Danfoss ECL Comfort 210, ECL Comfort 296, ECL Comfort 310 Operating guide

OperatingGuide
ECLComfort210/296/310,applicationA217/A317

1.0TableofContents

1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................11
2.4Placingthetemperaturesensors................................16
2.5Electricalconnections.............................................18
2.6InsertingtheECLApplicationKey..............................27
2.7Checklist............................................................34
2.8Navigation,ECLApplicationKeyA217/A317................35
3.0Dailyuse.........................................................41
3.1Howtonavigate...................................................41
3.2Understandingthecontrollerdisplay..........................42
3.3Ageneraloverview:Whatdothesymbolsmean?...........44
3.4Monitoringtemperaturesandsystem
components........................................................45
3.5Influenceoverview................................................46
3.6Manualcontrol.....................................................47
3.7Schedule............................................................48
4.0Settingsoverview............................................49
5.0Settings...........................................................51
5.1IntroductiontoSettings..........................................51
5.2Tanktemperature..................................................52
5.3Flowtemperature..................................................56
5.5Flow/powerlimit.................................................62
5.6Controlparameters................................................65
5.7Application.........................................................71
5.9Alarm................................................................80
5.10Alarmoverview....................................................83
6.0Commoncontrollersettings..............................84
6.1Introductionto‘Commoncontrollersettings’................84
6.2Time&Date.........................................................85
6.3Holiday..............................................................86
6.4Inputoverview.....................................................88
6.5Log...................................................................89
6.6Outputoverride....................................................90
6.8System...............................................................93
7.0Miscellaneous................................................100
7.1Severalcontrollersinthesamesystem......................100
7.2Frequentlyaskedquestions....................................103
7.3Definitions........................................................105
7.4Type(ID6001),overview.......................................109
7.5Automatic/manualupdateoffirmware.....................110
7.6ParameterIDoverview..........................................111
©Danfoss|2021.04AQ055186460331en-010501|1
OperatingGuideECLComfort210/296/310,applicationA217/A317

1.1Importantsafetyandproductinformation

1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA217 (ordercodeno.087H3807).
TheA217Keycontainstwosetsofapplications:oneset(A217.1/ A217.2/A217.3)andanotherset(A317.1/A317.2).
Thefunctionscanberealizedin: ECLComfort210(A217)forsimplesolutionsor ECLComfort310(A217/A317)foradvancedsolutions,e.g.M-bus, ModbusandEthernet(Internet)communication.
TheapplicationsA217/A317complywithECLComfortcontrollers 210/310asofsoftwareversion1.11(visibleatstart-upofthe controllerandin‘Commoncontrollersettings’in‘System’).
AdditionaldocumentationforECLComfort210and310,modules andaccessoriesisavailableonhttp://heating.danfoss.com/or
http://store.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare: ECLComfort210/310:0-55°C ECLComfort296:0-45°C. Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould bereadwithspecialattention.
2|©Danfoss|2021.04
Applicationkeysmightbereleasedbeforealldisplaytextsare translated.InthiscasethetextisinEnglish.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem settingswillbemarkedwithasystemtype.Allsystemtypesareshown inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK (Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
12174
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere arespecialsettingsforoneormoresystemtypes.Itwillbemarked withthesystemtypeinquestion(e.g.12174-A266.9).
1
-
Circuit1Parameterno.
2
Circuit2Parameterno.
174
AQ055186460331en-010501
©Danfoss|2021.04|3
OperatingGuideECLComfort210/296/310,applicationA217/A317
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back schemefortherecyclingofelectricalandelectronic equipment.
•Disposeoftheproductthroughchannelsprovided forthispurpose.
•Complywithalllocalandcurrentlyapplicablelaws andregulations.
4|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.0Installation

2.1Beforeyoustart

Thetwoapplications,A217.1/A317.1arealmostidentical. However,A317.1hassomeextrafunctionswhicharedescribed separately.
TheapplicationsA217.1/A317.1areveryflexible.Thesearethe basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesforthedesiredDHWtemperatureatS6).
Theheating/chargingtemperaturesensorS3isthemost importantsensor.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired DHWtemperature,theDHWheating/chargingpump(P1)is switchedON.
Themotorizedcontrolvalve(M1)iscontrolledinordertomaintain theheating/chargingtemperatureatS3.Thistemperatureis typically5–10degreeshigherthanthedesiredDHWtemperature. Amax.valuecanbeset.
DHWtankwith1temperaturesensor(S6): IfthemeasuredDHWtemperature(S6)getshigherthanthe desiredDHWtemperature,theDHWheating/chargingpump(P1) isswitchedOFF.Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8): IfthemeasuredDHWtemperature(S6)getshigherthanthedesired DHWtemperatureandthelowertemperature(atS8)getshigher thanthecut-outtemperature,theDHWheating/chargingpump (P1)isswitchedOFF.Thepost-runtimecanbeset.
InchargingapplicationstheDHWcirculationcanbethrough theDHWtank(connectionA)orthroughtheheat-exchanger (connectionB).
TypicalA217.1./A317.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
Chargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWchargingpump(DHWheatingpump)
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
ThesolutionwithconnectionAresultsinclosingofthemotorized controlvalveaftertheDHWtankchargingprocedure. ThesolutionwithconnectionBisusedtocompensateforthe heatlossintheDHWcirculationpipe.Furthermore,afterDHW tankcharging,thecirculationtemperature(atS3)iscontrolled accordingtothedesiredDHWtemperature.
Thereturntemperature(S5)tothedistrictheatingsupplyshould notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe adjusted(typicallytoalowervalue),thusresultinginagradual closingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3 ON-periodsperday.
AQ055186460331en-010501
©Danfoss|2021.04|5
OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationA217.1(usedinECLComfort210)/A317.1(usedin ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased onpulsesignalsandinECLComfort310basedonM-bussignal) canlimitthefloworenergytoasetmaximum.
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In ECLComfort310theM-busdatacanfurthermorebetransferred totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6) canbeactivatediftheactualflowtemperatureatS3differsfrom thedesiredDHWchargingtemperature.
A217.1/A317.1examplea:
A217.1/A317.1exampleb:
A217.1/A317.1examplec:
A217.1/A317.1exampled:
A217.1/A317.1examplee:
6|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thetwoapplications,A217.2/A317.2arealmostidentical. However,A317.2hassomeextrafunctionswhicharedescribed separately.
TheapplicationsA217.2/A317.2areveryflexible.Thesearethe basicprinciples:
DomesticHotWater(DHW):
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesforthedesiredDHWtemperatureatS6).
TheDHWheatingtemperaturesensorS3andthecharging temperaturesensorS4arethemostimportantsensors.
IfthemeasuredDHWtemperature(S6)getslowerthanthedesired DHWtemperature,theDHWheatingpump(P1)isswitchedON.The motorizedcontrolvalve(M1)iscontrolledinordertomaintainthe DHWheatingtemperatureatS3.TheDHWheatingtemperatureis determinedbythedesiredDHWchargingtemperatureatS4.
WhentheDHWheatingtemperatureisreached,theDHWcharging pumpP2isswitchedON.
IftheDHWchargingtemperatureatS4cannotbereached,the ECLcontrollergraduallyincreasesthedesiredDHWheating temperatureatS3inordertoobtainthechargingtemperature. Amax.valuecanbeset.
TheDHWchargingtemperatureatS4istypically5–10degrees higherthanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor(S6): IfthemeasuredDHWtemperature(S6)getshigherthanthedesired DHWtemperature,theDHWheatingpump(P1)andtheDHW chargingpump(P2)areswitchedOFF .Thepost-runtimecanbeset.
DHWtankwith2temperaturesensors(S6andS8): IfthemeasuredDHWtemperature(S6)getshigherthanthe desiredDHWtemperatureandthelowertemperature(atS8)gets higherthanthecut-outtemperature,theDHWheatingpump(P1) andtheDHWchargingpump(P2)areswitchedOFF .Thepost-run timecanbeset.
TypicalA217.2./A317.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWheatingtemperaturesensor
S4
DHWchargingtemperaturesensor
S5Returntemperaturesensor
S6
DHWtanktemperaturesensor,upper
S8
DHWtanktemperaturesensor,lower
P1
DHWheatingpump
P2
DHWchargingpump
P3
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
InchargingapplicationstheDHWcirculationcanbethrough theDHWtank(connectionA)orthroughtheheat-exchanger (connectionB). ThesolutionwithconnectionAresultsinclosingofthemotorized controlvalveaftertheDHWtankchargingprocedure. ThesolutionwithconnectionBisusedtocompensatefortheheat lossintheDHWcirculationpipe. Furthermore,afterDHWtankcharging,thecirculationtemperature (atS4)iscontrolledaccordingtothedesiredDHWtemperature.
AQ055186460331en-010501
©Danfoss|2021.04|7
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thereturntemperature(S5)tothedistrictheatingsupplyshould notbetoohigh.Ifso,thedesiredchargingtemperaturecanbe adjusted(typicallytoalowervalue),thusresultinginagradual closingofthemotorizedcontrolvalve. Inboiler-basedheatingsupplythereturntemperatureshouldnot betoolow(sameadjustmentprocedureasabove).
Thesupplytemperature,S2,isusedforadjustingtheproportional band(Xp)inordertogiveastabletemperaturecontrol.
Ananti-bacteriafunctionisavailableforactivationonselected daysoftheweek.
TheoutdoortemperaturesensorS1isusedtoprotectthe circulationcircuitagainstfrost.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3 ON-periodsperday.
ApplicationA217.2(usedinECLComfort210)/A317.2(usedin ECLComfort310)ingeneral:
ARemoteControlUnit,theECA30,canbeconnectedinorderto controltheECLcontrollerremotely.
Aconnectedfloworenergymeter(inECLComfort210itisbased onpulsesignalsandinECLComfort310basedonM-bussignal) canlimitthefloworenergytoasetmaximum.
A217.2/A317.2examplea:
A217.2/A317.2exampleb:
Unusedinputcan,bymeansofanoverrideswitch,beusedto overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In ECLComfort310theM-busdatacanfurthermorebetransferred totheModbuscommunication.
Alarmrelay(inECLComfort210itisR4andinECLComfort310R6) canbeactivatediftheactualflowtemperatureatS3differsfrom thedesiredDHWheatingtemperature.
8|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
TheapplicationA217.3isveryflexible.Thesearethebasic principles:
DomesticHotWater(DHW),examplea:
Bymeansofaweekschedulee(upto3‘Comfort’periods/day),the DHWcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent temperaturevaluesforthedesiredDHWtemperatureatS3).The DHWtemperaturesensorS3isthemostimportantsensor.
IfthemeasuredDHWtemperature(S3)islowerthanthedesired DHWtemperature,themotorizedcontrolvalve(M1)isopened graduallyandviceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted (typicallytoalowervalue)thusresultinginagradualclosingofthe motorizedcontrolvalve,i.e.thereturntemperaturewilldecrease.
Thecirculationpump,P1,iscontrolledbymeansofaseparateweek schedule(upto3‘Comfort’periods/day).
IfasupplytemperaturesensorS2isconnected,theproportional bandXpisadaptedtotheactualsupplytemperatureinorderto avoidcontrolinstability.
TypicalA217.3application,examplea:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplytemperaturesensor
S3
DHWsupplytemperaturesensor
S5Returntemperaturesensor
S8
(Flowswitch—examplesb,c,d)
P1
DHWcirculationpump
M1
Motorizedcontrolvalve
A1
Relayoutput,alarm
AQ055186460331en-010501
©Danfoss|2021.04|9
OperatingGuideECLComfort210/296/310,applicationA217/A317
A217.3examplea:
Exampleb:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW ondemand(DHWtapping/DHWdraw-off).Anidletemperature forthesupplytemperature(atS2)canbemaintainedtominimize theheat-uptimefortheDHW.
Examplec:
Aflowswitchsignal(S8)canbeappliedinordertoheattheDHW ondemand(DHWtapping/DHWdraw-off).Thetemperatureat S3ismaintainedduringthecomforttimesofthecirculationpump P1.Anidletemperatureforthesupplytemperature(atS2)canbe maintainedtominimizetheheat-uptimefortheDHW.
Exampled:
TheDHWtankisdirectlyheated.Thesettingofthereturn temperaturelimitation(atS5)canavoidatoohighflowinthe heatingcoil.Anidletemperatureforthesupplytemperature(at S2)canbemaintainedtominimizetheheat-uptimefortheDHW.
A217.3exampleb:
A217.3examplec:
A217.3exampled:
10|©Danfoss|2021.04
Thecontrollerispre-programmedwithfactorysettingsthatareshown inthe‘ParameterIDoverview’appendix.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.2Identifyingthesystemtype

Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange ofheating,domestichot-water(DHW)andcoolingsystemswith differentconfigurationsandcapacities.Ifyoursystemdiffers fromthediagramsshownhere,youmaywanttomakeasketch ofthesystemabouttobeinstalled.Thismakesiteasiertouse theOperatingGuide,whichwillguideyoustep-by-stepfrom installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe usedforvarioussystems.Basedontheshownstandardsystems, itispossibletoconfigureadditionalsystems.Inthischapteryou findthemostfrequentlyusedsystems.Ifyoursystemisnotquite asshownbelow,findthediagramwhichhasthebestresemblance withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow aswellasthereturn.Placethepumpaccordingtothemanufacturer’s specification.
AQ055186460331en-010501
©Danfoss|2021.04|11
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.3Mounting

2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart (forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure thecontrollerwiththelockingpin.
12|©Danfoss|2021.04
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto besecurelylockedintothebase.Forthispurpose,pressthelocking pinintothebaseuntilaclickisheardandthecontrollernolonger canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk thatthecontrollerduringoperationcanunlockfromthebaseandthe basewithterminals(andalsothe230Va.c.connections)areexposed. Topreventinjuriestopersons,alwaysmakesurethatthecontroller issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller shouldnotbeoperated!
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe electricalconnectionsandpositionthecontrollerinthebasepart. Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical connectionsandpositionthecontrollerinthebasepart.Secure thecontrollerwiththelockingpin.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe lockingpinbymeansofascrewdriver.Thecontrollercannowbe removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea screwdriveraslever.
AQ055186460331en-010501
©Danfoss|2021.04|13
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth surface.Establishtheelectricalconnections.PlacetheECA30/ 31inthebasepart.
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure thatthesupplyvoltageisdisconnected.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode no.087H3236).Establishtheelectricalconnections.Securethe framewiththeclamp.PlacetheECA30inthebasepart.TheECA 30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity functionistobeused.
14|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted intotheECLComfort310/310Bbasepartforadditionalinputand outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32 isa10-pole(2x5)connector.Theconnectionisautomatically establishedwhentheECLComfort310/310Bisplacedonthe basepart.
AQ055186460331en-010501
©Danfoss|2021.04|15
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.4Placingthetemperaturesensors

2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe ECLComfort210/296/310serieswhichnotallwillbeneeded foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems withheatexchanger,DanfossrecommendsthattheESMU-typeto beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit measuresarepresentativereturntemperature.
Roomtemperaturesensor (ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe controlled.Donotplaceitonoutsidewallsorclosetoradiators, windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill, however,resultinaslowertemperaturemeasurement.
16|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
AQ055186460331en-010501
©Danfoss|2021.04|17
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.5Electricalconnections

2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage, relaycontactsandtriacoutputsdonothavemutualsafetydistanceof minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis 0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
18|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thecommongroundterminalisusedforconnectionofrelevant components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c. (4Aforohmicload,2Afor inductiveload)
Triac(=electronic
0,2A/230Va.c.
relay)terminals
Wirecrosssection:0.5-1.5mm² Incorrectconnectioncandamagetheelectronicoutputs. Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
AQ055186460331en-010501
©Danfoss|2021.04|19
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.2Electricalconnections24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
Triac(=electronic relay)terminals
4(2)A/24Va.c. (4Aforohmicload,2Afor inductiveload)
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230 Va.c.from24Va.c.
20|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.3Electricalconnections,safetythermostats,230Va.c.or24Va.c.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey) forapplicationspecificconnections.
Theconnectiondiagramsshowvarioussolutions/examples:
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithoutsafetyfunction
Safetythermostat,1–stepclosing: Motorizedcontrolvalvewithsafetyfunction
Safetythermostat,2–stepclosing: Motorizedcontrolvalvewithsafetyfunction
WhenSTisactivatedbyahightemperature,thesafetycircuitinthe motorizedcontrolvalveclosesthevalveimmediately.
WhenST1isactivatedbyahightemperature(theTRtemperature),the motorizedcontrolvalveisclosedgradually.Atahighertemperature (theSTtemperature),thesafetycircuitinthemotorizedcontrolvalve closesthevalveimmediately.
AQ055186460331en-010501
©Danfoss|2021.04|21
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.4Electricalconnections,Pt1000temperaturesensorsandsignals
SeetheInstallationGuide(deliveredwiththeapplicationkey)for sensorandinputconnections.
A217/A317:
Sensor
S1
Description
Outdoortemperature sensor*(optional)
S2
Supplytemperaturesensor (optional)
S3
DHWheating/charging temperaturesensor** (A217.1/A317.1)
DHWheatingtemperature sensor**(A217.2/A317.2)
DHWtemperaturesensor** (A217.3)
S4
DHWchargingtemperature sensor**(A217.2/A317.2 only)
S5Returntemperaturesensor
(optional)
S6
DHWtanktemperature sensor,upper***
S7
Flow/heatmeter(pulse signalandECL210only)
S8
DHWtanktemperature sensor,lower(A217.1/ A217.2/A317.1/A317.2).
Flowswitch(A217.3) ECL310only:
Notused ECL310only:
Notused
Recommendedtype
ESMT
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESM-11/ESMB/ ESMC/ESMU
ESMB/ ESMU
ESMB/ ESMU
*
Usedforfrostprotectionpurposes.Iftheoutdoor temperaturesensorisnotconnectedorthecableis short-circuited,thecontrollerassumesthattheoutdoor temperatureis0(zero)°C.
**
DHWcharging/heatingtemperaturesensormustalwaysbe connectedinordertohavethedesiredfunctionality.Ifthe sensorisnotconnectedorthecableisshort-circuited,the motorizedcontrolvalvecloses(safetyfunction).
***
Thissensorisusedifonlyonetanktemperaturesensoris required.
22|©Danfoss|2021.04
Wirecrosssectionforsensorconnections:Min.0.4mm². Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus). Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Connectionofvoltagesignal(0–10V)forexternalcontrolof desiredflowtemperature
Connectionofflowmeter
SeetheInstallationGuide(deliveredwiththeapplicationkey).
AQ055186460331en-010501
©Danfoss|2021.04|23
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.5Electricalconnections,ECA30/31
Terminal ECL
Terminal ECA30/31
30 31
4
1 322 333
4
5
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
Description
Twistedpair
Twistedpair
Ext.roomtemperature sensor*
Type (recomm.)
Cable2x twistedpair
ESM-10
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A progressbarintheECA30/31isdisplayed.
Iftheactualapplicationcontainstwoheatingcircuits,itispossible toconnectanECA30/31toeachcircuit.Theelectricalconnections aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller ortoECLComfort210/296/310controllersinamaster-slavesystem.
SetupproceduresforECA30/31:Seesection‘Miscellaneous’ .
ECAinformationmessage: ‘Applicationreq.newerECA’: Thesoftware(firmware)ofyourECAdoesnotcomplywiththe
software(firmware)ofyourECLComfortcontroller.Pleasecontact yourDanfosssalesoffice.
Totalcablelength:Max.200m(allsensorsincl.internalECL485 communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
24|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.6Electricalconnections,master/slavesystems
Thecontrollercanbeusedasmasterorslaveinmaster/slave systemsviatheinternalECL485communicationbus(2xtwisted paircable).
TheECL485communicationbusisnotcompatiblewiththeECL businECLComfort110,200,300and301!
Someapplicationsdonotcontainfunctionsrelatedtoactualroom temperature.TheconnectedECA30/31willonlyfunctionasremote control.
Terminal
Description
Type (recomm.)
30
Commonterminal +12V*,ECL485communicationbus
31
*OnlyforECA30/31andmaster/ slavecommunication
32
B,ECL485communicationbus
33
A,ECL485communicationbus
Cable2x twistedpair
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
2.5.7Electricalconnections,communication
Electricalconnections,Modbus
ECLComfort210:Non-galvanicisolatedModbusconnections ECLComfort296:GalvanicisolatedModbusconnections ECLComfort310:GalvanicisolatedModbusconnections
AQ055186460331en-010501
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
©Danfoss|2021.04|25
OperatingGuideECLComfort210/296/310,applicationA217/A317
2.5.8Electricalconnections,communication
Electricalconnections,M-bus
ECLComfort210:Notimplemented ECLComfort296:Onboard,non-galvanicisolated.Max.cable length50m. ECLComfort310:Onboard,non-galvanicisolated.Max.cable length50m.
26|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.6InsertingtheECLApplicationKey

2.6.1InsertingtheECLApplicationKey
TheECLApplicationKeycontains
theapplicationanditssubtypes,
currentlyavailablelanguages,
factorysettings:e.g.schedules,desiredtemperatures, limitationvaluesetc.Itisalwayspossibletorecoverthefactory settings,
memoryforusersettings:specialuser/systemsettings.
Afterhavingpowered-upthecontroller,differentsituationsmight beexisting:
1.Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
2.Thecontrolleralreadyrunsanapplication.TheECLApplication Keyisinserted,buttheapplicationneedstobechanged.
3.Acopyofthecontrollerssettingsisneededforconfiguring anothercontroller.
ECLComfort210/310
ECLComfort210/310
Usersettingsare,amongothers,desiredroomtemperature,desired DHWtemperature,schedules,heatcurve,limitationvaluesetc.
Systemsettingsare,amongothers,communicationset-up,display brightnessetc.
AQ055186460331en-010501
ECLComfort296
©Danfoss|2021.04|27
OperatingGuideECLComfort210/296/310,applicationA217/A317
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe softwareisbeingupdated:
Progressbar
Duringupdate:
•DonotremovetheKEY Ifthekeyisremovedbeforethehour-glassisshown,youhave tostartafresh.
•Donotdisconnectthepower Ifthepowerisinterruptedwhenthehour-glassisshown,the controllerwillnotwork.
•Manualupdateofcontrollersoftware(firmware): Seethesection"Automatic/manualupdateoffirmware"
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
28|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationKey:Situation1 Thecontrollerisnewfromthefactory,theECLApplicationKey
isnotinserted.
AnanimationfortheECLApplicationKeyinsertionisdisplayed. InserttheApplicationKey.
ApplicationKeynameandVersionisindicated(example:A266 Ver.1.03).
IftheECLApplicationKeyisnotsuitableforthecontroller,a"cross" isdisplayedovertheECLApplicationKey-symbol.
Action:Purpose:
Selectlanguage
Confirm Selectapplication(subtype)
Somekeyshaveonlyoneapplication.
Confirmwith‘Yes’
Set'Time&Date' Turnandpushthedialtoselectand change'Hours' ,'Minutes','Date', 'Month'and'Year' .
Choose''Next'
Confirmwith‘Yes’
Goto‘Aut.daylight’ Choosewhether‘ Aut.daylight´*
shouldbeactiveornot
*‘Aut.daylight’istheautomaticchangeoverbetweensummer andwintertime.
DependingonthecontentsoftheECLApplicationKey,procedure AorBistakingplace:
A TheECLApplicationkeycontainsfactorysettings:
Thecontrollerreads/transfersdatafromtheECLApplicationKey toECLcontroller.
Examples:
YESorNO
Theapplicationisinstalled,andthecontrollerresetsandstartsup.
B TheECLApplicationkeycontainschangedsystemsettings:
Pushthedialrepeatedly.
’NO’:
’YES*:
Ifthekeycontainsusersettings:
Pushthedialrepeatedly.
‘NO:
‘YES*:
*If‘YES’cannotbechosen,theECLApplicationKeydoesnot containanyspecialsettings.
Choose‘Startcopying’andconfirmwith'Yes'.
AQ055186460331en-010501
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialsystemsettings(differingfromthefactory settings)willbecopiedtothecontroller.
OnlyfactorysettingsfromtheECLApplicationKeywill becopiedtothecontroller.
Specialusersettings(differingfromthefactorysettings) willbecopiedtothecontroller.
©Danfoss|2021.04|29
OperatingGuideECLComfort210/296/310,applicationA217/A317
(Example):
The"i"intheupperrightcornerindicatesthat-besidesthefactory settings-thesubtypealsocontainsspecialuser/systemssettings.
ApplicationKey:Situation2 Thecontrolleralreadyrunsanapplication.TheECLApplication
Keyisinserted,buttheapplicationneedstobechanged.
TochangetoanotherapplicationontheECLApplicationKey,the currentapplicationinthecontrollermustbeerased(deleted).
BeawarethattheApplicationKeymustbeinserted.
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Choose‘Keyfunctions’
Confirm
Choose‘Eraseapplication’
Confirmwith‘Yes’
Thecontrollerresetsandisreadytobeconfigured.
Followtheproceduredescribedinsituation1.
Examples:
30|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
ApplicationKey:Situation3 Acopyofthecontrollerssettingsisneededforconfiguring
anothercontroller.
Thisfunctionisused
forsaving(backup)ofspecialuserandsystemsettings
whenanotherECLComfortcontrollerofthesametype(210, 296or310)mustbeconfiguredwiththesameapplicationbut user/systemsettingsdifferfromthefactorysettings.
HowtocopytoanotherECLComfortcontroller:
Action:Purpose:
Choose‘MENU’
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Keyfunctions’
Confirm
Choose‘Copy’
Confirm
Choose‘To’ . ‘ECL’or‘KEY’willbeindicated.Choose ’ECL’orKEY’
Pushthedialrepeatedlytochoose copydirection
Choose‘Systemsettings’or‘User settings’
Pushthedialrepeatedlytochoose ‘Yes’or‘No’in‘Copy’ .Pushtoconfirm.
Choose‘Startcopying’ TheApplicationKeyorthecontroller
isupdatedwithspecialsystemoruser settings.
Examples:
*
’ECL’or‘KEY’ .
**
‘NO’or‘YES’
* ‘ECL’:
‘KEY’:
** ‘NO’:
‘YES’:
AQ055186460331en-010501
DatawillbecopiedfromtheApplicationKeytothe ECLController. DatawillbecopiedfromtheECLControllertothe ApplicationKey.
ThesettingsfromtheECLcontrollerwillnotbecopied totheApplicationKeyortotheECLComfortcontroller. Specialsettings(differingfromthefactorysettings)will becopiedtotheApplicationKeyortotheECLComfort controller.IfYEScannotbechosen,therearenospecial settingstobecopied.
©Danfoss|2021.04|31
OperatingGuideECLComfort210/296/310,applicationA217/A317
Language
Atapplicationupload,alanguagemustbeselected.* IfanotherlanguagethanEnglishisselected,theselectedlanguage ANDEnglishwillbeuploadedintotheECLcontroller. ThismakesserviceeasyforEnglishspeakingservicepeople,just becausetheEnglishlanguagemenuscanbevisiblebychanging theactualsetlanguageintoEnglish. (Navigation:MENU>Commoncontroller>System>Language)
Iftheuploadedlanguageisnotsuitable,theapplicationmustbe erased.UserandSystemsettingscanbesavedontheapplication keybeforeerasing. Afternewuploadwithpreferredlanguage,theexistingUserand Systemsettingscanbeuploaded.
*) (ECLComfort310,24Volt)Iflanguagecannotbeselected,the powersupplyisnota.c.(alternatingcurrent).
2.6.2ECLApplicationKey,copyingdata
Generalprinciples
Whenthecontrollerisconnectedandoperating,youcancheck andadjustallorsomeofthebasicsettings.Thenewsettingscan bestoredontheKey.
Factorysettingscanalwaysberestored.
HowtoupdatetheECLApplicationKeyaftersettingshave beenchanged?
AllnewsettingscanbestoredontheECLApplicationKey.
Howtostorefactorysettinginthecontrollerfromthe ApplicationKey?
PleasereadtheparagraphconcerningApplicationKey,Situation 1:Thecontrollerisnewfromthefactory,theECLApplicationKey isnotinserted.
HowtostorepersonalsettingsfromthecontrollertotheKey?
PleasereadtheparagraphconcerningApplicationKey,Situation3: Acopyofthecontrollerssettingsisneededforconfiguringanother controller
Asamainrule,theECLApplicationKeyshouldalwaysremainin thecontroller.IftheKeyisremoved,itisnotpossibletochange settings.
Makeanoteofnewsettingsinthe'Settingsoverview'table.
DonotremovetheECLApplicationKeywhilecopying.Thedataon theECLApplicationKeycanbedamaged!
ItispossibletocopysettingsfromoneECLComfortcontrollerto anothercontrollerprovidedthatthetwocontrollersarefromthesame series(210or310). Furthermore,whentheECLComfortcontrollerhasbeenuploaded withanapplicationkey,minimumversion2.44,itispossibletoupload personalsettingsfromapplicationkeys,minimumversion2.14.
32|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
AQ055186460331en-010501
©Danfoss|2021.04|33
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.7Checklist

IstheECLComfortcontrollerreadyforuse?
Makesurethatthecorrectpowersupplyisconnectedtoterminals9and10(230Vor24V).
Makesurethecorrectphaseconditionsareconnected: 230V:Live=terminal9andNeutral=terminal10 24V:SP=terminal9andSN=terminal10
Checkthattherequiredcontrolledcomponents(actuator,pumpetc.)areconnectedtothecorrectterminals.
Checkthatallsensors/signalsareconnectedtothecorrectterminals(see'Electricalconnections').
Mountthecontrollerandswitchonthepower.
IstheECLApplicationKeyinserted(see'InsertingtheApplicationKey').
DoestheECLComfortcontrollercontainanexistingapplication(see'InsertingtheApplicationKey').
Isthecorrectlanguagechosen(see'Language'in'Commoncontrollersettings').
Isthetime&datesetcorrectly(see'Time&Date'in'Commoncontrollersettings').
Istherightapplicationchosen(see'Identifyingthesystemtype').
Checkthatallsettingsinthecontroller(see'Settingsoverview')aresetorthatthefactorysettingscomplywithyour requirements.
Choosemanualoperation(see'Manualcontrol').Checkthatvalvesopenandclose,andthatrequiredcontrolled components(pumpetc.)startandstopwhenoperatedmanually.
Checkthatthetemperatures/signalsshowninthedisplaymatchtheactualconnectedcomponents.
Havingcompletedthemanualoperationcheck,choosecontrollermode(scheduled,comfort,savingorfrostprotection).
34|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

2.8Navigation,ECLApplicationKeyA217/A317

Navigation,applicationA217.1/A317.1(*A217.1only,**A317.1only)
Home
IDno.
MENU ScheduleSelectable Schedulecirc.PSelectable Settings
HolidaySelectable Alarm
Influenceoverview
Tanktemperature
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
DigitalS9**
Alarmoverview Des.DHWT
11193Chargedifference 11195 11194 11152 11030 11035 11036 11037
11111 11112 11113 11109 11115 11114 11174
11185 11186 11187 11189 11055 11054 11041 11500 11076 11093 11141 11142
11147 11148 11149 11150 11636 11637
DHW,circuit1
Function
Startdifference Stopdifference Max.chargeT Limit Infl.-max. Infl.-min. Adapt.time
Limit Adapt.time Filterconstant Inputtype Units Pulse* Motorpr. Xpactual Tn Mrun Nz Min.act.time Circ.Ppriority Cont.Tcontrol DHWPpost-run SenddesiredT Circ.PfrostT Frostpr.T Ext.input Ext.mode
Upperdifference Lowerdifference Delay Lowesttemp. Alarmvalue Alarmtime-out
Returnlim. Flow/powerlim. Holiday Ext.override Anti-bacteria SCADAoverride
AQ055186460331en-010501
©Danfoss|2021.04|35
OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.1/A317.1,Commoncontrollersettings(*A317.1only)
Home MENU Time&Date Scheduleoutput*Selectable Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
SupplyTLogtoday DHWflow&des. DHWreturnT&lim.Log2days TankTup.&des.Log4days TankTup.&low.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet M-busconfig EnergyMeters Display
Communication
Language
IDno.
60058 60059
38 2048 2150 2151 2050
Commoncontrollersettings
Function
Selectable
SupplyT DHWflowT DHWreturnT TankupperT TanklowerT S9status*
Logyesterday
M1,P1,P3,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable Backlight Contrast Modbusaddr. ECL485addr. Servicepin Ext.reset Language
36|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.2/A317.2(*A217.2only,**A317.2only)
Home
IDno.
MENU ScheduleSelectable Schedulecirc.PSelectable Settings
HolidaySelectable Alarm
Influenceoverview
Tanktemperature
11193Chargedifference 11195 11194 11152 11068
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
DigitalS9**
Alarmoverview Des.DHWT
11030 11035 11036 11037
11111 11112 11113 11109 11115 11114 11174
11185 11186 11187 11189 11055 11054 11041 11042 11500 11076 11093 11141 11142
11147 11148 11149 11150 11136 11137
DHW,circuit1
Function
Startdifference Stopdifference Max.chargeT FlowTadapttime Limit Infl.-max. Infl.-min. Adapt.time
Limit Adapt.time Filterconstant Inputtype Units Pulse* Motorpr. Xpactual Tn Mrun Nz Min.act.time Circ.Ppriority Cont.Tcontrol DHWPpost-run Char.Ppost-run SenddesiredT Circ.PfrostT Frostpr.T Ext.input Ext.mode
Upperdifference Lowerdifference Delay Lowesttemp. Alarmvalue Alarmtime-out
Returnlim. Flow/powerlim. Holiday Ext.override Anti-bacteria SCADAoverride
AQ055186460331en-010501
©Danfoss|2021.04|37
OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.2/A317.2,Commoncontrollersettings(*A217.2only,**A317.2only)
Home MENU Time&Date Scheduleoutput**Selectable Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
SupplyTLogtoday DHWflow&des. ChargeTLog2days DHWreturnT&lim.Log4days TankTup.&des. TankTup.&low.
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension Ethernet M-busconfig EnergyMeters Display
Communication
Language
IDno.
60058 60059
38 2048 2150 2151 2050
Commoncontrollersettings
Function
Selectable
SupplyT DHWflowT ChargeT* DHWreturnT TankupperT TanklowerT S9status**
Logyesterday
M1,P1,P2,P3,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
Selectable Selectable Backlight Contrast Modbusaddr. ECL485addr. Servicepin Ext.reset Language
38|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.3
Home
IDno.
MENU ScheduleSelectable Schedulecirc.PSelectable Settings
HolidaySelectable Alarm
Influenceoverview
Flowtemperature
11178Temp.max. 11177
Returnlimit
Flow/powerlimitActual
Controlpar.
Application
Anti-bacteriaSelectable
Temp.monitor.
Alarmoverview Des.DHWT
11030 11035 11036 11037 11085
11111 11112 11113 11109 11115 11114 11173 11174
11185 11186 11187 11189 11097 11096 11094 11095 11500 11022 11023 11076 11040 11093 11141 11142
11147 11148 11149 11150 11150
DHW,circuit1
Function
Temp.min. Limit Infl.-max. Infl.-min. Adapt.time Priority
Limit Adapt.time Filterconstant Inputtype Units Pulse Autotuning Motorpr. Xpactual Tn Mrun Nz Min.act.time SupplyT(idle) Tn(idle) Opentime Closetime SenddesiredT Pexercise Mexercise Circ.PfrostT Ppost-run Frostpr.T Ext.input Ext.mode
Upperdifference Lowerdifference Delay Lowesttemp. Lowesttemp. 2:Temp.monitor. Returnlim. Flow/powerlim. Holiday Ext.override Anti-bacteria SCADAoffset
AQ055186460331en-010501
©Danfoss|2021.04|39
OperatingGuideECLComfort210/296/310,applicationA217/A317
Navigation,applicationA217.3,Commoncontrollersettings
Home MENU Time&Date Inputoverview
Log(sensors)
Outputoverride
Keyfunctions
SystemECLversion
Commoncontrollersettings
IDno.
OutdoorTLogtoday DHWflow&des. DHWreturnT&lim.Log2days SupplyTLog4days
NewapplicationEraseapplication Application FactorysettingSystemsettings
Copy
Keyoverview
Extension(ECL310only) Ethernet(ECL310only)Selectable Portalconfig(ECL310only)
M-busconfig(ECL310only) EnergyMeters(ECL310only)Selectable Rawinputoverview Alarm Display
Communication
Language
Function
Selectable OutdoorT DHWflowT DHWreturnT SupplyT Flowswitch
Logyesterday
M1,P1,A1
Usersettings Gotofactory To Systemsettings Usersettings Startcopying
Codeno. Hardware Software Buildno. Serialno. MAC Productionweek
ECLportal Portalstatus Portalinfo Selectable
Selectable 32:Temp.monitor.
60058
Backlight
60059
Contrast
2048
ECL485addr.
38
Modbusaddr.
39
Band
2150
Servicepin
2151
Ext.reset
2050
Language
40|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.0Dailyuse

3.1Howtonavigate

Younavigateinthecontrollerbyturningthedialleftorrightto thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay( youare.
Pushthedialtoconfirmyourchoices().
Thedisplayexamplesarefromatwo-circuitapplication:One heatingcircuit()andonedomestichot-water(DHW)circuit(). Theexamplesmightdifferfromyourapplication.
)willalwaysshowyouwhere
ExampleshowsECL210/310
Heatingcircuit():DHWcircuit();
Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
AQ055186460331en-010501
©Danfoss|2021.04|41
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.2Understandingthecontrollerdisplay

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Choosingafavoritedisplay
Yourfavoritedisplayisthedisplayyouhavechosenasthedefault display.Thefavoritedisplaywillgiveyouaquickoverviewofthe temperaturesorunitsthatyouwanttomonitoringeneral.
Ifthedialhasnotbeenactivatedfor20min.,thecontrollerwill reverttotheoverviewdisplayyouhavechosenasfavorite.
Toshiftbetweendisplays:Turnthedialuntilyoureachthedisplay selector( turntochooseyourfavoriteoverviewdisplay.Pushthedialagain.
)atthebottomrightsideofthedisplay.Pushthedialand
DHWcircuit
Overviewdisplay1informsabout: actualDHWtemperature,controllermode,desiredDHW temperatureaswellasthecomfortscheduleofthecurrentday.
Overviewdisplay2informsabout: stateofthecontrolledcomponents,actualDHWtemperature, (desiredDHWtemperature),controllermode,returntemperature (limitationvalue),influenceondesiredDHWtemperature.
Dependentonchosendisplay,theoverviewdisplaysfortheDHW circuitinformyouabout:
•actualDHWtemperature(50.3)
•controllermode(
)
•desiredDHWtemperature(50°C)
•comfortscheduleofthecurrentday(0-12-24)
•stateofthecontrolledcomponents(M1,P1)
•actualDHWtemperature(50°C),(desiredDHWtemperature(50))
•returntemperature(--°C)(limitationtemperature(30))
Settingthedesiredtemperature
Dependingonthechosencircuitandmode,itispossibletoenter alldailysettingsdirectlyfromtheoverviewdisplays(seealsothe nextpageconcerningsymbols).
Overviewdisplay1:Overviewdisplay2:
Exampleofoverviewdisplaywith Influenceindication:
42|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
SettingthedesiredDHWtemperature
ThedesiredDHWtemperaturecaneasilybeadjustedinthe overviewdisplaysfortheDHWcircuit.
Action:Purpose:
DesiredDHWtemperature
Confirm
AdjustthedesiredDHWtemperature
Confirm
InadditiontotheinformationaboutdesiredandactualDHW temperature,thetoday'sscheduleisvisible.
Thedisplayexampleindicatesthatthecontrollerisinscheduled operationandincomfortmode.
Examples:
50
55
OverviewofsettingrangeandsettingsforDHWmodes:
Factorysetting
Frostprotection*
Mode
Comfort
Saving
Settingrange
10...150°C50°C
10...150°C10°C
5...40°C10°C
*relatedtodesiredflowtemperature
AQ055186460331en-010501
©Danfoss|2021.04|43
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.3Ageneraloverview:Whatdothesymbolsmean?

Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
Symbol
Temperature
Mode
Description
Alarm
Letter
Event
Monitoringtemperaturesensor connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
Fixedcomfortday(holiday)
Activeinfluence
Heatingactive(+) Coolingactive(-)
Activeoutputoverride
Optimizedstartorstoptime
Heating
Cooling
DHW
Commoncontrollersettings
PumpON
PumpOFF
FanON
FanOFF
Actuatoropens
Actuatorcloses Actuator,analoguecontrol
signal Pump/fanspeed
DamperON
Circuit
Controlled component
Numberofheatexchangers
Additionalsymbols,ECA30/31:
Symbol
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin thecontrolleraredisplayed.
Description
ECARemoteControlUnit
Connectionaddress(master:15,slaves:1-9)
15
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
44|©Danfoss|2021.04
DamperOFF
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.4Monitoringtemperaturesandsystemcomponents

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
DHWcircuit
TheoverviewdisplayintheDHWcircuitensuresaquickoverview oftheactualand(desired)temperaturesaswellastheactualstate ofthesystemcomponents.
Displayexample(heatexchanger):
50°C
(50)
--
(30)
Inputoverview
Anotheroptiontogetaquickoverviewofmeasuredtemperatures isthe'Inputoverview'whichisvisibleinthecommoncontroller settings(howtoenterthecommoncontrollersettings,see ‘Introductiontocommoncontrollersettings’ .)
Asthisoverview(seedisplayexample)onlystatesthemeasured actualtemperatures,itisread-only.
Flowtemperature
Desiredflowtemperature
Returntemperature:sensornotconnected
Returntemperaturelimitation
Displayexamplewithheatexchanger:
AQ055186460331en-010501
©Danfoss|2021.04|45
OperatingGuideECLComfort210/296/310,applicationA217/A317
3.5Influenceoverview
ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Themenugivesanoverviewoftheinfluencesonthedesired flowtemperature.Itdiffersfromapplicationtoapplicationwhich parametersarelisted.Itcanbehelpfulinaservicesituationto explainunexpectedconditionsortemperaturesamongothers.
Ifthedesiredflowtemperatureisinfluenced(corrected)byoneor moreparameters,itisindicatedbyasmalllinewitharrow-down, arrow-upordouble-arrow:
Arrow-down: Theparameterinquestionreducesthedesiredflowtemperature.
Arrow-up: Theparameterinquestionincreasesthedesiredflowtemperature.
Double-arrow: Theparameterinquestioncreatesanoverride(e.g.Holiday).
Straightline: Noactiveinfluence.
Intheexample,thearrowinthesymbolpointsdownwardsfor 'Roomlim. ' .Thismeansthattheactualroomtemperatureis higherthanthedesiredroomtemperaturewhichagainresultsina decreaseofthedesiredflowtemperature.
ExampleofoverviewdisplaywithInfluenceindication:
46|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.6Manualcontrol

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Itispossibletomanuallycontroltheinstalledcomponents.
Manualcontrolcanonlybeselectedinfavoritedisplaysinwhich thesymbolsforthecontrolledcomponents(valve,pumpetc.)are visible.
Action:Purpose:
Choosemodeselector
Confirm
Choosemanualmode
Confirm
Choosepump
Confirm
SwitchONthepump
SwitchOFFthepump.
Confirmpumpmode
Choosemotorizedcontrolvalve
Confirm
Openthevalve
Stopopeningthevalve
Closethevalve
Examples:
ControlledcomponentsCircuitselector
Duringmanualoperation:
•Allcontrolfunctionsaredeactivated
•Outputoverrideisnotpossible
•Frostprotectionisnotactive
Stopclosingthevalve
Confirmvalvemode
Toleavemanualcontrol,usethemodeselectortoselectthe desiredmode.Pushthedial.
Manualcontrolistypicallyusedwhencommisioningthe installation.Thecontrolledcomponents,valve,pumpetc.,canbe controlledforcorrectfunction.
AQ055186460331en-010501
Whenmanualcontrolisselectedforonecircuit,itisautomatically selectedforallcircuits!
Manualcontrolof0–10voltcontrolledactuator:
Theactuatorsymbolhasavalue(in%)whichcanbechanged.The% valueiscorrespondingtoavoltageintherange0–10volt.
©Danfoss|2021.04|47
OperatingGuideECLComfort210/296/310,applicationA217/A317

3.7Schedule

3.7.1Setyourschedule
ThissectiondescribesthescheduleingeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.Insomeapplications,however,theremightbemore thanoneschedule.Additionalschedulescanbefoundin‘Common controllersettings’ .
Thescheduleconsistsofa7-dayweek:
=
M
Monday
=
T
Tuesday
=
W
Wednesday
=
T
Thursday
=
F
Friday
=
S
Saturday
=
S
Sunday
Theschedulewillday-by-dayshowyouthestartandstoptimesof yourcomfortperiods(heating/DHWcircuits).
Changingyourschedule:
Action:
Purpose: Choose'MENU'inanyoftheoverview
displays Confirm
Confirmthechoice'Schedule'
Choosethedaytochange
Confirm*
GotoStart1
Confirm
Adjustthetime
Confirm
GotoStop1,Start2etc.etc.
Returnto'MENU'
Confirm
Choose'Yes'or'No'in'Save'
Confirm
Examples:
*Severaldayscanbemarked
Thechosenstartandstoptimeswillbevalidforallthechosendays (inthisexampleThursdayandSaturday).
Youcansetmax.3comfortperiodsaday.Youcandeleteacomfort periodbysettingstartandstoptimestothesamevalue.
48|©Danfoss|2021.04
Eachcircuithasitsownschedule.Tochangetoanothercircuit,goto 'Home',turnthedialandchoosethedesiredcircuit.
Thestartandstoptimescanbesetinhalf-hourly(30min.)intervals.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

4.0Settingsoverview

Forfactorysettingsandsettingrange,seeappendix“ParameterIDoverview” . ParametersindicatedwithanIDno.like"1x607"meanauniversalparameter.xstandsforcircuit/parametergroup.
SettingIDPage
Actual(actualfloworpower)
Xpactual
Day
Starttime
Duration
DesiredT
Pexercise(pumpexercise)
Mexercise(valveexercise)
Limit(returntemp.limitation)
Infl.-max.(returntemp.limitation-max.influence)
Infl.-min.(returntemp.limitation-min.influence)
Adapt.time(adaptationtime)
Ppost-run
DHWPpost-run(DHWpump,post-run)
Char.Ppost-run(DHWchargingpump,post-run)
Cont.Tcontrol
Circ.Ppriority
FlowTadapttime(Flowtemperature,adaptationtime)
Circ.PfrostT
Priority(priorityforreturntemp.limitation)
Frostpr.T(frostprotectiontemp.)
Opentime
Closetime
Tn(idle)
SupplyT(idle)
Inputtype
Limit(limitationvalue)
Adapt.time(adaptationtime)
Filterconstant
Pulse
Units
Ext.input(externaloverride)
Ext.mode(externaloverridemode)
Upperdifference
Lowerdifference
Delay,example
Lowesttemp.
Max.chargeT(maximumheating/chargingtemperature)
Autotuning
1x022
1x023
1x03059
1x03559
1x03660
1x03761
1x040
1x041
1x04272
1x05472
1x05572
1x06852
1x07672
1x08561
1x09373
1x09466
1x09566
1x09667
1x09767
1x10962
1x111
1x11263
1x11363
1x114
1x115
1x141
1x142
1x147
1x14880
1x14981
1x15081
1x15252
1x17367
Factorysettingsincircuit(s)
1
63
68
78
78
79
79
71
71
71
71
63
64
64
73
74
80
AQ055186460331en-010501
©Danfoss|2021.04|49
OperatingGuideECLComfort210/296/310,applicationA217/A317
SettingIDPage
Motorpr.(motorprotection)
Temp.min.
Temp.max.
Tn(integrationtimeconstant)
Mrun(runningtimeofthemotorizedcontrolvalve)
Nz(neutralzone)
Min.act.time(min.activationtimegearmotor)
Chargedifference
Stopdifference
Startdifference
SenddesiredT
Alarmvalue
Alarmtime-out
1x174
1x177
1x17856
1x18569
1x18669
1x18769
1x18970
1x19352
1x19453
1x195
1x50076
1x63681
1x63782
Factorysettingsincircuit(s)
1
68
56
54
50|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.0Settings

5.1IntroductiontoSettings

Descriptionsofsettings(parameter'sfunctions)aredividedinto groupsasusedintheECLComfort210/296/310controller's menustructure.Examples:"Flowtemperature" ,"Roomlimit"and soon.Eachgroupstartswithageneralexplanation.
Thedescriptionsofeachparameterareinnumericorder,relatedto theparameter'sIDnumbers.Youmightcomeacrossdifferences betweentheorderinthisOperatingGuideandtheECLComfort 210/296/310controllers.
Someparameterdescriptionsarerelatedtospecificapplication subtypes.Thismeansthatyoumightnotseetherelatedparameter intheactualsubtypeintheECLcontroller.
Thenote"SeeAppendix… "referstotheAppendixattheendof thisOperatingGuide,whereparameter'ssettingrangesandfactory settingsarelisted.
Thenavigationhints(forexampleMENU>Settings>Returnlimit …)covermultiplesubtypes.
AQ055186460331en-010501
©Danfoss|2021.04|51
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.2Tanktemperature

ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Tanktemperature
FlowTadapttime(Flowtemperature,adaptationtime)
Settheadaptationtime(inseconds)forthedesiredtemperatureinthe primarycircuit,basedonthedesiredchargingtemperature. TheECLComfortcontrollergraduallyincreasesthedesiredflowtemperature intheprimarycircuitinordertomaintainthedesiredchargingtemperature.
1x068
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredflowtemperatureintheprimarycircuitis notadaptedtothedesiredchargingtemperature.
Low
Theadaptationisquick.
value: High
Theadaptationisslow.
value:
MENU>Settings>Tanktemperature
Max.chargeT(maximumheating/chargingtemperature)
Setthemax.heating/chargingtemperaturefortheDHW.
1x152
SeeAppendix“ParameterIDoverview”
Value:Setthetemperature.
Thedesiredheating/chargingtemperaturecannotbehigherthanthe settemperaturein'Max.chargeT’ .
NOTE: ThedesiredDHWtemperaturewillbereducedif"Max.chargeT"is
lowerthan(DesiredDHWtemp.+Chargedifference).
Example:
DesiredDHWtemp.=
Chargedifference=
Max.chargeT=
50°C
10K
55°C
52|©Danfoss|2021.04
Result: DesiredDHWtemp.willbereducedto45°C.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Chargedifference
SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill resultintheDHWheating(charging)temperature.
SeeAppendix“ParameterIDoverview”
Value:
NumberofdegreestobeaddedtothedesiredDHW temperaturetoobtaintheDHWheating(charging) temperature.
1x193
=
X
#1#
#2#
#3#
#4#
#5#
ThedesiredDHWtemperatureisrelatedtothetanktemperature sensor.
Iftwotanktemperaturesensorsareinstalled,therelationistothe uppertanktemperaturesensor.
Time
=
Chargingdifference(ID1x193)
=
DesiredDHWtemperature
=
Startdifference(ID1x195)
=
ActualDHWtemperature
=
DHWheating/chargingactivity
AQ055186460331en-010501
©Danfoss|2021.04|53
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Stopdifference
OneDHWtanktemperaturesensor: SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill stoptheDHWheating(charging).
TwoDHWtanktemperaturesensors: SetthenumberofdegreesaboveorbelowthedesiredDHWtemperature, butmeasuredbythelowertanktemperaturesensorthatwillstoptheDHW heating(charging).
SeeAppendix“ParameterIDoverview”
–50...50:
Setthenumberofdegrees.
OneDHWtanktemperaturesensor(examplewithpositive‘Stop difference’value):
1x194
Temp.
Stopdifference
DesiredDHWtemp.
Time
DHWheating
OneDHWtanktemperaturesensor(examplewithnegative‘Stop difference’value):
Temp.
Stopdifference
DesiredDHWtemp.
Time
DHWheating
TwoDHWtanktemperaturesensors,upperandlower
Temp.
UpperDHWtemp.sensor
Stopdifference
DesiredDHWtemp.
LowerDHWtemp.sensor
Time
DHWheating
54|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Tanktemperature
Startdifference
SetthenumberofdegreesbelowthedesiredDHWtemperaturethatwill starttheDHWheating(charging).
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofdegrees.
1x195
=
X
#1#
#2#
#3#
#4#
#5#
Example:
DesiredDHWtemp.:
Startdifference:
Result: TheDHWheatingstartswhenthetemperaturemeasuredbythetank
temperaturesensor(upper)islowerthan52°C.
Time
=
Chargingdifference(ID1x193)
=
DesiredDHWtemperature
=
Startdifference(ID1x195)
=
ActualDHWtemperature
=
DHWheating/chargingactivity
55°C
-3K
AQ055186460331en-010501
©Danfoss|2021.04|55
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.3Flowtemperature

TheECLComfort210/296/310controlstheDHWtemperature accordingtothedesiredflowtemperatureforexampleunderthe influenceofthereturntemperature. ThedesiredDHWtemperatureissetintheoverviewdisplay.
ActualDHWtemp.
50.3:
50:
ActualDHWtemperature
DesiredDHWtemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Flowtemperature
Temp.min.
1x177
SeeAppendix“ParameterIDoverview”
Setthemin.flowtemperatureforthesystem.Thedesiredflow temperaturewillnotbelowerthanthissetting.Adjustthefactory setting,ifrequired.
DesiredDHW temp.
‘Temp.min.’isoverruledif'Totalstop'isactiveinSavingmodeor 'Cut-out'isactive.
‘Temp.min.’canbeoverruledbytheinfluencefromthereturn temperaturelimitation(see'Priority').
MENU>Settings>Flowtemperature
Temp.max.
1x178
SeeAppendix“ParameterIDoverview”
Setthemax.flowtemperatureforthesystem.Thedesired temperaturewillnotbehigherthanthissetting.Adjustthefactory setting,ifrequired.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
Thesettingof‘heatcurve’ispossibleforheatingcircuitsonly.
Thesettingfor‘Temp.max. ’hashigherprioritythan‘Temp.min.’ .
56|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.4Returnlimit

Thereturntemperaturelimitationisbasedontheoutdoor temperature.Typicallyindistrictheatingsystemsahigherreturn temperatureisacceptedatadecreaseinoutdoortemperature.The relationshipbetweenthereturntemperaturelimitsandoutdoor temperatureissetintwocoordinates. Theoutdoortemperaturecoordinatesaresetin'HighToutX1' and'LowToutX2' .Thereturntemperaturecoordinatesaresetin 'HighlimitY2'and'LowlimitY1' . Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthecalculatedlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
X Y #X1# #X2# #Y1# #Y2#
=
Outdoortemperature
=
Limitationtemperature
=
HighTout(1x031)
=
LowTout(1x033)
=
Lowlimit(1x032)
=
Highlimit(1x034)
DHWcircuit
Thereturntemperaturelimitationisbasedonaconstant temperaturevalue. Thecontrollerautomaticallychangesthedesiredflowtemperature toobtainanacceptablereturntemperaturewhenthereturn temperaturefallsbeloworgetshigherthanthesetlimit. ThislimitationisbasedonaPIregulationwhereP('Infl.'factor) respondsquicklytodeviationsandI('Adapt.time')responds slowerandovertimeremovesthesmalloffsetsbetweenthe desiredandactualvalues.Thisisdonebychangingthedesired flowtemperature.
Thecalculatedlimitisshowninbrackets()inthemonitoringdisplay. Seethesection"Monitoringtemperaturesandsystemcomponents" .
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
AQ055186460331en-010501
©Danfoss|2021.04|57
OperatingGuideECLComfort210/296/310,applicationA217/A317
Example,maximumreturntemperaturelimitation; returntemperaturegetshigherthanlimit
=
T
Y
X
#1#
#2#
#3#
#4#
Temperature
=
Temperature
=
Time
=
Returntemperature
=
Returntemperaturelimit
=
Desiredflowtemperature
=
Actionpoint
58|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Example,minimumreturntemperaturelimitation; returntemperaturegetslowerthanlimit
=
T
Temperature
=
Y
Temperature
=
X
Time
=
#1#
Returntemperature
=
#2#
Returntemperaturelimit
=
#3#
Desiredflowtemperature
=
#4#
Actionpoint
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Returnlimit
Limit(returntemp.limitation)
Setthereturntemperaturevalueyouacceptforthesystem.
1x030
SeeAppendix“ParameterIDoverview”
Whenthereturntemperaturefallsbeloworgetshigherthanthe setvalue,thecontrollerautomaticallychangesthedesiredflow/ ducttemperaturetoobtainanacceptablereturntemperature.The influenceissetin'Infl.-max. 'and'Infl.-min.' .
AQ055186460331en-010501
©Danfoss|2021.04|59
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Returnlimit
Infl.-max.(returntemp.limitation-max.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureishigherthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetshigherthanthecalculatedlimit.
1x035
=
X #1#
#2#
#3#
#4#
#5#
Returntemperature
=
Limitationtemperature
Negativeinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp. Negativeinfluence(1x036)whenreturntemp.getslowerthan
=
limit.temp. Positiveinfluence(1x036)whenreturntemp.getslowerthanlimit.
=
temp. Positiveinfluence(1x035)whenreturntemp.getshigherthan
=
limit.temp.
Ifthe‘Infl. ’factoristoohighand/orthe‘Adapt.time’toolow,thereis ariskofunstablecontrol.
Example
Thereturnlimitisactiveabove50°C. Theinfluenceissetto-2.0. Theactualreturntemperatureis2degreestoohigh. Result: Thedesiredflowtemperatureischangedby-2.0x2=-4.0degrees.
Normally,thissettingislowerthan0indistrictheatingsystemsto avoidatoohighreturntemperature.
Typically,thissettingis0inboilersystemsbecauseahigherreturn temperatureisacceptable(seealso'Infl.-min. ').
60|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Returnlimit
Infl.-min.(returntemp.limitation-min.influence)
Determineshowmuchthedesiredflowtemperaturewillbeinfluencedifthe returntemperatureislowerthanthecalculatedlimit.
SeeAppendix“ParameterIDoverview”
Influencehigherthan0:
Thedesiredflowtemperatureisincreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
Influencelowerthan0:
Thedesiredflowtemperatureisdecreased,whenthereturn temperaturegetsbelowthecalculatedlimit.
MENU>Settings>Returnlimit
Adapt.time(adaptationtime)
Controlshowfastthereturntemperatureadaptstothedesiredreturn temperaturelimit(Integrationcontrol).
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
Example
1x036
1x037
Thereturnlimitisactivebelow50°C. Theinfluenceissetto-3.0. Theactualreturntemperatureis2degreestoolow. Result: Thedesiredflowtemperatureischangedby-3.0x2=-6.0degrees.
Normally,thissettingis0indistrictheatingsystemsbecausealower returntemperatureisacceptable.
Typically,thissettingishigherthan0inboilersystemstoavoidatoo lowreturntemperature(seealso'Infl.-max.').
Theadaptationfunctioncancorrectthedesiredflowtemperature withmax.8K.
MENU>Settings>Returnlimit
Priority(priorityforreturntemp.limitation)
Choosewhetherthereturntemperaturelimitationshouldoverruletheset min.flowtemperature‘Temp.min. ’.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Themin.flowtemperaturelimitisnotoverruled. Themin.flowtemperaturelimitisoverruled.
1x085
IfyouhaveaDHWapplication: Pleasealsosee‘Paralleloperation’(ID11043).
IfyouhaveaDHWapplication: Whendependentparalleloperationisinfunction:
•Desiredflowtemperaturefortheheatingcircuitwillbeminimum limited,when"Priorityforreturntemperature"(ID1x085)isset toOFF.
•Desiredflowtemperaturefortheheatingcircuitwillnotbe minimumlimited,when"Priorityforreturntemperature" (ID1x085)issettoON.
AQ055186460331en-010501
©Danfoss|2021.04|61
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.5Flow/powerlimit

Dependingoncontrollertype,theflow/powerlimitisbasedon differentinputtypes:
ECLKey
application
A2xx
A3xx
AfloworenergymetercanbeconnectedtotheECLcontrollerin ordertolimitthefloworconsumedpower.Thesignalfromthe floworenergymetercanbebasedonpulseorM-bussignal.
Whentheflow/powergetshigherthanthesetlimit,thecontroller graduallyreducesthedesiredDHWtemperaturetoobtainan acceptablemax.floworpowerconsumption.
DHWcircuit
Afloworenergymetercanbeconnected(M-bussignal)totheECL controllerinordertolimitthefloworconsumedpower. Whentheflow/powergetshigherthanthesetlimit,thecontroller graduallyreducesthedesiredflowtemperaturetoobtainan acceptablemax.floworpowerconsumption.
ECLComfort210
ECLComfort310
controller
PulsesignalPulsesignal
NotpossibleM-bussignal
controller
Flow/power limitation
Desiredflow temp.
Limit
Time
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
=
X
Y
#1#
#2#
#3#
Time
=
Floworpower
=
Floworpowerlimit
=
Actualfloworenergy
=
Desiredflowtemperature
62|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Flow/powerlimit
Inputtype
Choiceofinputtypefromflow/energymeter
SeeAppendix“ParameterIDoverview”
OFF:
IM1-
Noinput
Flow/energymetersignalbasedonpulses.
IM5: EM1-
Flow/energymetersignalfromM-bus.
EM5:
MENU>Settings>Flow/powerlimit
Actual(actualfloworpower)
Thevalueistheactualfloworpowerbasedonthesignalfromflow/energy meter.
MENU>Settings>Flow/powerlimit
Limit(limitationvalue)
Thisvalueisinsomeapplicationsacalculatedlimitationvalue,basedonthe actualoutdoortemperature. Inotherapplicationsthevalueisaselectablelimitationvalue.
1x109
ThesettingrangeforIMandEMdependsonchosensubtype.
1x111
SeeAppendix“ParameterIDoverview”
MENU>Settings>Flow/powerlimit
Adapt.time(adaptationtime)
Controlshowfasttheflow/powerlimitationadaptstothedesired limitation.
SeeAppendix“ParameterIDoverview”
OFF:
Thecontrolfunctionisnotinfluencedbythe‘Adapt. time’ .
Minor
Thedesiredtemperatureisadaptedquickly.
value: Major
Thedesiredtemperatureisadaptedslowly.
value:
1x112
Ifthe‘Adapt.time’istoolow,thereisariskofunstablecontrol.
AQ055186460331en-010501
©Danfoss|2021.04|63
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Flow/powerlimit
Filterconstant
Thevalueofthefilterconstantdeterminesthedampeningofthemeasured value. Thehigherthevalue,themoredampening. Bythis,atooquickchangeofthemeasuredvaluecanbeavoided.
SeeAppendix“ParameterIDoverview”
Minor
Lowerdampening
value: Major
Higherdampening
value:
MENU>Settings>Flow/powerlimit
Pulse
Setthevalueofthepulsesfromtheflow/energymeter.
SeeAppendix“ParameterIDoverview”
OFF:
1...9999:
Noinput.
Pulsevalue.
1x113
Example:
1x114
Onepulsecanrepresentanumberoflitres(fromaflowmeter) oranumberofkWh(fromaenergymeter).
MENU>Settings>Flow/powerlimit
Units
Choiceofunitsformeasuredvalues.
SeeAppendix“ParameterIDoverview”
Unitstotheleft:pulsevalue. Unitstotheright:actualandlimitationvalues.
Thevaluefromtheflowmeterisexpressedasmlorl. ThevaluefromtheenergymeterisexpressedasWh,kWh,MWh orGWh.
Thevaluesfortheactualflowandtheflowlimitationareexpressed asl/horm³/h.
Thevaluesfortheactualpowerandthepowerlimitationare expressedaskW,MWorGW.
1x115
Listforsettingrangeof'Units': ml,l/h l,l/h ml,m³/h l,m³/h Wh,kW kWh,kW kWh,MW MWh,MW MWh,GW GWh,GW
Example1:
'Units'(11115):
'Pulse'(11114):
l,m³/h 10
Eachpulserepresents10litresandtheflowisexpressedascubic meters(m³)perhour.
Example2:
'Units'(11115):
'Pulse'(11114):
kWh,kW(=kiloWatthour,kiloWatt) 1
Eachpulserepresents1kiloWatthourandthepoweris expressedinkiloWatt.
64|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.6Controlparameters

Controlofvalves
Themotorizedcontrolvalvesarecontrolledbymeansof3-point controlsignal.
Valvecontrol: Themotorizedcontrolvalveisopenedgraduallywhentheflow temperatureislowerthanthedesiredflowtemperatureandvice versa. Thewaterflowthroughthecontrolvalveismanagedbymeans ofanelectricactuator.Thecombination"actuator"and"control valve"isalsocalledmotorizedcontrolvalve.Theactuatorcanin thiswaygraduallyincreaseordecreasetheflowinordertochange thesuppliedenergy.Differenttypesofactuatorsareavailable.
3-pointcontrolledactuator: Theelectricactuatorcontainsareversiblegear-motor.Electric "open"and"close"signalscomefromtheelectronicoutputsofthe ECLComfortcontrollerinordertomanagethecontrolvalve.The signalsareintheECLComfortcontrollerexpressedas"Arrow-up" (open)and"Arrow-down"(close)anddisplayedatthevalvesymbol. Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,shortopen-signalscomefromtheECL Comfortcontrollerinordertograduallyincreasetheflow.Bythis, theflowtemperaturewillalignwiththedesiredtemperature. Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,shortclose-signalscomefromtheECLComfort controllerinordertograduallyreducetheflow.Again,theflow temperaturealignswiththedesiredtemperature. Neitheropen-signalsnorclose-signalswillcomeaslongastheflow temperaturecorrespondstothedesiredtemperature.
AQ055186460331en-010501
©Danfoss|2021.04|65
OperatingGuideECLComfort210/296/310,applicationA217/A317
Thermo-hydraulicactuator,ABV
Danfossthermo-actuatortypeABVisaslowactingvalveactuator. InsidetheABVanelectricheatcoilwillheatathermostaticelement whenanelectricsignalisapplied.Whenheatingthethermostatic elementitexpandsinordertomanagethecontrolvalve.
Twobasictypesareavailable:ABVNC(NormalClosed)andABVNO (normalopen).Forexample,ABVNCkeepsa2-portcontrolvalve closedwhennoopen-signalsareapplied.
Electricopen-signalscomefromtheelectronicoutputoftheECL Comfortcontrollerinordertomanagethecontrolvalve.When open-signalsareappliedtotheABVNC,thevalvegraduallyopens.
Open-signalsareintheECLComfortcontrollerexpressedas "Arrow-up"(open)anddisplayedatthevalvesymbol.
Whentheflowtemperature(forexampleatS3)islowerthanthe desiredflowtemperature,relativelylongopen-signalscomefrom theECLComfortcontrollerinordertoincreasetheflow.Bythis, theflowtemperaturewillovertimebealignedwiththedesired temperature.
Oppositely,whentheflowtemperatureishigherthanthedesired flowtemperature,relativelyshortopen-signalscomefromtheECL Comfortcontrollerinordertoreducetheflow.Again,theflow temperaturealigns,overtime,withthedesiredtemperature.
ThecontroloftheDanfossthermo-actuatortypeABVusesaunique designedalgorithmandisbasedonthePWMprinciple(Pulse WidthModulation),wherethedurationofthepulsedetermines themanagementofthecontrolvalve.Thepulsesarerepeated each10sec.
Aslongastheflowtemperaturecorrespondstothedesired temperature,thedurationoftheopen-signalswillremainconstant.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Controlparameters
Opentime
The‘Opentime’istheforcedtime(inseconds)thatittakestoopenthe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isdetected(the flowswitchisactivated).Thisfunctioncompensatesforthedelaybeforethe flowtemperaturesensormeasuresachangeintemperature.
1x094
SeeAppendix“ParameterIDoverview”
66|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Closetime
The‘Closetime’istheforcedtime(inseconds)thatittakestoclosethe motorizedcontrolvalvewhenaDHWdraw-off(tapping)isstopped(the flowswitchisdeactivated).Thisfunctioncompensatesforthedelaybefore theflowtemperaturesensormeasuresachangeintemperature.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
Tn(idle)
WhennoDHWdraw-off(tapping)isdetected(theflowswitchisdeactivated), thetemperatureismaintainedatalowlevel(savingtemperature).The integrationtime‘Tn(idle)’canbesettoobtainaslowbutstablecontrol.
SeeAppendix“ParameterIDoverview”
MENU>Settings>Controlparameters
SupplyT(idle)
The‘supplyT(idle)’isthesupplytemperaturewhenthereisnoDHW draw-off(tapping).WhenDHWdraw-offisnotdetected(theflowswitch isdeactivated),thetemperatureismaintainedatalowerlevel(saving temperature).Choosewhichtemperaturesensoristomaintainthesaving temperature.
1x095
1x096
1x097
Ifthesupplytemperaturesensorisnotconnected,theidlesupply temperaturewillbemaintainedattheDHWflowtemperaturesensor.
SeeAppendix“ParameterIDoverview”
OFF:
ThesavingtemperatureismaintainedattheDHWflow temperaturesensor.
ON:
Thesavingtemperatureismaintainedatthesupply temperaturesensor.
AQ055186460331en-010501
©Danfoss|2021.04|67
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Autotuning
AutomaticallydeterminesthecontrolparametersfortheDHWcontrol.'Xp' 'Tn'and'Mrun'donotneedtobeset,whenusingautotuning.'Nz'must beset.
1x173
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Autotuningisnotactivated. Autotuningisactivated.
Theautotuningfunctionautomaticallydeterminesthecontrol parametersforDHWcontrol.Thusyoudonotneedtosetthe'Xp', 'Tn'and'Mrun',astheyareautomaticallysetwhentheautotuning functionissettoON.
Autotuningistypicallyusedinconnectionwiththeinstallationof thecontroller,butitcanbeactivatedwhenneeded,e.g.foran extracheckofthecontrolparameters.
Beforestartingtheautotuning,thetappingflowshouldbe adjustedtotherelevantvalue(seetable).
Ifpossible,anyadditionalDHWconsumptionshouldbeavoided duringtheautotuningprocess.Shouldthetappingloadvarytoo much,theautotuningandcontrollerwillreturntothedefault settings.
No.of apartments
Heat transfer
ConstantDHWdraw-off(l/min)
(kW)
1-230-493 3-950-796 10-4980-14912
50-129150-24918
130-210250-35024
Inordertomeetthesummer-/wintervariations,theECLclockmust besettothecorrectdateforansuccessfulautotuning.
Themotorprotectionfunction('Motorpr.')hastobedeactivated duringautotuning.Duringautotuningthecirculationpumpfortap watermustbeswitchedoff.Thisisdoneautomaticallyifthepumpis controlledbytheECLcontroller.
Autotuningisonlyapplicableinconnectionwithvalvesthatare approvedforautotuning,i.e.theDanfosstypesVB2andVM2with splitcharacteristicaswellaslogarithmicvalvessuchasVFandVFS.
(or1tap25%open) (or1tap50%open) (or1tap100%open)
(or1tap100%+1tap50% open)
(or2taps100%open)
AutotuningisactivatedbysettingthefunctiontoON.Whenthe autotuningisended,thefunctionisautomaticallyconvertedto OFF(defaultsetting).Thiswillbeindicatedinthedisplay.
Theautotuningprocesstakesupto25minutes.
MENU>Settings>Controlparameters
Motorpr.(motorprotection)
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection increasesthelifetimeofallinvolvedcomponents.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Motorprotectionisnotactivated.
Motorprotectionisactivatedafterthesetactivation delayinminutes.
1x174
Recommendedforductsystemswithvariableload.
68|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Xpactual
CircuitSettingrange
1
‘Xpactual’istheread-outoftheactualXp(proportionalband)basedon thesupplytemperature.Xpisdeterminedbysettingsrelatedtothesupply temperature.Typically,thehigherthesupplytemperature,thehighertheXp mustbeinordertoachieveastabletemperaturecontrol.
Read-outonly
Factorysetting
Xpsettingrange:
5...250K
Fixedsupplytemperaturesettings:65°Cand90°C Factorysettings:
(65,40)and(90,120)
Thismeansthatthe‘Xp’is40Kat65°Csupplytemperature,and ‘Xp’is120Kat90°C.
SetthedesiredXpvaluesatthetwofixedsupplytemperatures.
Ifthesupplytemperatureisnotmeasured(thesupplytemperature sensorisnotconnected),theXpvalueatthesetting65°Cisused.
MENU>Settings>Controlparameters
Tn(integrationtimeconstant)
1x185
SeeAppendix“ParameterIDoverview”
Setahighintegrationtimeconstant(inseconds)toobtainaslow butstablereactiontodeviations.
Alowintegrationtimeconstantwillmakethecontrollerreactfast butwithlessstability.
MENU>Settings>Controlparameters
Mrun(runningtimeofthemotorizedcontrolvalve)
‘Mrun’isthetimeinsecondsittakesthecontrolledcomponenttomove fromfullyclosedtofullyopenposition.
SeeAppendix“ParameterIDoverview”
Setthe‘Mrun’accordingtotheexamplesormeasuretherunning timebymeansofastopwatch.
1x186
Howtocalculatetherunningtimeofamotorizedcontrolvalve
Therunningtimeofthemotorizedcontrolvalveiscalculatedusing thefollowingmethods:
Seatedvalves
Runningtime=
Example:
Rotatingvalves
Runningtime=
Example:90degr.x2sec./degr.=180sec.
Valvestroke(mm)xactuatorspeed(sec./mm)
5.0mmx15sec./mm=75sec.
Turningdegreesxactuatorspeed(sec./degr.)
AQ055186460331en-010501
©Danfoss|2021.04|69
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Controlparameters
Nz(neutralzone)
Whentheactualflowtemperatureiswithintheneutralzone,thecontroller doesnotactivatethemotorizedcontrolvalve.
SeeAppendix“ParameterIDoverview”
Settheacceptableflowtemperaturedeviation.
Settheneutralzonetoahighvalueifyoucanacceptahigh variationinflowtemperature.
MENU>Settings>Controlparameters
Min.act.time(min.activationtimegearmotor)
Themin.pulseperiodof20ms(milliseconds)foractivationofthegear motor.
SeeAppendix“ParameterIDoverview”
1x187
Theneutralzoneissymmetricalaroundthedesiredflowtemperature value,i.e.halfthevalueisaboveandhalfthevalueisbelowthis temperature.
SettingexampleValuex20ms
1x189
240ms 10200ms 501000ms
Thesettingshouldbekeptashighasacceptabletoincreasethe lifetimeoftheactuator(gearmotor).
IfyouwanttotunethePIregulationprecisely,youcanusethefollowingmethod:
Setthe‘Tn’(integrationtimeconstant)toitsmax.value(999sec.).
Decreasethevalueforthe‘Xp’(proportionalband)untilthesystemstartshunting(i.e.getsunstable)withaconstantamplitude(it mightbenecessarytoforcethesystembysettinganextremelowvalue).
Findthecriticaltimeperiodonthetemperaturerecorderoruseastopwatch.
Temp.
Criticaltimeperiod
Time
Thiscriticaltimeperiodwillbecharacteristicforthesystem,andyoucanevaluatethesettingsfromthiscriticalperiod. ‘Tn’=
0.85xcriticaltimeperiod
‘Xp’=
2.2xproportionalbandvalueinthecriticaltimeperiod
Iftheregulationseemstobetooslow,youcandecreasetheproportionalbandvalueby10%.Makesurethereisaconsumption whenyousettheparameters.
70|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.7Application

Thesection"Application"describesspecificapplicationrelated issues. Someoftheparameterdescriptionsareuniversalfordifferent applicationkeys.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Application
Pexercise(pumpexercise)
Exercisesthepumptoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thepumpexerciseisnotactive.
ThepumpisswitchedONfor1minuteeverythirddayat noon(12:14hours).
MENU>Settings>Application
Mexercise(valveexercise)
Exercisesthevalvetoavoidblockinginperiodswithoutheatdemand.
SeeAppendix“ParameterIDoverview”
OFF:
ON:
Thevalveexerciseisnotactive.
Thevalveopensfor7minutesandclosesfor7minutes everythirddayatnoon(12:00hours).
MENU>Settings>Application
1x022
1x023
Ppost-run
Heatingapplications:
ThecirculationpumpintheheatingcircuitcanbeONforanumberof minutes(m)afterheatingstop.Heatingstopiswhenthedesiredflow temperaturegetslowerthanthesettingin'PheatT'(IDno.1x078).
Coolingapplications:
ThecirculationpumpinthecoolingcircuitcanbeONforanumberof minutes(m)aftercoolingstop.Coolingstopiswhenthedesiredflow temperaturegetshigherthanthesettingin'PcoolT'(IDno.1x070). ThisPpost-runfunctioncanutilizetheremainingenergyinforexamplea heatexchanger.
SeeAppendix“ParameterIDoverview”
0:
Thecirculationpumpstopsimmediatelyafterheating orcoolingstop.
Value:
ThecirculationpumpisONforthesettimeafterheating orcoolingstop.
AQ055186460331en-010501
1x040
©Danfoss|2021.04|71
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
DHWPpost-run(DHWpump,post-run)
SettheDHWpumppost-runtime(minutes).TheDHWpumpcancontinue tobeswitchedONaftertheDHWheatingprocedureinordertoutilizethe remainingheatintheheatexchanger/boiler.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
Char.Ppost-run(DHWchargingpump,post-run)
SettheDHWchargingpumppost-runtime(minutes).TheDHWcharging pumpcancontinuetobeswitchedONaftertheDHWheatingprocedurein ordertoutilizetheremainingheatintheheatexchanger.
SeeAppendix“ParameterIDoverview”
Value:
Setthenumberofminutesforthepost-run.
MENU>Settings>Application
1x041
1x042
Cont.Tcontrol
ThedesiredDHWheating/chargingtemperaturecanbeloweredwhenthe DHWheating/chargingprocedurehaselapsed.
SeeAppendix“ParameterIDoverview”
OFF:
Thedesiredheating/chargingtemperatureislowered to10°C.Typically,theDHWiscirculatedthroughthe DHWtank.
ON:
Thedesiredheating/chargingtemperatureislowered tothedesiredDHWtemperature.Typically,theDHW iscirculatedthroughtheheatexchangerinorderto compensatefortheheatlossintheDHWcirculation pipe.
MENU>Settings>Application
Circ.Ppriority
ChoosewhethertheDHWcirculationpumpshouldbeONduringDHW heating.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisswitchedOFFduringDHW heating.
ON:
TheDHWcirculationpumpisnotswitchedOFFduring DHWheating.
1x054
1x055
Whenthe'Circ.Ppriority'issettoOFF ,theschedulefortheDHW circulationpumpisoverruled.
72|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
Circ.PfrostT
SettheoutdoortemperaturevalueatwhichtheDHWcirculationpumpisto beactivetoprotecttheDHWcircuitagainstfrost.
SeeAppendix“ParameterIDoverview”
OFF:
TheDHWcirculationpumpisnotactive.
Value:TheDHWcirculationpumpisactivewhentheoutdoor
temperatureislowerthanthesetvalue.
MENU>Settings>Application
Frostpr .T(frostprotectiontemp.)
SetthedesiredflowtemperatureattemperaturesensorS3toprotectthe systemagainstfrost(atheatingcut-out,totalstopetc.). WhenthetemperatureatS3getslowerthanthesetting,themotorized controlvalveopensgradually.
SeeAppendix“ParameterIDoverview”
1x076
1x093
Thefrostprotectiontemperaturecanalsobesetinyourfavorite displaywhenthemodeselectorisinfrostprotectionmode.
AQ055186460331en-010501
©Danfoss|2021.04|73
OperatingGuideECLComfort210/296/310,applicationA217/A317
Overridemodefunctions:
ThefollowingsettingsdescribethefunctioningeneralfortheECL Comfort210/296/310series.Theexplainedmodesaretypical andnotapplicationrelated.Theymightdifferfromtheoverride modesinyourapplication.
MENU>Settings>Application
Ext.input(externaloverride)
Choosetheinputfor'Ext.input'(externaloverride).Bymeansofaswitch thecontrollercanbeoverriddento‘Comfort’,'Saving' ,'Frostprotection'or 'Constanttemperature'mode.
1x141
SeeAppendix“ParameterIDoverview”
OFF:
S1...S16:
Noinputshavebeenselectedforexternaloverride. Inputselectedforexternaloverride.
IfS1...S6ischosenasoverrideinput,theoverrideswitchmusthave gold-platedcontacts. IfS7...S16ischosenasoverrideinput,theoverrideswitchcanbea standardcontact.
Seethedrawingsforconnectionexamplesofoverrideswitchand overriderelaytoinputS8.
S7...S16arerecommendedforoverrideswitch.
Example:Connectionofanoverrideswitch
Example:Connectionofanoverriderelay
IfECA32ismounted,alsoS11...S16canbeused.
IfECA35ismounted,alsoS11orS12canbeused.
Chooseonlyanunusedinputforoverride.Ifanalreadyusedinputis appliedforoverride,thefunctionalityofthisinputisalsoneglected.
Seealso‘Ext.mode’.
74|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
Ext.mode(externaloverridemode)
ThemodeoverridecanbeactivatedforSaving,Comfort,Frostpr.or ConstantTmode. Foroverride,thecontrollermodemustbeinscheduledmode.
SeeAppendix“ParameterIDoverview”
Chooseanoverridemode:
SAVING:
Thecircuitinquestionisinsavingmodewhenthe overrideswitchisclosed.
COMFORT:
Thecircuitinquestionisincomfortmodewhenthe overrideswitchisclosed.
FROSTPR.:
TheheatingorDHWcircuitcloses,butisstillfrost protected.
CONSTANTT:
Thecircuitinquestioncontrolsaconstant temperature*)
*)
Seealso'DesiredT'(1x004),settingofdesiredflow temperature(MENU>Settings>Flowtemperature) Seealso'Con.T,ret.Tlim. '(1x028),settingofreturn temperaturelimitation(MENU>Settings>Return limit)
Theprocessdiagramsshowthefunctionality.
1x142
Seealso‘Ext.input’.
Example:OverridetoComfortmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Comfort) #3#=Time
Example:OverridetoSavingmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Saving) #3#=Time
Theresultofoverrideto'Saving'modedependsonthesettingin 'Totalstop'.
Totalstop=OFF:Heatingreduced Totalstop=ON:Heatingstopped
AQ055186460331en-010501
©Danfoss|2021.04|75
OperatingGuideECLComfort210/296/310,applicationA217/A317
Example:OverridetoFrostprotectionmode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Frostpr.) #3#=Time
Example:OverridetoConstanttemperaturemode
#1#=Overrideswitch(notactivated/activated) #2#=Functionmode(Schedule/Const.T) #3#=Time
The"Const.T"valuecanbeinfluencedby:
•temp.max.
•temp.min.
•roomtemp.limit
•returntemp.limit
•flow/powerlimit
76|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Application
SenddesiredT
Whenthecontrolleractsasaslavecontrollerinamaster/slavesystem, informationaboutthedesiredflowtemperaturecanbesenttothemaster controllerviatheECL485bus. Stand-alonecontroller: Sub-circuitscansendthedesiredflowtemperaturetothemastercircuit.
SeeAppendix“ParameterIDoverview”
OFF:
Informationaboutthedesiredflowtemperatureisnot senttothemastercontroller.
ON:
Informationaboutthedesiredflowtemperatureissent tothemastercontroller.
1x500
Inthemastercontroller,'Demandoffset'mustbesettoavalueinorder toreactonadesiredflowtemperaturefromaslavecontroller.
Whenthecontrolleractsasaslave,itsaddressmustbe1,2,3...9in ordertosendthedesiredtemperaturetothemaster(seethesection ‘Miscellaneous’ ,‘Severalcontrollersinthesamesystem’).
AQ055186460331en-010501
©Danfoss|2021.04|77
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.8Anti-bacteria

OnselecteddaysduringtheweektheDHWtemperaturecan beincreasedinordertoneutralizebacteriaintheDHWsystem. ThedesiredDHWtemperature'DesiredT'(typically80°C)willbe presentfortheselectedday(s)andduration. Theanti-bacteriafunctionisnotactiveinfrostprotectionmode.
=
X Y #1# #2# #3# #4# #5#
Time
=
DesiredDHWtemperature
=
Duration
=
DesiredAnti-bacteriatemperaturevalue
=
DesiredAnti-bacteriatemperature
=
DesiredDHWtemperaturevalue
=
Starttime
MENU>Settings>Anti-bacteria
Day
Select(mark)theday(s)oftheweekwheretheanti-bacteriafunctionmust beactive.
=
Monday
M
=
Tuesday
T
=
Wednesday
W
=
Thursday
T
=
Friday
F
=
Saturday
S
=
Sunday
S
Duringtheanti-bacteriaprocess,thereturntemperaturelimitationis notactive.
78|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Anti-bacteria
Starttime
Setthestarttimefortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
Duration
Settheduration(minutes)fortheanti-bacteriafunction.
MENU>Settings>Anti-bacteria
DesiredT
SetthedesiredDHWtemperaturefortheanti-bacteriafunction.
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Theanti-bacteriafunctionisnotactive. DesiredDHWtemperatureduringtheanti-bacteria
functionperiod.
AQ055186460331en-010501
©Danfoss|2021.04|79
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.9Alarm

ManyapplicationsintheECLComfort210and310serieshavean alarmfunction.Thealarmfunctiontypicallyactivatesrelay4(ECL Comfort210)orrelay6(ECLComfort310).
Thealarmrelaycanactivatealamp,ahorn,aninputtoanalarm transmittingdeviceetc.
Therelayinquestionisactivatedaslongasthealarmcondition ispresent.
Typicalalarms:
Actualflowtemperaturediffersfromthedesiredflow temperature.
ParametersindicatedwithanIDno.like"1x607"meanauniversal parameter.
xstandsforcircuit/parametergroup.
5.9.1Temp.monitor.
MENU>Settings>Alarm
Upperdifference
Thealarmisactivatediftheactualflowtemperatureincreasesmorethan thesetdifference(acceptabletemperaturedifferenceabovethedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsabovetheacceptabledifference.
1x147
Upperdifference
=
X
=
Y
=
#1#
=
#2#
Time Temperature
Upperdifference Desiredflowtemperature
80|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Alarm
Lowerdifference
Thealarmisactivatediftheactualflowtemperaturedecreasesmorethan thesetdifference(acceptabletemperaturedifferencebelowthedesired flowtemperature).Seealso'Delay' .
SeeAppendix“ParameterIDoverview”
1x148
Lowerdifference
OFF:
Value:
Therelatedalarmfunctionisnotactive. Thealarmfunctionisactiveiftheactualtemperature
getsbelowtheacceptabledifference.
MENU>Settings>Alarm
Delay,example
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is presentforalongertimethanthesetdelay(inminutes),thealarmfunction isactivated.
SeeAppendix“ParameterIDoverview”
Value:
Thealarmfunctionwillbeactivatedifthealarm conditionremainsafterthesetdelay.
=
X Y #1# #2#
Delay,example
1x149
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
MENU>Settings>Alarm
Lowesttemp.
Thealarmfunctionwillnotbeactivatedifthedesiredflowtemperature islowerthanthesetvalue.
SeeAppendix“ParameterIDoverview”
=
X Y #1# #2# #3# #4#
1x150
Ifthecauseofthealarmdisappears,thealarmindicationandoutput alsodisappear.
Time
=
Temperature
=
Lowerdifference
=
Desiredflowtemperature
=
Actualflowtemperature
=
Delay(ID1x149)
AQ055186460331en-010501
©Danfoss|2021.04|81
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Settings>Alarm
Alarmvalue
AfirethermostatcanbeconnectedtotheS8input.Whenthetemperature, measuredbythefirethermostat,getsabovethesetvalue,theS8inputwill beactivated. Thefirealarmcanbeactivatedwhenthecontactsinthefirethermostat openorclose.
SeeAppendix“ParameterIDoverview”
0:
Thefirealarmisactivatedwhenthecontactsinthefire thermostatclose.
1:
Thefirealarmisactivatedwhenthecontactsinthefire thermostatopen.
MENU>Settings>Alarm
Alarmtime-out
Thealarmisactivatedwhenthealarmreasonhasbeenpresentforalonger time(inseconds)thanthesetvalue.
SeeAppendix“ParameterIDoverview”
Value:Setthealarmtime-out
1x636
Anactivefirealarmisindicatedbyainthedisplay.
S8inputstatus: MENU>Commoncontroller>System>Rawinputoverview>S8: 0=Inputactivated.1=inputnotactivated
Seealso'Alarmtime-out' ,parameter1x637.
1x637
82|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

5.10Alarmoverview

MENU>Alarm>Alarmoverview
Thismenushowsthealarmtypes,forexample:
"2:T emp.monitor"
"32:Tsensordefect"
Thealarmhasbeenactivatedifthealarmsymbol(abell)( presenttotherightofthealarmtype.
)is
Resettinganalarm,ingeneral:
MENU>Alarm>Alarmoverview: Lookforalarmsymbolinspecificline.
(Example:"2:Temp.monitor") Movecursortothelineinquestion. Pushdial.
Alarmoverview:
Alarmsourcesarelistedinthisoverviewmenu.
Someexamples: "2:Temp.monitor" "5:Pump1" "10:DigitalS12" "32:Tsensordefect"
Relatedtotheexamples,thenumbers2,5and10areusedinthealarm communicationtotheBMS/SCADAsystem.
Relatedtotheexamples,"Temp.monitor" ,"Pump1"and"DigitalS12" arethealarmpoints.
Relatedtotheexamples,"32:Tsensordefect"indicatesthemonitoring ofconnectedsensors.
Alarmnumbersandalarmpointsmightdifferdependingonactual application.
AQ055186460331en-010501
©Danfoss|2021.04|83
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.0Commoncontrollersettings

6.1Introductionto‘Commoncontrollersettings’

Somegeneralsettingswhichapplytotheentirecontrollerare locatedinaspecificpartofthecontroller.
Toenter‘Commoncontrollersettings’:
Action:Purpose:
Choose‘MENU’inanycircuit
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choose‘Commoncontrollersettings’
Confirm
Examples:
Circuitselector
84|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.2Time&Date

Itisonlynecessarytosetthecorrectdateandtimeinconnection withthefirstuseoftheECLComfortcontrollerorafterapower breakofmorethan72hours.
Thecontrollerhasa24hourclock.
Aut.daylight(Daylightsavingtimechangeover)
YES:
NO:
Thecontroller’sbuilt-inclockautomaticallychanges+/
-onehouronthestandardizeddaysfordaylightsaving timechangeoverforCentralEurope.
Youchangemanuallybetweensummerandwintertime bysettingtheclockbackwardorforward.
Howtosettimeanddate:
Action:
Purpose:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm
Choose'Commoncontrollersettings'
Confirm
Goto‘Time&Date’
Confirm Placethecursoratthepositiontobe
changed
Confirm
Enterthedesiredvalue
Confirm
Movethecursortothenextposition tobechanged.Continueuntil‘Time& Date’hasbeenset.
Finallymovethecursorto‘MENU’
Whencontrollersareconnectedasslavesinamaster/slavesystem
Examples:
(viaECL485communicationbus),theywillreceive‘Time&Date’from themaster.
Confirm
Movethecursorto‘HOME’
Confirm
AQ055186460331en-010501
©Danfoss|2021.04|85
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.3Holiday

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Thereisaholidayprogramforeachcircuitandaholidayprogram forthecommoncontroller.
Eachholidayprogramcontainsoneormoreschedules.Each schedulecanbesettoastartdateandanenddate.Thesetperiod startsonthestartdateat00.00andstopsontheenddateat00.00.
SelectablemodesareComfort,Saving,FrostprotectionorComfort 7-23(before7andafter23,themodeisscheduled).
Howtosetyourholidayschedule:
Action:
Purpose:
Examples:
Choose‘MENU’
Confirm Choosethecircuitselectoratthetop
rightcornerinthedisplay
Confirm Chooseacircuitor'Commoncontroller
settings' Heating
DHW Commoncontrollersettings
Confirm
Goto‘Holiday’
Confirm
Theholidayprograminthe‘Commoncontrollersettings’isvalidfor allcircuits.Theholidayprogramcanalsobesetindividuallyinthe heatingorDHWcircuits.
Theenddatemustbeatleastbeonedaylaterthanthestartdate.
Chooseaschedule
Confirm
Confirmchoiceofmodeselector
Choosemode
Comfort
·Comfort7–23
Saving
·Frostprotection
Confirm Enterthestarttimefirstandthenthe
endtime Confirm
Goto‘Menu’
Confirm Choose‘Yes’or‘No’in‘Save’ .Choose
thenextschedule,ifrequired
86|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
Holiday,specificcircuit/CommonController
Whensettingoneholidayprograminspecificcircuitandanother holidayprograminCommonController,aprioritywillbetaken intoaccount:
1.Comfort
2.Comfort7-23
3.Saving
4.Frostprotection
Holiday,deletingasetperiod:
ChoosetheScheduleinquestion
Changethemodeto"Clock"
Confirm
Example1:
Circuit1: Holidaysetto"Saving"
CommonController: Holidaysetto"Comfort"
Result: Aslongas"Comfort"isactiveinCommonController,circuit1willbein
"Comfort".
Example2:
Circuit1: Holidaysetto"Comfort"
CommonController: Holidaysetto"Saving"
Result: Aslongas"Comfort"isactiveincircuit1,itwillbein"Comfort".
Example3:
Circuit1: Holidaysetto"Frostprotection"
TheECA30/31cannotoverridetheholidayscheduleofthe controllertemporarily.
However,itispossibletomakeuseofthefollowingoptionsfrom theECA30/31whenthecontrollerisinscheduledmode:
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
CommonController: Holidaysetto"Saving"
Result: Aslongas"Saving"isactiveinCommonController,circuit1willbe
in"Saving".
Energy-savingtrick: Use'Goingout'(theextendedsavingperiod)forairingpurposes(e.g. forventilatingtheroomsbymeansoffreshairfromopenwindows).
ConnectionsandsetupproceduresforECA30/31: Seesection'Miscellaneous'.
Quickguide"ECA30/31tooverridemode":
1.GotoECAMENU
2.Movecursorto"Clock"symbol
3.Selectthe"Clock"symbol
4.Chooseandselectoneof4overridefunctions
5.Belowtheoverridesymbol:Sethoursordate
6.Belowhours/date:Setdesiredroomtemperaturefortheoverride period
AQ055186460331en-010501
©Danfoss|2021.04|87
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.4Inputoverview

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Theinputoverviewislocatedinthecommoncontrollersettings.
Thisoverviewwillalwaysshowyoutheactualtemperaturesinthe system(read-only).
"Outdooracc.T"means"Accummulatedoutdoortemperature"andis acalculatedvalueintheECLComfortcontroller.
88|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.5Log

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Thelogfunction(temperaturehistory)allowsyoutomonitorthe logsoftoday,yesterday,thepast2daysaswellasthepast4days fortheconnectedsensors.
Thereisalogdisplayfortherelevantsensor,showingthemeasured temperature.
Thelogfunctionisonlyavailableinthe'Commoncontroller settings'.
Example1:
1daylogforyesterdayshowingthedevelopmentinoutdoor temperatureduringthepast24hours.
Example2:
Today’slogfortheactualheatingflowtemperatureaswellasthe desiredtemperature.
Example3:
Yesterday’slogfortheDHWflowtemperatureaswellasthedesired temperature.
AQ055186460331en-010501
©Danfoss|2021.04|89
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.6Outputoverride

ThissectiondescribesthefunctioningeneralfortheECLComfort 210/296/310series.Theshowndisplaysaretypicalandnot applicationrelated.Theymightdifferfromthedisplaysinyour application.
Theoutputoverrideisusedtodisableoneormoreofthecontrolled components.Thiscouldamongothersbeusefulinaservice situation.
Action:Purpose:
Choose'MENU'inanyoftheoverview displays
Confirm
Choosethecircuitselectoratthetop rightcornerinthedisplay
Confirm
Choosecommoncontrollersettings
Confirm
Choose'Outputoverride'
Confirm
Chooseacontrolledcomponent
Confirm
Adjustthestatusofthecontrolled component: Motorizedcontrolvalve:AUTO,STOP , CLOSE,OPEN Pump:AUTO,OFF ,ON
Confirmstatuschange
Examples:
M1,P1etc.
ControlledcomponentsCircuitselector
"Manualcontrol"hashigherprioritythan"Outputoverride".
Whentheselectedcontrolledcomponent(output)isnot‘AUTO’ ,the ECLComfortcontrollerdoesnotcontrolthecomponentinquestion (pumpormotorizedcontrolvalvee.g.).Frostprotectionisnotactive.
Remembertochangethestatusbackagainassoonasanoverride isnotrequiredanylonger.
90|©Danfoss|2021.04
Whenoutputoverrideofacontrolledcomponentisactivethesymbol ‘!’isshowntotherightofthemodeindicatorintheenduserdisplays.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.7Keyfunctions

NewapplicationEraseapplication:
ApplicationGivesanoverviewovertheactual
FactorysettingSystemsettings:
Copy
Keyoverview
Removestheexistingapplication.As soonastheECLkeyisinserted,another applicationcanbechosen.
applicationintheECLcontroller.Push thedialagaintoexittheoverview.
Systemsettingsare,amongothers, communicationset-up,display brightnessetc.
Usersettings:
Usersettingsare,amongothers,desired roomtemperature,desiredDHW temperature,schedules,heatcurve, limitationvaluesetc.
Gotofactory:
Restoresthefactorysettings.
To:
Copydirection
Systemsettings
Usersettings
Startcopying
GivesanoverviewovertheinsertedECL key.(Example:A266Ver.2.30). Turnthedialtoseethesubtypes.Push thedialagaintoexittheoverview.
Amoredetaileddescriptionofhowtousetheindividual‘Key functions’canalsobeseenin‘InsertingtheECLapplicationkey’ .
AQ055186460331en-010501
©Danfoss|2021.04|91
OperatingGuideECLComfort210/296/310,applicationA217/A317
The“Keyoverview”doesnotinform—throughECA30/31—about thesubtypesoftheapplicationkey.
Keyinserted/notinserted,description:
ECLComfort210/310,controllerversionslowerthan1.36:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;for20minutes settingscanbechanged.
ECLComfort210/310,controllerversions1.36andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
ECLComfort296,controllerversions1.58andup:
-
Takeouttheapplicationkey;for20minutes settingscanbechanged.
-
Powerupthecontrollerwithoutthe applicationkeyinserted;settingscannotbe changed.
92|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317

6.8System

6.8.1ECLversion
In‘ECLversion’youwillalwaysbeabletofindanoverviewofthe datarelatedtoyourelectroniccontroller.
Pleasehavethisinformationavailableifyouneedtocontactyour Danfosssalesorganizationconcerningthecontroller.
InformationaboutyourECLApplicationKeycanbefoundin‘Key functions’and‘Keyoverview’ .
Codeno.:
Hardware:
Software:Software(firmware)versionof
Serialno.:
Productionweek:Weekno.andyear(WW.YYYY)
6.8.2Extension
ECLComfort310/310B: ‘Extension’willofferyouinformationaboutadditionalmodules,if any.AnexamplecouldbetheECA32module.
TheDanfosssalesandorderno. forthecontroller
Hardwareversionofthe controller
thecontroller Uniquenumberforthe
individualcontroller
Example,ECLversion
6.8.3Ethernet
ECLComfort296/310/310BhaveaModbus/TCPcommunication interfacethatallowstheECLcontrollertobeconnectedtoan Ethernetnetwork.ThisallowsremoteaccesstotheECL296/310/ 310Bcontrollerbasedonstandardcommunicationinfrastructures.
In‘Ethernet’itispossibletosetuptherequiredIPaddresses.
6.8.4Portalconfig
ECLComfort296/310/310BhaveaModbus/TCPcommunication interfacethatallowstheECLcontrollertobemonitoredand controlledviatheECLPortal.
ECLPortalrelatedparametersaresethere.
DocumentationforECLPortal:Seehttps://ecl.portal.danfoss.com
6.8.5M-busconfig
ECLComfort296/310/310BhaveanM-buscommunication interfacethatallowsenergymeterstobeconnectedasslaves.
M-busrelatedparametersaresethere.
AQ055186460331en-010501
©Danfoss|2021.04|93
OperatingGuideECLComfort210/296/310,applicationA217/A317
6.8.6EnergymeterandM-bus,generalinformation
ECLComfort296/310/310Bonly
WhenusingtheApplicationKeyintheECLComfort296/310 /310B,upto5energymeterscanbeconnectedtotheM-bus connections.
Connectionofenergymetercan:
limittheflow
limitthepower
transferenergymeterdatatotheECLPortal,viaEthernet,and/ oraSCADAsystem,viaModbus.
Manyapplicationswithcontrolofheating,DHWorcoolingcircuit havethepossibilitytoreactonenergymeterdata. Toverifyifactualapplicationkeycanbesettoreactonenergy meterdata: SeeCircuit>MENU>Settings>Flow/power.
TheECLComfort296/310/310Bcanalwaysbeusedfor monitoringpurposeofupto5energymeters.
TheECLComfort296/310/310BactasanM-busmasterandmust besettocommunicatewithconnectedenergymeter(s). SeeMENU>Commoncontroller>System>M-busconfig.
EnergymeterdataacquisitionfromECLPortalispossiblewithout settinguptheM-busconfiguration.
Technicalinfo:
TheM-busdataarebasedonstandardEN-1434.
DanfossrecommendsACsuppliedenergymetersinorderto avoidbatterydraining.
MENU>Commoncontroller>System>M-busconfig.
State
CircuitSettingrange
Read-out
Factorysetting
---
InformationaboutthecurrentM-busactivity.
IDLE:
INIT:
SCAN:
GATEW:
Normalstate
Thecommandforinitializationhasbeenactivated Thecommandforscanninghasbeenactivated ThecommandGatewayhasbeenactivated
MENU>Commoncontroller>System>M-busconfig.
TheECLComfort296/310/310BwillreturntoIDLEwhencommands havebeencompleted.
Gatewayisusedforread-outofenergymeterviaECLPortal.
Baud(bitspersecond)
CircuitSettingrange
-
300/600/1200/2400
ThecommunicationspeedbetweenECLComfort296/310/310B andtheconnectedenergymeter(s).
94|©Danfoss|2021.04
5997
Factorysetting
300
Typically,300or2400baudisused. IfECLComfort296/310/310BareconnectedtotheECLPortal,abaud
rateof2400isrecommendable,providedtheenergymeterallowsthis.
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Commoncontroller>System>M-busconfig.
Command
CircuitSettingrange
-
NONE/INIT/SCAN/GA TEWNONE
Factorysetting
TheECLComfort296/310/310BareM-busmasters.Inordertoverify connectedenergymeters,differentcommandscanbeactivated.
NONE:
INIT:
SCAN:
Nocommandactivated Initializationisactivated
Scanningisactivatedinordertosearchforconnected energymeters.TheECLComfort296/310/310B detecttheM-busaddressesofupto5connected energymetersandplacetheseautomaticallyinthe "Energymeters"section.Theverifiedaddressisplaced after"Energymeter1(2,3,4,5)"
GATEW:
TheECLComfort296/310/310Bactasagateway betweenenergymetersandECLPortal.Usedonlyfor service.
MENU>Commoncontroller>System>M-busconfig.
M-busaddress Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-255255
Factorysetting
Thesetorverifiedaddressofenergymeter1(2,3,4,5).
5998
Scantimecantakeupto12minutes. Whenallenergymetersarefound,thecommandcanbechanged
toINITorNONE.
6000
0:
1-250:
251-254:
Normallynotused ValidM-busaddresses
Specialfunctions.UseonlyM-busaddress254when oneenergymeterisconnected.
255:
Notused
MENU>Commoncontroller>System>M-busconfig.
Type Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-40
Factorysetting
SelectingdatarangefromtheM-bustelegram..
0:
1:
2:
3:
4:
Smalldataset,smallunits Smalldataset,largeunits Largedataset,smallunits Largedataset,largeunits Volumeandenergydataonly
(example:HydroPortPulse)
6001
Dataexamples:
0: Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy.
3: Flowtemp.,returntemp.,flow,power,acc.volume,acc.energy, tariff1,tariff2.
Seealsothe"Instructions,ECLComfort210/310,communication description"forfurtherdetails.
SeealsoAppendixfordetaileddescriptionof"Type".
AQ055186460331en-010501
©Danfoss|2021.04|95
OperatingGuideECLComfort210/296/310,applicationA217/A317
MENU>Commoncontroller>System>M-busconfig.
Scantime Energymeter1(2,3,4,5)
CircuitSettingrange
-
1-3600sec60sec
Factorysetting
Settingthescanningtimeforacquiringdataofconnectedenergy meter(s).
MENU>Commoncontroller>System>M-busconfig.
ID Energymeter1(2,3,4,5)
CircuitSettingrange
Factorysetting
---
Informationabouttheenergymeter'sserialno.
MENU>Commoncontroller>System>Energymeters
Energymeter1(2,3,4,5)
CircuitSettingrange
-
0-40
Factorysetting
Informationfromactualenergymeterabout,forexample,ID, temperatures,flow/volume,power/energy. Theshowninformationdependsonthesettingsmadeinthe“M-bus config. ”menu.
Read-out
Read-out
6002
Iftheenergymeterisbatterypowered,thescantimeshouldbesetto ahighvaluetopreventatoofastbatterydraining.
Oppositely,iftheflow/powerlimitationfunctionisusedintheECL Comfort310,thescantimeshouldbesettoalowvalueinorderto havequicklimitation.
6.8.7EnergyMeters
TheECLComfort296/310/310Ballowcommunicationwithup to5energymetersviaM-bus.In‘EnergyMeters’datacanberead thefromM-busconnectedenergymeters
96|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
6.8.8Rawinputoverview
Measuredtemperatures,inputstatusandvoltagesaredisplayed.
Inaddition,adetectionofmalfunctionscanbechosenforactivated temperatureinputs.
Monitoringthesensors: Choosethesensorwhichmeasuresatemperature,forexamplethe S5.Whenthedialispressed,amagnifyingglass selectedline.TheS5temperatureisnowbeingmonitored.
Alarmindication: Shouldtheconnectiontothetemperaturesensorbedisconnected, short-circuitedorthesensoritselfbedefective,thealarmfunction isactivated.
Inthe"Rawinputoverview"analarmsymbolisshownatthe defectivetemperaturesensorinquestion.
Resettingthealarm: Choosethesensor(Snumber)forwhichyouwanttoclearthe alarm.Pressthedial.Themagnifyingglass disappear.
Whenthedialispressedagain,themonitoringfunctionis reactivated.
appearsinthe
andalarmsymbols
Thetemperaturesensorinputshaveameasuringrangefrom-60... 150°C.
Ifatemperaturesensororitsconnectionbreaks,thevalueindication is"--".
Ifatemperaturesensororitsconnectionisshort-circuited,thevalue indicationis"---" .
6.8.9Sensoroffset(newfunctionalityasfromfirmware1.59)
Themeasuredtemperaturecanbeoffsetadjustedinorderto compensateforcableresistanceoranot-optimumplaceforthe temperaturesensor.Theadjustedtemperaturecanbeseenin"Raw inputoverview"and"Inputoverview".
Commoncontroller>System>Sensoroffset
Sensor1...(temperaturesensor)
CircuitSettingrange
Factorysetting
**
Settingtheoffsetofthemeasuredtemperature.
Positive
Thetemperaturevalueisincreased
offset value:
Negative
Thetemperaturevalueisdecreased
offset value:
6.8.10Display
Backlight(displaybrightness)
CircuitSettingrange
60058
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
10:
Weakbacklight. Strongbacklight.
AQ055186460331en-010501
©Danfoss|2021.04|97
OperatingGuideECLComfort210/296/310,applicationA217/A317
Contrast(displaycontrast)
CircuitSettingrange
0...103
Adjustthecontrastofthedisplay.
0:
10:
Lowcontrast.
Highcontrast.
6.8.11Communication
Modbusaddr .
CircuitSettingrange
1...247
SettheModbusaddressifthecontrollerispartofaModbus network.
1...247:
AssigntheModbusaddresswithinthestatedsetting range.
60059
Factorysetting
38
Factorysetting
1
ECL485addr.(master/slaveaddress)
CircuitSettingrange
Factorysetting
0...15
Thissetttingisrelevantifmorecontrollersareworkinginthesame ECLComfortsystem(connectedviatheECL485communication bus)and/orRemoteControlUnits(ECA30/31)areconnected.
0:
Thecontrollerworksasslave. Theslavereceivesinformationabouttheoutdoor temperature(S1),systemtime,andsignalforDHW demandinthemaster.
1...9:
Thecontrollerworksasslave. Theslavereceivesinformationabouttheoutdoor temperature(S1),systemtime,andsignalforDHW demandinthemaster.Theslavesendsinformation aboutthedesiredflowtemperaturetothemaster.
10...14:
15:
Reserved. TheECL485communicationbusisactive.
Thecontrollerismaster.Themastersendsinformation abouttheoutdoortemperature(S1)andsystemtime. ConnectedRemoteControlUnits(ECA30/31)are powered.
TheECLComfortcontrollerscanbeconnectedviatheECL485 communicationbustoperformalargersystem(theECL485 communicationbuscanconnecttomax.16devices).
2048
15
Thetotalcablelengthofmax.200m(alldevicesincl.theinternalECL 485communicationbus)shouldnotbeexceeded.
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
InasystemwithMASTER/SLAVEcontrollers,onlyoneMASTER controllerwithaddress15isallowed.
IfbymistakemoreMASTERcontrollersarepresentinanECL485 communicationbussystem,decidewhichcontrolleristobeMASTER. Changetheaddressintheremainingcontrollers.However,thesystem willoperatebutnotbestablewithmorethanoneMASTERcontroller.
IntheMASTERcontroller,theaddressin‘ECL485addr.(master/slave address)’ ,IDno.2048,mustalwaysbe15.
Eachslavemustbeconfiguredwithitsownaddress(1...9).
However,moreslavescanhavetheaddress0iftheyonlyhaveto receiveinformationaboutoutdoortemperatureandsystemtime (listeners).
98|©Danfoss|2021.04
AQ055186460331en-010501
OperatingGuideECLComfort210/296/310,applicationA217/A317
ServicePin
CircuitSettingrange
Factorysetting
0/1
Thissettingisonlyusedinconnectionwithset-upofModbus communication.
Notapplicableforthetimebeingandreservedforfuture use!
Ext.reset
CircuitSettingrange
Factorysetting
0/1
Thissettingisonlyusedinconnectionwithset-upofModbus communication.
0:
1:
Resetnotactivated. Reset.
6.8.12Language
2150
0
2151
0
Language
CircuitSettingrange
Chooseyourlanguage.
English/‘Local’English
2050
Factorysetting
Locallanguageisselectedduringinstallation.Ifyouwanttochangeto anotherlocallanguage,theapplicationmustbereinstalled.However, itisalwayspossibletochangebetweenthelocallanguageandEnglish.
AQ055186460331en-010501
©Danfoss|2021.04|99
OperatingGuideECLComfort210/296/310,applicationA217/A317

7.0Miscellaneous

7.1Severalcontrollersinthesamesystem

WhenECLComfortcontrollersareinterconnectedbymeansof theECL485communicationbus(cabletype:2xtwistedpair),the mastercontrollerwillbroadcastthefollowingsignalstotheslave controllers:
Outdoortemperature(measuredbyS1)
Timeanddate
DHWtankheating/chargingactivity
Furthermore,themastercontrollercanreceiveinformationabout:
thedesiredflowtemperature(demand)fromslavecontrollers
and(asfromECLcontrollerversion1.48)DHWtankheating/ chargingactivityinslavecontrollers
Situation1:
SLAVEcontrollers:Howtomakeuseoftheoutdoor temperaturesignalsentfromtheMASTERcontroller
Theslavecontrollersonlyreceiveinformationaboutoutdoor temperatureanddate/time.
SLAVEcontrollers: Changethefactorysetaddressfrom15toaddress0.
In
,gotoSystem>Communication>ECL485addr.
ECL485buscable
MaximumrecommendedlengthoftheECL485busiscalculatedlike this:
Subtract"TotallengthofallinputcablesofallECLcontrollersinthe master-slavesystem"from200m.
Simpleexamplefortotallengthofallinputcables,3xECL:
1xECL
3xECL
3xECLReturntemp.sensor:
3xECLRoomtemp.sensor:
Total:
Outdoortemp.sensor:
Flowtemp.sensor:
15m
18m
18m
30m
81m
ECL485addr.(master/slaveaddress)
CircuitSettingrange
2048
Choose
0...150
MaximumrecommendedlengthoftheECL485bus: 200-81m=119m
InasystemwithMASTER/SLAVEcontrollers,onlyoneMASTER controllerwithaddress15isallowed.
IfbymistakemoreMASTERcontrollersarepresentinanECL485 communicationbussystem,decidewhichcontrolleristobeMASTER. Changetheaddressintheremainingcontrollers.However,thesystem willoperatebutnotbestablewithmorethanoneMASTERcontroller.
IntheMASTERcontroller,theaddressin‘ECL485addr.(master/slave address)’ ,IDno.2048,mustalwaysbe15. Navigation:
•In
SLAVEcontrollersmustbesettoanotheraddressthan15: Navigation:
•In
,gotoSystem>Communication>ECL485addr.
,gotoSystem>Communication>ECL485addr.
100|©Danfoss|2021.04
'Demandoffset'withavalueistobeusedintheMastercontrolleronly.
AQ055186460331en-010501
Loading...