Danfoss DSP MINI light Data sheet

Data Sheet
DSP MINI light
a Danfoss Platform for Flensburg Secondary Network
General description and application
The DSP MINI is designed for use in district heating networks, suitable for heating and for providing DHW for single family houses. It provides an alter­native solution to an oil or gas boiler. The DSP MINI is designed for heating, do mestic hot water and floor heating. The wall- mounted construction saves space which is needed for installation and service.
The DSP MINI is designed as a wall -mounted sta tion. Each station is equipped with micro plate heat exchangers for DHW and optional for heating man­ufactured by Danfoss, which significantly increase substation performance and lifetime. All compo­nents are placed at the front of the station, which makes it very easy to access them during mainte­nance or servicing. The mounting bracket signifi­cantly reduces the time required to mount the sub­station to the wall. The connections are predefined and allow installers to prepare installation before station is available on the site, which reduces the time between deliver y and startup. Piping prepared with automatic welding machines ensures th e high­est possible welding quality.
DSP MINI is equipped with high quality Danfoss components, which are tested, approved and opti­mized for safe and reliable operation:
• ECL Comfort 110 controller
• Motorized control valve VS2 with AMV actuator
• AVTB self-acting temperature controller
• AVPB-F Differential pressure controller with flow limitation
• Brazed MicroPlate™ Heat exchanger, XB06
• Primary side polyurethane insulation according 50% ENEV 2013
• Metal box with door
Operating parameters
Materials
Primary side
Maximum temperature 95°C Maximum pressure 10 bar (g) Connection DN 20 / Rp ¾”
Heating
Maximum temperature* 95°C Maximum pressure* 10 bar (g)
Connection DN 20 / Rp ¾”
Domestic Hot Water
Maximum temperature 95°C Maximum pressure 10 bar (g) Connection DN 20 / Rp ¾”
Max dimensions (mm)
Width ⁄ Height ⁄ Depth 770 / 1000 / 330 mm Weight (incl. packing) max. 80 kg
* In case of floor heating with heat exchanger the maximum
temperature is 50 °C and the maximum pressure is 3 bar(g)
Pipes, fittings, valves (primary side) P235GH, CuSn5ZnPb (Rg5), Red bronze (Rg5), brass MS58 (nickel plated) Pipes, fittings, valves (heating side) P235GH , EN - GJL-150 (GG15) Pipes, fittings, valves (DHW side) 1.4404, 1.4301, CW617N Heat exchanger 1.4404 with Cu brazed Insulation (heat exchanger) PU foam (λ=0.035 W/mK) Insulation (piping primary side) PU foam (λ<0.025 W/mK)
© Danfoss | 2019.12
AI301539974826en-DE0101 | 1
Data Sheet DSP MINI light a Danfoss Platform for Flensburg Secondary Network
Circuit diagram
DSP-1-MINI APP1 DHE TWE
DSP-2-MINI APP2 MHE TWE
1 Ball valve with M10 sensor connection 2 Manometer 3 Manovalve 4 Strainer 5 Drain valve 6 Insert energy meter 7 Pressure controller AVPB-F
2 | © Danfoss | 2019.12
8 Control valve VS2 9 Heat exchanger 10 Shut off valve 6 mm 11 Temperature controller AVTB 12 Pump 13 Heat exchanger 14 Safety valve 15 Ball valve
18 Bimetal thermometer 21 ECL 25 Temperature sensor 27 Safety temperature monitor (STW) 28 Check valve
AI301539974826en-DE0101
Data Sheet DSP MINI light a Danfoss Platform for Flensburg Secondary Network
Floor heating
DSP-1-MINI APP3 FBH TWE
DSP-2-MINI APP4 FBH TWE
1 Ball valve with M10 sensor connection 2 Manometer 3 Manovalve 4 Strainer 5 Drain valve 6 Insert energy meter 7 Pressure controller AVPB-F
8 Control valve VS2 9 Heat exchanger 10 Shut off valve 6 mm 11 Temperature controller AVTB 12 Pump 13 Heat exchanger 14 Safety valve 15 Ball valve
Floor heating
18 Bimetal thermometer 21 ECL 25 Temperature sensor 27 Safety temperature monitor (STW) 28 Check valve
AI301539974826en-DE0101
© Danfoss | 2019.12 | 3
Data Sheet DSP MINI light a Danfoss Platform for Flensburg Secondary Network
Function
The DSP Mini substation is the connecting part between the h eat supplier and the consumer of the heating and domestic hot water. The task of the substation is to adapt the heat con­dition suitable for the consumer and meet the demand from the heat supplier and consumer. The water is coming from the district heating utility and is fed into the station at the appropriate pres­sure and temperature. This can be higher in winter and lower in the summer. The district heating water flows in the primary fl ow through the shut-off valves and the strainer. Pressure gauges and thermom eters are installed in the flow and return to detect the pressure and temperature. Depending on the variant, the connection of the secondary side (heating) is carried out directly or indirectly (via heat exchanger). Furthermore, on the primary side, in the flow circuit we have a control valve, depending on the variant, control valves are used to adapt the heat condi tions (secondary temperature) by controling the flow of district heating water. The input s are comming from
using our Danfoss ECL Comfort 310 controller with weather compensating function. The district heating water then flows back to the district heating supply via the primary return through the shut-off valves and the strainer. On the primary side, high tem perature connections for radi ator heating or similar are used depending on the application selected. In the secondary circuit, a circulating pump distrib­utes the heating water to the heating devices, this is available depending on the application. If the application selected has domestic hot water production included, this is connected to the pri­mary side and is prepare via a heat exchanger and with a self-acting control valve. To limit the flow of primary district heating water, a flow limiter with integrated differential pressure control is provided in the return of th e primary side, here the maximum flow from the contract can be adjusted. To measure the energy consumed, an insert for a heat meter is available and M10 connec­tions are provided in the primary side ball valves.
-
4 | © Danfoss | 2019.12
AI301539974826en-DE0101
Data Sheet DSP MINI light a Danfoss Platform for Flensburg Secondary Network
Capacity, weight and dimensions
Capacity
Code Description
Typ e
1 146G0015 DSP-1-MINI DHE T WE 14* 50*** n/a XB 06H -1-26 2 146G0016 DSP-1-MINI MHE TWE 14* 50*** n/a XB 06H -1-26 65 66* FL-S-DL37-R-D-17/11 3 146G0017 DSP-1-MINI FBH TWE 10 ** 50*** n/a XB 06H -1-26 65 65** FL-S-DL37-R/FB-D-17/11 4 146G0018 DSP-2-MINI FBH TWE 10** 50*** XB06L-1-10 XB06H -1-26 70 55**
[kW]
HE DHW HE DHW DH HE
* Calculated with 15 deg ΔT (40/65 °C)
Heat exchanger Pipe diameter
DHW
DN 20 / R p ¾”
DSP-1-MINI DHE TWE
Weight
Max Heating
Dp available
(kg)
60 18**** FL-S-DL37-U-D-17/11
kPa
approval number
FL-S-DL37-R/FB/WT-D-17/11
** Calculated with 10 deg ΔT (25/35 °C) *** Calculated with 40 deg ΔT (10/50 °C) **** No pump is available in this application
173 129
95 83 72
0
285
Typ e Type of heating Type of DHW
DHE = Direct heating TWE = Instantaneus FBH = Floor heating Domestic Hot Water MHE = Mixing heating
330
760
998
960
908
Drain val ve
0
45
90
227
205
395
305
575
485
Primary o ut
Primary in
MAG
Configuration Contact the sales staff responsible for additional
details and a quotation for the DSP MINI.
Domestic cold water
Domestic hot water
Heating supply
Heating return
998
960
908
AI301539974826en-DE0101
© Danfoss | 2019.12 | 5