Danfoss DSH090, DSH600 Application guide

Application Guide
Scroll compressors DSH090 to DSH600
R410A - R454B - R452B, 50Hz -60Hz
www.danfoss.com
Scroll compressors, DSH090 to DSH600 | Contents

Contents

Safety and warnings 5
Introduction 6
Product identication 8
Name Plate 8
Certicates, declarations and approvals 10
Certicates, declarations, and approvals 10
Refrigerants 11
R410A 11
R452B 11
R454B 11
Technical specication 12
Performance data 13
Sound and vibration data 16
Operating envelope data 18
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 2
Scroll compressors, DSH090 to DSH600 | Contents
Dimensions 21
Mechanical connections 26
Electrical connections 37
Electrical Specications 39
Application 45
Packaging 64
Single pack 64
Ordering 65
Single pack 65
Accessories and Spare parts 68
Gaskets 68
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 3
Scroll compressors, DSH090 to DSH600 | Contents
Lubricant 70
Trio kits 72
Online support 73
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 4
Scroll compressors, DSH090 to DSH600 | Safety and warnings

Safety and warnings

Danfoss compressors are designed and manufactured according to the state of the art and to valid European and US regulations. Particular emphasis has been placed on safety and reliability. Related instructions are highlighted with the following icons:
This icon indicates instructions to avoid safety risk.
This icon indicates instructions to avoid reliability risk.
The purpose of this guideline is to help customers qualify compressors in the unit. You are strongly advise to follow these instructions. For any deviation from the guidelines, please contact Danfoss Technical Support. In any case, Danfoss accepts no liability as a result of the improper integration of the compressor into the unit by the system manufacturer.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 5
1 2
4
5
6
3
CC-000005
12345
6
Intermediate discharge valves (IDVs) increase
seasonal eciency
Heat shield lowers the heat transfer between
discharge and suction gas and the sound level
Internal Non Return Valve (INRV) prevents
excessive leak rate from high pressure side
Lead free polymer bearings improve behavior
under poor lubrication conditions
Patented motor cap for optimal motor cooling and
higher resistance to liquid slugging
Organ pipe masters oil circulation in manifold
conguration.
Scroll compressors, DSH090 to DSH600 | Introduction

Introduction

Product description

Danfoss scroll compressor DSH for R410A, R454B and R452B is available as single compressor and can be assembled in tandem or trio combinations.
DSH series scroll compressor benet from an improved design to achieve the highest eciency and increased life time.

Cut Away DSH090-184

Figure 1: Cut Away DSH090-184
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 6
1
2
3
4
5
6
7
CC-000006
1234567
Intermediate discharge valves (IDVs) increase
seasonal eciency
Heat shield lowers the heat transfer between
discharge and suction gas and the sound level
Internal Non Return Valve (INRV) prevents
excessive leak rate from high pressure side
Integrated discharge gas temperature protection
(DGT)
Lead free polymer bearings improve behavior
under poor lubrication conditions
Patented gas path ow with gas intake design
induce higher resistance to liquid slugging
Organ pipe masters oil circulation in manifold
conguration
Scroll compressors, DSH090 to DSH600 | Introduction

Cut Away DSH240-600

Figure 2: Cut Away DSH240-600

How do IDVs work?

Figure 3: Intermediate Discharge Valve (IDV)
Danfoss Intermediate Discharge Valves (IDVs) are located close to the discharge side of the compressor. They reduce excessive compression of refrigerant under part-load conditions while maintaining the same cooling capacity. The IDVs open when discharge pressure falls below the built-in optimization point. They adapt the eort of the motor to the varying load and pressure conditions in the system, thus reducing the eort of the motor and its electrical consumption and improving the system’s seasonal energy eciency.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 7
M A D E I N F R A N C E
Model no : DSH485B4APC
Serial no : JC112345678
380-415V 3~50Hz 460V 3~60Hz LR 344A MAX OPER. 91 A Thermally protected system P.E.D. Marking PS TS Max TS Min Volume Lubricant:P.O.E. 160SZ
LP Side HP Side
31,20 bar 52,0 C
-35,0 C 28,5 L
48,70 bar 150 C
-35 C 3,9 L
H
2019
Refrigerant: R410A R452B R454B
876543210
PROTECTED BY DOMESTIC AND FOREIGN PATENTS
0038 089
1
5
6
7
2
3
4
123
4567Model number
Serial number
Approvals
Refrigerant
Supply voltage, Starting current & Maximum
operating current
Housing service pressure
Factory charged lubricant
Family, lubricant & refrigerant DSH: Scroll, POE lubricant,
R410A and R454B/R452B (according to version)
Motor protection
A: Electronic module, 24V AC, R410A only B: Electronic module, 110-240V, R410A only P: Electonic module, 110-240V, R410A/R454B/R452B X: Electonic module,24V AC, R410A/R454B/R452B L: Internal overload protector, R410A/R454B/R452B
Suction and discharge connections
A: Brazed connections
Family,
lubricant
& refrigerant
Nominal capacity
Approvals Voltage Version Evolution
index
Evolution index
A~Z
C4DSH B AB485
Motor voltage code
3: 200-230V/3~/60Hz 4: 380-415V/3~/50Hz - 460V/3~/60Hz 7: 575V/3~/60Hz 9: 380-400V/3~/60Hz
for DSH240 and DSH381: 380V/3~/60Hz
UL index
Nominal capacity
in thousand Btu/h at 60Hz ARI conditions
Scroll compressors, DSH090 to DSH600 | Product identication
Product identication

Name Plate

Figure 4: Name Plate

Nomenclature

The example below presents the compressor nomenclature which equals the technical reference as shown on the compressor nameplate. Code numbers for ordering are listed in section Ordering.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 8
Year code 8 Digit serial number
12345678A 25B
Plant assembly line code
Month code
Year code
Month code
Plant assembly line code
Year
Code
Month
Code
Plant
Code
1990, 2010
A
January
A
Trévoux, France
11
1991, 2011
B
February
B
1992, 2012
C
March
C
1993, 2013
D
April
D
Wuqing ,China
25
1994, 2014
E
May
E
1995, 2015
F
June
F
1996, 2016
G
July
G
1997, 2017
H
August
H
1998, 2018
J
September
J
1999, 2019
K
October
K
2000, 2020
L
November
L
2001, 2021
M
December
M
2002, 2022
N
2003, 2023
P
2004, 2024
Q
2005, 2025
R
2006, 2026
S
2007, 2027
T
2008, 2028
U
2009, 2029
V
Scroll compressors, DSH090 to DSH600 | Product identication

Compressors serial number

Table 1: Serial number code legend table
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 9
Certicates, declarations, and approvals
Certication logo
Models
CE 0062, CE 0038 or CE 0094 (European Directive)
All DSH models
UL (Underwriters Laboratories)
All DSH models Other approvals / certicates
Contact Danfoss
Products
DSH models
Declaration of conformity
Contact Danfoss
Products
DSH models
Manufacturer’s declaration of incorporation
Contact Danfoss
Products
DSH090 to 184
DSH240-295
DSH381-485-600
Category PED R410A
IIIIIII
Category PED R452B / R454B
III
III
IV
Maximum / Minimum temperature - Ts
-35°C < Ts < 55°C
-31°F < Ts < 131°F
-35°C < Ts < 52°C
-31°F < Ts < 125.6°F
-35°C < Ts < 52°C
-31°F < Ts < 125.6°F
Maximum allowable pressure (Low side) - Ps
R410A : 33.3 bar (g) / R452B and R454B : 31.2 bar(g) R410A : 483 psig / R452B and R454B : 453 psig
31.2 bar(g) 451 psig
31.2bar(g) 451psig
Maximum allowable pressure (High side) - Ps
48.7 bar(g) 706 psig
48.7 bar(g) 706 psig
48.7 bar(g) 706 psig
Declaration of conformity
Contact Danfoss
Contact Danfoss
Contact Danfoss
Products
Internal free volume without oil
Low pressure side
High pressure side
Total
[litre]
[cu.inch]
[litre]
[cu.inch]
[litre]
[cu.inch]
DSH090
11.7
714
0.74312.4
757
DSH105
13.6
830
0.74314.3
873
DSH120
13.6
830
0.74314.3
873
DSH140
13.6
830
0.74314.3
873
DSH161
13.6
830
0.74314.3
873
DSH184
13.9
848
0.74314.6
891
DSH240
27.5
1678
2.9
177
30.4
1855
DSH295
27.1
1654
2.8
171
29.9
1825
DSH381
31.1
1898
4.0
244
35.1
2142
DSH485
28.5
1739
3.9
238
32.4
1977
DSH600
30.1
1837
4.0
244
34.1
2081
Scroll compressors, DSH090 to DSH600 | Certicates, declarations and approvals
Certicates, declarations and approvals
Certicates, declarations, and approvals
DSH scroll compressors comply with the following approvals and certicates. Certicate are listed on:
Documentation for Commercial Compressor | Danfoss
Table 2: Certicates, declarations, and approvals

Low voltage directive 2014/35/EU

Table 3: Low voltage directive 2014/35/EU

Machines directive 2006/42/EC

Table 4: Machines directive 2006/42/EC

Pressure equipment directive 2014/68/EU

Table 5: Pressure equipment directive 2014/68/EU

Internal free volume

Table 6: Internal free volume
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 10
Scroll compressors, DSH090 to DSH600 | Refrigerants

Refrigerants

General Information

When choosing a refrigerant, dierent aspects must be taken into consideration:
• Legislation (now and in the future)
• Safety
• Application envelope in relation to expected running conditions
• Compressor capacity and eciency
• Compressor manufacturer recommendations & Guidelines
Additional points could inuence the nal choice:
• Environmental considerations
• Standardisation of refrigerants and lubricants
• Refrigerant cost
• Refrigerant availability

R410A

R410A is a HFC blend (R32: 50%; R125: 50%) with a zero Ozone Depletion Potential (ODP=0) and a Global Warming Potential of 1924/AR5 (2088/AR4). It is a near-azeotropic mixture with a temperature glide less than 0.2 K.
With its high net refrigeration eect coupled to a high density, the R410A has appeared in last decade to be the preferred refrigerant for use in commercial air conditioners and heat pumps.

R452B

R452B is a HFO/HFC blend (R32: 67%; R125: 7%; R1234yf: 26%) with a zero Ozone Depletion Potential(ODP=0) and a low Global Warming Potential (GWP: 676/AR5 ; 698/AR4). It is a near-azeotropic mixture with a temperature glide around 1 K.
R452B has very close capacities versus R410A and due to its very limited discharge temperature dierence it appears today as the best candidate for a direct drop in of R410A.
R452B is classied A2L with low ammability properties. Please refer to European regulations and directives about the use of refrigerant of the A2L safety group ( EN378, EN60335). Outside Europe refer to the local regulation.

R454B

R454B is a HFO/HFC blend (R32 :68.9%; R1234yf: 31.1%) with a zero Ozone Depletion Potential (ODP=0) and a low Global Warming Potential (GWP: 467/AR5; 466/AR4). It is a near-azeotropic mixture with a temperature glide around 1 K.
R454B has very close match to R410A in terms of capacity and discharge temperature dierence, and it oers better eciencies compared to R410A.
R454B is classied A2L with low ammability properties. Please refer to European regulations and directives about the use of refrigerant of the A2L safety group (EN378, EN60335). Outside Europe refer to the local regulation
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 11
Model
Nominal
tons 60 Hz
Swept volume
Displacement (50 Hz)
(1)
Displacement (60 Hz)
(2)
Oil charge
Net weight
(3)
TR
cm3/rev
cu.in/rev
m3/h
cu.ft/h
m3/h
cu.ft/h
dm
3
ozkglbs
DSH090
7.5
88.4
5.39
15.4
544
18.6
657310258128
DSH1059103.5
6.3218636
21.8
770
3.3
11264141
DSH12010116.9
7.13
20.3
717
24.6
869
3.3
11264141
DSH14012133
8.12
23.1
816
27.9
985
3.3
11267148
DSH16113151.7
9.26
26.4
932
31.9
1127
3.3
11269152
DSH18415170.3
10.39
29.6
1045
35.8
1264
3.6
122
71.5
158
DSH24020227.6
13.89
39.6
1398
47.8
1688
6.1
206
114
251
DSH29525276.2
16.85
48.1
1699582048
6.1
206
117
258
DSH38130345
21.05602119
72.3
2553
6.1
206
162
357
DSH48540442.6
27.01772719
92.9
3281
6.1
206
176
388
DSH60050553
33.75
96.2
3397
116.1
4100
6.1
206
215
474
Scroll compressors, DSH090 to DSH600 | Technical specication
Technical specication

50-60 Hz data Single compressor

Table 7: Technical specication 50-60 Hz data Single compressor
(1)
(1)
Displacement at nominal speed: 2900rpm at 50 Hz
Displacement at nominal speed: 2900rpm at 50 Hz
(2)
(2)
Displacement at nominal speed: 3500rpm at 60 Hz
Displacement at nominal speed: 3500rpm at 60 Hz
(3)
(3)
Net weight with oil charge
Net weight with oil charge
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 12
Model
Nominal tons
60 Hz
Nominal cooling capacity
Power input
COP
E.E.R.
TRWBtu/hkWW/W
Btu/h/W
50Hz
DSH090
7.5
20048
68402
6.57
3.05
10.40
DSH105
9.0
23578
80449
7.69
3.07
10.47
DSH120
10.0
26787
91396
8.65
3.10
10.57
DSH140
12.0
30370
103621
9.74
3.12
10.64
DSH161
13.0
34894
119059
11.09
3.15
10.74
DSH184
15.0
39036
133191
12.42
3.14
10.72
DSH240
20.0
52730
179920
17.04
3.09
10.56
DSH295
25.0
64520
220149
20.35
3.17
10.82
DSH381
30.0
80707
275379
25.83
3.12
10.66
DSH485
40.0
104687
357202
32.39
3.23
11.03
DSH600
50.0
128864
439698
40.60
3.17
10.83
60Hz
DSH090
7.5
27471
93730
8.60
3.19
10.90
DSH105
9.0
32279
110136
10.06
3.21
10.94
DSH120
10.0
36629
124977
11.31
3.24
11.05
DSH140
12.0
41510
141631
12.81
3.24
11.06
DSH161
13.0
47222
161122
14.77
3.20
10.91
DSH184
15.0
53157
181371
16.44
3.23
11.03
DSH240
20.0
71760
244852
22.46
3.20
10.90
DSH295
25.0
87610
298934
26.96
3.25
11.09
DSH381
30.0
110116
375726
34.41
3.20
10.92
DSH485
40.0
143956
491192
43.03
3.35
11.42
DSH600
50.0
175344
598291
53.80
3.26
11.12
Scroll compressors, DSH090 to DSH600 | Performance data

Performance data

R410A 50-60 Hz, Single compressor

Table 8: 50-60 Hz Performance data
NOTE:
TR: Ton of Refrigeration, COP: Coecient Of Performance EER: Energy Eciency Ratio
Standard rating conditions For 50 Hz: Evaporating temperature: 5°C (41°F), Condensing temperature: 50°C (122°F), Superheat: 10K (18°F), Subcooling: 0K (0°F)
For 60 Hz: Evaporating temperature: 7.2°C (45°F), Condensing temperature: 54.4°C (130°F), Superheat: 11.1K (20°F), Subcooling: 8.3K (15°F)
Subject to modication without prior notication.
Data given for motor code 4 compressor with above conditions
For regular updates and detailed capacities, please refer to Coolselector®2.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 13
Model
Nominal cooling capacity
Power input
COP
E.E.R.WBtu/hkWW/W
Btu/h/W
50Hz
DSH090
19590
66839
6.46
3.03
10.35
DSH105
23451
80016
7.40
3.17
10.81
DSH120
26366
89961
8.24
3.20
10.92
DSH140
30180
102974
9.35
3.23
11.01
DSH161
34855
118924
10.58
3.30
11.25
DSH184
38779
132313
11.83
3.28
11.18
DSH240
52130
177873
16.1
3.23
11.02
DSH295
63995
218359
19.4
3.30
11.27
DSH381
78977
269477
24.8
3.19
10.89
DSH485
102623
350160
30.69
3.34
11.41
60Hz
DSH090
26652
90936
8.38
3.18
10.85
DSH105
31925
108929
9.64
3.31
11.30
DSH120
35779
122078
10.89
3.29
11.21
DSH140
40984
139838
12.51
3.28
11.18
DSH161
46938
160152
13.84
3.39
11.57
DSH184
52181
178040
15.81
3.30
11.26
DSH240
70756
241427
21.4
3.31
11.30
DSH295
86418
294866
25.5
3.39
11.57
DSH381
105020
358339
32.5
3.23
11.02
DSH485
138878
473866
40.92
3.39
11.58
Model
Nominal cooling capacity
Power input
COP
E.E.R.WBtu/hkWW/W
Btu/h/W
50Hz
DSH090
19346
66010
6.37
3.03
10.36
DSH105
22940
78270
7.26
3.16
10.78
DSH120
26220
89463
8.16
3.21
10.97
DSH140
29879
101946
9.28
3.22
10.98
DSH161
34151
116525
10.45
3.27
11.15
DSH184
37926
129403
11.70
3.24
11.06
DSH240
50691
172964
15.92
3.18
10.87
DSH295
62304
212589
19.07
3.27
11.15
DSH381
78379
267438
24.41
3.21
10.96
DSH485
101653
346851
30.39
3.34
11.41
Scroll compressors, DSH090 to DSH600 | Performance data

R452B 50-60 Hz, Single compressor

Table 9: 50-60 Hz Performance data
NOTE:
TR: Ton of Refrigeration, COP: Coecient Of Performance EER: Energy Eciency Ratio
Standard rating conditions For 50 Hz: Evaporating temperature: 5°C (41°F), Condensing temperature: 50°C (122°F), Superheat: 10K (18°F), Subcooling: 0K (0°F)
For 60 Hz: Evaporating temperature: 7.2°C (45°F), Condensing temperature: 54.4°C (130°F), Superheat: 11.1K (20°F), Subcooling: 8.3K (15°F)
Subject to modication without prior notication.
Data given for motor code 4 compressor with above conditions
For regular updates and detailed capacities, please refer to Coolselector®2.

R454B 50-60 Hz, Single compressor

Table 10: 50-60 Hz Performance data
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 14
Model
Nominal cooling capacity
Power input
COP
E.E.R.WBtu/hkWW/W
Btu/h/W
60Hz
DSH090
26320
89804
8.18
3.22
10.98
DSH105
31296
106782
9.49
3.30
11.25
DSH120
35528
121223
10.66
3.33
11.37
DSH140
40482
138126
12.19
3.32
11.33
DSH161
45966
156834
13.79
3.33
11.38
DSH184
51267
174922
15.36
3.34
11.39
DSH240
68133
232478
20.81
3.27
11.17
DSH295
83489
284872
24.94
3.35
11.42
DSH381
105020
358339
32.50
3.23
11.02
DSH485
137206
468160
40.43
3.39
11.58
Scroll compressors, DSH090 to DSH600 | Performance data
NOTE:
TR: Ton of Refrigeration, COP: Coecient Of Performance EER: Energy Eciency Ratio
Standard rating conditions For 50 Hz: Evaporating temperature: 5°C (41°F), Condensing temperature: 50°C (122°F), Superheat: 10K (18°F), Subcooling: 0K (0°F)
For 60 Hz: Evaporating temperature: 7.2°C (45°F), Condensing temperature: 54.4°C (130°F), Superheat: 11.1K (20°F), Subcooling: 8.3K (15°F)
Subject to modication without prior notication.
Data given for motor code 4 compressor with above conditions
For regular updates and detailed capacities, please refer to Coolselector®2.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 15
Compressor model
50 Hz
60 Hz
Acoustic hood
code number
Sound power dB(A)
Attenuation dB(A)
(1)
Sound power dB(A)
Attenuation dB(A)
(1)
DSH090736766
120Z0034
DSH105756786
102Z0035
DSH120756786
120Z0035
DSH140766796
120Z0035
DSH161766796
120Z0035
DSH184786816
120Z0135
DSH240826854
120Z0022
DSH295826854
120Z0022
DSH381896914
120Z0022
120Z0579
(2)
DSH485
(3)
894914120Z0022
DSH600
(3)
91/93//
Compressor model
50 Hz
60 Hz
Acoustic hood code number
Sound power dB(A)
Attenuation dB(A)
(1)
Sound power dB(A)
Attenuation dB(A)
(1)
Body
Top
DSH090734764
120Z0490
120Z0493
DSH105754785
120Z0491
120Z0493
DSH120754785
120Z0491
120Z0493
DSH140764795
120Z0491
120Z0493
DSH161764795
120Z0491
120Z0493
DSH184785816
120Z0492
120Z0493
DSH240825854
120Z0768
DSH295825854
120Z0768
DSH381
(2)
894914120Z0768
DSH485
(2)
894914120Z0768
Scroll compressors, DSH090 to DSH600 | Sound and vibration data

Sound and vibration data

Typical sounds and vibrations in systems can be broken down into the following three categories:
• Sound radiation (through air)
• Mechanical vibrations (through parts and structure)
• Gas pulsation (through refrigerant)
The following sections focus on the causes and methods of mitigation for each of the above sources.

Compressor sound radiation - Single

For sound radiating from the compressors, the emission path is air and the sound waves are travelling directly from the machine in all directions.
Table 11: Compressor sound radiation (R410A/R452B/R454B Max. DGT 135°C)
(1)
(1)
Attenuation given with acoustic hood
Attenuation given with acoustic hood
(2)
(2)
For DSH381code 3
For DSH381code 3
(3)
(3)
No acoustic hood available for DSH485 code 3 and DSH600
No acoustic hood available for DSH485 code 3 and DSH600
Table 12: Compressor sound radiation(R452B/R454B Max. DGT 150°C)
(1)
(1)
Attenuation given with acoustic hood
Attenuation given with acoustic hood
(2)
(2)
No acoustic hood available for DSH381code 3 and DSH485 code3
No acoustic hood available for DSH381code 3 and DSH485 code3
NOTE:
Sound power and attenuation are given at ARI conditions, measured in free space
For compressors running simultaneously,
- The global sound level of “n” identical compressors is:
L
Example for the trio
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 16
=Li+10  Log10 n
GLOBAL
Scroll compressors, DSH090 to DSH600 | Sound and vibration data
DSH720=3  ×  DSH240(50  Hz)
L
L
 =82dB(A)
DSH240
=82+10  Log10 3=86 . 8dB(A)
DSH720
- The global sound level of “n” dierent compressors with respectively Li sound level is:
L
GLOBAL
i = n
 = 10
i = 1
log10(∑ 10
0.1
Li)
Example for the tandem
DSH424=DSH184+DSH240(50  Hz)
L
L
DSH184
DSH424
=78dB(A),L
 =10Log10(10
DSH240
0 . 1×78
=82dB(A)
0 . 1×82
+10
)=  83 . 5dB(A)

Mechanical vibrations

A compressor generates some vibrations that propagate into the surrounding parts and structure. The vibration level of a DSH compressor alone does not exceed 120µm peak to peak for DSH090 to DSH184, and 154µm peak to peak for DSH240 to DSH600. However, when system structure natural frequencies are close to running frequency, vibrations are amplied due to resonance phenomenon.
A high vibration level is damageable for piping reliability and generates high sound levels.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 17
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 5 K (9°F)
S.H. = 30 K (54°F)
CC-000040
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 5 K (9°F)
S.H. = 30 K (54°F)
CC-000042
Scroll compressors, DSH090 to DSH600 | Operating envelope data

Operating envelope data

The Operating envelope for DSH scroll compressors guarantees reliable operations of the compressor for steady-
state operation.
Steady-state operation envelope is valid for a suction superheat within 5K to 30K range at nominal Voltage.

Operating envelope

Figure 5: R410A - DSH090 to DSH184
Figure 6: R410A - DSH240 to DSH600
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 18
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 30 K (54°F)
S.H. = 5 K (9°F)
CC-000039
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 5 K (9°F)
S.H. = 30 K (54°F)
CC-000038
Scroll compressors, DSH090 to DSH600 | Operating envelope data
Figure 7: R452B / R454B - DSH090 to DSH105 (Max. DGT 150°C)
Figure 8: R452B / R454B - DSH120 to DSH184 (Max. DGT 150°C)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 19
Condensing temperature (°C)
Evaporating temperature (°C)
Evaporating temperature (°F)
Condensing temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-40 -31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
41
50
59
68
77
86
95
104
113
122
131
140
149
158
S.H. = 30 K (54°F)
S.H. = 5 K (9°F)
CC-000041
Pressure settings
R410A
R452B / R454B
Working range high side
bar(g)
9.9-44.7
9-41.7
psig
144-648
131-605
Working range low side
bar(g)
1.7-15.5
1.7-14.4
psig
25-225
25-209
Maximum high pressure safety switch setting
bar(g)
46.1
43.1
psig
669
625
Minimum low pressure safety switch setting
bar(g)
1.5
1.5
psig
22
22
Minimum low pressure pump-down switch setting
bar(g)
1.5 bar below nominal evap. pressure with minimum of 1.7 bar(g)
psig
22 psi below nominal evap. pressure with minimum of 25 psig
Scroll compressors, DSH090 to DSH600 | Operating envelope data
Figure 9: R452B / R454B - DSH240 to DSH485
NOTE:
The application envelope of a cross-platform manifold results in the conjunction of map limitations of compressors composing the tandem.
Pressure settings
Table 13: Pressure settings
High and low pressure protection
Low-pressure (LP) and high-pressure (HP) safety switches must never be bypassed nor delayed and must stop all
the compressors.
LP switch auto restart must be limited to 5 times within 12 hours.
HP safety switch must be reset manually.
Depending on application operating envelope, you must dene HP and LP limits within operating envelope and pressure setting table above.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 20
Ø D
H1
Ø19.05mm (0.75 inch)
L3
L2
190.5mm (7.5 inch)
190.5mm
(7.5 inch)
L1
30°
H2
H
30°
CC-000055
Ø D
H
H2
H1
L1
L3
L2
8556208
H
H2
H1
Ø D
L2
L3
L1
8556199
Compressor model
Motor volt‐
age code
DHH1H2L1L2L3
Outline drawing
number
mm
inchmminchmminchmminchmminchmminchmminch
DSH090
3,4,7,9
243
9.57
485
19.09
235
9.25
451
17.76
180
7.09
230
9.06
230
9.0618560176
DSH105-120-140-161
3
(1)
,4,7,9
243
9.57
542
21.34
278
10.94
509
20.04
180
7.09
230
9.06
230
9.0618560177
DSH140-161
3
243
9.57
542
21.34
278
10.94
509
20.04
201
7.91
230
9.06
230
9.0618560041
DSH184
3,4,7,9
243
9.57
558
21.97
299
11.77
524
20.63
201
7.91
230
9.06
230
9.0618560178
DSH240
3,4,7,9
320
12.6
653
25.71
302
11.87
618
24.33
427
16.81
371
14.61
371
14.6128556208
DSH295
3,4,7,9
320
12.6
653
25.71
302
11.87
618
24.33
427
16.81
371
14.61
371
14.6128556208
DSH381
4,7,9
333
13.11
726
28.58
302
11.87
667
26.26
429
16.89
371
14.61
371
14.6138556199
DSH381
3
333
13.11
726
28.58
302
11.87
667
26.26
478
18.82
371
14.61
371
14.6138556239
DSH485
4,7,9
333
13.11
726
28.58
302
11.87
667
26.26
429
16.89
371
14.61
371
14.6138556198
DSH485
3
333
13.11
726
28.58
302
11.87
667
26.26
446
17.56
371
14.61
371
14.6138556237
DSH600
4, 7
333
13.11
799
31.46
302
11.87
732
28.82
429
16.89
371
14.61
371
14.6138556192
Scroll compressors, DSH090 to DSH600 | Dimensions

Dimensions

Single compressors

Figure 10: Outline drawing number 1
Figure 11: Outline drawing number 2
Figure 12: Outline drawing number 3
Table 14: Single compressors
(1)
(1)
DSH105-120
DSH105-120
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 21
H
L
8556230
D
L1
H1
H
L
L1
H1
D
8556228
D
H
L
L1
H1
8556222
L1
H1
H
L
D
8556223
H1
CC-000056
L1
L
H
D
Tandem model
Motor voltage
code
Composition
LDHL1H1
Outline drawing
number
mm
inchmminchmminchmminchmminch
DSH180E
3, 4, 7, 9
DSH090 + DSH090
850
33.46
384
15.12
507
19.96
240
9.45
242
9.5318560115
DSH195U
3, 4, 7, 9
DSH090 + DSH105
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556233
DSH210U
3, 4, 7, 9
DSH090 + DSH120
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556233
DSH210E
3, 4, 7, 9
DSH105 + DSH105
850
33.46
384
15.12
565
22.24
240
9.45
242
9.5318560114
DSH230U
3, 4, 7, 9
DSH090 + DSH140
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556233
DSH240E
3, 4, 7, 9
DSH120 + DSH120
850
33.46
384
15.12
565
22.24
240
9.45
242
9.5318560114
DSH251U
3, 4, 7, 9
DSH090 + DSH161
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556233
DSH260U
3, 4, 7, 9
DSH140 + DSH120
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556230
DSH274U
3, 4, 7, 9
DSH090 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318556232
DSH281U
3, 4, 7, 9
DSH161 + DSH120
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556230
DSH280E
3, 4, 7, 9
DSH140 + DSH140
850
33.46
384
15.12
565
22.24
240
9.45
242
9.5318560114
DSH289U
3, 4, 7, 9
DSH105 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318556231
DSH301U
3, 4, 7, 9
DSH161 + DSH140
850
33.46
386
15.2
565
22.24
240
9.45
242
9.5318556230
DSH304U
3, 4, 7, 9
DSH120 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318556231
DSH322E
3, 4, 7, 9
DSH161 + DSH161
850
33.46
384
15.12
565
22.24
240
9.45
242
9.5318560114
DSH324U
3, 4, 7, 9
DSH140 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318556231
DSH345U
3, 4, 7, 9
DSH161 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318556231
DSH368E
3, 4, 7, 9
DSH184 + DSH184
850
33.46
428
16.85
580
22.83
240
9.45
242
9.5318560113
DSH360X
3, 4, 7, 9
DSH120 + DSH240
903
35.55
533
20.98
731
28.78
359
14.13
211
8.3158560128
DSH424X
3, 4, 7, 9
DSH184 + DSH240
903
35.55
533
20.98
731
28.78
359
14.13
211
8.3158556259
DSH456X
3, 4, 7, 9
DSH161 + DSH295
903
35.55
533
20.98
731
28.78
359
14.13
211
8.3158560128
Scroll compressors, DSH090 to DSH600 | Dimensions

Tandem assemblies

Figure 13: Outline drawing number 1
Figure 16: Outline drawing number 4
Figure 14: Outline drawing number 2
Figure 17: Outline drawing number 5
Figure 15: Outline drawing number 3
Table 15: Tandem assemblies
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 22
Tandem model
Motor voltage
code
Composition
LDHL1H1
Outline drawing
number
mm
inchmminchmminchmminchmminch
DSH479X
3, 4, 7, 9
DSH184 + DSH295
903
35.55
533
20.98
731
28.78
359
14.13
211
8.3158556259
DSH565X
3, 4, 7, 9
DSH184 + DSH381
903
35.55
533
20.98
803
31.61
359
14.13
211
8.3158556260
DSH482E
3, 4, 7, 9
DSH240 + DSH240
1025
40.35
527
20.75
701
27.6
535
21.06
211
8.3128556228
DSH535U
3, 4, 7, 9
DSH240 + DSH295
1025
40.35
527
20.75
701
27.6
535
21.06
211
8.3128556228
DSH590E
3, 4, 7, 9
DSH295 + DSH295
1025
40.35
527
20.75
701
27.6
535
21.06
211
8.3128556228
DSH620U
4, 7, 9
DSH240 + DSH381
1025
40.35
527
20.75
774
30.5
535
21.06
211
8.3138556222
DSH620U
3
DSH240 + DSH381
1025
40.35
576
22.68
774
30.5
535
21.06
211
8.3138556222
DSH675U
4, 7, 9
DSH295 + DSH381
1025
40.35
527
20.75
774
30.5
535
21.06
211
8.3138556222
DSH675U
3
DSH295 + DSH381
1025
40.35
576
22.68
774
30.5
535
21.06
211
8.3138556222
DSH725U
4, 7, 9
DSH240 + DSH485
1025
40.35
546
21.5
774
30.5
535
21.06
211
8.3138556207
DSH725U
3
DSH240 + DSH485
1025
40.35
563
22.17
774
30.5
535
21.06
211
8.3138556207
DSH760E
4, 7, 9
DSH381 + DSH381
1025
40.35
527
20.75
774
30.5
535
21.06
211
8.3148556223
DSH760E
3
DSH381 + DSH381
1025
40.35
576
22.68
774
30.5
535
21.06
211
8.3148556223
DSH780U
4, 7, 9
DSH295 + DSH485
1025
40.35
546
21.5
774
30.5
540
21.26
211
8.3138556220
DSH780U
3
DSH295 + DSH485
1025
40.35
563
22.17
774
30.5
540
21.26
211
8.3138556220
DSH865U
4, 7, 9
DSH381 + DSH485
1025
40.35
546
21.5
774
30.5
540
21.26
211
8.3148556224
DSH865U
3
DSH381 + DSH485
1025
40.35
563
22.17
774
30.5
540
21.26
211
8.3148556224
DSH970E
4, 7, 9
DSH485 + DSH485
1025
40.35
546
21.5
774
30.5
540
21.26
211
8.3148556205
DSH970E
3
DSH485 + DSH485
1025
40.35
563
22.17
774
30.5
540
21.26
211
8.3148556205
DSH895U
4, 7
DSH295 + DSH600
1050
41.39
550
21.65
870
34.25
545
21.46
206
8.1148556250
DSH1085U
4, 7
DSH485 + DSH600
1058
41.65
550
21.65
870
34.25
545
21.46
206
8.1148556248
DSH1200E
4, 7
DSH600 + DSH600
1085
42.72
550
21.65
870
34.25
545
21.46
206
8.1148556247
Scroll compressors, DSH090 to DSH600 | Dimensions
NOTE:
Tandems to be achieved by assembly of individual compressors.
By convention, the last letter of tandems designation have been set to help to discern easily which type of manifold we are considering
U : Uneven tandem E : Even tandem X: Crossplatfom (medium-large) tandem
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 23
CC-000057
H
D
H1
L1
L
CC-000058
H
D
H1
L1
L
H1
L1
H
L
8556217
L
H1
L1
H
8556216
Trio model
Motor votlage
code
Composition
LDH
L1 (Minimum)
H1
Outline drawing
number
mm
inchmminchmminchmminchmminch
DSH420T
3, 4, 7, 9
3×DSH140
1230
48.4
402
15.8
571
22.5
205
8.1
242
9.568560134
1326
52.2
402
15.8
571
22.5
622
24.5
242
9.578560134
DSH483T
3, 4, 7, 9
3×DSH161
1230
48.4
402
15.8
571
22.5
205
8.1
242
9.568560134
1326
52.2
402
15.8
571
22.5
622
24.5
242
9.578560134
DSH552T
3, 4, 7, 9
3×DSH184
1236
48.7
433
17.0
587
23.1
205
8.1
242
9.568560133
1326
52.2
433
17.0
587
23.1
622
24.5
242
9.578560133
DSH720T
3, 4, 7, 9
3×DSH240
1467
57.76
543
21.38
701
27.6
535
21.06
211
8.3188556217
DSH885T
3, 4, 7, 9
3×DSH295
1467
57.76
543
21.38
701
27.6
535
21.06
211
8.3188556217
DSH971T
4, 7, 9
2×DSH295 + DSH381
152460545
21.46
774
30.5
535
21.06
211
8.3198556317
DSH1140T
4, 7, 9
3×DSH381
1467
57.76
545
21.46
774
30.5
535
21.06
211
8.3198556229
DSH1140T33×DSH381
1467
57.76
594
23.39
774
30.5
535
21.06
211
8.3198556229
DSH1245T
4, 7, 9
2×DSH381 + DSH485
1520
59.84
573
22.56
774
30.5
535
21.06
211
8.3198556234
DSH1245T
3
2×DSH381 + DSH485
1520
59.84
594
23.39
774
30.5
535
21.06
211
8.3198556234
DSH1350T
4, 7, 9
DSH381 + 2 x DSH485
1520
59.84
573
22.56
774
30.5
640
25.19
244
9.6198556235
DSH1350T
3
DSH381 + 2×DSH485
1520
59.84
590
23.23
774
30.5
640
25.19
244
9.6198556235
DSH1455T
4, 7, 9
3×DSH485
1520
59.84
573
22.56
774
30.5
640
25.19
244
9.6198556216
DSH1455T33×DSH485
1520
59.84
590
23.23
774
30.5
640
25.19
244
9.6198556216
DSH1570T
4, 7
2×DSH485 + DSH600
1584
62.36
573
22.56
870
34.25
628
24.72
257
10.1298556246
DSH1685T
4, 7
DSH485 + 2xDSH600
1584
62.36
573
22.56
870
34.25
628
24.72
257
10.1298556245
DSH1800T
4, 7
3×DSH600
1605
63.19
573
22.56
870
34.25
628
24.72
257
10.1298556244
Scroll compressors, DSH090 to DSH600 | Dimensions

Trio assemblies

Figure 18: Outline drawing number 6
Figure 20: Outline drawing number 8
Figure 19: Outline drawing number 7
Figure 21: Outline drawing number 9
Table 16: Trio assemblies
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 24
Scroll compressors, DSH090 to DSH600 | Dimensions
NOTE:
Trio to be achieved by assembly of individual compressors
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 25
CC-000167
CC-000168

Connection Details

DSH090
DSH105-120-140-161-184
DSH240-295-381
DSH485
DSH600
Suction connection
Brazed 1"1/8
Brazed 1"3/8
Brazed 1"5/8
Brazed 1"5/8
Brazed 2"1/8
Discharge connection
Brazed 7/8"
Brazed 7/8"
Brazed 1"1/8
Brazed 1"3/8
Brazed 1"3/8
Oil sight glass
Threaded
(1"1/8 – 18 UN-
EF)
Threaded
(1"1/8 – 18 UNEF)
Threaded
(1"1/8 – 18 UN-
EF)
Threaded
(1"1/8 – 18 UN-
EF)
Threaded
(1"1/8 – 18 UN-
EF)
Oil equalization connection
Rotolock 1"3/4
Rotolock 1"3/4
Rotolock 2"1/4
Rotolock 2"1/4
Rotolock 2"1/4
Oil drain connection
None
Female ¼" Flare incorporating a Schrader valve
Low pressure gauge port (Shrader)
Male ¼" Flare incorporating a Schrader valve
Outline drawing11
222
Scroll compressors, DSH090 to DSH600 | Mechanical connections

Mechanical connections

Connection Details
Table 17: Connection Details
Figure 22: Outline drawing 1
Figure 23: Outline drawing 2

Design compressor mounting

General requirements
Compressors used in single applications must be mounted with exible grommets.
Compressors used in parallel applications must be mounted with rigid spacers onto rails (or directly on rails according to compressor models) and the manifold assembly must be mounted with exible grommets onto the frame.
During operation, the maximum inclination from the vertical plane must not exceed 3 degrees.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 26
15 mm
(0.59 Inch)
1
2 3
4
5
6
7
cc-0048
1234567
Tightening torque 15 Nm
HM 8 bolt (4 pcs)
Lock washer (4 pcs)
Flat washer (4 pcs)
Steel mounting sleeve (4 pcs)
Rubber grommet (4 pcs)
Nut (4 pcs)
1
CC-0000001
27.5 mm (1.08 inch)
CC-0049
2
8
3 4
5
6
7
1234567
8
Rubber grommets from kit 8156138
HM 8 bolt (4 pcs)
Lock washer (4 pcs)
Flat washer (4 pcs)
Steel mounting sleeve (4 pcs)
Rubber grommet (4 pcs)
Nut (4 pcs)
Compressor base plate
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Single requirements DSH090-105-120-140-161-184 mounting
Compressors DSH090-105-120-140-161-184 are delivered with rubber grommets and steel mounting sleeve used to isolated the compressor from the base frame.
The grommets must be compressed until contact between the at washer and the steel mounting sleeve is established. The required bolt size for the DSH090-105-120-140-161-184 compressors is HM8-40. This bolt must be tightened to a torque of 15Nm.
Figure 24: Rubber grommets
Part 2, 3, 4, 5, 6 and 7 are delivered along with compressor
Single requirements DSH240-295-381-485 -600 mounting
To be used in single applications, an additional accessory including exible grommets is necessary kit 8156138.
The grommets must be compressed until contact between the at washer and the steel mounting sleeve is established. The required bolt size for the DSH240-295-381-485-600 compressors is HM8-55. This bolt must be tightened to a torque of 21Nm.
Figure 25: Rubber grommets from kit 8156138
Figure 26: Rubber grommets
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 27
2
3
4
1
CC-000002
1234Tightening torque 15Nm
Not supplied Φ8x75mm 0.31x2.95inch
Tightening torque 15Nm
4mm (0.16 inch) thickness
Supplied with the compressor
Included in manifolding kit
Not supplied
1
2
3
4
5
CC-000003
4
3
2
1
CC-000004
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Manifolding requirements DSH180E-210E-240E-280E-322E-368E and DSH260U-281U-301U mounting
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be installed below the rails.
The rigid mounting spacers are included in tandem accessory kits. The rubber grommets are supplied with compressor.
For more details about parallel mounting feet, please see parallel unit outline drawing.
Figure 27: DSH180E to DSH368E and DSH260U-281U-301U mounting
Manifolding requirements DSH195U-210U-230U-251U-274U-289U-304U-324U-345U mounting
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be installed below the rails.
The rigid mounting spacers are included in tandem accessory kits. The rubber grommets are supplied with compressor.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 28
1
2
3
4
CC-000009
1234Tightening torque 15Nm
Not supplied HM8mm 0.31 inch
Tightening torque 15 Nm
3mm (0.12inch) Thickness
Supplied with the compressor
Included in manifolding kit
Not supplied
12345
Tightening torque 15Nm
Not supplied HM8mm 0.31 inch
Tightening torque 15 Nm
4mm (0.16 inch) Thickness
Additional rigid spacer (Refer to table below)
Supplied with the compressor
Included in manifolding kit
Not supplied
Tandem
Additionnal rigid spacer (to be added on the smallest compressor of the tan‐ dem)
DSH195U-210U-230U-251U-289U-304U-345U
7 mm
DSH274U
14 mm
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Table 18: Additionnal rigid spacer
Tandem requirements DSH420T-483T-552T
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be installed below the rails.
The rigid mounting spacers and rubber grommets are included in tandem accessory kits.
Figure 28: DSH420T-483T-552T mounting
Tandem requirements DSH360X-424X-456X-479X-565X mounting
The large compressor, DSH240, 295 or 381, is mounted with rigid spacers on the rails.
The DSH120, 161 or 184 compressor is xed on beams by rigid spacer, and the beams are mounted with rigid spacers on the rails. Rubber grommets and spacers must be installed below the rails.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 29
1
CC-000010
4
5
2
3
7
6
5
CC-000011
2
1
3
CC-000012
123
HM10 x 30 class 10.9 Tightening torque 50
Nm
HM10 x 100 class 10.9 Tightening torque
50Nm
Thickness : 5mm (0.2 inch) (6mm (0.24 inch)
for manifold congurations using one or
several DSH600)
Included in tandem/trio kit
Not supplied
1234567
Tightening torque 16Nm
Not supplied Φ10mm
Tightening torque 50Nm
Tightening torque 55Nm
5mm (0.2inch) thickness
Tightening torque 15Nm
4mm (0.16inch) thickness
Supplied with the compressor
Included in manifolding kit
Not supplied
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Figure 29: DSH240-295-381 mounting
Figure 30: DSH120-161-184 mounting
Tandem requirements DSH482 to DSH1800 mounting (except DSH565)
For parallel mounting, the compressors can be mounted directly on the rails. Rubber grommets and spacers must be installed below the rails.
These parts are included in accessories.
Figure 31: DSH482 to DSH1800 mounting (except DSH565)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 30
HP
3
3
2
2
5
4 m*
4 m*
6
6
6
1
LP
4
CC-0043
123456*
Evaporator
0.5% slope
4m/s or more
8 to 12 m/s
To condenser
U-trap, as short as possible
Max.
CC-000162
HP
LP
3
1
2
123
3D exibility
Upper loop
Condenser
Scroll compressors, DSH090 to DSH600 | Mechanical connections

Design piping

General requirements
Proper piping practices should be employed to:
1.
Ensure adequate oil return, even under minimum load conditions (refrigerant speed, piping slopes…). For validation tests see section Manage oil in the circuit.
2.
Avoid condensed liquid refrigerant from draining back to the compressor when stopped (discharge piping upper loop). For validation tests see section Manage o cycle migration.
3.
Piping should be designed with adequate three-dimensional exibility to avoid excess vibration. It should not be in contact with the surrounding structure, unless a proper tubing mount has been installed. For more information on noise and vibration, see section Sound and vibration data.
Figure 32: Proper piping - Evaporator
Figure 33: Proper piping - Condenser
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 31
CC-000037
Included in tandem or trio accessory kit
Not supplied
Cp3
Cp2
Cp1
CC-000035
1
Cp3
Cp2
Cp1
2
CC-000036
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Tandem and trio requirements (Static)
Tandem and trio use static oil balancing principle to equalize oil level between the compressors by gravity. This is ensured by a precise suction and oil equalization piping design.
The discharge line has no impact on oil balancing. It is shown with tee, to indicate that both left and right side discharge headers are possible.
By default, DSH tandems and trios are not factory-built. To complete an assembly in the eld, you will need:
• Tubings, according to specic outline drawings indicated in the following table.
• Manifolding accessory kit.
• Compressors.
Suction and oil equalization piping drawings must be respected (diameters, minimum straight lengths, …)
Suction washer position
Depending on manifold conguration, it is essential to equalize the pressure of compressor sumps. Hence, a suction washer must be added on certain compressors according to the table. Suction washers are included in tandem or trio accessory kits as described in the illustrations.
Figure 34: Suction washer position
By convention, the compressor order (No.1, No.2 ...) is dened counting from left to right, placed on the side facing the electrical boxes of the compressors (see example below on a trio)
Figure 35: Example of right suction
Figure 36: Example of left suction
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 32
12Cp1
Cp2
Cp3
Trio models with Right suction
Trio models with Left suction
Compressor 1
Compressor 2
Compressor 3
Tandem
model
Composition Cp1 + Cp2
Suction
Dis‐
charge
Oil equaliza‐
tion
Outline
drawing
number
Suction
from
Washer inner di‐
ameter
Washer in suction
of
Tandem kit
code
DSH180E
DSH090+DSH090
1"5/8
1" 3/8
1" 1/8
8560115
Left
Not needed
-
120Z0634
Right
DSH195U
DSH090+DSH105
1"5/8
1" 3/8
1" 1/8
8556233
Left
25mm(0.98 inch)
Cp2
120Z0694
Right
26mm(1.02 inch)
Cp2
DSH210U
DSH090+DSH120
1"5/8
1" 3/8
1" 1/8
8556233
Left
27mm(1.06 inch)
Cp2
120Z0694
Right
27mm(1.06 inch)
Cp2
DSH210E
DSH105+DSH105
1"5/8
1" 3/8
1" 1/8
8560114
Left
Not needed
-
120Z0634
Right
DSH230U
DSH090+DSH140
1"5/8
1" 3/8
1" 1/8
8556233
Left
23mm(0.91inch)
Cp1
120Z0694
Right
23mm(0.91inch)
Cp1
DSH240E
DSH120+DSH120
1"5/8
1" 3/8
1" 1/8
8560114
Left
Not needed
-
120Z0634
Right
DSH251U
DSH090+DSH161
1"5/8
1" 3/8
1" 1/8
8556233
Left
21mm(0.83inch)
Cp1
120Z0694
Right
21mm(0.83inch)
Cp1
DSH260U
DSH140+DSH120
1"5/8
1" 3/8
1" 1/8
8556230
Left
27mm(1.06 inch)
Cp1
120Z0692
Right
27mm(1.06 inch)
Cp1
DSH274U
DSH090+DSH184
1"5/8
1" 3/8
1" 1/8
8556232
Left
20mm(0.79inch)
Cp1
120Z0693
Right
20mm(0.79inch)
Cp1
DSH281U
DSH161+DSH120
1"5/8
1" 3/8
1" 1/8
8556230
Left
25mm(098 inch)
Cp1
120Z0692
Right
25mm(098 inch)
Cp1
DSH280E
DSH140+DSH140
1"5/8
1" 3/8
1" 1/8
8560114
Left
Not needed
-
120Z0634
Right
DSH289U
DSH105+DSH184
1"5/8
1" 3/8
1" 1/8
8556231
Left
23mm(0.91inch)
Cp1
120Z0693
Right
23mm(0.91inch)
Cp1
DSH301U
DSH161+DSH140
1"5/8
1" 3/8
1" 1/8
8556230
Left
27.5mm(1.08 inch)
Cp1
120Z0692
Right
26mm(1.02 inch)
Cp1
DSH304U
DSH120+DSH184
1"5/8
1" 3/8
1" 1/8
8556231
Left
24mm(0.94inch)
Cp1
120Z0694
Right
24mm(0.94inch)
Cp1
DSH322E
DSH161+DSH161
1"5/8
1" 3/8
1" 1/8
8560114
Left
Not needed
-
120Z0634
Right
DSH324U
DSH140+DSH184
1"5/8
1" 3/8
1" 1/8
8556231
Left
25mm(0.98 inch)
Cp1
120Z0694
Right
25mm(0.98 inch)
Cp1
DSH345U
DSH161+DSH184
1"5/8
1" 3/8
1" 1/8
8556231
Left
27.5mm(1.08 inch)
Cp1
120Z0694
Right
27.5mm(1.08 inch)
Cp1
DSH360X
DSH120+DSH240
2"1/8
1" 3/8
1" 3/8
8560128
Left
24mm(0.94inch)
Cp1
120Z0781
Right
25mm(0.98 inch)
Cp1
DSH368E
DSH184+DSH184
1"5/8
1" 3/8
1" 1/8
8560113
Left
Not needed
-
120Z0634
Right
DSH424X
DSH184+DSH240
2"1/8
1" 3/8
1" 3/8
8556259
Left
35.5mm(1.4 inch)
Cp2
120Z0781
Right
35.5mm(1.4 inch)
Cp2
DSH456X
DSH161+DSH1295
2"1/8
1" 3/8
1" 3/8
8560128
Left
25mm(0.98 inch)
Cp1
120Z0781
Right
26mm(1.02 inch)
Cp1
DSH479X
DSH184+DSH295
2"1/8
1" 3/8
1" 3/8
8556259
Left
26mm(1.02 inch)
Cp1
120Z0781
Right
26mm(1.02 inch)
Cp1
DSH482E
DSH240+DSH240
2"1/8
1" 5/8
1" 3/8
8556228
Left
Not needed
-
120Z0792
Right
DSH535U
DSH240+DSH295
2"1/8
1" 5/8
1" 3/8
8556228
Left
31mm(1.22 inch)
Cp1
120Z0796
Right
31mm(1.22 inch)
Cp1
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Tandem models
Table 19: Tandem models
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 33
Tandem
model
Composition Cp1 + Cp2
Suction
Dis‐
charge
Oil equaliza‐
tion
Outline
drawing
number
Suction
from
Washer inner di‐
ameter
Washer in suction
of
Tandem kit
code
DSH565X
DSH184+DSH381
2"1/8
1" 3/8
1" 3/8
8556260
Left
24mm(0.94inch)
Cp1
120Z0781
Right
24mm(0.94inch)
Cp1
DSH590E
DSH295+DSH295
2"1/8
1" 5/8
1" 3/8
8556228
Left
Not needed
-
120Z0792
Right
DSH620U
DSH240+DSH381
2"1/8
1" 5/8
1" 3/8
8556222
Left
29mm(1.14 inch)
Cp1
120Z0791
Right
29mm(1.14 inch)
Cp1
DSH675U
DSH295+DSH381
2"1/8
1" 5/8
1" 3/8
8556222
Left
31mm(1.22 inch)
Cp1
120Z0796
Right
31mm(1.22 inch)
Cp1
DSH725U
DSH240+DSH485
2"1/8
1" 5/8
1" 5/8
8556207
Left
24mm(0.94inch)
Cp1
120Z0786
Right
24mm(0.94inch)
Cp1
DSH760E
DSH381+DSH381
2"1/8
1" 5/8
1" 3/8
8556223
Left
Not needed
-
120Z0792
Right
DSH780U
DSH295+DSH485
2"5/8
1" 5/8
1" 5/8
8556220
Left
27mm(1.06 inch)
Cp1
120Z0787
Right
27mm(1.06 inch)
Cp1
DSH865U
DSH381+DSH485
2"5/8
1" 5/8
1" 5/8
8556224
Left
30mm(1.18 inch)
Cp1
120Z0788
Right
30mm(1.18 inch)
Cp1
DSH895U
DSH295+DSH600
2"5/8
1" 5/8
1" 5/8
8556250
Left
Not needed
-
120Z0726
Right
DSH970E
DSH485+DSH485
2"5/8
1" 5/8
1" 5/8
8556205
Left
Not needed
-
120Z0785
Right
DSH1085U
DSH485 + DSH600
2"5/8
1" 5/8
1" 5/8
8556248
Left
Not needed
-
120Z0726
Right
38mm(1.5 inch)
Cp2
120Z0821
DSH1200E
DSH600 + DSH600
2"5/8
1" 5/8
2" 1/8
8556247
Left
Not needed
-
120Z0726
Right
Trio model
Composition Cp1 + Cp2
+Cp3
Suction
Dis‐
charge
Oil equaliza‐
tion
Outline drawing number
Suction
from
Washer inner di‐
ameter
Washer in suction of
Trio kit code
DSH420T
DSH140+DSH140 +DSH140
2"1/8
1" 3/8
1" 1/8
8560134
Left
26mm(1.02 inch)
Cp1
120Z0714
25mm(0.98 inch)
Cp3
Right
26mm(1.02 inch)
Cp1
24mm(0.94inch)
Cp3
DSH483T
DSH161+DSH161 +DSH161
2"1/8
1" 3/8
1" 1/8
8560134
Left
26mm(1.02 inch)
Cp1
120Z0714
25mm(0.98 inch)
Cp3
Right
26mm(1.02 inch)
Cp1
25mm(0.98 inch)
Cp3
DSH552T
DSH184+DSH184 +DSH184
2"1/8
1" 3/8
1" 1/8
8560133
Left
26mm(1.02 inch)
Cp1
120Z0714
25mm(0.98 inch)
Cp3
Right
25.5mm(1.00 inch)
Cp1
25mm(0.98 inch)
Cp3
DSH720T
DSH240+DSH240+DSH240
2"5/8
1" 5/8
1" 5/8
8556217
Left
30 mm(1.18 inch)
Cp3
120Z0784
Right
34.5 mm(1.36 inch)
Cp1 & Cp3
120Z0794
DSH885T
DSH295+DSH295+DSH295
2"5/8
1" 5/8
1" 5/8
8556217
Left
30 mm(1.18 inch)
Cp3
120Z0784
Right
34.5 mm(1.36 inch)
Cp1 & Cp3
120Z0794
DSH971T
DSH295+DSH295+DSH381
2"5/8
1" 5/8
1" 5/8
8556317
Left
Not needed
-
120Z0790
Right
Not needed
-
120Z0790
DSH1140T
DSH381+DSH381+DSH381
2"5/8
1" 5/8
1" 5/8
8556229
Left
31 mm(1.22 inch)
Cp1
120Z0783
29 mm(1.14 inch)
Cp3
Right
31 mm(1.22 inch)
Cp1
120Z0782
DSH1245T
DSH381+DSH381 +DSH485
2"5/8
2" 1/8
1" 5/8
8556234
Left
29 mm(1.14 inch)
Cp1
120Z0789 Right
29 mm(1.14 inch)
Cp1
DSH1350T
DSH485+DSH485 +DSH381
3"1/8
2" 1/8
1" 5/8
8556235
Left
29 mm(1.14 inch)
Cp3
120Z0789 Right
29 mm(1.14 inch)
Cp3
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Trio models
Table 20: Trio models
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 34
1 2
CC-000034
12Organ pipe
Tightening torque 100Nm
Supplied with the compressor
Included in tandem kit
Trio model
Composition Cp1 + Cp2
+Cp3
Suction
Dis‐
charge
Oil equaliza‐
tion
Outline drawing number
Suction
from
Washer inner di‐
ameter
Washer in suction of
Trio kit code
DSH1455T
DSH485+DSH485+DSH485
3"1/8
2" 1/8
1" 5/8
8556216
Left
33 mm(1.3 inch)
Cp2 & Cp3
120Z0793 Right
29 mm(1.14 inch)
Cp3
DSH1570T
DSH485+DSH485+DSH600
3"1/8
2" 1/8
1" 5/8
8556246
Left
36mm(1.42 inch)
Cp3
120Z0822
Right
36mm(1.42 inch)
Cp3
120Z0822
DSH1685T
DSH485+DSH600+DSH600
3"1/8
2" 1/8
1" 5/8
8556245
Left
42mm (1.65 inch)
Cp2
120Z0819
Right
41mm (1.61 inch)
Cp3
120Z0820
DSH1800T
DSH600+DSH600+DSH600
3"1/8
2" 1/8
1" 5/8
8556244
Left
Not needed
-
120Z0712 Right
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Oil equalization design DSH180E to DSH368E
The oil level is balanced by a pipe of 1"1/8 oil equalization line.
In order ensure best oil balance, the organ pipe need to be mounted inside the oil equalization port as indicated on below picture. To connect the equalization line on rotolock connections, the organ pipe adaptor and teon gasket are included in the tandem kit must be used.
The organ pipe needs to be installed in the direction indicated by the label attached on pipe surface, which will
ensure best oil balance.
Oil equalization design DSH360X-424X-456X-479X-565X
The oil level is balanced by a pipe of 1"3/8 oil equalization line.
In order to ensure best oil balance, the organ pipe need to be mounted inside the DSH120, 161 or 184 oil equalization port as indicated on below picture. DSH240, 295 or 381 has integrated organ pipe inside the oil equalization port.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 35
1 2
CC-000032
3
CC-0000333CC-000033
3
Tightening torque 145Nm
Supplied with the compressor
Included in tandem kit
123
Organ pipe
Tightening torque 100Nm
Tightening torque 145Nm
Supplied with the compressor
Included in tandem kit
Scroll compressors, DSH090 to DSH600 | Mechanical connections
To connect the equalization line on rotolock connections, the organ pipe, adaptor sleeves, Teon gaskets included in the tandem accessory kit must be used.
Figure 37: For DSH120, DSH161 or DSH184
Figure 38: DSH240, DSH295 or DSH381
Oil equalization design DSH482-535, DSH590 to DSH1800
The oil level is balanced by a pipe of 1"3/8 or 1"5/8. To connect the equalization line on rotolock connections, the adaptor sleeves included in the tandem or trio accessory kit must be used.
Figure 39: DSH482-535, DSH590 to DSH1800
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 36
4
1
2
3
CC-0031
1234Terminal box
Ø 29mm (φ1.14inch) knockout
Ø 25.5mm (φ1inch) knockout
Power supply
3
2
1
CC-0400
123
Ø 16.5mm (φ0.65inch) knockout
Ø 40.5mm (φ1.59inch) hole
Power supply
Scroll compressors, DSH090 to DSH600 | Electrical connections

Electrical connections

Wiring connections

According to compressor model, electrical power is connected to the compressor terminals either by 4.8mm (10-32) screws or by M5 studs and nuts. In both cases the maximum tightening torque is 3 Nm.
Cable gland or similar protection component must be used on electrical box's knockouts to against accidental
contact with electrical parts inside.
DSH090-105-120-140-161 (*except DSH140-161 code3)
The terminal box is provided with a Ø 25.5mm (φ1 inch) (ISO25) and a Ø 29mm (φ1.14) (PG21) knockouts.
Figure 40: Wiring connections for DSH090-105-120-140-161 (*except DSH140-161 code3)
DSH140-161 code3 & DSH184
The terminal box is provided with a Ø 40.5mm (φ1.59inch) hole (ISO40) for power supply and a Ø 16.5mm (φ0.65inch) knockout (ISO16).
Figure 41: Wiring connections for DSH140-161 code3 & DSH184
DSH240-295-381*-485* -600 (*except code 3)
The terminal box is provided with 2 triple knockouts and 1 single knockout for power supply and 4 double knockouts for the safety control circuit.
The 3 power supply knockouts accommodate the following diameters:
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 37
2
3
1
8
6
7
4
3
2
1
5
L1
L N S1 S2 M1M2
L2 L3
CC-0517
12345678Black
Blue
Brown
M1, M2 Control circuit
Module power supply
Sump heater
Faston 1/4" tabs
Power supply
L1
L N S1 S2 M1M2
L2 L3
9
7
8
5
3 4
2
1
6
CC-0420
123456789
Cover holding screws (x3). Torque 2.2 Nm
Black
Blue
Brown
Sump heater
M1, M2 Control circuit
Power supply
Terminal box
Power supply
Scroll compressors, DSH090 to DSH600 | Electrical connections
• Ø 50.8mm (φ 2inch) (UL 1"1/2 conduit) & Ø 43.7mm (φ 1.72inch) (UL 1"1/4 conduit) & Ø 34.5mm (φ 1.36 inch) (UL 1" conduit)
• Ø 40.5mm (φ 1.59inch) (ISO40) & Ø 32.2mm (φ 1.27inch) (ISO32) & Ø 25.5 mm (φ 1 inch) (ISO25)
• Ø 25.5 mm (φ 1 inch) (ISO25)
The 4 others knockouts are as follows:
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2") & Ø 16.5mm (φ 0.65inch) (ISO16) (x2)
• Ø 20.7mm (φ 0.81inch) (ISO20 or PG13.5) (x2)
Figure 42: Wiring connections for DSH240-295-381*-485* -600 (*except code 3)
DSH381 code 3
The terminal box is provided with:
• Ø 50.5mm (φ 1.98inch) (ISO 50 & UL1"1/2 conduit) hole with possible Ø 63.5mm (φ 2.5inch) (ISO63 and UL 2"conduit) knockout for power supply
• 2 x Ø 22.5mm (φ 0.89inch) (PG16 and UL 1/2" conduit) knockouts for safety control circuit.
Figure 43: Wiring connections for DSH381 code 3
DSH485 code 3
The terminal box is provided with 2 triple knockouts for power supply, 2 double knockouts and 3 simple knockouts for the safety control circuit.
The 2 power supply knockouts accommodate the following diameters:
• Ø 63.5mm (φ 2.5inch) (ISO63 and UL 2"conduit) & Ø 54.2mm (φ 2.13inch) (PG42)& 43.7mm (UL 1"1/4 conduit)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 38
2
2
2
1
CC-000013
12M1, M2 Control circuit
Power supply
L N S1 S2 M1 M2
L1 L2 L3
2
3 4
5
1
CC-0035
12345
Phase sequence input
Internal control contact
Safety circuit
Thermistor connection
Module power
Frequency
Motor voltage code
Code 3
Code 4
Code 7
Code 9
50 Hz
Nominal voltage
-
380-415V-3ph
-
-
60 Hz
Nominal voltage
208-230V-3ph
460V-3ph
575V-3ph
380-400V-3ph
380V-3ph
(1)
Scroll compressors, DSH090 to DSH600 | Electrical connections
The 5 other knockouts are as follows:
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2") & Ø 16.5mm (φ 0.65 inch) (ISO16)
• Ø 25.5mm (φ 1inch) (ISO25) & 20mm (φ 0.79inch) (ISO20 or PG13.5)
• Ø 22.5mm (φ 0.89inch) (PG16) (UL 1/2")
• Ø 25.5mm (φ 1inch) (ISO25) (x2)
Figure 44: Wiring connections for DSH485 code 3
Motor protection module
The motor protection modules come preinstalled within the terminal box. Phase sequence protection connections and thermistor connections are pre-wired and should not be removed.
The module must be connected to a power supply of the appropriate voltage. The module terminals are 6.3mm (0.25inch) size Faston type.
Figure 45: Motor protection module
Electrical Specications
Motor voltage
Danfoss scroll compressors DSH are available in four dierent motor voltages as listed below.
Table 21: Motor voltage
(1)
(1)
DSH240-9 and DSH381
DSH240-9 and DSH381
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 39
Vavg
V1-2
V1-3
V2-3
Mean voltage of phases 1, 2, 3.
Voltage between phases 1 and 2.
Voltage between phases 1 and 3.
Voltage between phases 2 and 3.
Compressor model
LRA
RLA
Max. operating current
Winding resistance
AAA
Ω
DSH090
2033138
0.39
DSH105
2673645
0.27
DSH120
2674448
0.27
DSH140
3044656
0.24
DSH161
3154964
0.22
DSH184
3515471
0.22
DSH240
48575103
0.16
DSH295
56087112
0.13
DSH381
717
110
152
0.09
DSH485
761
143
185
0.07
Scroll compressors, DSH090 to DSH600 | Electrical connections
NOTE:
Voltage range: Nominal voltage ± 10%. The voltage range indicates where the compressor can run in the majority of the application envelope. A boundary voltage supply which accumulates under specic conditions such as high ambiance, high superheat, or map boundary conditions, may lead to a compressor trip.
Voltage imbalance
The maximum allowable voltage imbalance is 2%. Voltage imbalance causes high amperage over one or several phases, which in turn leads to overheating and possible motor damage. Voltage imbalance is given by the formula:
%  voltageimbalance = 
|  Vavg   V12  | + |  Vavg   V13  | + |  Vavg   V23  |
2×Vavg
×100
IP rating
The compressor terminal box according to IEC60529 is IP54 for all models when correctly sized IP54 rated cable glands are used.
First numeral, level of protection against contact and foreign objects
5 - Dust protected
Second numeral, level of protection against water
4 - Protection against water splashing
Terminal box temperature
The temperature inside the terminal box must not exceed 70°C (158°F). Consequently, if the compressor is installed in an enclosure, precautions must be taken to avoid that the temperature around the compressor and in the terminal box would rise too much. A ventilation installation on the enclosure panels may be necessary. If not, the electronic protection module may not operate properly. Any compressor damage related to this will not be covered by Danfoss warranty. In the same manner, cables must be selected in a way that ensures the terminal box temperature does not exceed 70°C (158°F).
Three phase electrical characteristics
Table 22: Motor voltage code 3
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 40
Compressor model
LRA
RLA
Max. operating current
Winding resistance
AAA
Ω
DSH0909816191.47
DSH105
1421822
1.05
DSH120
1422124
1.05
DSH140
1472128
0.92
DSH161
1582531
0.83
DSH184
1972836
0.83
DSH240
2153349
0.62
DSH295
2604456
0.52
DSH381
2945072
0.45
DSH485
3447691
0.28
DSH600
42780116
0.23
Compressor model
LRA
RLA
Max. operating current
Winding resistance
AAA
Ω
DSH0908413142.34
DSH105
1031617
1.57
DSH120
1031719
1.57
DSH140
1221922
1.38
DSH161
1362124
1.32
DSH184
1352528
1.32
DSH240
1752838
0.94
DSH295
2103144
0.82
DSH381
2354058
0.56
DSH485
2965571
0.36
DSH600
3387091
0.38
Compressor model
LRA
RLA
Max. operating current
Winding resistance
AAA
Ω
DSH090
1241923
1.05
DSH105
1602426
0.72
DSH120
1602529
0.72
DSH140
1682633
0.62
DSH161
1772937
0.57
DSH184
2393641
0.57
DSH240
2604158
0.42
DSH295
3104769
0.36
DSH381
3826088
0.24
DSH485
47583109
0.16
Scroll compressors, DSH090 to DSH600 | Electrical connections
Table 23: Motor voltage code 4
Table 24: Motor voltage code 7
Table 25: Motor voltage code 9
LRA (Locked Rotor Amp)
Locked Rotor Amp value is the higher average current as measured on mechanically blocked compressors tested under nominal voltage. The LRA value can be used as a rough estimation for the starting current. However, in most cases, the real starting current will be lower. A soft starter can be applied to reduce starting current (see section Soft
starts).
RLA (Rated Load Amperage)
The RLA values presented are simply calculated by dividing the maximum current before tripping at overload test conditions by 1.4.
MOC (Maximum Operating Current)
The max operating current is the amperage the compressor will draw when it operates at maximum load of operating envelope within the voltages printed on the nameplate.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 41
t
25°CtambR25°C (77°F)
R
amb
a
reference temperature = 25°C (77°F)
temperature during measurement °C (°F)
winding resistance at 25°C (77°F)
winding resistance at tamb
Coecient a = 234.5
Scroll compressors, DSH090 to DSH600 | Electrical connections
MOC can be used as a basis for contactors selection.
Winding resistance
Winding resistance is the resistance between phases at 25°C (77°F) (resistance value +/- 7%). Winding resistance is generally low and it requires adapted tools for precise measurement. Use a digital ohm-meter, a “4 wires” method and measure under stabilised ambient temperature. Winding resistance varies strongly with winding temperature. If the compressor is stabilised at a dierent value than 25°C (77°F), the measured resistance must be corrected using the following formula:
R
tamb
 = R
25°C(77°F)
a + t
a + t
amb
25°C(77°F)
Motor protection
DSH090 to DSH184
Compressor models DSH 090 to 184 are provided with internal overload motor protection to prevent against excessive current and temperature caused by overloading, low refrigerant ow or phase loss.
The protector is located in star point of motor and, should it be activated, will cut out all three phases. It will be reset automatically.
While not compulsory, an additional thermal magnetic motor circuit breaker is still advisable for either alarm or manual reset.
Then it must be set at the Max Operating Current value (MOC):
• When the motor temperature is too high, then the internal protector will trip.
• When the current is too high the thermal magnetic motor circuit breaker will trip before the internal protection therefore oering possibility of manual reset.
DSH240 to DSH600
Compressor models DSH240-295-381-485-600 are delivered with a pre-installed motor protection module inside the terminal box. This device provides ecient and reliable protection against overheating and overloading as well as phase loss/reversal.
The motor protector comprises a control module and PTC sensors embedded in the motor winding.
The motor temperature is being constantly measured by a PTC thermistor loop connected on S1-S2 . If any thermistor exceeds its response temperature, its resistance increases above the trip level (4.500 Ω) and the output relay then trips – i.e. contacts M1-M2 are open. After cooling to below the response temperature (resistance < 2.750 Ω), a 5-minute time delay is activated.
After this delay has elapsed, the relay is once again pulled in – i.e. contacts M1-M2 are closed. The time delay may be cancelled by means of resetting the mains (L-N -disconnect) for approximately 5 sec.
A red/green twin LED is visible on the module (except on DSH485-3). A solid green LED denotes a fault free condition. A blinking red LED indicates an identiable fault condition:
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 42
460 ms
1s*
40 ms 460 ms40 ms
1s*
80 ms 920 ms
Cp
Ph
0 1s 6s
St
CpPhSt
Compressor
Phase monitoring
start*approx. 1 second
Scroll compressors, DSH090 to DSH600 | Electrical connections
Figure 46: PTC Overheat
While not compulsory, an additional thermal magnetic motor circuit breaker is still advisable for either alarm or manual reset.
Then it must be set at the Max Operating Current value (MOC) :
• When the motor temperature is too high, then the internal PTC over temp. and module is activated.
• When the current is too high the thermal magnetic motor circuit breaker will trip before the module activate therefore oering possibility of manual reset.
Figure 47: Delay timer active (after PTC over temp.)
Phase sequence and reverse rotation protection
Use a phase meter to establish the phase orders and connect line phases L1, L2 and L3 to terminals T1, T2 and T3, respectively.
DSH090 to DSH184
Compressor models DSH 090 to 184 incorporates an internal reverse vent valve which will react when the compressor is run in reverse and will allow refrigerant to circulate through a by-pass from the suction to the discharge. Although reverse rotation is not destructive for these models, it should be corrected as soon as possible. Repeated reverse rotation over 24 hours may have negative impact on the bearings.
Reverse rotation will be obvious to the user as soon as power is turned on: the compressor will not build up pressure, the sound level will be abnormally high and power consumption will be minimal. If reverse rotation symptoms occur, shut the compressor down and connect the phases to their proper terminals. If reverse rotation is not halted, the compressor will cycle o-on the motor protection.
DSH240 to DSH600
Use a phase meter to establish the phase orders and connect line phases L1, L2 and L3 to terminals T1, T2 and T3, respectively.
Compressor models DSH 240 to 600 are delivered with an electronic module which provides protection against phase reversal and phase loss at start-up.
The phase sequencing and phase loss monitoring functions are active during a 5-sec window 1 second after compressor start-up (power on L1-L2-L3).
Figure 48: Phase sequence module logic
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 43
760 ms*
120 ms 400 ms120 ms 120 ms
1 s*
500 ms 500 ms
*
Approximate
Scroll compressors, DSH090 to DSH600 | Electrical connections
Should one of these parameters be incorrect, the relay would lock out (contact M1-M2 open). The red LED on the module will show the following blink code (except on DSH485-3):
Figure 49: In case of phase reverse error
Figure 50: In case of phase loss error:
The lockout may be cancelled by resetting the power mains (disconnect L-N) for approximately 5 seconds.
For more detailed information see “ Instructions for electronic module” AN160986418236.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 44
1.
2.
3.
1.
2.
3.
1.
2.
Split type
Single compressor
Manifold compressors
Non split
Test No.1
Test No.1+2
Split
Test No.1+3
Test No.1+2+3
Test No.
Purpose
Test conditions
Pass criteria
Solutions
1
Check proper oil return
A
Lowest foreseeable evaporation, and highest foreseeable condensation. Minimum number of compressor run­ning for 6 hours. For reversible system, perform test in both heating and cooling mode.
Oil level must be visible or full in the sight glass when the compressor is run­ning and when all compressors of the circuit are stopped.
Top-up with oil, generally 3% of the total system refrigerant charge (in weight). Above 3% look for poten­tial oil trap in the system. Integrate a function in control logic to run all compressors simultane­ously in order to boost oil return (for more details see section Con­trol logic) Oil separator can be added
2
Check oil balanc­ing
A
Lowest foreseeable evaporation and highest foreseeable condensation and nominal capacity condition for tandem 2 compressors running for 6 hours, for trio, compressor running fol­low the running sequence: (1+2+3)2hrs (1+2)2hrs (2+3)2hrs (1+3)2hrs For reversible system, perform test in both heating and cooling mode.
Oil level must be visible or full in the sight glass when the compressors are running and when all compressors of the circuit are stopped
Top-up with oil, generally 3% of the total system refrigerant charge (in weight). Check that manifold piping is con­form to Danfoss requirements. Integrate a function in control logic to stop manifold periodically in or­der to balance oil (for more details see section Control logic)
3
Oil return in split systems
Since each installation is unique, test 1 and 2 can not fully validate the oil re­turn. Oil level must be checked and ad­justed at commissioning.
Oil level must be visible or full in the sight glass when the compressor is run­ning and when all compressors of the circuit are stopped.
Pay special attention to “Piping de­sign” Oil separator is strongly recommen­ded, espacially in case of part load.
Scroll compressors, DSH090 to DSH600 | Application

Application

Manage oil in the circuit

Requirement
Oil level must be visible or full in the sight glass when the compressor is running and when all compressors of
the circuit are stopped. For DSH140-184 medium trio models, top-up oil quantity 1L at least as mandatory.
System evaluation
Table 26: Manage oil in the circuit - System evaluation
Test, criteria and solutions
Table 27: Manage oil in the circuit - Test, criteria and solutions

Manage sound and vibration

Sound radiations
Mitigations methods: We can consider two means to reduce compressors sound radiations:
1.
Acoustic hoods are quick and easy to install and do not increase the overall size of the compressors. Acoustic hoods are available from Danfoss as accessories. Refer to the tables above for sound levels, attenuation and code numbers.
2.
Use of sound-insulation materials on the inside of unit panels is also an eective mean to reduce sound radiation.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 45
Scroll compressors, DSH090 to DSH600 | Application
NOTE:
During compressor shut down, a short reverse rotation sound is generated. The duration of this sound depends on the pressure dierence at shut down and should be less than 3 seconds. This phenomenon has no impact on compressor reliability.
Gas pulsation
The compressor has been designed and tested to ensure that gas pulsation is optimized for the most commonly encountered air conditioning pressure ratio. Manifolded compressors are equivalents to lagged sources of gas pulsation. Therefore, pulse level can vary during time.
Mitigations methods: If an unacceptable level is identied, a discharge muer with the appropriate resonant volume and mass can be installed.
Mitigation Methods
1.
To ensure minimum vibrations transmission to the structure, strictly follow Danfoss mounting requirements (mounting feet, rails etc..). For further information on mounting requirements, please refer to section Design
compressor mounting.
2.
Ensure that there is no direct contact (without insulation) between vibrating components and structure.
3.
To avoid resonance phenomenon, pipings and frame must have natural frequencies as far as possible from running frequencies(50 or 60 Hz). Solutions to change natural frequencies are to work on structure stiness and mass (brackets, metal sheet thickness or shape…)

Manage Operating envelope

The Operating envelope for DSH scroll compressors guarantees reliable operations of the compressor for steady-
state operation.
Steady-state operation envelope is valid for a suction superheat within 5K to 30K range at nominal Voltage.
High and low pressure protection
Low-pressure (LP) and high-pressure (HP) safety switches must never be bypassed nor delayed and must stop all
the compressors.
LP switch auto restart must be limited to 5 times within 12 hours.
HP safety switch must be reset manually.
Depending on application operating envelope, you must dene HP and LP limits within operating envelope and pressure setting table above.
Discharge temperature protection
DSH240 to DSH600 include an integrated discharge temperature protection. Excessive discharge temperature will result in tripping of electronic module ouput relay.
This protection, eective for suction superheat above 5K (9°), should be considered as a compressor safety device and its purpose is not to ensure operation map control.
In case of basic map control by pressure switches that can not ensure totally that the compressor will remain in its operating envelope, an additionnal external discharge protection is required. (see below Figure 51: Discharge
temperature protection examples)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 46
3
2
1
4
CC-0056
1234Thermostat or temperature sensor
Discharge line
Bracket
Insulation
Condensing temperature (°C)
Condensing temperature (°F)
Evaporating temperature (°C)
Evaporating temperature (°F)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
41
50
59
68
77
86
95
104
113
122
131
140
149
158
-35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30
-31 -22 -13 -4 5 14 23 32 41 50 59 68 77 86
Example 2
LP2
DGT - limit
LP1
R410A
Example 1
HP1
HP2
CC-000165
Scroll compressors, DSH090 to DSH600 | Application
Figure 51: Discharge temperature protection examples
Example 1 (R410A, SH = 11K) LP switch setting: LP1 = 3.8 bar (g) (-15°C), HP switch setting: HP1 =38 bar (g) (62°C) Risk of operation beyond the application envelope. DGT protection required.
Example 2 (R410A, SH = 11K) LP switch setting: LP2 = 4.7 bar (g) (-10°C), HP switch setting: HP2 = 31 bar (g) (52°C) No risk of operation beyond the application envelope. No DGT protection required.
DSH090 to 184 have no integrated discharge temperature protection, an external protection is required.
This external protection device can be a thermostat or a temperature sensor. The discharge gas temperature protection must trip the power supply when it reaches the setting point to protect the compressor from overheating.
For R410A application the discharge gas protection should be set to open at a maximum discharge gas temperature of 135°C(275°F). The discharge gas thermostat accessory kit (code 7750009) is recommended.
For R452B/R454B application, the discharge gas protection should be set to open at a maximum discharge gas temperature of 150°C(302°F). A PT1000 is recommended.
The discharge gas thermostat or sensor must be attached to the discharge line within 150mm (5.91 inch) from the compressor discharge port and must be thermally insulated and tightly xed on the pipe (see Figure 52: Discharge
Gas Temperature protection (DGT))
Figure 52: Discharge Gas Temperature protection (DGT)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 47
Basic
Advanced
• HP and LP switch
• MOP (Max Operating Pressure) ensured by expansion device
• Condensing pressure control
• DGT external setting points: R410A max 135°C (275°F), R454B/R452B max 150°C (302°F)
• HP and LP sensor
• Operating envelope limits integrated into control logic
• Temperature measurement (monitoring by sensor)
HP switch setting
CC-000166
Condensing pressure control
MOP < Max evap T°
LP switch setting
tests No1 and 2
DGT
Whole operating envelope limits integrated into control logic
CC-000192
Application
Tests to perform
Non reversible
Liquid
ood back test
Reversible
Liquid
ood back test
Defrost test
Scroll compressors, DSH090 to DSH600 | Application
System evaluation
HP and LP must be monitored to respect operating envelope limitation. We consider two types of operating envelope management: Basic and Advanced.
Table 28: System evaluation

Manage superheat

During normal operation, refrigerant enters the compressor as a superheated vapor. Liquid ood back occurs when a part of the refrigerant entering the compressor is still in liquid state.
Liquid ood back can cause oil dilution and, in extreme situations lead to liquid slugging that can damage the compressor.
Requirement
In steady state conditions the expansion device must ensure a suction superheat within 5K to 30K (9 to 54°F).
System evaluation
Use the table in relation with the application to quickly evaluate the potential tests to perform.
Table 29: System evaluation
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 48
1
CC-000023
1
Oil temperature sensor must be placed on the bottom of the baseplate.
1.
2.
1.
2.
Test
Purpose
Test condition
Pass criteria
Solutions
Liquid ood back test
Steady-state
A
Liquid ood back testing must be carried out under expansion valve threshold operating conditions:
• Lowest foreseeable evaporation, and highest foreseeable condensation.
• Minimum number of compressor running.
For reversible system, perform test in both heating and cooling mode.
Suction superheat >5K (9°F) and the oil superheat shall not be more than 60 sec below the safe limit dened in the Dilu­tion Chart. (see Dilution Chart -
DSH090 to DSH184 R410A)
Check expansion valve se­lection and setting.
For Thermostatic ex-
pansion valve (TXV ) check bulb position...
For Electronic expan-
sion valve (EXV) check measurement chain
and PID....
Add a suction accumulator
(1)
Transient
Tests must be carried out with most unfavorable conditions :
• fan staging,
• compressor staging
• …
Oil superheat shall not be more than 60 sec per hour below the safe limit dened in the Dilu­tion Chart. (see Dilution Chart -
DSH090 to DSH184 R452B / R454B)
Defrost test
Check liquid oodback dur­ing defrost cy­cle
Defrost test must be carried out in the most unfavorable condi­tions (at 0°C (32°F) evaporating temperature).
Oil superheat shall not be more than 60 sec per hour below the safe limit dened in the Dilu­tion Chart. (see Dilution Chart -
DSH240 to DSH600 R410A/ R452B / R454B)
Check defrost logic. In re­versible systems, the de­frost logic can be worked out to limit liquid ood- back eect. (for more de­tails see Control logic). Add a suction accumulator
(1)
Scroll compressors, DSH090 to DSH600 | Application
Test, criteria and solutions
Table 30: Test, criteria and solutions
(1)
(1)
Suction accumulator oers protection by trapping the liquid refrigerant upstream from the compressor. The accumulator should be sized at
Suction accumulator oers protection by trapping the liquid refrigerant upstream from the compressor. The accumulator should be sized at least 50 % of the total system charge. Suction accumulator dimensions can impact oil return (gas velocity, oil return hole size…), therefore oil
least 50 % of the total system charge. Suction accumulator dimensions can impact oil return (gas velocity, oil return hole size…), therefore oil return has to be checked according to section Manage oil in the circuit.
return has to be checked according to section Manage oil in the circuit.
Placing oil temperature sensor
Oil temperature sensor must be placed on the bottom of the baseplate. Some thermal paste shall be used to improve the conductivity. The sensor must also be correctly thermally insulated from the ambiance.
The Oil superheat is dened as: (Oil temperature - Evaporating temperature)
Figure 53: Placing oil temperature sensor
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 49
22.5
25
20
17.5
15
12.5
10
7.5
5
-25-30 -20 -15 -10 -5 0 5 10 15 20 25
-13-22 -4 5 14 23 32 41 50 59 68 77
2.5
0
40.5
45
36
31.5
27
22.5
18
13.5
9
4.5
0
Unsafe Area (60 sec max per hour)
Safe Area
Evaporating Temperature (°C)
Evaporating Temperature (°F)
Oil Superheat (K)
Oil Superheat (°F)
CC-000024
22.5
25
20
17.5
15
12.5
10
7.5
5
-25-30 -20 -15 -10 -5 0 5 10 15 20 25
-13-22 -4 5 14 23 32 41 50 59 68 77
2.5
0
40.5
45
36
31.5
27
22.5
18
13.5
9
4.5
0
Unsafe Area (60 sec max per hour)
Safe Area
Evaporating Temperature (°C)
Evaporating Temperature (°F)
Oil Superheat (K)
Oil Superheat (°F)
CC-000025
Scroll compressors, DSH090 to DSH600 | Application
Dilution Chart - DSH090 to DSH184 R410A
Figure 54: Dilution Chart (reference at 20°C / 68°F ambient temperature)
Dilution Chart - DSH090 to DSH184 R452B / R454B
Figure 55: Dilution Chart (reference at 20°C / 68°F ambient temperature)
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 50
15
12.5
10
7.5
5
-25-30 -20 -15 -10 -5 0 5 10 15 20 25
-13-22 -4 5 14 23 32 41 50 59 68 77
2.5
0
27
22.5
18
13.5
9
4.5
0
CC-000026
Evaporating Temperature (°F)
Safe Area
Unsafe Area (60 sec max per hour)
Evaporating Temperature (°C)
Oil Superheat (K)
Oil Superheat (°F)
Application
BELOW charge limit
ABOVE charge limit
All
Ensure tightness between condenser & evaporator when system is OFF
• Thermostatic expansion Valve (TXV) , Liquid Line Solenoid Valve LLSV strongly recommended
• Electronic expansion valve (EXV) must close when system stop including in power shut down situation
Non split
No test or additional safeties required
• Surface Sump Heater
Split
Since each installation is unique, refrigerant charge may vary
• Surface Sump Heater
• Liquid Line Solenoid Valve+ pump-down cycle
Scroll compressors, DSH090 to DSH600 | Application
Dilution Chart - DSH240 to DSH600 R410A/ R452B / R454B
Figure 56: Dilution Chart (reference at 20°C / 68°F ambient temperature)
Manage o cycle migration
O -cycle refrigerant migration happens:
• when the compressor is located at the coldest part of the installation, refrigerant vapor condenses in the compressor.
• or directly in liquid-phase by gravity or pressure dierence. When the compressor restarts, the refrigerant diluted in the oil, or stored in evaporator, generates poor lubrication conditions, and may reduce bearings life time. In extreme situations, this leads to liquid slugging that can damage the compressor scroll set.
Requirement
• Compressor can tolerate occasional ooded start, but it should remain exceptional situation and unit design must prevent that this situation happen at each start.
• Right after start, liquid refrigerant must not ow massively to compressor
• The charge limit is a threshold beyond some protective measures must be taken to limit risk of liquid slugging and extreme dilution at start.
System evaluation
Use the table below in relation with the system charge and the application to quickly dene necessary safeties to implement.
Table 31: System charge
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 51
Compressor Surrounding Ambient
Surface Sump Heater
Unit has enclosure, no wind
48W SSH
Unit has no enclosure, with wind
80W SSH
Unit has no enclosure, wind >5m/s (ft/s)& ambient temperature <-5°C
80W SSH + additional SSH/thermal insulation
Scroll compressors, DSH090 to DSH600 | Application
Surface Sump heater
The surface sump heater are designed to protect the compressor against o-cycle migration of refrigerant.
For DSH090-105-120-140-161-184, the surface sump heater is located on the compressor shell. For better standby energy consumption, Danfoss provides 48W and 80W two optional surface sump heater. The selection of surface sump heater could be refered to Table 32: surface sump selection principle
Figure 57: DSH090 to 184
Table 32: surface sump selection principle
For DSH240-295-381-485-600, the 56W surface sump seater is located below the sump, associated with a thermal insulation.
Figure 58: DSH240 to DSH485
The heater must be turned on whenever all the compressors are o. Surface sump heater accessories are available from Danfoss (see section Accessories and Spare parts).
Liquid line solenoid valve (LLSV)
A Liquid line solenoid valve (LLSV) is used to isolate the liquid charge on the condenser side, thereby preventing against charge transfer to the compressor during o -cycles. The quantity of refrigerant on the low-pressure side of the system can be further reduced by using a pump-down cycle in association with the LLSV.
Pump-down cycle
By decreasing pressure in the sump, pump down system:
• evacuates refrigerant from oil
• set the sump saturating pressure much lower than ambiance temperature and due to that, avoid refrigerant condensation in the compressor.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 52
Models
Composition
Refrigerant charge limit
kg
lbs
DSH090-818DSH105-1022DSH120-1022DSH140-1022DSH161-1022DSH184-1022DSH240-1533DSH295-1533DSH381-1737DSH485-1737DSH600-17
37
Models
Composition
Refrigerant charge limit
kg
lbs
DSH180E
2×DSH0901226
DSH195U
DSH090 + DSH105
1226DSH210U
DSH090 + DSH120
1226DSH210E
2×DSH1051226
DSH230U
DSH090 + DSH140
1226DSH240E
2×DSH1201226
DSH251U
DSH090 + DSH161
1226DSH260U
DSH140 + DSH120
1226DSH274U
DSH090 + DSH184
1226DSH281U
DSH161 + DSH120
1226DSH280E
2×DSH1401431
DSH289U
DSH105 + DSH184
1226DSH301U
DSH161 + DSH140
1431DSH304U
DSH120 + DSH184
1226DSH322E
2×DSH1611431
DSH324U
DSH140 + DSH184
1431DSH345U
DSH161 + DSH184
1431DSH368E
2×DSH1841431
DSH360X
DSH120 + DSH240
1431DSH424X
DSH184 + DSH240
1431DSH456X
DSH161 + DSH295
1431DSH479X
DSH184 + DSH295
1431DSH565X
DSH184 + DSH381
1431DSH482E
2×DSH2402146
DSH535U
DSH240 + DSH295
2146DSH590E
2×DSH2952555
DSH620U
DSH240 + DSH381
2146DSH675U
DSH295 + DSH381
2555DSH760E
2×DSH3812964
DSH725U
DSH240 + DSH485
2146DSH780U
DSH295 + DSH485
2555DSH865U
DSH381 + DSH485
2964DSH895U
DSH295 + DSH600
2555DSH970E
2×DSH4853475
DSH1085U
DSH485 + DSH600
3475DSH1200E
DSH600 + DSH600
44
97
Scroll compressors, DSH090 to DSH600 | Application
Pump-down must be set higher than 1.7bar(g) (25 psig). For more details on pump-down cycle see section Control logic.
Charge limits
Table 33: Charge limits for single models
Table 34: Charge limits for Tandem models
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 53
Models
Composition
Refrigerant charge limit
kg
lbs
DSH420T
3×DSH1401431
DSH483T
3×DSH1611431
DSH552T
3×DSH1841431
DSH720T
3×DSH2402146
DSH885T
3×DSH2952555
DSH971T
2×DSH295 + DSH381
2555DSH1140T
3×DSH3812964
DSH1245T
2×DSH381 + DSH485
2964DSH1350T
DSH381 + 2×DSH485
2964DSH1455T
3×DSH4853475
DSH1570T
2×DSH485 + DSH600
3475DH1685T
DSH485 + 2×DSH600
3475DSH1800T
3×DSH6004497
Scroll compressors, DSH090 to DSH600 | Application
Table 35: Charge limits for Trio models

Power supply and electrical protection

Wiring information Requirements
Protect the compressor from short circuit and overcurrent by a thermal magnetic motor circuit breaker set to Max.
• operating current or lower (see table in section Three phase electrical characteristics). For DSH090-105-120-140-161-184, phase sequence protection is strongly recommended.
• Compressor models DSH240-295-381-485-600 are delivered with a pre-installed motor protection module inside the terminal box that must be powered on.
• HP safety switch, DGT (only for DSH090 to DSH184) and electronic module relay output (M1-M2, only for DSH240 to DSH600) must be wired in the safety chain. Other safety devices such as LP can be either hardware or software managed.
• Provide separate electrical supply for the heaters so that they remain energized even when the machine is out of service (e.g. seasonal shutdown).
The wiring diagrams below are examples for a safe and reliable compressor wiring:
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 54
M
DGT
HP
UC
SS CC
F1 F1
KM
CB
Ph
L1L1L3 L2
L3
L2
T1
T3
T2
KM
SSH
LPS
Ph
CC-0036
MPM
S
SSH
CCSS
LPS
KM
CB
F1 F1
HP
L1 L3 L2
KM
T2
M
T1
T3
DGT
UC
CC-0041
Scroll compressors, DSH090 to DSH600 | Application
Figure 59: Compressor model DSH 090 - 105 - 120 - 140 - 161 - 184
Figure 60: Compressor model DSH240-295-381
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 55
CC
SS
LPS
KM
F1 F1
HP
L1 L3 L2
KM
DGT
MPM
CB
UC
M
S
SSH
T2
T1
T3
CC-000020
1
2
3
L1 L3
L2
7
8
9
L1
L3L3
L2
L2
S
L1
MPM
MPM
F1
F1
SS CC
LPS
HP
KM
UC
CB
KM
SSH
CC-000021
Scroll compressors, DSH090 to DSH600 | Application
Figure 61: Compressor model DSH485 (except code 3) and model DSH600
Figure 62: Compressor model DSH485 code 3
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 56
CB
CC
DGT
F1HPKM
LPSMMPM
PhSSS
SSHUCThermal magnetic motor circuit breaker
Control circuit
Discharge gas thermistor (embedded in com-
pressor)
Fuses
High pressure safety switch
Compressor contactor
Safety pressure switch
Compressor motor
Motor Protection Module
Phase sequence relay
Thermistor chain (motor and discharge tem-
perature)
Seprate supply
Surface sump heater
Unit Controller
Safeties
Tripping conditions
Re-start conditions
Value
Time
Value
Time
HP safety switch
See Pressure settings ta­ble from section Operat-
ing envelope data
Immediate, no delay. No by-pass
Conditions back to nor­mal. Switch closed again
Manual reset
LP safety switch
Maximum 5 auto reset during a period of 12 hours, then manual reset.
Electronic module (Motor protection, DGT)
(1)
Contact M1-M2 opened
Scroll compressors, DSH090 to DSH600 | Application
Soft starts
Soft starters are designed to reduce the starting current of 3-phase AC motors. Soft starters can be used on DSH compressor but, in order to ensure proper lubrication of compressor parts, the settings must ensure that the compressor start-up time is always less than 0.5 seconds.
Ramp-down must be set to minimum to ensure proper discharge valve closing.
In case of use with R454B or R452B make sure that the softstarter selected is compatible with A2L refrigerants.

Control logic

Safety control logic requirements
Table 36: Safety control logic requirements
(1)
(1)
Only for DSH240 to DSH600.
Only for DSH240 to DSH600.
Cycle rate limit requirements
Danfoss requires a minimum compressor running time of 2 minutes to ensure proper oil return and sucient motor cooling.
Additionally, compressor must not exceed 12 starts per hour. 12 starts per hour must not be considered as an average, this is the maximum number of starts acceptable to keep a good regulation accuracy during low load.
Oil management logic recommendations
In some cases, oil management can be enhanced by control logic:
• If oil return test failed, a function can be integrated in control logic to run all compressors simultaneously during 2
minutes every hour in order to boost oil return. Time and delay can be ne-tuned by oil return test N°1 in section
Manage oil in the circuit. During oil boost, pay special attention to superheat management to avoid liquid ood
back.
• In trio system, after running long time in same state with 2 or 3 compressors, (1+2+3) or (1+2), (2+3) or (3+1), oil
unbalance may appears. A function can be implemented in control logic to stop all compressors during one minute every two hours in order to balance oil. Time and sequence can be ne-tuned during Oil balancing test in section Manage oil in the circuit.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 57
Cp 1
Cp 2ONH
12345
678
9
1
Cp 1 ON
Cp 2 ON
H
100%
2 65 8 973
4
CC-000019
4WV
EXV
Compressor 1
Compressor 2
On
Heating
Defrost start. Stop all compressors
4 Way Valve (4WV) stays in heating mode. EXV opened to transfer liquid from outdoor to indoor
exchanger thanks to pressure dierence.
When pressures are almost balanced
(1)
, change 4WV to cooling mode.
Start Cp1 and Cp 2 with 0.5 seconds delay between 2 successive starts
Defrost
Defrost end. Stop all compressors
4 WV stays in cooling mode. EXV opened to transfer liquid from indoor to outdoor exchanger thanks to
pressure dierence
When pressures are almost balanced
(1)
, change 4WV to heating mode.
Start Cp1 and Cp 2 with 0.5 seconds delay between 2 successive starts
Scroll compressors, DSH090 to DSH600 | Application
Defrost logic recommendations / Reversible systems
In reversible systems, the defrost logic can be worked out to limit liquid ood back eect by:
1.
Running full load during defrost to share liquid refrigerant between all compressors.
2.
Reducing refrigerant ooding to compressor by transferring liquid refrigerant from one exchanger to the other before reversing valve thanks to pressures.
The following defrost logic combines both advantages:
Figure 63: Defrost logic advantages
In reversible systems, to ensure compressor reliability, the 4-way valve must not reverse when the compressor is stopped due to heating or cooling demand (stop on thermostat).
(1)
(1)
EXV Opening degree and time have to be set to keep a minimum pressure for 4 way valve moving. In any case, defrost logics must respect
EXV Opening degree and time have to be set to keep a minimum pressure for 4 way valve moving. In any case, defrost logics must respect requirements and tests described in sections Manage superheat and Operating envelope data.
requirements and tests described in sections Manage superheat and Operating envelope data.
Pump-down logic recommendations
Pump down is initiated prior to shutting down the last compressor on the circuit by de-energizing a liquid line solenoid valve or closing electronic expansion valve. When suction pressure reached the cut-out pressure, compressor is stopped, and liquid solenoid valve or electronic expansion valve remains closed.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 58
Scroll compressors, DSH090 to DSH600 | Application
Two types of pump-down exist:
• One shot pump down (preferred): when last compressor of the circuit stops, suction presssure is decreased 1.5bar
(22psi) below nominal evaporating pressure with minimum of 1.7bar(g) (25psig). Even if suction pressure increases again, the compressor will not restart.
• Continuous pump-down: traditional pump-down, Compressor restarts automatically when suction pressure
increases up to 4 cycles maximum.
Non Return Valve (NRV)
DSH090 to DSH600 compressors integrate tight internal non return valve (INRV), therefore no external Non Return Valve (NRV) is needed.

Reduce moisture in the system

Excessive air and moisture
• can increase condensing pressure and cause high discharge temperatures.
• can create acid giving rise to copper platting.
• can destroy the lubricating properties of the oil.
All these phenomena can reduce service life and cause mechanical and electrical compressor failure.
Requirements
• The compressors are delivered with < 100ppm moisture level.
• At the time of commissioning, system moisture content may be up to 100ppm.
• During operation, the lter drier must reduce this to a level between 20 and 50ppm.
Solutions
To achieve this requirement, a properly sized and type of drier is required. Important selection criteria’s include:
• driers water content capacity,
• system refrigeration capacity,
• system refrigerant charge.
For new installations of compressors with polyolester oil, Danfoss recommends using the Danfoss DML (100% molecular sieve) solid core lter drier.

Assembly line procedure

Compressor storage
Store the compressor not exposed to rain, corrosive or ammable atmosphere between -35°C (-31°F) and 70°C (158°F) when charged with nitrogen and between -35°C (-31°F) and Ts max value (see section Pressure equipment
directive 2014/68/EU) when charged with refrigerant.
Compressor holding charge
Each compressor is shipped with a nominal dry nitrogen holding charge between 0.3bar (4 psi) and 0.7bar (10psi) and is sealed with elastomer plugs.
Respect the following sequence to avoid discharge check valve gets stuck in open position:
• Remove the suction plug rst
• Remove the discharge plug afterwards
An opened compressor must not be exposed to air for more than 20 minutes to avoid moisture is captured by the POE oil.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 59
HEAVY
do not lift
manually
123
3
2
1
cc-0066
Slings
Spreader bars
Frame
Circuit contamination possible cause:
Requirement:
Brazing and welding oxides
During brazing,
ow nitrogen through the system.
Particles and burrs
Remove any particles and burrs generated by tube cutting and hole drilling.
Moisture and air
Use only clean and dehydrated refrigeration grade copper tubing. Opened compressor must not be exposed to air more than 20 minutes to avoid moisture captured by oil.
Scroll compressors, DSH090 to DSH600 | Application
Handling
Each Danfoss DSH scroll compressor is equipped with two lift rings on the top shell.
• Always use both these rings when lifting the compressor.
• Use lifting equipment rated and certied for the weight of the compressor or compressor assembly.
• A spreader bar rated for the weight of the compressor is highly recommended to ensure a better load distribution.
• The use of lifting hooks closed with a clasp is recommended.
• For tandem and trio assemblies, use a spreader bar and all compressor rings as shown in picture below.
• Never use the lift rings on the compressor to lift the full unit.
Maintain the compressor in an upright position during all handling manoeuvres (maximum of 15° from vertical).
Figure 64: Heavy
Figure 65: Correct Figure 66: Incorrect
Figure 67: Handling
Piping assembly
Good practices for piping assembly is a pre-requisite to ensure compressor life time (system cleanliness, brazing procedure etc.)
Table 37: System cleanliness
Brazing procedure:
• Brazing operations must be performed by qualied personnel.
• Make sure that no electrical wiring is connected to the compressor.
• To prevent compressor shell and electrical box overheating, use a heat shield and/or a heat-absorbent compound.
• Clean up connections with degreasing agent
• Flow nitrogen through the compressor.
• It is recommended to use double-tipped torch using acetylene to ensure a uniform heating of connection.
• For discharge connections brazing time should be less than 2 minutes to avoid NRVI damages if any.
• To enhance the resistance to rust, a varnish on the connection is recommended.
DSH compressors connectors are made of steel copper coated, which benet to protect against corrosion and facilitate adhesion during brazing operation.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 60
CC-0052
1
1
Heat shield
Maximum compressor test pressures
DSH090-105-120-140-161-184
DSH240-295 -381-485-600
Maximum compressor test pressure high side (HP)
53.6 bar (g) (777 psig) HP-LP<37 bar (537 psi)
53.6 bar (g) (777 psig) HP-LP<37 bar (537 psi)
Maximum compressor test pressure low side (LP)
36.7 bar (g) (532 psig) LP-HP<5bar (73psi) Maximum speed 4.8bar/s (70psi/s)
(1)
34.3bar (g) (497psig) LP – HP <5bar (73psi) Maximum speed 4.8bar/s (70psi/s)
(1)
Scroll compressors, DSH090 to DSH600 | Application
As per standards practice in the refrigeration industry, Danfoss Commercial Compressor recommend to use of silver cadmium free solder alloy and ux (added or ux coated rods). The signicant silver content in these brazing alloy will help the brazing operation, providing an excellent uidity and a limited heating temperature. It will bring also a good resistance to corrosion, a proper elongation compatible with system vibration, and good behavior under thermal variation improving the strength of connection and limiting fractures and refrigerant leaks. (Crucial with A2L refrigerants) A typical content of 34% Ag (Silver) is recommended by Danfoss.
The use of self-ux alloys (as phosphorous alloys) is not recommended by Danfoss. This type of brazing require a higher working temperature, that may overheat the connectors, damaging the thin layer of copper ,resulting in phosphides creation and joint zone embrittlement.
For more detailed information see “ Brazing technique for compressors connectors" AP192186420580.
Figure 68: Brazing procedure
Before eventual un-brazing of the compressor or any system component, the refrigerant charge must be removed and the installation vacuumed (especially with A2L refrigerants).
System pressure test and leak detection
The compressor has been strength tested and leak proof tested (<3g/year) at the factory. For system tests:
• Always use an inert gas such as Nitrogen or Helium.
• Pressurize the system on HP side rst then LP side.
• Do not exceed the following pressures indicated in table below
Table 38: System pressure test and leak detection
(1)
(1)
The maximum pressurizing speed must be respected to ensure pressure equalization between LP and HP side over scroll elements.
The maximum pressurizing speed must be respected to ensure pressure equalization between LP and HP side over scroll elements.
Vacuum evacuation and moisture removal
Requirements:
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP and HP sides.
• Evacuate the system to a pressure of 500 μm Hg (0.67 mbar/0.02 in.Hg) absolute.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 61
Scroll compressors, DSH090 to DSH600 | Application
Recommendations:
• Energized heaters improve moisture removal.
• Alternate vacuum phases and break vacuum with Nitrogen to improve moisture removal.
For more detailed information see “Vacuum pump-down and dehydration procedure” TI-026-0302.
Refrigerant charging
Initial charge:
• For the initial charge, the compressor must not run.
• Charge refrigerant as close as possible to the nominal system charge.
• This initial charging operation must be done in liquid phase between the condenser outlet and the lter drier.
If needed, a complement of charge can be done before evaporator, in liquid phase while compressor is running by slowly throttling liquid in.
Never bypass safety low pressure switch.
For more detailed information see “Recommended refrigerant system charging practice“ AP000086421422.
Dielectric strength and insulation resistance tests
Several tests have been performed on each compressor at the factory between each phase and ground.
• Dielectric strength test is done with a high potential voltage (hi-pot) of 2Un +1000V AC at least, and leakage
current must be less than 5 mA.
• Insulation resistance is measured with a 500 V DC megohm tester and must be higher than 1 megohm.
Recommendations:
• Additional dielectric test is not recommended as it may reduce motor lifetime. Nevertheless, if such as test is
necessary, it must be performed at a lower voltage.
• Insulation resistance test can be done.
• The presence of refrigerant around the motor windings will result in lower resistance values to ground and higher
leakage current readings. Such readings do not indicate a faulty compressor. To prevent this, the system can be rst operated briey to distribute refrigerant.
Do not use a megohm meter nor apply power to the compressor while it is under vacuum as this may cause internal damage.

Commissioning

Preliminary check
Check electrical power supply:
• Phase order: Reverse rotation is obvious if the compressor do not build up pressure and sound level is abnormal
high. For DSH090-184 compressors equipped with internal reverse vent valve which can protect compressor without damage within duration below 24h. For more details refer to section Phase sequence and reverse rotation protection.
For DSH240 to DSH600 compressors equipped with an electronic module, reverse rotation will be automatically detected. For more details refer to section Motor protection.
• Voltage and voltage unbalance within tolerance: For more details refer to section Motor voltage.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 62
Scroll compressors, DSH090 to DSH600 | Application
Initial start-up
• Surface sump heaters must be energized at least 6 hours in advance to remove refrigerant.
• A quicker start-up is possible by “jogging” the compressor to evacuate refrigerant. Start the compressor for 1
second, then wait for 1 to 2 minutes. After 3 or 4 jogs the compressor can be started. This operation must be repeated for each compressor individually.
System monitoring
The system must be monitored after initial startup for a minimum of 60 minutes to ensure proper operating characteristics such as:
• Correct superheat and subcooling.
• Current draw of individual compressors within acceptable values (max operating current).
• No abnormal vibrations and noise.
• Correct oil level.
If Oil Top-up is needed, it must be done while the compressor is idle. Use the schrader connector or any other accessible connector on the compressor suction line. Always use original Danfoss POE oil 160SZ from new cans. For more detailed information see “Lubricants lling in instructions for Danfoss Commercial Compressors”
AP000086435866.

Dismantle and disposal

Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its
site.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 63
Compressor
model
Length
Width
Height
Gross weight
mm
inchmminchmminchkglbs
DSH090
565
22.2
470
18.5
718
28.369152
DSH105
565
22.2
470
18.5
718
28.376168
DSH120
565
22.2
470
18.5
718
28.376168
DSH140
565
22.2
470
18.5
718
28.379174
DSH161
565
22.2
470
18.5
718
28.381179
DSH184
565
22.2
470
18.5
718
28.384185
DSH240
750
29.5
750
29.5
1050
41.3
128
282
DSH295
750
29.5
750
29.5
1050
41.3
131
289
DSH381
750
29.5
750
29.5
1050
41.3
178
392
DSH485
750
29.5
750
29.5
1050
41.3
195
430
DSH600
750
29.5
750
29.5
1050
41.3
234
516
Compressor
model
Compres‐
sors per
pack
Length
Width
Height
Gross weight
Static stack‐
ing pallets
mm
inchmminchmminchkglbs
DSH09081150
45.3
950
37.4
680
26.8
494
10892DSH10581150
45.3
950
37.4
750
29.5
544
11992DSH12081150
45.3
950
37.4
750
29.5
544
11992DSH14081150
45.3
950
37.4
750
29.5
566
12482DSH16181150
45.3
950
37.4
750
29.5
582
12832DSH18481150
45.3
950
37.4
750
29.5
606
13362DSH24061150
45.3
96538768
30.2
693
15282DSH29561150
45.3
96538768
30.2
712
15702DSH38141150
45.3
96538800
31.5
678
14942DSH48541150
45.3
96538800
31.5
744
16402DSH60041150
45.3
96538800
34.7
900
1984
2
Scroll compressors, DSH090 to DSH600 | Packaging

Packaging

Single pack

Table 39: Single pack packaging

Industrial pack

Table 40: Industrial pack packaging
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 64
Compressor model
Connections
Motor protection
Code no.
347
9
200-230/3/60
380-400 (415)/3/50
460/3/60
575/3/60
380-400/3/60
DSH090
Brazed
Internal
-
120H1511--
DSH105
Brazed
Internal
-
120H1521--
DSH120
Brazed
Internal
-
120H1531--
DSH140
Brazed
Internal
-
120H1541--
DSH161
Brazed
Internal
-
120H1551--
DSH184
Brazed
Internal
-
120H1561--
DSH240
Brazed
Module 24V AC
(1)
120H1749
120H1376
120H1734
-
DSH240
Brazed
Module 110-240V
(1)
120H1751
120H1374
120H1735
-
DSH295
Brazed
Module 24V AC
(1)
120H1745
120H1372
120H1732
-
DSH295
Brazed
Module 110-240V
(1)
120H1747
120H1370
120H1733
-
DSH381
Brazed
Module 24V AC
(1)
120H1741
120H1368
120H1730
-
DSH381
Brazed
Module 110-240V
(1)
120H1743
120H1366
120H1731
-
DSH485
Brazed
Module 24V AC
(1)
120H1737
120H1364
120H1728
-
DSH485
Brazed
Module 110-240V
(1)
120H1739
120H1362
120H1729
-
DSH600
Brazed
Module 24V AC
(1)
-
contact Danfoss
contact Danfoss
-
DSH600
Brazed
Module 110-240V
(1)
-
contact Danfoss
contact Danfoss
-
Scroll compressors, DSH090 to DSH600 | Ordering

Ordering

Danfoss scroll compressors DSH can be ordered in either industrial packs or in single packs. Please use the code numbers from below tables for ordering.
Compressors DSH090 to DSH184 are delivered with exible grommets.
For compressors DSH240 to DSH600 use in single applications, exible grommets are available as accessory kit
8156138.

Single pack

Compressors compatible R454B, R452B and R410A
Figure 69: Single pack
Table 41: Single pack compressors compatible R454B, R452B and R410A
(1)
(1)
Electronic motor protection, module located in terminal box.
Electronic motor protection, module located in terminal box.
Mounting kit for DSH240-295-381-485 single compressor applications : Ref 8156138
Mounting kit for DSH240-295-381-485 single compressor applications : Ref 8156138
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 65
Compressor model
Connections
Motor protection
Code no.
347
9
200-230/3/60
380-400 (415)/3/50
460/3/60
575/3/60
380-400/3/60
DSH090
Brazed
Internal
120H1507
-
120H1513
120H1515
DSH105
Brazed
Internal
120H1517
-
120H1523
120H1525
DSH120
Brazed
Internal
120H1527
-
120H1533
120H1535
DSH140
Brazed
Internal
120H1537
-
120H1543
120H1545
DSH161
Brazed
Internal
120H1547
-
120H1553
120H1555
DSH184
Brazed
Internal
120H1557
-
120H1563
120H1565
DSH240
Brazed
Module 24V AC
(1)
120H1291
120H1331
120H1299
120H1315
DSH240
Brazed
Module 110-240V
(1)
120H1289
120H1329
120H1298
120H1313
DSH295
Brazed
Module 24V AC
(1)
120H1287
120H1327
120H1297
120H1311
DSH295
Brazed
Module 110-240V
(1)
120H1285
120H1325
120H1296
120H1309
DSH381
Brazed
Module 24V AC
(1)
---
120H1307
DSH381
Brazed
Module 110-240V
(1)
---
120H1305
DSH485
Brazed
Module 24V AC
(1)
---
120H1303
DSH485
Brazed
Module 110-240V
(1)
---
120H1301
DSH600
Brazed
Module 24V AC
(1)
-
120H1380--
DSH600
Brazed
Module 110-240V
(1)
-
120H1378--
Compressor model
Connections
Motor protection
Code no.
347
9
200-230/3/60
380-400 (415)/3/50
460/3/60
575/3/60
380-400/3/60
DSH090
Brazed
Internal
-
120H1512--
DSH105
Brazed
Internal
-
120H1522--
DSH120
Brazed
Internal
-
120H1532--
DSH140
Brazed
Internal
-
120H1542--
DSH161
Brazed
Internal
-
120H1552--
DSH184
Brazed
Internal
-
120H1562--
DSH240
Brazed
Module 24V AC
(1)
120H1748
120H1375--
DSH240
Brazed
Module 110-240V
(1)
120H1750
120H1373--
DSH295
Brazed
Module 24V AC
(1)
120H1744
120H1371--
Scroll compressors, DSH090 to DSH600 | Ordering
Compressors compatible R410A only
Table 42: Single pack compressors compatible R410A only
(1)
(1)
Electronic motor protection, module located in terminal box.
Electronic motor protection, module located in terminal box.
Mounting kit for DSH240-295-381-485-600 single compressor applications : Ref 8156138
Mounting kit for DSH240-295-381-485-600 single compressor applications : Ref 8156138

Industrial pack

Compressors compatible R454B, R452B and R410A
Figure 70: Industrial pack
Table 43: Industrial pack compressors compatible R454B, R452B and R410A
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 66
Compressor model
Connections
Motor protection
Code no.
347
9
200-230/3/60
380-400 (415)/3/50
460/3/60
575/3/60
380-400/3/60
DSH295
Brazed
Module 110-240V
(1)
120H1746
120H1369--
DSH381
Brazed
Module 24V AC
(1)
120H1740
120H1367--
DSH381
Brazed
Module 110-240V
(1)
120H1742
120H1365--
DSH485
Brazed
Module 24V AC
(1)
120H1736
120H1363--
DSH485
Brazed
Module 110-240V
(1)
120H1738
120H1361--
Compressor model
Connections
Motor protection
Code no.
347
9
200-230/3/60
380-400 (415)/3/50
460/3/60
575/3/60
380-400/3/60
DSH090
Brazed
Internal
120H1508
-
120H1514
120H1516
DSH105
Brazed
Internal
120H1518
-
120H1524
120H1526
DSH120
Brazed
Internal
120H1528
-
120H1534
120H1536
DSH140
Brazed
Internal
120H1538
-
120H1544
120H1546
DSH161
Brazed
Internal
120H1548
-
120H1554
120H1556
DSH184
Brazed
Internal
120H1558
-
120H1564
120H1566
DSH240
Brazed
Module 24V AC
(1)
120H1290
120H1330
-
120H1314
DSH240
Brazed
Module 110-240V
(1)
120H1288
120H1328
-
120H1312
DSH295
Brazed
Module 24V AC
(1)
120H1286
120H1326
-
120H1310
DSH295
Brazed
Module 110-240V
(1)
120H1284
120H1324
-
120H1308
DSH381
Brazed
Module 24V AC
(1)
---
120H1306
DSH381
Brazed
Module 110-240V
(1)
---
120H1304
DSH485
Brazed
Module 24V AC
(1)
---
120H1302
DSH485
Brazed
Module 110-240V
(1)
---
120H1300
DSH600
Brazed
Module 24V AC
(1)
-
120H1381--
DSH600
Brazed
Module 110-240V
(1)
-
120H1379--
Scroll compressors, DSH090 to DSH600 | Ordering
(1)
(1)
Electronic motor protection, module located in terminal box
Electronic motor protection, module located in terminal box
Compressors compatible R410A only
Table 44: Industrial pack compressors compatible R410A only
(1)
(1)
Electronic motor protection, module located in terminal box
Electronic motor protection, module located in terminal box
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 67
Code no.
Description
Application
Packaging
Pack size
120Z0125
Rotolock adaptor set (1"3/4 ~ 1"1/8) , (1"1/4 ~ 7/8")
DSH090 (R410A)
Multipack
8
120Z0405
Rotolock adaptor set (1"3/4 ~ 1"3/8) , (1"1/4 ~ 7/8")
DSH105 to 184 (R410A)
Multipack
8
7765028
Rotolock adaptor set (2"1/4 ~ 1"5/8) , (1"3/4 ~ 1"1/8)
DSH240-295-381 (R410A)
Multipack
6
120Z0504
Rotolock adaptor set (2"1/4 ~ 1"5/8), (1"3/4 ~ 1"3/8)
DSH485 (R410A)
Multipack
6
CC-0413
Code no.
Description
Application
Packaging
Pack size
120Z0367
Adaptor (1"1/4 Rotolock - 7/8" ODS)
Models with 7/8" ODF (R410A)
Multipack
10
120Z0364
Adaptor (1"3/4 Rotolock - 1"1/8 ODS)
Models with 1"1/8 ODF (R410A)
Multipack
10
120Z0431
Adaptor (1"3/4 Rotolock - 1"3/8 ODS)
Models with 1"3/8 ODF (R410A)
Multipack
10
120Z0432
Adaptor (2"1/4 Rotolock - 1"5/8 ODS)
Models with 1"5/8 ODF (R410A)
Multipack
10
Code no.
Description
Application
Packaging
Pack size
8156131
Gasket, 1"1/4
Models with 1"1/4 rotolock connection
Multipack
10
7956002
Gasket, 1"1/4
Models with 1"1/4 rotolock connection
Industry pack
50
8156132
Gasket, 1"3/4
Models with 1"3/4 rotolock connection
Multipack
10
7956003
Gasket, 1"3/4
Models with 1"3/4 rotolock connection
Industry pack
50
8156133
Gasket, 2"1/4
Models with 2"1/4 rotolock connection
Multipack
10
7956004
Gasket, 2"1/4
Models with 2"1/4 rotolock connection
Industry pack
50
Code no.
Description
Application
Packaging
Pack size
8153004
Solder sleeve P02 (1"3/4 Rotolock - 1"1/8 ODF)
Models with 1"3/4 rotolock connection (R410A)
Multipack
10
8153008
Solder sleeve P04 (1"1/4 Rotolock - 3/4" ODF)
Models with 1"1/4 rotolock connection (R410A)
Multipack
10
8153012
Rotolock connector P05 (1"1/4 Rotolock - 7/8" ODF)
Models with 1"1/4 rotolock connection (R410A)
Multipack
10
Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts

Accessories and Spare parts

Solder sleeve adapter set

Table 45: Solder sleeve adapter set

Rotolock adapter

Table 46: Rotolock adapter

Gaskets

Table 47: Gaskets

Solder sleeve

Table 48: Solder sleeve
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 68
Code no.
Description
Application
Packaging
Pack size
8153013
Solder sleeve P07 (1"3/4 Rotolock - 7/8" ODF)
Models with 1"3/4 rotolock connection (R410A)
Multipack
10
8153003
Solder sleeve P10 (1"3/4 Rotolock - 1"3/8 ODF)
Models with 1"3/4 rotolock connection (R410A)
Multipack
10
8153006
Solder sleeve P03 (2"1/4 Rotolock - 1"5/8 ODF)
Models with 2"1/4 rotolock connection (R410A)
Multipack
10
Code no.
Description
Application
Packaging
Pack size
8153123
Rotolock nut,1"1/4
Models with 1-1/4" rotolock connection
Multipack
10
8153124
Rotolock nut,1"3/4
Models with 1-3/4" rotolock connection
Multipack
10
8153126
Rotolock nut, 2"1/4
Models with 2-1/4" rotolock connection
Multipack
10
Code no.
Description
Application
Packaging
Pack size
120Z0584
Electronic motor protection module, 24 V AC
DSH240-295-381-485*-600(*except code 3)
Single pack
1
120Z0585
Electronic motor protection module, 110/240 V
DSH240-295-381-485*-600(*except code 3)
Single pack
1
120Z0624
Electronic motor protection module, 24V AC
DSH485 code 3
Single pack
1
Code no.
Description
Application
Packaging
Pack size
120Z0667
48W 24V surface sump heater CE and UL
DSH090 to 184
Single pack
1
120Z0668
48W 230V surface sump heater CE and UL
DSH090 to 184
Single pack
1
120Z0669
48W 400V surface sump heater CE and UL
DSH090 to 184
Single pack
1
120Z0670
48W 460V surface sump heater CE and UL
DSH090 to 184
Single pack
1
120Z0671
48W 575V surface sump heater CE and UL
DSH090 to 184
Single pack
1
120Z0388
80W 24V surface sump heater CE and UL
DSH090 to 184
Multipack
8
120Z0389
80W 230V surface sump heater CE and UL
DSH090 to 184
Multipack
8
120Z0390
80W 400V surface sump heater CE and UL
DSH090 to 184
Multipack
8
120Z0391
80W 460V surface sump heater CE and UL
DSH090 to 184
Multipack
8
120Z0402
80W 575V surface sump heater CE and UL
DSH090 to 184
Multipack
8
120Z0769
56W 24V surface sump heater + bottom insulation, CE & UL
DSH240-295-381-485-600
Industry pack
12
120Z0770
56W 230V surface sump heater + bottom insulation, CE & UL
DSH240-295-381-485-600
Industry pack
12
120Z0771
56W 400V surface sump heater + bottom insulation, CE & UL
DSH240-295-381-485-600
Industry pack
12
120Z0772
56W 460V surface sump heater + bottom insulation, CE & UL
DSH240-295-381-485-600
Industry pack
12
120Z0773
56W 575V surface sump heater + bottom insulation, CE & UL
DSH240-295-381-485-600
Industry pack
12
Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts

Rotolock nut

Table 49: Rotolock nut

Motor protection modules

Table 50: Motor protection modules

Surface sump heaters

Table 51: Surface sump heaters
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 69
Code no.
Description
Application
Packaging
Pack size
7750009
Discharge thermostat kit
DSH090 to 184 (R410A)
Multipack
10
7973008
Discharge thermostat kit
DSH090 to 184 (R410A)
Industry pack
50
Code no.
Description
Application
Packaging
Pack size
120Z0066
Mounting kit for scroll compressors. Grommets, sleeves, bolts, washers
DSH090 to 184
Single pack
1
8156138
Mounting kit for scroll compressors. Grommets, sleeves, bolts, washers
DSH240 to 600 in single installa­tion
Single pack
1
7777045
Mounting kit for scroll compressors. including hexagon rigid spacers, Grom­mets, Sleeves, Bolts, Washers
DSH240 to 600 Manifold installa­tions 50 Hz when mounting di­rectly on rail is not wished
Single pack
1
120Z0495
Mounting kit for scroll compressors. including triangle rigid spacers, Grom­mets, Sleeves, Bolts, Washers
DSH240 to 600 Manifold installa­tions 60 Hz when mounting di­rectly on rail is not wished
Single pack
1
Code no.
Description
Packaging
Pack size
7754023
POE lubricant, 1 litre can
Multipack
12
120Z0571
POE lubricant, 2.5 litre can
Multipack
4
Code no.
Description
Application
Packaging
Pack Size
120Z0413
Terminal box cover
DSH184 - DSH140 code3 - DSH161 code3
Single pack
1
8156135
Service kit for terminal box 96 x 115 mm, including 1 cover, 1 clamp
DSH090 to 161 (except DSH140 code3 and DSH161 code3)
Multipack
10 8173230
T block connector 52 x 57 mm
DSH090 to 161 (except DSH140 code3 and DSH161 code3)
Multipack
10
8173021
T block connector 60 x 75 mm
DSH184 - DSH140 code3 - DSH161 code3
Multipack
10
120Z0774
T block connector 80 x 80 mm
DSH240-600
Multipack
10
120Z0458
Terminal box 210 x 190 mm, incl. cover
DSH240-295-381*-485*-600(*except code 3)
Single pack
1
120Z0604
Terminal box 210x340mm, incl. cover
DSH485 code 3
Single pack
1
Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts

Discharge temperature protection

Table 52: Discharge temperature protection

Mounting hardware

Table 53: Mounting hardware

Lubricant

Table 54: Lubricant

Terminal boxes, covers and T-block connectors

Table 55: Terminal boxes, covers and T-block connectors
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 70
Code no.
Description
Application
Packaging
Pack Size
120Z0034
Acoustic hood for scroll compressor
DSH090
Single pack
1
120Z0035
Acoustic hood for scroll compressor
DSH105 to 161 (except DSH161-140 code3)
Single pack
1
120Z0135
Acoustic hood for scroll compressor
DSH184 - DSH140 code3 - DSH161 code3
Single pack
1
120Z0022
Acoustic hood for scroll compressor
DSH240-295-381*-485*(* except code 3)
Single pack
1
120Z0768
Acoustic hood for scroll compressor
DSH240-295-381*-485* max dgt 150°C(* except code 3)
Single pack
1 120Z0579
Acoustic hood for scroll compressor
DSH381 code 3
Single pack
1
120Z0490
Acoustic hood body for scroll compressor
DSH090 R454B/R452B Max. DGT150°C
Single pack
1
120Z0491
Acoustic hood body for scroll compressor
DSH105-161 R454B/R452B Max. DGT150°C
Single pack
1
120Z0492
Acoustic hood body for scroll compressor
DSH184 R454B/R452B Max. DGT150°C
Single pack
1
120Z0493
Acoustic hood top for scroll compressor
DSH090-184 R454B/R452B Max. DGT150°C
Single pack
1
Code no.
Description
Packaging
Pack Size
8156019
Sight glass with gaskets (black & white)
Multipack
4
8156129
Gasket for oil sight glass, 1"1/8 (white teon)
Multipack
10
7956005
Gasket for oil sight glass, 1"1/8 (white teon)
Multipack
50
8154001
Danfoss Commercial Compressors blue spray paint
Single pack
1
Code no.
Description
Application
Packaging
Pack Size
120Z0634
Suction washer, rigid spacer, organ pipe, gasket
DSH180E-210E-240E-280E-322E-368E
Single pack
1
120Z0692
Suction washer, rigid spacer, organ pipe, gasket
DSH260U-281U-301U
Single pack
1
120Z0693
Suction washer, rigid spacer, organ pipe, gasket
DSH274U-289U
Single pack
1
120Z0694
Suction washer, rigid spacer, organ pipe, gasket
DSH195U-210U-230U-251U-304U-324U-345U
Single pack
1
120Z0781
Kit tandem crossplatform
DSH360X-424X-456X-479X-565X
Single pack
1
120Z0792
Kit Tandem, Solid, OEL 1” 3/8
DSH482.590.760E
Single pack
1
120Z0796
Kit Tandem, solid, washer 31mm, OEL 1” 3/8
DSH535.675U
Single pack
1
120Z0791
Kit Tandem, solid, washer 29mm, OEL 1” 3/8
DSH620U
Single pack
1
120Z0786
Kit Tandem, Solid, washer 24mm,OEL 1”5/8
DSH725U
Single pack
1
120Z0788
Kit Tandem, Solid, washer 30mm,OEL 1”5/8
DSH865U
Single pack
1
120Z0787
Kit Tandem, Solid, washer 27mm,OEL 1”5/8
DSH780U
Single pack
1
Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts

Acoustic hoods

Table 56: Acoustic hoods

Miscellaneous

Table 57: Miscellaneous

Tandem kits

Table 58: Tandem kits
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 71
Code no.
Description
Application
Packaging
Pack Size
120Z0785
Kit Tandem, Solid,OEL 1”5/8
DSH970E
Single pack
1
120Z0726
Kit Tandem, spacer 30mm
DSH895U.DSH1085U (left suction).DSH1200E
Single pack
1
120Z0821
Kit Tandem, spacer 30mm, washer 38mm
DSH1085U (right suction)
Single pack
1
Code no.
Description
Application
Packaging
Pack Size
120Z0712
Washers, grommets, sleeve for oil connect
DSH1800T
Single pack
1
120Z0714
Organ pipe, sleeves, rigid spacer, gasket, rubber grommet
DSH420T
Single pack
1
120Z0714
Organ pipe, sleeves, rigid spacer, gasket, rubber grommet
DSH483T
Single pack
1
120Z0714
Organ pipe, sleeves, rigid spacer, gasket, rubber grommet
DSH552T
Single pack
1
120Z0782
Kit Trio,solid,washer 31mm, OEL 1”5/8
DSH1140T (right suction)
Single pack
1
120Z0783
Kit Trio,solid,washer 29/31mm,OEL 1”5/8
DSH1140T (left suction)
Single pack
1
120Z0784
Kit Trio,solid,washer 30mm, OEL 1”5/8
DSH720T.885T (left suction)
Single pack
1
120Z0789
Kit Trio,solid,washer 29mm, OEL 1”5/8
DSH1245T.1350T
Single pack
1
120Z0790
Kit trio,solid,OEL 1"5/8
DSH971T
Single pack
1
120Z0793
Kit Trio,solid,washer 33mm, OEL 1”5/8
DSH1455T (left and right suction)
Single pack
1
120Z0794
Kit Trio,solid,washer 34,5mm, OEL 1”5/8
DSH720T.885T (right suction)
Single pack
1
120Z0819
Kit Trio, spacer 30mm, washer 42mm
DSH1685T (left suction)
Single pack
1
120Z0820
Kit Trio, spacer 30mm, washer 41mm
DSH1685T (right suction)
Single pack
1
120Z0822
Kit Trio, spacer 30mm, washer 36mm
DSH1570T
Single pack
1
Scroll compressors, DSH090 to DSH600 | Accessories and Spare parts

Trio kits

Table 59: Trio kits
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 72

Online support

Danfoss oers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certications, accessories, and more. Start browsing at store.danfoss.com.
Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to our ocial collection of data sheets, certicates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support
Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert—all in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
Coolselector®2 - nd the best components for you HVAC/R system
Coolselector®2 makes it easy for engineers, consultants, and designers to nd and order the best components for refrigeration and air conditioning systems. Run calculations based on your operating conditions and then choose the best setup for your system design.
Download Coolselector®2 for free at coolselector.danfoss.com.
Ref Tools – essential tools for HVACR professionals
Get the guidance, support, information, and tools you need—on the job and in eld. Ref Tools is a free, powerful app that contains essential tools every air conditioning and refrigeration technician needs in their digital toolbelt.
Download Ref Tools for free at coolapps.danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order conrmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, t or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | Climate Solutions | 2022.01 AB288965961751en-001301 | 73
Loading...