The desired flow temperature is influenced by for example return temperature.
The actuator closes the control valve.
The actuator opens the control valve.
The actuator does not activate the valve.
The circulation pump is ON.
Adjust temperatures and values.
Switch between menu lines.
Select / return.
2 sec.
Return to daily user menu.
The circulation pump is OFF.
The controller is in saving mode.
The controller is in comfort mode.
Safety Note
To avoid injury of persons and damages to the device, it is absolutely necessary to read and
observe these instructions carefully. The warning sign is used to emphasize special conditions
that should be taken into consideration.
This symbol indicates that this particular piece of information should be read with
special attention.
Operating guide for ECL 110 with appl. 131 (Cooling)
Application 131 controls the flow temperature in a cooling circuit.
Table of contents Line Page
Introduction 5
Settings overview 6
Daily use 8
Temperatures 8
Select control mode 9
Set your personal schedule 9
Maintenance 11
Date - time 1000 11
Flow temp. (flow temperature control) 2000 11
Comfort T (desired flow temperature in Comfort mode) 2018 11
Saving T (desired flow temperature in Saving mode) 2019 11
Temp. min. (minimum limitation of desired flow temp.) 2177 11
Temp. max. (maximum limitation of desired flow temp.) 2178 11
Room T limit (room temperature limitation) 3000 12
Comfort T (desired room temperature in Comfort mode) 3180 13
Saving T (desired room temperature in Saving mode) 3181 13
Gain - max. (room temp. limitation, maximum) 3182 13
Gain - min. (room temp. limitation, minimum) 3183 13
Intgr. time (Integration time) 3015 13
Compensation 1 and 2 4000 15
Temp. (Compensation temperature) 4060 16
Gain - max. (Compensation temp., limitation, maximum) 4062 16
Gain - min. (Compensation temp., limitation, minimum) 4063 16
Intgr. time (Integration time) 4061 16
Compensation 2 5000 17
Temp. (Compensation temperature) 5064 17
Gain - max. (Compensation temp., limitation, maximum) 5066 17
Gain - min. (Compensation temp., limitation, minimum) 5067 17
Intgr. time (Integration time) 5065 18
Return T limit (return temp. limitation) 6000 19
Limit (return temperature limitation value) 6030 20
Gain - max. (return temp. limitation, maximum) 6035 20
Gain - min. (return temp. limitation, minimum) 6036 20
Intgr. time (Integration time) 6037 20
Xp (proportional band) 7184 22
Tn (integration time constant) 7185 22
M1 run (running time of the motorized control valve) 7186 22
Nz (neutral zone) 7187 23
Min. on time (minimum activation time of valve actuator 7189 23
Application 8000 25
Total stop 8021 25
P1 exercise 8022 26
M1 exercise 8023 26
P1 start T (cooling demand) 8078 27
P1 post-run 8040 27
Standby T (standby temperature) 8093 27
Ext. (external override mode) 8141 27
S1 T filter (filtering of the S1 temperature) 8081 27
Daylight (daylight saving time changeover) 8198 28
ECL address (master / slave address) 8199 28
Type (application type) 8600 29
Mounting the ECL Comfort controller 32
Electrical connections - 230 V a.c. - in general 33
Connecting the temperature sensors and the ECL BUS 34
External override 34
How to identify your system type 35
Adapting the ECL Comfort 110 controller 36
Manual control 38
Placing the temperature sensors 39
Checklist, electrical connections 40
Frequently asked questions in relation to cooling application 41
Operation of the ECL Comfort is divided into two menu areas:
• Daily use (end user). Setting the desired flow temperature, mode and schedule
• Maintenance (installer’s level). Setting of, for example, control functions.
Access to Maintenance (installer’s level) on the ECL Comfort 110:
Press and hold “Arrow-down” button for 3 sec.
Basic principles of application 131 for ECL Comfort 110
Typically, the flow temperature is always adjusted according to your requirements.
The flow temperature sensor S3 is the most important sensor. The desired flow
temperature at S3 is set in the ECL Comfort controller.
By means of the week schedule, the cooling circuit can be in ‘Comfort’ or ‘Saving’ mode
(two values for the desired flow temperature).
The motorized control valve M1 is opened gradually when the flow temperature is
higher than the desired flow temperature and vice versa.
The return temperature S4 to the cooling supply (district cooling or cooling machine)
should not be too low. If so, the desired flow temperature can be adjusted (typically to a
higher value), thus resulting in a gradual closing of the motorized control valve.
The circulation pump P1 is ON when the desired flow temperature is lower than 40 °C (a
selectable value).
The Standby mode maintains a selectable flow temperature, for example 30 °C,
provided the circulation pump is in operation.
If the measured room temperature does not equal the desired room temperature, the
desired flow temperature can be adjusted.
The week schedule also controls two values (‘Comfort T’ and ‘Saving T’) for the desired
room temperature. If the measured room temperature does not equal the desired room
temperature, the desired flow temperature can be adjusted.
The compensation temperature S1 can be arranged to influence the desired flow
temperature. The higher the compensation temperature, the lower the desired flow
temperature.
An override input allows shift to constant Comfort or Saving mode.
°C (degrees Celsius) is an absolute temperature whereas K (Kelvin) is a relative temperature.
It is only necessary to set the correct date and time in connection with the first use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control) 2000
Comfort T (desired flow temperature in Comfort mode) 2018
Setting range-20.0 . . . 50.0 °C
Setting the desired flow temperature for Comfort mode.
The same value is set in the End user menu as desired flow temperature when in Comfort mode.
Saving T (desired flow temperature in Saving mode) 2019
Setting range-20.0 . . . 50.0 °C
Setting the desired flow temperature for Saving mode.
The same value is set in the End user menu as desired flow temperature when in Saving mode.
Temp. min. (minimum limitation of desired flow temp.) 2177
Setting range-20 ... 50 °C
Set the minimum flow temperature for your system. The desired flow temperature will not be lower
than this setting. Adjust the factory set ting, if required.
Temp. max. (maximum limitation of desired flow temp.) 2178
Setting range-20 ... 50 °C
Set the maximum flow temperature for your system. The desired flow temperature will not be higher
than this setting. Adjust the factory set ting, if required.
The setting for ‘Temp. min.’ has higher priority than ‘Temp. max.’.
Maintenance
Room T limit (room temperature limitation) 3000
This section is a general description for Room temperature limitation and is only relevant if
you have installed a room temperature sensor (S2).
The ECL Comfort 110 adjusts the desired flow temperature to compensate for the difference
between the desired and the actual room temperature.
If the room temperature is higher than the desired value, the desired flow temperature can
be reduced.
The ‘Gain-max.’ (Influence, max. room temp.) determines how much the desired flow
temperature should be reduced.
Use this influence type to avoid a too high room temperature.
If the room temperature is lower than the desired value, the desired flow temperature can
be increased.
The ‘Gain-min.´ (Influence, min. room temperature) determines how much the desired flow
temperature should be increased.
Use this influence type to avoid a too low room temperature.
A typical setting will be -4.0 for ‘Gain-max.’ and 4.0 for ‘Gain-min.´
X=Room temperature
# 1 #= Desired room temperature
# 2 #= Negative influence (3182) when actual room temp. gets higher than desired
room temp.
# 3 #= Positive influence (3183) when actual room temp. gets lower than desired
Comfort T (desired room temperature in Comfort mode) 3180
Setting range5 . . . 40 °C
Setting the desired room temperature for Comfor t mode.
Saving T (desired room temperature in Saving mode) 3181
Setting range5 . . . 40 °C
Setting the desired room temperature for Saving mode.
Gain - max. (room temp. limitation, maximum) 3182
Setting range-9.0 . . . 0.0
Determines how much the desired flow temperature will be influenced (decreased) if the ac tual room
temperature gets higher than the desired room temperature (P control).
0.0: No influence
-2.0: Minor influence
-5.0: Medium influence
-9.9: Maximum influence
Gain - min. (room temp. limitation, minimum) 3183
Setting range0.0 . . . 9.9
Determines how much the desired flow temperature will be influenced (increased) if the actual room
temperature gets lower than the desired room temperature (P control).
9.9: Maximum influence
5.0: Medium influence
2.0: Minor influence
0.0: No influence
Intgr. time (Integration time) 3015
Setting rangeOFF / 1 . . . 50 s
Controls how fast the actual room temperature adapts to the desired room temperature (I control).
The “Intgr. time” function can correct the desired flow temperature with max. 8 degrees.
OFF: The control function is not influenced by the ‘Intgr. time’.
Minor value: The desired room temperature is adapted quickly.
Major value: The desired room temperature is adapted slowly.
Maintenance
Example 1
The actual room temperature is 2 degrees too low.
The ‘Gain - max.’ is set to -3.5.
The ‘Gain - min.’ is set to 2.0.
Result:
The desired flow temperature is changed by 2 x 2.0 = 4.0 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The ‘Gain - max.’ is set to -3.5.
The ‘Gain - min.’ is set to 2.0.
Result:
The desired flow temperature is changed by 2 x (-3.5) = -7.0 degrees.