Danfoss DSP 1 MAXI Data sheet

Data sheet
Standard Welded Stations
Type DSP 1 MAXI
General description and application
Maximum operating parameters
District heating transfer stations provide the link between district heating suppliers and customers’ systems. They incorp orate the necessary equipment to tailor the supplied heat to the needs of the object premises as specied in the heating supply contract. In this they need to comply with all applicable stand­ards and with the supplier’s technical connection conditions.Indirect connections (in which district heating and in-house systems are hydraulically iso­lated)incorporate components to separate the sys­tems (heat exchanger), to limit the ow volume to that specied in the contract, regulate the se condary supply temperature and measure the energy con­sumption. The system described here is a standard type in which one dierent types of applications can be connecte d on the secondary.Thus, this system is especially suitable for biomass applications.
Primary
Maximum permissible supply temperature, primary Maximum permissible operating pressure, primary PZP 16 bar(g) = LT / optional 25 bar(g) = HT Rated pressure, primary PN 16 = LT / optional 25 = HT Maximum permissible pressure dierential, primary Maximum permissible ow volume, primary VZP 10,0 m3/h for w <= 1,5 m/s
TVP 100°C (PN16=LT) / 140 °C (PN25 = HT)
DPP 12 bar (PN16=LT) / 16 bar (PN25=HT)
Secondary
Maximum permissible supply temperature, secondary
Maximum permissible operating pressure, secondary Rated pressure, secondary PN 10 Maximum permissible ow volume, secondary VZS 19,5 m3/h for w <= 1,5 m/s
TVS 100 °C
PZS 3 bar(g)
Circuit diagram
200
220
400
430
210
DSL
HPU
410
210
500
S1
STW
10
M1
40
20
5DN3DN
S5
270 280
S3
440
410
100
BFLV
230
MAG
DSP1 MAXI 200 Shut- o device for primary (left/right conn.) 220 Dirt trap / strainer 430 Manometer 400 Thermometer 40 Insert or Heatmeter 20 Motorized Combi (Control) valve M1 Electrical actuator S5 Return temperature limiter primary 270 High-pressure drain valve 10 Heat exchanger 100 Safety valve S3 Supply temperature sensor secondar y STW Safety thermostat (optional for HT) MAG Pressure retention connector 280 Drain valve 440 Manometer 230 Dirt trap / strainer 500 Electronic controller S1 Outdoor sensor DSL Pump group - optional HPU Heating pump 210 Shut-o device secondary BFLV Shut-o valve set - optional 210 Shut-o device secondary 410 Thermometer
© Danfoss | 2022.03 AI143486465943en-010401 | 1
Data sheet DSP 1 MAXI
Materials
Function
Pipes and pipe ttings, anges P235GH-TC1, C22.8, CuSn5Pb5Zn5-C (RG-5) Heat exchanger 1.4404 with CU brazing compound Fittings CuSn5Pb5Zn5-C (RG-5), ST37.0, EN-GJS-400-18-LT (GGG40.3) Insulation PU-Hardfoam, black, λ = 0,027 W/mK
Hot water drawn from the pipeline of the local or district heating supply company is fed into the station at an appropriate temperature and pressure, which may be higher in winter than in summer.
In the primary supply line this hot water will ow through a shut-o valve and a dirt trap / strainer. The supply and return lines will incorporate a thermometer and a manometer to register the temperature and pressure.
There will also be regulatory equipment in the return lines of the primar y as specied by the circuit design.
The cooled heating water then ows back to the local or district heating supply company via the primary return pipe.
On secondary side dierent types of applications and systems can be connected.
Technical data
max.
max.
max.
VPP
type
max.
no.
[m3/h]DNpri.QP[m3/h]
01 3 25 3 6,3 XB12 H 90 4,5 32 51 60 19 DSL 25-120F MG1 750 1150 1670 14 09 119 0 1038 131 10 4 01 3 25 3 6,3 XB12 H 90 4,5 32 51 60 19 DSL 25-120F MG3 750 115 0 1670 14 09 119 0 1038 131 10 4
02 3,5 32 3,5 8 XB12 M 110 6,2 32 54 59 21 DSL 25-120F MG1 750 1150 1670 14 09 119 0 1038 136 107 02 3,5 32 3,5 8 XB12 M 110 6,2 32 54 59 21 DSL 25-120F MG3 750 1150 1670 14 09 119 0 1038 136 107 11 6 32 6 12, 5 XB52 M 50 7,1 40 69 81 19 DSL 32-120F MG1 750 1150 1670 14 09 119 0 1038 144 114 11 6 32 6 12, 5 XB52 M 50 7,1 40 69 81 19 DSL 32-120F MG3 750 115 0 1670 14 09 119 0 1038 14 4 114 12 6 32 6 12, 5 XB52 M 70 11,5 50 65 79 23 DSL 40-120F MG1 750 115 0 1670 1409 119 0 1038 153 123 12 6 32 6 12, 5 XB52 M 70 11,5 50 65 79 23 DSL 40-120F MG3 750 115 0 1670 1409 119 0 1038 153 123 21 8,2 40 10 16 XB59 M 80 11, 5 65 64 70 20 DSL 50-120F MG1 750 1150 1670 1423 12 97 1038 166 133 21 8,2 40 10 16 XB59 M 80 11, 5 65 64 70 20 DSL 50-120F MG3 750 1150 1670 1423 12 97 1038 166 133 22 8,2 40 10 16 XB59 M 110 15,8 65 63 69 22 DSL 50-120F MG1 750 1150 1670 14 43 1297 1038 175 142 22 8,2 40 10 16 XB59 M 110 15,8 65 63 69 22 DSL 50-120F MG3 750 1150 1670 1423 12 97 1038 175 142 31 10 50 10 20 XB59 M 110 15, 8 65 57 66 21 DSL 50-120F MG1 750 1150 1670 14 43 1297 1038 175 149 31 10 50 10 20 XB59 M 110 15, 8 65 57 66 21 DSL 50-120F MG3 750 1150 1670 14 43 1297 1038 175 149 32 10 50 10 20 XB59 M 140 19,3 65 61 72 23 DSL 50-150F MG1 750 1150 1670 1423 12 97 1038 195 158 32 10 50 10 20 XB59 M 140 19,3 65 61 72 23 DSL 50-150F MG3 750 1150 1670 1423 1297 1038 19 5 158
AVQM
Kvs
[m3/h] HEX type
VPS
max.
[m3/h]DNsec.
dpp
*
[kPa]
dpp
dps
**
***
[kPa]
[kPa] DSL typeD[mm]W[mm]H[mm]
A
[mm]
with
DSL
A1
[mm]
with BFLVB [mm]
mass
with
DSL [kg]
* without heatmeter (HM) / include insert ** include heatmeter (HM) SonoMeter 40 *** inside the Station
mass
with
BFLV
[kg]
type DSP 1 MAXI: - PD - 32 HT S100
Base type P = Electri cal box Typ e No. LT: Variant
Controller Danfoss HM SonoMeter 40 QP ..
D = ECL310 HT: Variant
NA = not available S060 = SonoMeter 40 QP 6,0 230V
PN16/100°C
PN25/140° C
Lenght of insert for HM or
S035 = SonoMeter 40 QP 3,5 230V
S100 = SonoMeter 40 QP 10,0 230V
I260 = Insert 260 mm
I300 = Insert 300 mm
Type designation for pump module
DSL - 40–120 F - MG1
Pump module Pump characteristics Pump model
MG1 = MAGNA 1 MG3 = MAGNA 3
2 | AI143486465943en-010401 © Danfoss | 2022.03