4.1 Multipoint serial bus infrastructure .......................................................................................................................................................................................3
6.0 Installation class and surge / lightning protection ....................................................................................................................................................................5
7.1 Central heating station ................................................................................................................................................................................................................7
7.2 Repeater stations (individual houses with repeater) .......................................................................................................................................................8
8.0 Annexure B ............................................................................................................................................................................................................................................ 10
8.1 Selection of parts ........................................................................................................................................................................................................................10
In smaller Modbus networks ligthning can be a challenge for the
connected devices like ECL Comfort 296 / ECL 310 controllers.
If not protected, Modbus interfaces are subject for being burned in
case of lightning.
This has resulted in the present service guide which includes
recommendations for new installations.
The document is prepared in compliance with www.modbus.org
This document is handling protection of the Modbus network.
Please be aware of the protection of the main site (230Vac) i.e. by
installing a Phoenix PLT-SEC-T3-230-FM.
3.0 Conclusion
1. Each nodes in the “Modbus network” (central heating station,
repeater station or individual house) are highly recommended
to have “surge protector”. It must be selected as per section 6
and installed as described in section 7.
2. A surge protection with a spark gab between Signal GND and
Protective Ground (PE) is required in the individual house installation.
3. Recommendation on Modbus reference common signal connection, shield connection, termination resistor connection may
be referred in section 5, 6, 7 and 8.
The ECL 296 / 310 Modbus physical layer interface is supported by
the half duplex RS485 interface (A, B, Signal Ground (S. Gnd.)).
1. Maximum trunk (ITr) length = 1200 meters for AWG24 (0,51mm
diameter) copper (less AWG= bigger diameter: is better).
Note: AWG= American wire gauge (AWG).
2. Maximum number of nodes in the network = 32 (including
master node, ECLs and repeater node).
Note: Each repeater node is capable of driving another 32
nodes (including repeater node) of 1200 meter.
I.e. 30 ECLs between two repeater stations (or) 31 ECLs in the
network connected to master node / repeater node. Refer the
figure below.
3. Maximum derivation cable length per node (per ECL) = 1,25
meters (calculated based on 40 m max. derivation cable length
for 32 nodes).
4. Line termination (to ensure the communication quality) = At
each extremity of the trunk cable (150 ohms (or) 120 ohms, 0,5
watts resistor at both ends.
Note: Repeaters are having internal termination resistors which
can be “switched on/ switched OFF” by the user.
a.
If “repeaters” are used in the extremity of the trunk cable, then
switch on the repeater termination (striped block, represented
by 3):
b.
If “repeaters” are used to make a branch from one of the intermediate nodes, then do not switch on the “repeater termination”
(unstriped block connected to ITr cable).
1) = surge protector
2) = repeater
3) = line termination (LT)
c.
If the ECL is used in the extremity node of the trunk cable, connect
an external line termination (150 ohm / 120 ohm, 0,5 watts resistor).
5. Grounding arrangements (to improve “general electrical safety”
and “communication quality”) - S. Gnd. must be connected directly to the protective ground (PE= Earth), at the master device
(ONE POINT ONLY).
6. Cables shield arrangements (to improve “general electrical
safety”) - One end of each cable’s shield must be connected to
protective ground (PE= Earth). Do not connect both ends of the
shield to PE as it forms an unwanted “group loop”.
6.0 Installation class and surge / lightning protection
“To secure the Modbus electronics (ECL 296 / 310, repeater…) from
surge / lightning in the network, “external protection devices” must
be selected based on the installation class of the network” and rightly
installed in “each site”.
Installation class 4 definitions:
Electrical environment where the interconnections are running as
outdoor cables along with power cables, and cables are used for
both electronic and electrical circuits.
“Surge protector requirements” for “installation class 4”, IEC 610004-5, (Modbus network with ECLs):
a)
Repeater ports are galvanic isolated. Based on the central heating
station architecture, more than one network (like left wing, right
wing) is possible. Single point earthing on S.Gnd and shield cable
to be maintained (Refer section 5 point 5, 6).
Attention: Dot on the intersection lines (S.Gnd, PE) means that
those two signals are electrically shorted.
Surge suppressor connection should match as in section 8.2.
7.2 Repeater stations (individual houses with repeater)
1) = surge protector 2) = repeater
Note:
a)
Normally repeaters’ ports are galvanic isolated. Check the resistance between input common reference signal (S.Gnd1) and
output common reference signal (S.Gnd2) using multimeter.
Only if signals are having >1 Mohm, then connect the output side
S. Gnd. to PE.
b)
Internal termination of repeaters can be switched ON if the connection matches with section 5 point 4.a
c)
Internal termination of repeaters is switched OFF if the connection matches with section 5 point 4.b
Input cable (coming from central heating station) shield MUST be
floating and output cable shield is connected to earth.
This is to maintain single point earthing in each network, on S.Gnd
and shield cable (Refer section 5 point 5, 6).
As there is no repeater used in this node, there is no galvanic isolated port created. S.Gnd is not connected to earth (PE).
Input cable (coming from central heating station) shield MUST be floating and output cable shield is connected to earth. Or the input and
output shield continuity is maintained and it is not connected to earth (As shown above).
This is to maintain single point earthing in each network, on common reference signal (S.Gnd) and shield cable (Refer section 5 point 5,
There are many prebuilt connection options available on the market
on “surge protector base parts”, which may lead to the unwanted
ground looping and hence low quality / loss of communication (section 5 point 5).
These parts look alike in part numbering system and in component
outlook. So care must be taken to select the right parts. Refer the
below for example:
Possibilities for grounding the base element:
• PT 1x2-BE - S.Gnd. (pin 9/10) is shorted to PE (protective earth)
(3/4)
• PT 1x2+F-BE - spark gap between signal ground (pin 9/10) to
PE (protective earth) (3/4)
PT 1x2-BE
PT 1X2 +F-BE
Attention:
S.Gnd. must be connected to earth ONLY ONE POINT (section 5 point 5).
So use “PT 1X2 +F-BE”
The correct wiring is equally important to get the best “surge protection in the network level.
The “gas discharge tubes” (between pin 7, 11 to 9 in the juxtaposed
example) is capable of handling higher surge current, but this device
is slow responding.
The “transils” (between pin 8 to 12 and 10) are capable of handling
low surge current, but very fast responding.
These two sets of components (gas discharge tubes and transils) are
separated by a resistor which forces the surge to be first suppressed
by the gas discharge tube and the residue will be suppressed by
the transils.
PT 3-PB-ST and PT 1X2+F-BE logical drawing:
3-wire, PROFIBUS (up to 12 MHz)
Total width 17.7 mm
Refer the juxtaposed drawing for example.
• Odd numbered connection of PT 1X2+F-BE meant for outer filed
cables (both IN and OUT cable wires of field cable)
• Even numbered connection of PT 1X2+F-BE meant for repeater/
ECLs wires (both IN and OUT cable wires of ECLs / repeaters)
The surge / lightning protected Modbus cables “must be separated from
mains / switched mains signal” even for a short run. Other signals in
ECL 296 / 310 (M Bus, sensor signals, RS485 signals), which are meant
for indoor wiring, “must be separated from mains / switched mains
signal” even for a short run. Modbus signals may be taken along with
MBus, sensor signal and other RS485 signals.
Recommended:
1) = surge protector
1. Even for a short distance well separated (≥ 7mm) from mains
signal.