle)’canbesettoobtainaslowbutstablecontrol.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
SupplyT(idle)
The‘supplyT(idle)’isthesupplytemperaturewhenthereisnoDHW
draw-off(tapping).WhenDHWdraw-offisnotdetected(theflowswitch
isdeactivated),thetemperatureismaintainedatalowerlevel(saving
temperature).Choosewhichtemperaturesensoristomaintainthesaving
temperature.
1x095
1x096
1x097
Ifthesupplytemperaturesensorisnotconnected,theidlesupply
temperaturewillbemaintainedattheDHWflowtemperaturesensor.
SeeAppendix“ParameterIDoverview”
OFF:
ThesavingtemperatureismaintainedattheDHWflow
temperaturesensor.
ON:
Thesavingtemperatureismaintainedatthesupply
temperaturesensor.
AQ055186460331en-010501
©Danfoss|2021.04|67

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp'
'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must
beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated.
Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol
parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp',
'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning
functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof
thecontroller,butitcanbeactivatedwhenneeded,e.g.foran
extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe
adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided
duringtheautotuningprocess.Shouldthetappingloadvarytoo
much,theautotuningandcontrollerwillreturntothedefault
settings.
No.of
apartments
Heat
transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493
3-950-796
10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust
besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated
duringautotuning.Duringautotuningthecirculationpumpfortap
watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis
controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare
approvedforautotuning,i.e.theDanfosstypesVB2andVM2with
splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open)
(or1tap50%open)
(or1tap100%open)
(or1tap100%+1tap50%
open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe
autotuningisended,thefunctionisautomaticallyconvertedto
OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting
actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection
increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation
delayinminutes.
1x174
Recommendedforductsystemswithvariableload.
68|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Xpactual
CircuitSettingrange
1
‘Xpactual’istheread-outoftheactualXp(proportionalband)basedon
thesupplytemperature.Xpisdeterminedbysettingsrelatedtothesupply
temperature.Typically,thehigherthesupplytemperature,thehighertheXp
mustbeinordertoachieveastabletemperaturecontrol.
Read-outonly
Factorysetting
Xpsettingrange:
5...250K
Fixedsupplytemperaturesettings:65°Cand90°C
Factorysettings:
(65,40)and(90,120)
Thismeansthatthe‘Xp’is40Kat65°Csupplytemperature,and
‘Xp’is120Kat90°C.
SetthedesiredXpvaluesatthetwofixedsupplytemperatures.
Ifthesupplytemperatureisnotmeasured(thesupplytemperature
sensorisnotconnected),theXpvalueatthesetting65°Cisused.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow
butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast
butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove
fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning
timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing
thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
AQ055186460331en-010501
©Danfoss|2021.04|69

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller
doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh
variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear
motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature
value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis
temperature.
SettingexampleValuex20ms
1x189
240ms
10200ms
501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe
lifetimeoftheactuator(gearmotor).
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
•Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
•Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it
mightbenecessarytoforcethesystembysettinganextremelowvalue).
•Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod.
‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption
whenyousettheparameters.
70|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.7Application
Thesection"Application"describesspecificapplicationrelated
issues.
Someoftheparameterdescriptionsareuniversalfordifferent
applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat
noon(12:14hours).
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes
everythirddayatnoon(12:00hours).
MENU>Settings>Application
1x022
1x023
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof
minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow
temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof
minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow
temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070).
ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea
heatexchanger.
SeeAppendix“ParameterIDoverview”
0:
Thecirculationpumpstopsimmediatelyafterheating
orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating
orcoolingstop.
AQ055186460331en-010501
1x040
©Danfoss|2021.04|71

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
DHWPpost-run(DHWpump,post-run)
SettheDHWpumppost-runtime(minutes).TheDHWpumpcancontinue
tobeswitchedONaftertheDHWheatingprocedureinordertoutilizethe
remainingheatintheheatexchanger/boiler.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
Char.Ppost-run(DHWchargingpump,post-run)
SettheDHWchargingpumppost-runtime(minutes).TheDHWcharging
pumpcancontinuetobeswitchedONaftertheDHWheatingprocedurein
ordertoutilizetheremainingheatintheheatexchanger.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
1x041
1x042
Cont.Tcontrol
ThedesiredDHWheating/chargingtemperaturecanbeloweredwhenthe
DHWheating/chargingprocedurehaselapsed.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredheating/chargingtemperatureislowered
to10°C.Typically,theDHWiscirculatedthroughthe
DHWtank.
ON:
Thedesiredheating/chargingtemperatureislowered
tothedesiredDHWtemperature.Typically,theDHW
iscirculatedthroughtheheatexchangerinorderto
compensatefortheheatlossintheDHWcirculation
pipe.
MENU>Settings>Application
Circ.Ppriority
ChoosewhethertheDHWcirculationpumpshouldbeONduringDHW
heating.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisswitchedOFFduringDHW
heating.
ON:
TheDHWcirculationpumpisnotswitchedOFFduring
DHWheating.
1x054
1x055
Whenthe'Circ.Ppriority'issettoOFF ,theschedulefortheDHW
circulationpumpisoverruled.
72|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
Circ.PfrostT
SettheoutdoortemperaturevalueatwhichtheDHWcirculationpumpisto
beactivetoprotecttheDHWcircuitagainstfrost.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisnotactive.
Value:TheDHWcirculationpumpisactivewhentheoutdoor
temperatureislowerthanthesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe
systemagainstfrost(atheatingcut-out,totalstopetc.).
WhenthetemperatureatS3getslowerthanthesetting,themotorized
controlvalveopensgradually.
SeeAppendix“ParameterIDoverview”
1x076
1x093
Thefrostprotectiontemperaturecanalsobesetinyourfavorite
displaywhenthemodeselectorisinfrostprotectionmode.
AQ055186460331en-010501
©Danfoss|2021.04|73

OperatingGuideECLComfort210/296/310,applicationA217/A317
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL
Comfort210/296/310series.Theexplainedmodesaretypical
andnotapplicationrelated.Theymightdifferfromtheoverride
modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch
thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or
'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride.
Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave
gold-platedcontacts.
IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea
standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand
overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,alsoS11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis
appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
74|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or
ConstantTmode.
Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe
overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe
overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost
protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant
temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow
temperature(MENU>Settings>Flowtemperature)
Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn
temperaturelimitation(MENU>Settings>Return
limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated)
#2#=Functionmode(Schedule/Comfort)
#3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated)
#2#=Functionmode(Schedule/Saving)
#3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin
'Totalstop'.
Totalstop=OFF:Heatingreduced
Totalstop=ON:Heatingstopped
AQ055186460331en-010501
©Danfoss|2021.04|75

OperatingGuideECLComfort210/296/310,applicationA217/A317
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated)
#2#=Functionmode(Schedule/Frostpr.)
#3#=Time
Example:OverridetoConstanttemperaturemode
#1#=Overrideswitch(notactivated/activated)
#2#=Functionmode(Schedule/Const.T)
#3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
76|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
SenddesiredT
Whenthecontrolleractsasaslavecontrollerinamaster/slavesystem,
informationaboutthedesiredflowtemperaturecanbesenttothemaster
controllerviatheECL485bus.
Stand-alonecontroller:
Sub-circuitscansendthedesiredflowtemperaturetothemastercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Informationaboutthedesiredflowtemperatureisnot
senttothemastercontroller.
ON:
Informationaboutthedesiredflowtemperatureissent
tothemastercontroller.
1x500
Inthemastercontroller,'Demandoffset'mustbesettoavalueinorder
toreactonadesiredflowtemperaturefromaslavecontroller.
Whenthecontrolleractsasaslave,itsaddressmustbe1,2,3...9in
ordertosendthedesiredtemperaturetothemaster(seethesection
‘Miscellaneous’ ,‘Severalcontrollersinthesamesystem’).
AQ055186460331en-010501
©Danfoss|2021.04|77

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.8Anti-bacteria
OnselecteddaysduringtheweektheDHWtemperaturecan
beincreasedinordertoneutralizebacteriaintheDHWsystem.
ThedesiredDHWtemperature'DesiredT'(typically80°C)willbe
presentfortheselectedday(s)andduration.
Theanti-bacteriafunctionisnotactiveinfrostprotectionmode.
=
X
Y
#1#
#2#
#3#
#4#
#5#
Time
=
DesiredDHWtemperature
=
Duration
=
DesiredAnti-bacteriatemperaturevalue
=
DesiredAnti-bacteriatemperature
=
DesiredDHWtemperaturevalue
=
Starttime
MENU>Settings>Anti-bacteria
Day
Select(mark)theday(s)oftheweekwheretheanti-bacteriafunctionmust
beactive.
=
Monday
M
=
Tuesday
T
=
Wednesday
W
=
Thursday
T
=
Friday
F
=
Saturday
S
=
Sunday
S
Duringtheanti-bacteriaprocess,thereturntemperaturelimitationis
notactive.
78|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Anti-bacteria
Starttime
Setthestarttimefortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
Duration
Settheduration(minutes)fortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
DesiredT
SetthedesiredDHWtemperaturefortheanti-bacteriafunction.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theanti-bacteriafunctionisnotactive.
DesiredDHWtemperatureduringtheanti-bacteria
functionperiod.
AQ055186460331en-010501
©Danfoss|2021.04|79

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.9Alarm
ManyapplicationsintheECLComfort210and310serieshavean
alarmfunction.Thealarmfunctiontypicallyactivatesrelay4(ECL
Comfort210)orrelay6(ECLComfort310).
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm
transmittingdeviceetc.
Therelayinquestionisactivatedaslongasthealarmcondition
ispresent.
Typicalalarms:
•Actualflowtemperaturediffersfromthedesiredflow
temperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
5.9.1Temp.monitor.
MENU>Settings>Alarm
Upperdifference
Thealarmisactivatediftheactualflowtemperatureincreasesmorethan
thesetdifference(acceptabletemperaturedifferenceabovethedesired
flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Therelatedalarmfunctionisnotactive.
Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
1x147
Upperdifference
=
X
=
Y
=
#1#
=
#2#
Time
Temperature
Upperdifference
Desiredflowtemperature
80|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Alarm
Lowerdifference
Thealarmisactivatediftheactualflowtemperaturedecreasesmorethan
thesetdifference(acceptabletemperaturedifferencebelowthedesired
flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
1x148
Lowerdifference
OFF:
Value:
Therelatedalarmfunctionisnotactive.
Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
MENU>Settings>Alarm
Delay,example
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is
presentforalongertimethanthesetdelay(inminutes),thealarmfunction
isactivated.
SeeAppendix“ParameterIDoverview”
Value:
Thealarmfunctionwillbeactivatedifthealarm
conditionremainsafterthesetdelay.
=
X
Y
#1#
#2#
Delay,example
1x149
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
MENU>Settings>Alarm
Lowesttemp.
Thealarmfunctionwillnotbeactivatedifthedesiredflowtemperature
islowerthanthesetvalue.
SeeAppendix“ParameterIDoverview”
=
X
Y
#1#
#2#
#3#
#4#
1x150
Ifthecauseofthealarmdisappears,thealarmindicationandoutput
alsodisappear.
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
=
Actualflowtemperature
=
Delay(ID1x149)
AQ055186460331en-010501
©Danfoss|2021.04|81

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Alarm
Alarmvalue
AfirethermostatcanbeconnectedtotheS8input.Whenthetemperature,
measuredbythefirethermostat,getsabovethesetvalue,theS8inputwill
beactivated.
Thefirealarmcanbeactivatedwhenthecontactsinthefirethermostat
openorclose.
SeeAppendix“ParameterIDoverview”
0:
Thefirealarmisactivatedwhenthecontactsinthefire
thermostatclose.
1:
Thefirealarmisactivatedwhenthecontactsinthefire
thermostatopen.
MENU>Settings>Alarm
Alarmtime-out
Thealarmisactivatedwhenthealarmreasonhasbeenpresentforalonger
time(inseconds)thanthesetvalue.
SeeAppendix“ParameterIDoverview”
Value:Setthealarmtime-out
1x636
Anactivefirealarmisindicatedbyainthedisplay.
S8inputstatus:
MENU>Commoncontroller>System>Rawinputoverview>S8:
0=Inputactivated.1=inputnotactivated
Seealso'Alarmtime-out' ,parameter1x637.
1x637
82|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
5.10Alarmoverview
MENU>Alarm>Alarmoverview
Thismenushowsthealarmtypes,forexample:
•"2:T emp.monitor"
•"32:Tsensordefect"
Thealarmhasbeenactivatedifthealarmsymbol(abell)(
presenttotherightofthealarmtype.
)is
Resettinganalarm,ingeneral:
MENU>Alarm>Alarmoverview:
Lookforalarmsymbolinspecificline.
(Example:"2:Temp.monitor")
Movecursortothelineinquestion.
Pushdial.
Alarmoverview:
Alarmsourcesarelistedinthisoverviewmenu.
Someexamples:
"2:Temp.monitor"
"5:Pump1"
"10:DigitalS12"
"32:Tsensordefect"
Relatedtotheexamples,thenumbers2,5and10areusedinthealarm
communicationtotheBMS/SCADAsystem.
Relatedtotheexamples,"Temp.monitor" ,"Pump1"and"DigitalS12"
arethealarmpoints.
Relatedtotheexamples,"32:Tsensordefect"indicatesthemonitoring
ofconnectedsensors.
Alarmnumbersandalarmpointsmightdifferdependingonactual
application.
AQ055186460331en-010501
©Danfoss|2021.04|83

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.0Commoncontrollersettings
6.1Introductionto‘Commoncontrollersettings’
Somegeneralsettingswhichapplytotheentirecontrollerare
locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
84|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.2Time&Date
Itisonlynecessarytosetthecorrectdateandtimeinconnection
withthefirstuseoftheECLComfortcontrollerorafterapower
breakofmorethan72hours.
Thecontrollerhasa24hourclock.
Aut.daylight(Daylightsavingtimechangeover)
YES:
NO:
Thecontroller’sbuilt-inclockautomaticallychanges+/
-onehouronthestandardizeddaysfordaylightsaving
timechangeoverforCentralEurope.
Youchangemanuallybetweensummerandwintertime
bysettingtheclockbackwardorforward.
Howtosettimeanddate:
Action:
Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Time&Date’
Confirm
Placethecursoratthepositiontobe
changed
Confirm
Enterthedesiredvalue
Confirm
Movethecursortothenextposition
tobechanged.Continueuntil‘Time&
Date’hasbeenset.
Finallymovethecursorto‘MENU’
Whencontrollersareconnectedasslavesinamaster/slavesystem
Examples:
(viaECL485communicationbus),theywillreceive‘Time&Date’from
themaster.
Confirm
Movethecursorto‘HOME’
Confirm
AQ055186460331en-010501
©Danfoss|2021.04|85

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.3Holiday
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Thereisaholidayprogramforeachcircuitandaholidayprogram
forthecommoncontroller.
Eachholidayprogramcontainsoneormoreschedules.Each
schedulecanbesettoastartdateandanenddate.Thesetperiod
startsonthestartdateat00.00andstopsontheenddateat00.00.
SelectablemodesareComfort,Saving,FrostprotectionorComfort
7-23(before7andafter23,themodeisscheduled).
Howtosetyourholidayschedule:
Action:
Purpose:
Examples:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Chooseacircuitor'Commoncontroller
settings'
Heating
DHW
Commoncontrollersettings
Confirm
Goto‘Holiday’
Confirm
Theholidayprograminthe‘Commoncontrollersettings’isvalidfor
allcircuits.Theholidayprogramcanalsobesetindividuallyinthe
heatingorDHWcircuits.
Theenddatemustbeatleastbeonedaylaterthanthestartdate.
Chooseaschedule
Confirm
Confirmchoiceofmodeselector
Choosemode
Comfort
·Comfort7–23
Saving
·Frostprotection
Confirm
Enterthestarttimefirstandthenthe
endtime
Confirm
Goto‘Menu’
Confirm
Choose‘Yes’or‘No’in‘Save’ .Choose
thenextschedule,ifrequired
86|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
Holiday,specificcircuit/CommonController
Whensettingoneholidayprograminspecificcircuitandanother
holidayprograminCommonController,aprioritywillbetaken
intoaccount:
1.Comfort
2.Comfort7-23
3.Saving
4.Frostprotection
Holiday,deletingasetperiod:
•ChoosetheScheduleinquestion
•Changethemodeto"Clock"
•Confirm
Example1:
Circuit1:
Holidaysetto"Saving"
CommonController:
Holidaysetto"Comfort"
Result:
Aslongas"Comfort"isactiveinCommonController,circuit1willbein
"Comfort".
Example2:
Circuit1:
Holidaysetto"Comfort"
CommonController:
Holidaysetto"Saving"
Result:
Aslongas"Comfort"isactiveincircuit1,itwillbein"Comfort".
Example3:
Circuit1:
Holidaysetto"Frostprotection"
TheECA30/31cannotoverridetheholidayscheduleofthe
controllertemporarily.
However,itispossibletomakeuseofthefollowingoptionsfrom
theECA30/31whenthecontrollerisinscheduledmode:
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
CommonController:
Holidaysetto"Saving"
Result:
Aslongas"Saving"isactiveinCommonController,circuit1willbe
in"Saving".
Energy-savingtrick:
Use'Goingout'(theextendedsavingperiod)forairingpurposes(e.g.
forventilatingtheroomsbymeansoffreshairfromopenwindows).
ConnectionsandsetupproceduresforECA30/31:
Seesection'Miscellaneous'.
Quickguide"ECA30/31tooverridemode":
1.GotoECAMENU
2.Movecursorto"Clock"symbol
3.Selectthe"Clock"symbol
4.Chooseandselectoneof4overridefunctions
5.Belowtheoverridesymbol:Sethoursordate
6.Belowhours/date:Setdesiredroomtemperaturefortheoverride
period
AQ055186460331en-010501
©Danfoss|2021.04|87

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.4Inputoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Theinputoverviewislocatedinthecommoncontrollersettings.
Thisoverviewwillalwaysshowyoutheactualtemperaturesinthe
system(read-only).
"Outdooracc.T"means"Accummulatedoutdoortemperature"andis
acalculatedvalueintheECLComfortcontroller.
88|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.5Log
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Thelogfunction(temperaturehistory)allowsyoutomonitorthe
logsoftoday,yesterday,thepast2daysaswellasthepast4days
fortheconnectedsensors.
Thereisalogdisplayfortherelevantsensor,showingthemeasured
temperature.
Thelogfunctionisonlyavailableinthe'Commoncontroller
settings'.
Example1:
1daylogforyesterdayshowingthedevelopmentinoutdoor
temperatureduringthepast24hours.
Example2:
Today’slogfortheactualheatingflowtemperatureaswellasthe
desiredtemperature.
Example3:
Yesterday’slogfortheDHWflowtemperatureaswellasthedesired
temperature.
AQ055186460331en-010501
©Danfoss|2021.04|89

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.6Outputoverride
ThissectiondescribesthefunctioningeneralfortheECLComfort
210/296/310series.Theshowndisplaysaretypicalandnot
applicationrelated.Theymightdifferfromthedisplaysinyour
application.
Theoutputoverrideisusedtodisableoneormoreofthecontrolled
components.Thiscouldamongothersbeusefulinaservice
situation.
Action:Purpose:
Choose'MENU'inanyoftheoverview
displays
Confirm
Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choosecommoncontrollersettings
Confirm
Choose'Outputoverride'
Confirm
Chooseacontrolledcomponent
Confirm
Adjustthestatusofthecontrolled
component:
Motorizedcontrolvalve:AUTO,STOP ,
CLOSE,OPEN
Pump:AUTO,OFF ,ON
Confirmstatuschange
Examples:
M1,P1etc.
ControlledcomponentsCircuitselector
"Manualcontrol"hashigherprioritythan"Outputoverride".
Whentheselectedcontrolledcomponent(output)isnot‘AUTO’ ,the
ECLComfortcontrollerdoesnotcontrolthecomponentinquestion
(pumpormotorizedcontrolvalvee.g.).Frostprotectionisnotactive.
Remembertochangethestatusbackagainassoonasanoverride
isnotrequiredanylonger.
90|©Danfoss|2021.04
Whenoutputoverrideofacontrolledcomponentisactivethesymbol
‘!’isshowntotherightofthemodeindicatorintheenduserdisplays.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.7Keyfunctions
NewapplicationEraseapplication:
ApplicationGivesanoverviewovertheactual
FactorysettingSystemsettings:
Copy
Keyoverview
Removestheexistingapplication.As
soonastheECLkeyisinserted,another
applicationcanbechosen.
applicationintheECLcontroller.Push
thedialagaintoexittheoverview.
Systemsettingsare,amongothers,
communicationset-up,display
brightnessetc.
Usersettings:
Usersettingsare,amongothers,desired
roomtemperature,desiredDHW
temperature,schedules,heatcurve,
limitationvaluesetc.
Gotofactory:
Restoresthefactorysettings.
To:
Copydirection
Systemsettings
Usersettings
Startcopying
GivesanoverviewovertheinsertedECL
key.(Example:A266Ver.2.30).
Turnthedialtoseethesubtypes.Push
thedialagaintoexittheoverview.
Amoredetaileddescriptionofhowtousetheindividual‘Key
functions’canalsobeseenin‘InsertingtheECLapplicationkey’ .
AQ055186460331en-010501
©Danfoss|2021.04|91

OperatingGuideECLComfort210/296/310,applicationA217/A317
The“Keyoverview”doesnotinform—throughECA30/31—about
thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;for20minutes
settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes
settingscanbechanged.
-
Powerupthecontrollerwithoutthe
applicationkeyinserted;settingscannotbe
changed.
92|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.8System
6.8.1ECLversion
In‘ECLversion’youwillalwaysbeabletofindanoverviewofthe
datarelatedtoyourelectroniccontroller.
Pleasehavethisinformationavailableifyouneedtocontactyour
Danfosssalesorganizationconcerningthecontroller.
InformationaboutyourECLApplicationKeycanbefoundin‘Key
functions’and‘Keyoverview’ .
Codeno.:
Hardware:
Software:Software(firmware)versionof
Serialno.:
Productionweek:Weekno.andyear(WW.YYYY)
6.8.2Extension
ECLComfort310/310B:
‘Extension’willofferyouinformationaboutadditionalmodules,if
any.AnexamplecouldbetheECA32module.
TheDanfosssalesandorderno.
forthecontroller
Hardwareversionofthe
controller
thecontroller
Uniquenumberforthe
individualcontroller
Example,ECLversion
6.8.3Ethernet
ECLComfort296/310/310BhaveaModbus/TCPcommunication
interfacethatallowstheECLcontrollertobeconnectedtoan
Ethernetnetwork.ThisallowsremoteaccesstotheECL296/310/
310Bcontrollerbasedonstandardcommunicationinfrastructures.
In‘Ethernet’itispossibletosetuptherequiredIPaddresses.
6.8.4Portalconfig
ECLComfort296/310/310BhaveaModbus/TCPcommunication
interfacethatallowstheECLcontrollertobemonitoredand
controlledviatheECLPortal.
ECLPortalrelatedparametersaresethere.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com
6.8.5M-busconfig
ECLComfort296/310/310BhaveanM-buscommunication
interfacethatallowsenergymeterstobeconnectedasslaves.
M-busrelatedparametersaresethere.
AQ055186460331en-010501
©Danfoss|2021.04|93

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.8.6EnergymeterandM-bus,generalinformation
ECLComfort296/310/310Bonly
WhenusingtheApplicationKeyintheECLComfort296/310
/310B,upto5energymeterscanbeconnectedtotheM-bus
connections.
Connectionofenergymetercan:
•limittheflow
•limitthepower
•transferenergymeterdatatotheECLPortal,viaEthernet,and/
oraSCADAsystem,viaModbus.
Manyapplicationswithcontrolofheating,DHWorcoolingcircuit
havethepossibilitytoreactonenergymeterdata.
Toverifyifactualapplicationkeycanbesettoreactonenergy
meterdata:
SeeCircuit>MENU>Settings>Flow/power.
TheECLComfort296/310/310Bcanalwaysbeusedfor
monitoringpurposeofupto5energymeters.
TheECLComfort296/310/310BactasanM-busmasterandmust
besettocommunicatewithconnectedenergymeter(s).
SeeMENU>Commoncontroller>System>M-busconfig.
EnergymeterdataacquisitionfromECLPortalispossiblewithout
settinguptheM-busconfiguration.
Technicalinfo:
•TheM-busdataarebasedonstandardEN-1434.
•DanfossrecommendsACsuppliedenergymetersinorderto
avoidbatterydraining.
MENU>Commoncontroller>System>M-busconfig.
State
CircuitSettingrange
Read-out
Factorysetting
---
InformationaboutthecurrentM-busactivity.
IDLE:
INIT:
SCAN:
GATEW:
Normalstate
Thecommandforinitializationhasbeenactivated
Thecommandforscanninghasbeenactivated
ThecommandGatewayhasbeenactivated
MENU>Commoncontroller>System>M-busconfig.
TheECLComfort296/310/310BwillreturntoIDLEwhencommands
havebeencompleted.
Gatewayisusedforread-outofenergymeterviaECLPortal.
Baud(bitspersecond)
CircuitSettingrange
-
300/600/1200/2400
ThecommunicationspeedbetweenECLComfort296/310/310B
andtheconnectedenergymeter(s).
94|©Danfoss|2021.04
5997
Factorysetting
300
Typically,300or2400baudisused.
IfECLComfort296/310/310BareconnectedtotheECLPortal,abaud
rateof2400isrecommendable,providedtheenergymeterallowsthis.
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Commoncontroller>System>M-busconfig.
Command
CircuitSettingrange
-
NONE/INIT/SCAN/GA TEWNONE
Factorysetting
TheECLComfort296/310/310BareM-busmasters.Inordertoverify
connectedenergymeters,differentcommandscanbeactivated.
NONE:
INIT:
SCAN:
Nocommandactivated
Initializationisactivated
Scanningisactivatedinordertosearchforconnected
energymeters.TheECLComfort296/310/310B
detecttheM-busaddressesofupto5connected
energymetersandplacetheseautomaticallyinthe
"Energymeters"section.Theverifiedaddressisplaced
after"Energymeter1(2,3,4,5)"
GATEW:
TheECLComfort296/310/310Bactasagateway
betweenenergymetersandECLPortal.Usedonlyfor
service.
MENU>Commoncontroller>System>M-busconfig.
M-busaddress
Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-255255
Factorysetting
Thesetorverifiedaddressofenergymeter1(2,3,4,5).
5998
Scantimecantakeupto12minutes.
Whenallenergymetersarefound,thecommandcanbechanged
toINITorNONE.
6000
0:
1-250:
251-254:
Normallynotused
ValidM-busaddresses
Specialfunctions.UseonlyM-busaddress254when
oneenergymeterisconnected.
255:
Notused
MENU>Commoncontroller>System>M-busconfig.
Type
Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-40
Factorysetting
SelectingdatarangefromtheM-bustelegram..
0:
1:
2:
3:
4:
Smalldataset,smallunits
Smalldataset,largeunits
Largedataset,smallunits
Largedataset,largeunits
Volumeandenergydataonly
(example:HydroPortPulse)
6001
Dataexamples:
0:
Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy.
3:
Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy,
tariff1,tariff2.
Seealsothe"Instructions,ECLComfort210/310,communication
description"forfurtherdetails.
SeealsoAppendixfordetaileddescriptionof"Type".
AQ055186460331en-010501
©Danfoss|2021.04|95

OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Commoncontroller>System>M-busconfig.
Scantime
Energymeter1(2,3,4,5)
CircuitSettingrange
-
1-3600sec60sec
Factorysetting
Settingthescanningtimeforacquiringdataofconnectedenergy
meter(s).
MENU>Commoncontroller>System>M-busconfig.
ID
Energymeter1(2,3,4,5)
CircuitSettingrange
Factorysetting
---
Informationabouttheenergymeter'sserialno.
MENU>Commoncontroller>System>Energymeters
Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-40
Factorysetting
Informationfromactualenergymeterabout,forexample,ID,
temperatures,flow/volume,power/energy.
Theshowninformationdependsonthesettingsmadeinthe“M-bus
config. ”menu.
Read-out
Read-out
6002
Iftheenergymeterisbatterypowered,thescantimeshouldbesetto
ahighvaluetopreventatoofastbatterydraining.
Oppositely,iftheflow/powerlimitationfunctionisusedintheECL
Comfort310,thescantimeshouldbesettoalowvalueinorderto
havequicklimitation.
6.8.7EnergyMeters
TheECLComfort296/310/310Ballowcommunicationwithup
to5energymetersviaM-bus.In‘EnergyMeters’datacanberead
thefromM-busconnectedenergymeters
96|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
6.8.8Rawinputoverview
Measuredtemperatures,inputstatusandvoltagesaredisplayed.
Inaddition,adetectionofmalfunctionscanbechosenforactivated
temperatureinputs.
Monitoringthesensors:
Choosethesensorwhichmeasuresatemperature,forexamplethe
S5.Whenthedialispressed,amagnifyingglass
selectedline.TheS5temperatureisnowbeingmonitored.
Alarmindication:
Shouldtheconnectiontothetemperaturesensorbedisconnected,
short-circuitedorthesensoritselfbedefective,thealarmfunction
isactivated.
Inthe"Rawinputoverview"analarmsymbolisshownatthe
defectivetemperaturesensorinquestion.
Resettingthealarm:
Choosethesensor(Snumber)forwhichyouwanttoclearthe
alarm.Pressthedial.Themagnifyingglass
disappear.
Whenthedialispressedagain,themonitoringfunctionis
reactivated.
appearsinthe
andalarmsymbols
Thetemperaturesensorinputshaveameasuringrangefrom-60...
150°C.
Ifatemperaturesensororitsconnectionbreaks,thevalueindication
is"--".
Ifatemperaturesensororitsconnectionisshort-circuited,thevalue
indicationis"---" .
6.8.9Sensoroffset(newfunctionalityasfromfirmware1.59)
Themeasuredtemperaturecanbeoffsetadjustedinorderto
compensateforcableresistanceoranot-optimumplaceforthe
temperaturesensor.Theadjustedtemperaturecanbeseenin"Raw
inputoverview"and"Inputoverview".
Commoncontroller>System>Sensoroffset
Sensor1...(temperaturesensor)
CircuitSettingrange
Factorysetting
**
Settingtheoffsetofthemeasuredtemperature.
Positive
Thetemperaturevalueisincreased
offset
value:
Negative
Thetemperaturevalueisdecreased
offset
value:
6.8.10Display
Backlight(displaybrightness)
CircuitSettingrange
60058
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
10:
Weakbacklight.
Strongbacklight.
AQ055186460331en-010501
©Danfoss|2021.04|97

OperatingGuideECLComfort210/296/310,applicationA217/A317
Contrast(displaycontrast)
CircuitSettingrange
0...103
Adjustthecontrastofthedisplay.
0:
10:
Lowcontrast.
Highcontrast.
6.8.11Communication
Modbusaddr .
CircuitSettingrange
1...247
SettheModbusaddressifthecontrollerispartofaModbus
network.
1...247:
AssigntheModbusaddresswithinthestatedsetting
range.
60059
Factorysetting
38
Factorysetting
1
ECL485addr.(master/slaveaddress)
CircuitSettingrange
Factorysetting
0...15
Thissetttingisrelevantifmorecontrollersareworkinginthesame
ECLComfortsystem(connectedviatheECL485communication
bus)and/orRemoteControlUnits(ECA30/31)areconnected.
0:
Thecontrollerworksasslave.
Theslavereceivesinformationabouttheoutdoor
temperature(S1),systemtime,andsignalforDHW
demandinthemaster.
1...9:
Thecontrollerworksasslave.
Theslavereceivesinformationabouttheoutdoor
temperature(S1),systemtime,andsignalforDHW
demandinthemaster.Theslavesendsinformation
aboutthedesiredflowtemperaturetothemaster.
10...14:
15:
Reserved.
TheECL485communicationbusisactive.
Thecontrollerismaster.Themastersendsinformation
abouttheoutdoortemperature(S1)andsystemtime.
ConnectedRemoteControlUnits(ECA30/31)are
powered.
TheECLComfortcontrollerscanbeconnectedviatheECL485
communicationbustoperformalargersystem(theECL485
communicationbuscanconnecttomax.16devices).
2048
15
Thetotalcablelengthofmax.200m(alldevicesincl.theinternalECL
485communicationbus)shouldnotbeexceeded.
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
InasystemwithMASTER/SLAVEcontrollers,onlyoneMASTER
controllerwithaddress15isallowed.
IfbymistakemoreMASTERcontrollersarepresentinanECL485
communicationbussystem,decidewhichcontrolleristobeMASTER.
Changetheaddressintheremainingcontrollers.However,thesystem
willoperatebutnotbestablewithmorethanoneMASTERcontroller.
IntheMASTERcontroller,theaddressin‘ECL485addr.(master/slave
address)’ ,IDno.2048,mustalwaysbe15.
Eachslavemustbeconfiguredwithitsownaddress(1...9).
However,moreslavescanhavetheaddress0iftheyonlyhaveto
receiveinformationaboutoutdoortemperatureandsystemtime
(listeners).
98|©Danfoss|2021.04
AQ055186460331en-010501

OperatingGuideECLComfort210/296/310,applicationA217/A317
ServicePin
CircuitSettingrange
Factorysetting
0/1
Thissettingisonlyusedinconnectionwithset-upofModbus
communication.
Notapplicableforthetimebeingandreservedforfuture
use!
Ext.reset
CircuitSettingrange
Factorysetting
0/1
Thissettingisonlyusedinconnectionwithset-upofModbus
communication.
0:
1:
Resetnotactivated.
Reset.
6.8.12Language
2150
0
2151
0
Language
CircuitSettingrange
Chooseyourlanguage.
English/‘Local’English
2050
Factorysetting
Locallanguageisselectedduringinstallation.Ifyouwanttochangeto
anotherlocallanguage,theapplicationmustbereinstalled.However,
itisalwayspossibletochangebetweenthelocallanguageandEnglish.
AQ055186460331en-010501
©Danfoss|2021.04|99

OperatingGuideECLComfort210/296/310,applicationA217/A317
7.0Miscellaneous
7.1Severalcontrollersinthesamesystem
WhenECLComfortcontrollersareinterconnectedbymeansof
theECL485communicationbus(cabletype:2xtwistedpair),the
mastercontrollerwillbroadcastthefollowingsignalstotheslave
controllers:
•Outdoortemperature(measuredbyS1)
•Timeanddate
•DHWtankheating/chargingactivity
Furthermore,themastercontrollercanreceiveinformationabout:
•thedesiredflowtemperature(demand)fromslavecontrollers
•and(asfromECLcontrollerversion1.48)DHWtankheating/
chargingactivityinslavecontrollers
Situation1:
SLAVEcontrollers:Howtomakeuseoftheoutdoor
temperaturesignalsentfromtheMASTERcontroller
Theslavecontrollersonlyreceiveinformationaboutoutdoor
temperatureanddate/time.
SLAVEcontrollers:
Changethefactorysetaddressfrom15toaddress0.
•In
,gotoSystem>Communication>ECL485addr.
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike
this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe
master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
ECL485addr.(master/slaveaddress)
CircuitSettingrange
2048
Choose
0...150
MaximumrecommendedlengthoftheECL485bus:
200-81m=119m
InasystemwithMASTER/SLAVEcontrollers,onlyoneMASTER
controllerwithaddress15isallowed.
IfbymistakemoreMASTERcontrollersarepresentinanECL485
communicationbussystem,decidewhichcontrolleristobeMASTER.
Changetheaddressintheremainingcontrollers.However,thesystem
willoperatebutnotbestablewithmorethanoneMASTERcontroller.
IntheMASTERcontroller,theaddressin‘ECL485addr.(master/slave
address)’ ,IDno.2048,mustalwaysbe15.
Navigation:
•In
SLAVEcontrollersmustbesettoanotheraddressthan15:
Navigation:
•In
,gotoSystem>Communication>ECL485addr.
,gotoSystem>Communication>ECL485addr.
100|©Danfoss|2021.04
'Demandoffset'withavalueistobeusedintheMastercontrolleronly.
AQ055186460331en-010501