Danfoss DTIE-10, DTIE-DTIE-17 Operating guide

Operating Guide
ECL Comfort 110, application 131
(valid as of software version 2.00)
English version
www.danfoss.com
How to navigate?
COMFORT<
Temp. 10.4@½
What do the symbols mean?
1000 Mode
The desired flow temperature is influenced by for example return temperature.
The actuator closes the control valve.
The actuator opens the control valve.
The actuator does not activate the valve.
The circulation pump is ON.
Adjust temperatures and values.
Switch between menu lines.
Select / return.
2 sec. Return to daily user menu.
The circulation pump is OFF.
The controller is in saving mode.
The controller is in comfort mode.
Safety Note
This symbol indicates that this particular piece of information should be read with special attention.
2 | © Danfoss | 2021.01 AQ197186466655en-010301
Table of contents
Operating guide for ECL 110 with appl. 131 (Cooling)
Application 131 controls the flow temperature in a cooling circuit.
Table of contents Line Page
Introduction 5
Settings overview 6
Daily use 8
Temperatures 8 Select control mode 9 Set your personal schedule 9
Maintenance 11
Date - time 1000 11 Flow temp. (flow temperature control) 2000 11
Comfort T (desired flow temperature in Comfort mode) 2018 11 Saving T (desired flow temperature in Saving mode) 2019 11 Temp. min. (minimum limitation of desired flow temp.) 2177 11 Temp. max. (maximum limitation of desired flow temp.) 2178 11
Room T limit (room temperature limitation) 3000 12
Comfort T (desired room temperature in Comfort mode) 3180 13 Saving T (desired room temperature in Saving mode) 3181 13 Gain - max. (room temp. limitation, maximum) 3182 13 Gain - min. (room temp. limitation, minimum) 3183 13 Intgr. time (Integration time) 3015 13
Compensation 1 and 2 4000 15
Temp. (Compensation temperature) 4060 16 Gain - max. (Compensation temp., limitation, maximum) 4062 16 Gain - min. (Compensation temp., limitation, minimum) 4063 16 Intgr. time (Integration time) 4061 16
Compensation 2 5000 17
Temp. (Compensation temperature) 5064 17 Gain - max. (Compensation temp., limitation, maximum) 5066 17 Gain - min. (Compensation temp., limitation, minimum) 5067 17 Intgr. time (Integration time) 5065 18
Return T limit (return temp. limitation) 6000 19
Limit (return temperature limitation value) 6030 20 Gain - max. (return temp. limitation, maximum) 6035 20 Gain - min. (return temp. limitation, minimum) 6036 20 Intgr. time (Integration time) 6037 20
AQ197186466655en-010301 © Danfoss | 2021.01 | 3
Table of contents
Line Page
Control param. (control parameters) 7000 22
Xp (proportional band) 7184 22 Tn (integration time constant) 7185 22 M1 run (running time of the motorized control valve) 7186 22 Nz (neutral zone) 7187 23 Min. on time (minimum activation time of valve actuator 7189 23
Application 8000 25
Total stop 8021 25 P1 exercise 8022 26 M1 exercise 8023 26 P1 start T (cooling demand) 8078 27 P1 post-run 8040 27 Standby T (standby temperature) 8093 27 Ext. (external override mode) 8141 27 S1 T filter (filtering of the S1 temperature) 8081 27 Daylight (daylight saving time changeover) 8198 28 ECL address (master / slave address) 8199 28 Type (application type) 8600 29
Service 9000 30
Code no. 9300 30 Ver. (version no.) 9301 30 Backlight (display brightness) 9310 30 Contrast (display contrast) 9311 30 Language 9315 31 MOD address (MODBUS address) 9320 31
Installation 32
Mounting the ECL Comfort controller 32 Electrical connections - 230 V a.c. - in general 33 Connecting the temperature sensors and the ECL BUS 34 External override 34 How to identify your system type 35 Adapting the ECL Comfort 110 controller 36 Manual control 38 Placing the temperature sensors 39
Checklist, electrical connections 40
Frequently asked questions in relation to cooling application 41
Definitions in relation to cooling application 42
4 | © Danfoss | 2021.01 AQ197186466655en-010301
Introduction
How to use this guide
The instructions is divided into six parts:
• Introduction
• Settings overview
• Daily use
• Maintenance
• Installation
• Check
Operation of the ECL Comfort is divided into two menu areas:
• Daily use (end user). Setting the desired flow temperature, mode and schedule
• Maintenance (installer’s level). Setting of, for example, control functions.
Access to Maintenance (installer’s level) on the ECL Comfort 110: Press and hold “Arrow-down” button for 3 sec.
Basic principles of application 131 for ECL Comfort 110
Typically, the flow temperature is always adjusted according to your requirements. The flow temperature sensor S3 is the most important sensor. The desired flow temperature at S3 is set in the ECL Comfort controller.
By means of the week schedule, the cooling circuit can be in ‘Comfort’ or ‘Saving’ mode (two values for the desired flow temperature).
The motorized control valve M1 is opened gradually when the flow temperature is higher than the desired flow temperature and vice versa.
The return temperature S4 to the cooling supply (district cooling or cooling machine) should not be too low. If so, the desired flow temperature can be adjusted (typically to a higher value), thus resulting in a gradual closing of the motorized control valve.
The circulation pump P1 is ON when the desired flow temperature is lower than 40 °C (a selectable value).
The Standby mode maintains a selectable flow temperature, for example 30 °C, provided the circulation pump is in operation.
If the measured room temperature does not equal the desired room temperature, the desired flow temperature can be adjusted. The week schedule also controls two values (‘Comfort T’ and ‘Saving T’) for the desired room temperature. If the measured room temperature does not equal the desired room temperature, the desired flow temperature can be adjusted.
The compensation temperature S1 can be arranged to influence the desired flow temperature. The higher the compensation temperature, the lower the desired flow temperature. An override input allows shift to constant Comfort or Saving mode.
°C (degrees Celsius) is an absolute temperature whereas K (Kelvin) is a relative temperature.
Settings overview
Setting: Line: Page: Factory setting: Your setting:
Date – time 1000 11
Flow temp. – Comfort T 2018 11 8.0 °C
Flow temp. – Saving T 2019 11 45.0 °C
Flow temp. – Temp. min. 2177 11 0 °C
Flow temp. – Temp. max. 2178 11 50 °C
Room T limit – Comfort T 3180 13 20 °C
Room T limit – Saving T 3181 13 40 °C
Room T limit – Gain – max. 3182 13 0.0
Room T limit – Gain – min. 3183 13 0.0
Room T limit – Intgr. time 3015 13 OFF
Compensation 1 – Temp. 4060 16 5 °C
Compensation 1 – Gain - max. 4062 16 0.0
Compensation 1 – Gain - min. 4063 16 0.0
Compensation 1 – Intgr. time 40 61 16 OFF
Compensation 2 – Temp. 5064 17 25 °C
Compensation 2 – Gain - max. 5066 17 0.0
Compensation 2 – Gain - min. 5067 17 0.0
Compensation 2 – Intgr. time 5065 18 OFF
Return T limit – Limit 6030 20 14 °C
Return T limit – Gain - max. 6035 20 0.0
Return T limit – Gain - min. 6036 20 0.0
Return T limit – Intgr. time 6037 20 OFF
Control param. – Xp 7184 22 80 K
Control param. – Tn 7185 22 30 s
Control param. – M1 run 7186 22 96 s
Control param. – Nz 7187 23 2 K
Control param. – Min. on time 7189 23 10
!
6 | © Danfoss | 2021.01 AQ197186466655en-010301
Settings overview
Setting: Line: Page: Factory setting: Your setting:
Application – Total stop 8021 25 ON
Application – P1 exercise 8022 26 ON
Application – M1 exercise 8023 26 OFF
Application – P1 start T 8078 27 40 °C
Application – P1 post-run 8040 27 3 m
Application – Standby T 8093 27 40 °C
Application – Ext. 8141 27 COMFORT
Application – S1 T filter 8081 27 100
Application – Daylight 819 8 28 ON
Application – ECL address 8199 28 15
Application – Type 8600 29 131
Service – Code no. 9300 30 087B1670
Service – Ver. 9301 30 D200010516
Service – Backlight 9310 30 16
Service – Contrast 9311 30 10
Service – Language 9315 31 ENGLISH
Service – MOD address 9320 31 5
!
Daily use
Temperatures
Push any button to switch on the backlight.
Temp. 10.4 < Mode COMFORT
Setting the desired flow temperature
Change the desired temperature.
Temperature overview
2 sec.
Push the button to see the sensor (S1-S4) temperatures.
Change between the temperature displays:
S1: Actual S1 temperature
S1 act. T 13@
S2: Actual room temperature Desired room temperature
S3: Actual flow temperature Desired flow temperature
S2 act. T 20@ S2 des. T 21@
S3 act. T 12@ S3 des. T 11@
S4: Actual return temperature Desired return temperature limitation
8 | © Danfoss | 2021.01 AQ197186466655en-010301
S4 act. T 16@ S4 lim. T 15@
Daily use
Push to exit ‘Temperature overview’.
If the temperature value is displayed as "- -" the sensor in question is not connected. "- - -" the sensor is short-circuited.
Select control mode
During scheduled operation (AUTO), the symbols will show you the control mode.
Mode COMFORT< Wednesday
Change the mode (AUTO, COMFORT, SAVING, or STANDBY).
Set your personal schedule
It is only possible to set the personal schedules if the ECL Comfort 110 controller has a built-in ECA 110 timer program.
Wednesday < 04-01-12 8:32
This display will show the current day and time.
Choose the day for which you wish to change the settings.
Daily use
Today’s schedule
The first display will show you the start of the first comfort period (‘Start1’). See or change the start of this period.
The first bar will blink.
Start1
09:00
Wed ]]]][!]]]!!]
See or change the end (‘Stop1’) of the first comfort period.
The next bar will blink.
Stop1 12:00 Wed ]]]][!{]]!!]
See or change the start (‘Start2’) of the next comfort period.
Start2 18:00 Wed ]]]][!{]]!!]
See or change the next start / stop periods, if necessary.
Stop2 22:00 Wed ]]]][!{]]!!]
The schedule has always two comfort periods a day. The start and stop times can be set in half-hourly intervals (30 min.).
To arrange only one comfort period on a day: Set Start2 and Stop2 times to the same time value.
10 | © Danfoss | 2021.01 AQ197186466655en-010301
Maintenance
2 sec.
Enter the maintenance menus.
Date - time 1000
It is only necessary to set the correct date and time in connection with the first use of the ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control) 2000
Comfort T (desired flow temperature in Comfort mode) 2018
Setting range -20.0 . . . 50.0 °C
Setting the desired flow temperature for Comfort mode. The same value is set in the End user menu as desired flow temperature when in Comfort mode.
Saving T (desired flow temperature in Saving mode) 2019
Setting range -20.0 . . . 50.0 °C
Setting the desired flow temperature for Saving mode. The same value is set in the End user menu as desired flow temperature when in Saving mode.
Temp. min. (minimum limitation of desired flow temp.) 2177
Setting range -20 ... 50 °C
Set the minimum flow temperature for your system. The desired flow temperature will not be lower than this setting. Adjust the factory set ting, if required.
Temp. max. (maximum limitation of desired flow temp.) 2178
Setting range -20 ... 50 °C
Set the maximum flow temperature for your system. The desired flow temperature will not be higher than this setting. Adjust the factory set ting, if required.
The setting for ‘Temp. min.’ has higher priority than ‘Temp. max.’.
Maintenance
Room T limit (room temperature limitation) 3000
This section is a general description for Room temperature limitation and is only relevant if you have installed a room temperature sensor (S2).
The ECL Comfort 110 adjusts the desired flow temperature to compensate for the difference between the desired and the actual room temperature.
If the room temperature is higher than the desired value, the desired flow temperature can be reduced. The ‘Gain-max.’ (Influence, max. room temp.) determines how much the desired flow temperature should be reduced. Use this influence type to avoid a too high room temperature.
If the room temperature is lower than the desired value, the desired flow temperature can be increased. The ‘Gain-min.´ (Influence, min. room temperature) determines how much the desired flow temperature should be increased. Use this influence type to avoid a too low room temperature.
A typical setting will be -4.0 for ‘Gain-max.’ and 4.0 for ‘Gain-min.´
X = Room temperature
# 1 # = Desired room temperature
# 2 # = Negative influence (3182) when actual room temp. gets higher than desired
room temp.
# 3 # = Positive influence (3183) when actual room temp. gets lower than desired
room temp.
12 | © Danfoss | 2021.01 AQ197186466655en-010301
Maintenance
Comfort T (desired room temperature in Comfort mode) 3180
Setting range 5 . . . 40 °C
Setting the desired room temperature for Comfor t mode.
Saving T (desired room temperature in Saving mode) 3181
Setting range 5 . . . 40 °C
Setting the desired room temperature for Saving mode.
Gain - max. (room temp. limitation, maximum) 3182
Setting range -9.0 . . . 0.0
Determines how much the desired flow temperature will be influenced (decreased) if the ac tual room
temperature gets higher than the desired room temperature (P control).
0.0: No influence
-2.0: Minor influence
-5.0: Medium influence
-9.9: Maximum influence
Gain - min. (room temp. limitation, minimum) 3183
Setting range 0.0 . . . 9.9
Determines how much the desired flow temperature will be influenced (increased) if the actual room
temperature gets lower than the desired room temperature (P control).
9.9: Maximum influence
5.0: Medium influence
2.0: Minor influence
0.0: No influence
Intgr. time (Integration time) 3015
Setting range OFF / 1 . . . 50 s
Controls how fast the actual room temperature adapts to the desired room temperature (I control). The “Intgr. time” function can correct the desired flow temperature with max. 8 degrees.
OFF: The control function is not influenced by the ‘Intgr. time’. Minor value: The desired room temperature is adapted quickly. Major value: The desired room temperature is adapted slowly.
Maintenance
Example 1
The actual room temperature is 2 degrees too low. The ‘Gain - max.’ is set to -3.5. The ‘Gain - min.’ is set to 2.0. Result: The desired flow temperature is changed by 2 x 2.0 = 4.0 degrees.
Example 2
The actual room temperature is 2 degrees too high. The ‘Gain - max.’ is set to -3.5. The ‘Gain - min.’ is set to 2.0. Result: The desired flow temperature is changed by 2 x (-3.5) = -7.0 degrees.
14 | © Danfoss | 2021.01 AQ197186466655en-010301
Loading...
+ 30 hidden pages