Scroll compressors, DSH090 to DSH600 | Safety and warnings
Safety and warnings
Danfoss compressors are designed and manufactured according to the state of the art and to valid European and US
regulations. Particular emphasis has been placed on safety and reliability. Related instructions are highlighted with
the following icons:
This icon indicates instructions to avoid safety risk.
This icon indicates instructions to avoid reliability risk.
The purpose of this guideline is to help customers qualify compressors in the unit. You are strongly advise to follow
these instructions. For any deviation from the guidelines, please contact Danfoss Technical Support. In any case,
Danfoss accepts no liability as a result of the improper integration of the compressor into the unit by the system
manufacturer.
Scroll compressors, DSH090 to DSH600 | Introduction
Cut Away DSH240-600
Figure 2: Cut Away DSH240-600
How do IDVs work?
Figure 3: Intermediate Discharge Valve (IDV)
Danfoss Intermediate Discharge Valves (IDVs) are located close to the discharge side of the compressor. They reduce
excessive compression of refrigerant under part-load conditions while maintaining the same cooling capacity. The
IDVs open when discharge pressure falls below the built-in optimization point. They adapt the eort of the motor to
the varying load and pressure conditions in the system, thus reducing the eort of the motor and its electrical
consumption and improving the system’s seasonal energy eciency.
Scroll compressors, DSH090 to DSH600 | Product identication
Product identication
Name Plate
Figure 4: Name Plate
Nomenclature
The example below presents the compressor nomenclature which equals the technical reference as shown on the
compressor nameplate. Code numbers for ordering are listed in section Ordering.
R410A is a HFC blend (R32: 50%; R125: 50%) with a zero Ozone Depletion Potential (ODP=0) and a Global Warming
Potential of 1924/AR5 (2088/AR4). It is a near-azeotropic mixture with a temperature glide less than 0.2 K.
With its high net refrigeration eect coupled to a high density, the R410A has appeared in last decade to be the
preferred refrigerant for use in commercial air conditioners and heat pumps.
R452B
R452B is a HFO/HFC blend (R32: 67%; R125: 7%; R1234yf: 26%) with a zero Ozone Depletion Potential(ODP=0) and a
low Global Warming Potential (GWP: 676/AR5 ; 698/AR4). It is a near-azeotropic mixture with a temperature glide
around 1 K.
R452B has very close capacities versus R410A and due to its very limited discharge temperature dierence it
appears today as the best candidate for a direct drop in of R410A.
R452B is classied A2L with low ammability properties. Please refer to European regulations and directives about
the use of refrigerant of the A2L safety group ( EN378, EN60335). Outside Europe refer to the local regulation.
R454B
R454B is a HFO/HFC blend (R32 :68.9%; R1234yf: 31.1%) with a zero Ozone Depletion Potential (ODP=0) and a low
Global Warming Potential (GWP: 467/AR5; 466/AR4). It is a near-azeotropic mixture with a temperature glide around
1 K.
R454B has very close match to R410A in terms of capacity and discharge temperature dierence, and it oers better
eciencies compared to R410A.
R454B is classied A2L with low ammability properties. Please refer to European regulations and directives about
the use of refrigerant of the A2L safety group (EN378, EN60335). Outside Europe refer to the local regulation
Scroll compressors, DSH090 to DSH600 | Sound and vibration data
DSH720=3 × DSH240(50 Hz)
L
L
=82dB(A)
DSH240
=82+10 Log10 3=86 . 8dB(A)
DSH720
- The global sound level of “n” dierent compressors with respectively Li sound level is:
L
GLOBAL
i = n
= 10
i = 1
log10(∑ 10
0.1
∗ Li)
Example for the tandem
DSH424=DSH184+DSH240(50 Hz)
L
L
DSH184
DSH424
=78dB(A),L
=10Log10(10
DSH240
0 . 1×78
=82dB(A)
0 . 1×82
+10
)= 83 . 5dB(A)
Mechanical vibrations
A compressor generates some vibrations that propagate into the surrounding parts and structure. The vibration
level of a DSH compressor alone does not exceed 120µm peak to peak for DSH090 to DSH184, and 154µm peak to
peak for DSH240 to DSH600. However, when system structure natural frequencies are close to running frequency,
vibrations are amplied due to resonance phenomenon.
A high vibration level is damageable for piping reliability and generates high sound levels.
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Mechanical connections
Connection Details
Table 17: Connection Details
Figure 22: Outline drawing 1
Figure 23: Outline drawing 2
Design compressor mounting
General requirements
Compressors used in single applications must be mounted with exible grommets.
Compressors used in parallel applications must be mounted with rigid spacers onto rails (or directly on rails
according to compressor models) and the manifold assembly must be mounted with exible grommets onto the
frame.
During operation, the maximum inclination from the vertical plane must not exceed 3 degrees.
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Single requirements DSH090-105-120-140-161-184 mounting
Compressors DSH090-105-120-140-161-184 are delivered with rubber grommets and steel mounting sleeve used to
isolated the compressor from the base frame.
The grommets must be compressed until contact between the at washer and the steel mounting sleeve is
established. The required bolt size for the DSH090-105-120-140-161-184 compressors is HM8-40. This bolt must be
tightened to a torque of 15Nm.
Figure 24: Rubber grommets
Part 2, 3, 4, 5, 6 and 7 are delivered along with
compressor
Single requirements DSH240-295-381-485 -600 mounting
To be used in single applications, an additional accessory including exible grommets is necessary kit 8156138.
The grommets must be compressed until contact between the at washer and the steel mounting sleeve is
established. The required bolt size for the DSH240-295-381-485-600 compressors is HM8-55. This bolt must be
tightened to a torque of 21Nm.
Additionnal rigid spacer (to be added on the smallest compressor of the tan‐
dem)
DSH195U-210U-230U-251U-289U-304U-345U
7 mm
DSH274U
14 mm
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Table 18: Additionnal rigid spacer
Tandem requirements DSH420T-483T-552T
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be
installed below the rails.
The rigid mounting spacers and rubber grommets are included in tandem accessory kits.
Figure 28: DSH420T-483T-552T mounting
Tandem requirements DSH360X-424X-456X-479X-565X mounting
The large compressor, DSH240, 295 or 381, is mounted with rigid spacers on the rails.
The DSH120, 161 or 184 compressor is xed on beams by rigid spacer, and the beams are mounted with rigid
spacers on the rails. Rubber grommets and spacers must be installed below the rails.
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Design piping
General requirements
Proper piping practices should be employed to:
1.
Ensure adequate oil return, even under minimum load conditions (refrigerant speed, piping slopes…). For
validation tests see section Manage oil in the circuit.
2.
Avoid condensed liquid refrigerant from draining back to the compressor when stopped (discharge piping
upper loop). For validation tests see section Manage o cycle migration.
3.
Piping should be designed with adequate three-dimensional exibility to avoid excess vibration. It should not be
in contact with the surrounding structure, unless a proper tubing mount has been installed. For more
information on noise and vibration, see section Sound and vibration data.
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Tandem and trio requirements (Static)
Tandem and trio use static oil balancing principle to equalize oil level between the compressors by gravity. This is
ensured by a precise suction and oil equalization piping design.
The discharge line has no impact on oil balancing. It is shown with tee, to indicate that both left and right side
discharge headers are possible.
By default, DSH tandems and trios are not factory-built. To complete an assembly in the eld, you will need:
• Tubings, according to specic outline drawings indicated in the following table.
• Manifolding accessory kit.
• Compressors.
Suction and oil equalization piping drawings must be respected (diameters, minimum straight lengths, …)
Suction washer position
Depending on manifold conguration, it is essential to equalize the pressure of compressor sumps. Hence, a
suction washer must be added on certain compressors according to the table. Suction washers are included in
tandem or trio accessory kits as described in the illustrations.
Figure 34: Suction washer position
By convention, the compressor order (No.1, No.2 ...) is dened counting from left to right, placed on the side facing
the electrical boxes of the compressors (see example below on a trio)
Scroll compressors, DSH090 to DSH600 | Mechanical connections
Oil equalization design DSH180E to DSH368E
The oil level is balanced by a pipe of 1"1/8 oil equalization line.
In order ensure best oil balance, the organ pipe need to be mounted inside the oil equalization port as indicated on
below picture. To connect the equalization line on rotolock connections, the organ pipe adaptor and teon gasket
are included in the tandem kit must be used.
The organ pipe needs to be installed in the direction indicated by the label attached on pipe surface, which will
The oil level is balanced by a pipe of 1"3/8 oil equalization line.
In order to ensure best oil balance, the organ pipe need to be mounted inside the DSH120, 161 or 184 oil
equalization port as indicated on below picture. DSH240, 295 or 381 has integrated organ pipe inside the oil
equalization port.
Scroll compressors, DSH090 to DSH600 | Mechanical connections
To connect the equalization line on rotolock connections, the organ pipe, adaptor sleeves, Teon gaskets included
in the tandem accessory kit must be used.
Figure 37: For DSH120, DSH161 or DSH184
Figure 38: DSH240, DSH295 or DSH381
Oil equalization design DSH482-535, DSH590 to DSH1800
The oil level is balanced by a pipe of 1"3/8 or 1"5/8. To connect the equalization line on rotolock connections, the
adaptor sleeves included in the tandem or trio accessory kit must be used.
Scroll compressors, DSH090 to DSH600 | Electrical connections
Electrical connections
Wiring connections
According to compressor model, electrical power is connected to the compressor terminals either by 4.8mm (10-32)
screws or by M5 studs and nuts. In both cases the maximum tightening torque is 3 Nm.
Cable gland or similar protection component must be used on electrical box's knockouts to against accidental
contact with electrical parts inside.
DSH090-105-120-140-161 (*except DSH140-161 code3)
The terminal box is provided with a Ø 25.5mm (φ1 inch) (ISO25) and a Ø 29mm (φ1.14) (PG21) knockouts.
Figure 40: Wiring connections for DSH090-105-120-140-161 (*except DSH140-161 code3)
DSH140-161 code3 & DSH184
The terminal box is provided with a Ø 40.5mm (φ1.59inch) hole (ISO40) for power supply and a Ø 16.5mm
(φ0.65inch) knockout (ISO16).
Figure 41: Wiring connections for DSH140-161 code3 & DSH184
DSH240-295-381*-485* -600 (*except code 3)
The terminal box is provided with 2 triple knockouts and 1 single knockout for power supply and 4 double
knockouts for the safety control circuit.
The 3 power supply knockouts accommodate the following diameters:
The motor protection modules come preinstalled within the terminal box. Phase sequence protection connections
and thermistor connections are pre-wired and should not be removed.
The module must be connected to a power supply of the appropriate voltage. The module terminals are 6.3mm
(0.25inch) size Faston type.
Figure 45: Motor protection module
Electrical Specications
Motor voltage
Danfoss scroll compressors DSH are available in four dierent motor voltages as listed below.
Scroll compressors, DSH090 to DSH600 | Electrical connections
NOTE:
Voltage range: Nominal voltage ± 10%. The voltage range indicates where the compressor can run in the majority
of the application envelope. A boundary voltage supply which accumulates under specic conditions such as high
ambiance, high superheat, or map boundary conditions, may lead to a compressor trip.
Voltage imbalance
The maximum allowable voltage imbalance is 2%. Voltage imbalance causes high amperage over one or several
phases, which in turn leads to overheating and possible motor damage. Voltage imbalance is given by the formula:
The compressor terminal box according to IEC60529 is IP54 for all models when correctly sized IP54 rated cable
glands are used.
First numeral, level of protection against contact and foreign objects
5 - Dust protected
Second numeral, level of protection against water
4 - Protection against water splashing
Terminal box temperature
The temperature inside the terminal box must not exceed 70°C (158°F). Consequently, if the compressor is installed
in an enclosure, precautions must be taken to avoid that the temperature around the compressor and in the
terminal box would rise too much. A ventilation installation on the enclosure panels may be necessary. If not, the
electronic protection module may not operate properly. Any compressor damage related to this will not be covered
by Danfoss warranty. In the same manner, cables must be selected in a way that ensures the terminal box
temperature does not exceed 70°C (158°F).
Scroll compressors, DSH090 to DSH600 | Electrical connections
Table 23: Motor voltage code 4
Table 24: Motor voltage code 7
Table 25: Motor voltage code 9
LRA (Locked Rotor Amp)
Locked Rotor Amp value is the higher average current as measured on mechanically blocked compressors tested
under nominal voltage. The LRA value can be used as a rough estimation for the starting current. However, in most
cases, the real starting current will be lower. A soft starter can be applied to reduce starting current (see section Soft
starts).
RLA (Rated Load Amperage)
The RLA values presented are simply calculated by dividing the maximum current before tripping at overload test
conditions by 1.4.
MOC (Maximum Operating Current)
The max operating current is the amperage the compressor will draw when it operates at maximum load of
operating envelope within the voltages printed on the nameplate.
Scroll compressors, DSH090 to DSH600 | Electrical connections
MOC can be used as a basis for contactors selection.
Winding resistance
Winding resistance is the resistance between phases at 25°C (77°F) (resistance value +/- 7%). Winding resistance is
generally low and it requires adapted tools for precise measurement. Use a digital ohm-meter, a “4 wires” method
and measure under stabilised ambient temperature. Winding resistance varies strongly with winding temperature. If
the compressor is stabilised at a dierent value than 25°C (77°F), the measured resistance must be corrected using
the following formula:
R
tamb
= R
25°C(77°F)
a + t
a + t
amb
25°C(77°F)
Motor protection
DSH090 to DSH184
Compressor models DSH 090 to 184 are provided with internal overload motor protection to prevent against
excessive current and temperature caused by overloading, low refrigerant ow or phase loss.
The protector is located in star point of motor and, should it be activated, will cut out all three phases. It will be reset
automatically.
While not compulsory, an additional thermal magnetic motor circuit breaker is still advisable for either alarm or
manual reset.
Then it must be set at the Max Operating Current value (MOC):
• When the motor temperature is too high, then the internal protector will trip.
• When the current is too high the thermal magnetic motor circuit breaker will trip before the internal protection
therefore oering possibility of manual reset.
DSH240 to DSH600
Compressor models DSH240-295-381-485-600 are delivered with a pre-installed motor protection module inside
the terminal box. This device provides ecient and reliable protection against overheating and overloading as well
as phase loss/reversal.
The motor protector comprises a control module and PTC sensors embedded in the motor winding.
The motor temperature is being constantly measured by a PTC thermistor loop connected on S1-S2 . If any
thermistor exceeds its response temperature, its resistance increases above the trip level (4.500 Ω) and the output
relay then trips – i.e. contacts M1-M2 are open. After cooling to below the response temperature (resistance < 2.750
Ω), a 5-minute time delay is activated.
After this delay has elapsed, the relay is once again pulled in – i.e. contacts M1-M2 are closed. The time delay may be
cancelled by means of resetting the mains (L-N -disconnect) for approximately 5 sec.
A red/green twin LED is visible on the module (except on DSH485-3). A solid green LED denotes a fault free
condition. A blinking red LED indicates an identiable fault condition:
Scroll compressors, DSH090 to DSH600 | Electrical connections
Figure 46: PTC Overheat
While not compulsory, an additional thermal magnetic motor circuit breaker is still advisable for either alarm or
manual reset.
Then it must be set at the Max Operating Current value (MOC) :
• When the motor temperature is too high, then the internal PTC over temp. and module is activated.
• When the current is too high the thermal magnetic motor circuit breaker will trip before the module activate
therefore oering possibility of manual reset.
Figure 47: Delay timer active (after PTC over temp.)
Phase sequence and reverse rotation protection
Use a phase meter to establish the phase orders and connect line phases L1, L2 and L3 to terminals T1, T2 and T3,
respectively.
DSH090 to DSH184
Compressor models DSH 090 to 184 incorporates an internal reverse vent valve which will react when the
compressor is run in reverse and will allow refrigerant to circulate through a by-pass from the suction to the
discharge. Although reverse rotation is not destructive for these models, it should be corrected as soon as possible.
Repeated reverse rotation over 24 hours may have negative impact on the bearings.
Reverse rotation will be obvious to the user as soon as power is turned on: the compressor will not build up
pressure, the sound level will be abnormally high and power consumption will be minimal. If reverse rotation
symptoms occur, shut the compressor down and connect the phases to their proper terminals. If reverse rotation is
not halted, the compressor will cycle o-on the motor protection.
DSH240 to DSH600
Use a phase meter to establish the phase orders and connect line phases L1, L2 and L3 to terminals T1, T2 and T3,
respectively.
Compressor models DSH 240 to 600 are delivered with an electronic module which provides protection against
phase reversal and phase loss at start-up.
The phase sequencing and phase loss monitoring functions are active during a 5-sec window 1 second after
compressor start-up (power on L1-L2-L3).
Scroll compressors, DSH090 to DSH600 | Electrical connections
Should one of these parameters be incorrect, the relay would lock out (contact M1-M2 open). The red LED on the
module will show the following blink code (except on DSH485-3):
Figure 49: In case of phase reverse error
Figure 50: In case of phase loss error:
The lockout may be cancelled by resetting the power mains (disconnect L-N) for approximately 5 seconds.
For more detailed information see “ Instructions for electronic module” AN160986418236.
Lowest foreseeable evaporation, and
highest foreseeable condensation.
Minimum number of compressor running for 6 hours.
For reversible system, perform test in
both heating and cooling mode.
Oil level must be visible or full in the
sight glass when the compressor is running and when all compressors of the
circuit are stopped.
Top-up with oil, generally 3% of the
total system refrigerant charge (in
weight). Above 3% look for potential oil trap in the system.
Integrate a function in control logic
to run all compressors simultaneously in order to boost oil return
(for more details see section Control logic)
Oil separator can be added
2
Check oil balancing
A
Lowest foreseeable evaporation and
highest foreseeable condensation and
nominal capacity condition
for tandem 2 compressors running for 6
hours, for trio, compressor running follow the running sequence:
(1+2+3)2hrs→ (1+2)2hrs →(2+3)2hrs→
(1+3)2hrs
For reversible system, perform test in
both heating and cooling mode.
Oil level must be visible or full in the
sight glass when the compressors are
running and when all compressors of
the circuit are stopped
Top-up with oil, generally 3% of the
total system refrigerant charge (in
weight).
Check that manifold piping is conform to Danfoss requirements.
Integrate a function in control logic
to stop manifold periodically in order to balance oil (for more details
see section Control logic)
3
Oil return in split
systems
Since each installation is unique, test 1
and 2 can not fully validate the oil return. Oil level must be checked and adjusted at commissioning.
Oil level must be visible or full in the
sight glass when the compressor is running and when all compressors of the
circuit are stopped.
Pay special attention to “Piping design”
Oil separator is strongly recommended, espacially in case of part load.
Scroll compressors, DSH090 to DSH600 | Application
Application
Manage oil in the circuit
Requirement
Oil level must be visible or full in the sight glass when the compressor is running and when all compressors of
the circuit are stopped. For DSH140-184 medium trio models, top-up oil quantity 1L at least as mandatory.
System evaluation
Table 26: Manage oil in the circuit - System evaluation
Test, criteria and solutions
Table 27: Manage oil in the circuit - Test, criteria and solutions
Manage sound and vibration
Sound radiations
Mitigations methods: We can consider two means to reduce compressors sound radiations:
1.
Acoustic hoods are quick and easy to install and do not increase the overall size of the compressors. Acoustic
hoods are available from Danfoss as accessories. Refer to the tables above for sound levels, attenuation and code
numbers.
2.
Use of sound-insulation materials on the inside of unit panels is also an eective mean to reduce sound
radiation.
Scroll compressors, DSH090 to DSH600 | Application
NOTE:
During compressor shut down, a short reverse rotation sound is generated. The duration of this sound depends on
the pressure dierence at shut down and should be less than 3 seconds. This phenomenon has no impact on
compressor reliability.
Gas pulsation
The compressor has been designed and tested to ensure that gas pulsation is optimized for the most commonly
encountered air conditioning pressure ratio. Manifolded compressors are equivalents to lagged sources of gas
pulsation. Therefore, pulse level can vary during time.
Mitigations methods: If an unacceptable level is identied, a discharge muer with the appropriate resonant
volume and mass can be installed.
Mitigation Methods
1.
To ensure minimum vibrations transmission to the structure, strictly follow Danfoss mounting requirements
(mounting feet, rails etc..). For further information on mounting requirements, please refer to section Design
compressor mounting.
2.
Ensure that there is no direct contact (without insulation) between vibrating components and structure.
3.
To avoid resonance phenomenon, pipings and frame must have natural frequencies as far as possible from
running frequencies(50 or 60 Hz). Solutions to change natural frequencies are to work on structure stiness and
mass (brackets, metal sheet thickness or shape…)
Manage Operating envelope
The Operating envelope for DSH scroll compressors guarantees reliable operations of the compressor for steady-
state operation.
Steady-state operation envelope is valid for a suction superheat within 5K to 30K range at nominal Voltage.
High and low pressure protection
Low-pressure (LP) and high-pressure (HP) safety switches must never be bypassed nor delayed and must stop all
the compressors.
LP switch auto restart must be limited to 5 times within 12 hours.
HP safety switch must be reset manually.
Depending on application operating envelope, you must dene HP and LP limits within operating envelope and
pressure setting table above.
Discharge temperature protection
DSH240 to DSH600 include an integrated discharge temperature protection. Excessive discharge temperature will
result in tripping of electronic module ouput relay.
This protection, eective for suction superheat above 5K (9°), should be considered as a compressor safety device
and its purpose is not to ensure operation map control.
In case of basic map control by pressure switches that can not ensure totally that the compressor will remain in its
operating envelope, an additionnal external discharge protection is required. (see below Figure 51: Discharge
Scroll compressors, DSH090 to DSH600 | Application
Figure 51: Discharge temperature protection examples
Example 1 (R410A, SH = 11K)
LP switch setting: LP1 = 3.8 bar (g) (-15°C), HP switch setting: HP1 =38 bar (g) (62°C)
Risk of operation beyond the application envelope.
DGT protection required.
Example 2 (R410A, SH = 11K)
LP switch setting: LP2 = 4.7 bar (g) (-10°C), HP switch setting: HP2 = 31 bar (g) (52°C)
No risk of operation beyond the application envelope.
No DGT protection required.
DSH090 to 184 have no integrated discharge temperature protection, an external protection is required.
This external protection device can be a thermostat or a temperature sensor. The discharge gas temperature
protection must trip the power supply when it reaches the setting point to protect the compressor from
overheating.
For R410A application the discharge gas protection should be set to open at a maximum discharge gas temperature
of 135°C(275°F). The discharge gas thermostat accessory kit (code 7750009) is recommended.
For R452B/R454B application, the discharge gas protection should be set to open at a maximum discharge gas
temperature of 150°C(302°F). A PT1000 is recommended.
The discharge gas thermostat or sensor must be attached to the discharge line within 150mm (5.91 inch) from the
compressor discharge port and must be thermally insulated and tightly xed on the pipe (see Figure 52: Discharge
Gas Temperature protection (DGT))
Figure 52: Discharge Gas Temperature protection (DGT)
• MOP (Max Operating Pressure) ensured by expansion device
• Condensing pressure control
• DGT external setting points: R410A max 135°C (275°F), R454B/R452B max
150°C (302°F)
• HP and LP sensor
• Operating envelope limits integrated into control logic
• Temperature measurement (monitoring by sensor)
HP switch setting
CC-000166
Condensing pressure control
MOP < Max evap T°
LP switch setting
tests No1 and 2
DGT
Whole operating envelope limits integrated into control logic
CC-000192
Application
Tests to perform
Non reversible
Liquid
ood back test
Reversible
Liquid
ood back test
Defrost test
Scroll compressors, DSH090 to DSH600 | Application
System evaluation
HP and LP must be monitored to respect operating envelope limitation. We consider two types of operating
envelope management: Basic and Advanced.
Table 28: System evaluation
Manage superheat
During normal operation, refrigerant enters the compressor as a superheated vapor. Liquid ood back occurs when
a part of the refrigerant entering the compressor is still in liquid state.
Liquid ood back can cause oil dilution and, in extreme situations lead to liquid slugging that can damage the
compressor.
Requirement
In steady state conditions the expansion device must ensure a suction superheat within 5K to 30K (9 to 54°F).
System evaluation
Use the table in relation with the application to quickly evaluate the potential tests to perform.
Oil temperature sensor must be placed on the bottom of the baseplate.
1.
2.
1.
2.
Test
Purpose
Test condition
Pass criteria
Solutions
Liquid ood
back test
Steady-state
A
Liquid ood back testing must be carried out under expansion
valve threshold operating conditions:
• Lowest foreseeable evaporation, and highest foreseeable
condensation.
• Minimum number of compressor running.
For reversible system, perform test in both heating and cooling
mode.
Suction superheat >5K (9°F)
and the oil superheat shall not
be more than 60 sec below the
safe limit dened in the Dilution Chart. (see Dilution Chart -
DSH090 to DSH184 R410A)
Check expansion valve selection and setting.
◦ For Thermostatic ex-
pansion valve (TXV )
check bulb position...
◦ For Electronic expan-
sion valve (EXV) check
measurement chain
and PID....
Add a suction accumulator
(1)
Transient
Tests must be carried out with most unfavorable conditions :
• fan staging,
• compressor staging
• …
Oil superheat shall not be more
than 60 sec per hour below the
safe limit dened in the Dilution Chart. (see Dilution Chart -
DSH090 to DSH184 R452B /
R454B)
Defrost test
Check liquid
oodback during defrost cycle
Defrost test must be carried out in the most unfavorable conditions (at 0°C (32°F) evaporating temperature).
Oil superheat shall not be more
than 60 sec per hour below the
safe limit dened in the Dilution Chart. (see Dilution Chart -
DSH240 to DSH600 R410A/
R452B / R454B)
Check defrost logic. In reversible systems, the defrost logic can be worked
out to limit liquid ood-backeect. (for more details see Control logic).
Add a suction accumulator
(1)
Scroll compressors, DSH090 to DSH600 | Application
Test, criteria and solutions
Table 30: Test, criteria and solutions
(1)
(1)
Suction accumulator oers protection by trapping the liquid refrigerant upstream from the compressor. The accumulator should be sized at
Suction accumulator oers protection by trapping the liquid refrigerant upstream from the compressor. The accumulator should be sized at
least 50 % of the total system charge. Suction accumulator dimensions can impact oil return (gas velocity, oil return hole size…), therefore oil
least 50 % of the total system charge. Suction accumulator dimensions can impact oil return (gas velocity, oil return hole size…), therefore oil
return has to be checked according to section Manage oil in the circuit.
return has to be checked according to section Manage oil in the circuit.
Placing oil temperature sensor
Oil temperature sensor must be placed on the bottom of the baseplate. Some thermal paste shall be used to
improve the conductivity. The sensor must also be correctly thermally insulated from the ambiance.
The Oil superheat is dened as: (Oil temperature - Evaporating temperature)
• when the compressor is located at the coldest part of the installation, refrigerant vapor condenses in the
compressor.
• or directly in liquid-phase by gravity or pressure dierence. When the compressor restarts, the refrigerant diluted
in the oil, or stored in evaporator, generates poor lubrication conditions, and may reduce bearings life time. In
extreme situations, this leads to liquid slugging that can damage the compressor scroll set.
Requirement
• Compressor can tolerate occasional ooded start, but it should remain exceptional situation and unit design must
prevent that this situation happen at each start.
• Right after start, liquid refrigerant must not ow massively to compressor
• The charge limit is a threshold beyond some protective measures must be taken to limit risk of liquid slugging and
extreme dilution at start.
System evaluation
Use the table below in relation with the system charge and the application to quickly dene necessary safeties to
implement.
Unit has no enclosure, wind >5m/s (ft/s)& ambient temperature <-5°C
80W SSH + additional SSH/thermal insulation
Scroll compressors, DSH090 to DSH600 | Application
Surface Sump heater
The surface sump heater are designed to protect the compressor against o-cycle migration of refrigerant.
For DSH090-105-120-140-161-184, the surface sump heater is located on the compressor shell. For better standby
energy consumption, Danfoss provides 48W and 80W two optional surface sump heater. The selection of surface
sump heater could be refered to Table 32: surface sump selection principle
Figure 57: DSH090 to 184
Table 32: surface sump selection principle
For DSH240-295-381-485-600, the 56W surface sump seater is located below the sump, associated with a thermal
insulation.
Figure 58: DSH240 to DSH485
The heater must be turned on whenever all the compressors are o. Surface sump heater accessories are available
from Danfoss (see section Accessories and Spare parts).
Liquid line solenoid valve (LLSV)
A Liquid line solenoid valve (LLSV) is used to isolate the liquid charge on the condenser side, thereby preventing
against charge transfer to the compressor during o -cycles. The quantity of refrigerant on the low-pressure side of
the system can be further reduced by using a pump-down cycle in association with the LLSV.
Pump-down cycle
By decreasing pressure in the sump, pump down system:
• evacuates refrigerant from oil
• set the sump saturating pressure much lower than ambiance temperature and due to that, avoid refrigerant
condensation in the compressor.
Scroll compressors, DSH090 to DSH600 | Application
Table 35: Charge limits for Trio models
Power supply and electrical protection
Wiring information Requirements
Protect the compressor from short circuit and overcurrent by a thermal magnetic motor circuit breaker set to Max.
•
operating current or lower (see table in section Three phase electrical characteristics). For
DSH090-105-120-140-161-184, phase sequence protection is strongly recommended.
• Compressor models DSH240-295-381-485-600 are delivered with a pre-installed motor protection module inside
the terminal box that must be powered on.
• HP safety switch, DGT (only for DSH090 to DSH184) and electronic module relay output (M1-M2, only for DSH240
to DSH600) must be wired in the safety chain. Other safety devices such as LP can be either hardware or software
managed.
• Provide separate electrical supply for the heaters so that they remain energized even when the machine is out of
service (e.g. seasonal shutdown).
The wiring diagrams below are examples for a safe and reliable compressor wiring:
Maximum 5 auto reset during a period of 12 hours,
then manual reset.
Electronic module (Motor
protection, DGT)
(1)
Contact M1-M2 opened
Scroll compressors, DSH090 to DSH600 | Application
Soft starts
Soft starters are designed to reduce the starting current of 3-phase AC motors. Soft starters can be used on DSH
compressor but, in order to ensure proper lubrication of compressor parts, the settings must ensure that the
compressor start-up time is always less than 0.5 seconds.
Ramp-down must be set to minimum to ensure proper discharge valve closing.
In case of use with R454B or R452B make sure that the softstarter selected is compatible with A2L refrigerants.
Control logic
Safety control logic requirements
Table 36: Safety control logic requirements
(1)
(1)
Only for DSH240 to DSH600.
Only for DSH240 to DSH600.
Cycle rate limit requirements
Danfoss requires a minimum compressor running time of 2 minutes to ensure proper oil return and sucient motor
cooling.
Additionally, compressor must not exceed 12 starts per hour. 12 starts per hour must not be considered as an
average, this is the maximum number of starts acceptable to keep a good regulation accuracy during low load.
Oil management logic recommendations
In some cases, oil management can be enhanced by control logic:
• If oil return test failed, a function can be integrated in control logic to run all compressors simultaneously during 2
minutes every hour in order to boost oil return. Time and delay can be ne-tuned by oil return test N°1 in section
Manage oil in the circuit. During oil boost, pay special attention to superheat management to avoid liquid ood
back.
• In trio system, after running long time in same state with 2 or 3 compressors, (1+2+3) or (1+2), (2+3) or (3+1), oil
unbalance may appears. A function can be implemented in control logic to stop all compressors during one
minute every two hours in order to balance oil. Time and sequence can be ne-tuned during Oil balancing test in
section Manage oil in the circuit.
4 Way Valve (4WV) stays in heating mode. EXV opened to transfer liquid from outdoor to indoor
exchanger thanks to pressure dierence.
When pressures are almost balanced
(1)
, change 4WV to cooling mode.
Start Cp1 and Cp 2 with 0.5 seconds delay between 2 successive starts
Defrost
Defrost end. Stop all compressors
4 WV stays in cooling mode. EXV opened to transfer liquid from indoor to outdoor exchanger thanks to
pressure dierence
When pressures are almost balanced
(1)
, change 4WV to heating mode.
Start Cp1 and Cp 2 with 0.5 seconds delay between 2 successive starts
Scroll compressors, DSH090 to DSH600 | Application
Defrost logic recommendations / Reversible systems
In reversible systems, the defrost logic can be worked out to limit liquid ood back eect by:
1.
Running full load during defrost to share liquid refrigerant between all compressors.
2.
Reducing refrigerant ooding to compressor by transferring liquid refrigerant from one exchanger to the other
before reversing valve thanks to pressures.
The following defrost logic combines both advantages:
Figure 63: Defrost logic advantages
In reversible systems, to ensure compressor reliability, the 4-way valve must not reverse when the compressor is
stopped due to heating or cooling demand (stop on thermostat).
(1)
(1)
EXV Opening degree and time have to be set to keep a minimum pressure for 4 way valve moving. In any case, defrost logics must respect
EXV Opening degree and time have to be set to keep a minimum pressure for 4 way valve moving. In any case, defrost logics must respect
requirements and tests described in sections Manage superheat and Operating envelope data.
requirements and tests described in sections Manage superheat and Operating envelope data.
Pump-down logic recommendations
Pump down is initiated prior to shutting down the last compressor on the circuit by de-energizing a liquid line
solenoid valve or closing electronic expansion valve. When suction pressure reached the cut-out pressure,
compressor is stopped, and liquid solenoid valve or electronic expansion valve remains closed.
Scroll compressors, DSH090 to DSH600 | Application
Two types of pump-down exist:
• One shot pump down (preferred): when last compressor of the circuit stops, suction presssure is decreased 1.5bar
(22psi) below nominal evaporating pressure with minimum of 1.7bar(g) (25psig). Even if suction pressure
increases again, the compressor will not restart.
• Continuous pump-down: traditional pump-down, Compressor restarts automatically when suction pressure
increases up to 4 cycles maximum.
Non Return Valve (NRV)
DSH090 to DSH600 compressors integrate tight internal non return valve (INRV), therefore no external Non Return
Valve (NRV) is needed.
Reduce moisture in the system
Excessive air and moisture
• can increase condensing pressure and cause high discharge temperatures.
• can create acid giving rise to copper platting.
• can destroy the lubricating properties of the oil.
All these phenomena can reduce service life and cause mechanical and electrical compressor failure.
Requirements
• The compressors are delivered with < 100ppm moisture level.
• At the time of commissioning, system moisture content may be up to 100ppm.
• During operation, the lter drier must reduce this to a level between 20 and 50ppm.
Solutions
To achieve this requirement, a properly sized and type of drier is required. Important selection criteria’s include:
• driers water content capacity,
• system refrigeration capacity,
• system refrigerant charge.
For new installations of compressors with polyolester oil, Danfoss recommends using the Danfoss DML (100%
molecular sieve) solid core lter drier.
Assembly line procedure
Compressor storage
Store the compressor not exposed to rain, corrosive or ammable atmosphere between -35°C (-31°F) and 70°C
(158°F) when charged with nitrogen and between -35°C (-31°F) and Ts max value (see section Pressure equipment
directive 2014/68/EU) when charged with refrigerant.
Compressor holding charge
Each compressor is shipped with a nominal dry nitrogen holding charge between 0.3bar (4 psi) and 0.7bar (10psi)
and is sealed with elastomer plugs.
Respect the following sequence to avoid discharge check valve gets stuck in open position:
• Remove the suction plug rst
• Remove the discharge plug afterwards
An opened compressor must not be exposed to air for more than 20 minutes to avoid moisture is captured by
the POE oil.
Remove any particles and burrs generated by tube cutting and hole drilling.
Moisture and air
Use only clean and dehydrated refrigeration grade copper tubing.
Opened compressor must not be exposed to air more than 20 minutes to avoid moisture captured by oil.
Scroll compressors, DSH090 to DSH600 | Application
Handling
Each Danfoss DSH scroll compressor is equipped with two lift rings on the top shell.
• Always use both these rings when lifting the compressor.
• Use lifting equipment rated and certied for the weight of the compressor or compressor assembly.
• A spreader bar rated for the weight of the compressor is highly recommended to ensure a better load distribution.
• The use of lifting hooks closed with a clasp is recommended.
• For tandem and trio assemblies, use a spreader bar and all compressor rings as shown in picture below.
• Never use the lift rings on the compressor to lift the full unit.
Maintain the compressor in an upright position during all handling manoeuvres (maximum of 15° from vertical).
Figure 64: Heavy
Figure 65: CorrectFigure 66: Incorrect
Figure 67: Handling
Piping assembly
Good practices for piping assembly is a pre-requisite to ensure compressor life time (system cleanliness, brazing
procedure etc.)
Table 37: System cleanliness
Brazing procedure:
• Brazing operations must be performed by qualied personnel.
• Make sure that no electrical wiring is connected to the compressor.
• To prevent compressor shell and electrical box overheating, use a heat shield and/or a heat-absorbent compound.
• Clean up connections with degreasing agent
• Flow nitrogen through the compressor.
• It is recommended to use double-tipped torch using acetylene to ensure a uniform heating of connection.
• For discharge connections brazing time should be less than 2 minutes to avoid NRVI damages if any.
• To enhance the resistance to rust, a varnish on the connection is recommended.
DSH compressors connectors are made of steel copper coated, which benet to protect against corrosion and
facilitate adhesion during brazing operation.
36.7 bar (g) (532 psig)
LP-HP<5bar (73psi)
Maximum speed 4.8bar/s (70psi/s)
(1)
34.3bar (g) (497psig)
LP – HP <5bar (73psi)
Maximum speed 4.8bar/s (70psi/s)
(1)
Scroll compressors, DSH090 to DSH600 | Application
As per standards practice in the refrigeration industry, Danfoss Commercial Compressor recommend to use of silver
cadmium free solder alloy and ux (added or ux coated rods). The signicant silver content in these brazing alloy
will help the brazing operation, providing an excellent uidity and a limited heating temperature. It will bring also a
good resistance to corrosion, a proper elongation compatible with system vibration, and good behavior under
thermal variation improving the strength of connection and limiting fractures and refrigerant leaks. (Crucial with
A2L refrigerants) A typical content of 34% Ag (Silver) is recommended by Danfoss.
The use of self-ux alloys (as phosphorous alloys) is not recommended by Danfoss. This type of brazing require a
higher working temperature, that may overheat the connectors, damaging the thin layer of copper ,resulting in
phosphides creation and joint zone embrittlement.
For more detailed information see “ Brazing technique for compressors connectors" AP192186420580.
Figure 68: Brazing procedure
Before eventual un-brazing of the compressor or any system component, the refrigerant charge must be
removed and the installation vacuumed (especially with A2L refrigerants).
System pressure test and leak detection
The compressor has been strength tested and leak proof tested (<3g/year) at the factory. For system tests:
• Always use an inert gas such as Nitrogen or Helium.
• Pressurize the system on HP side rst then LP side.
• Do not exceed the following pressures indicated in table below
Table 38: System pressure test and leak detection
(1)
(1)
The maximum pressurizing speed must be respected to ensure pressure equalization between LP and HP side over scroll elements.
The maximum pressurizing speed must be respected to ensure pressure equalization between LP and HP side over scroll elements.
Vacuum evacuation and moisture removal
Requirements:
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP and HP sides.
• Evacuate the system to a pressure of 500 μm Hg (0.67 mbar/0.02 in.Hg) absolute.
Scroll compressors, DSH090 to DSH600 | Application
Recommendations:
• Energized heaters improve moisture removal.
• Alternate vacuum phases and break vacuum with Nitrogen to improve moisture removal.
For more detailed information see “Vacuum pump-down and dehydration procedure” TI-026-0302.
Refrigerant charging
Initial charge:
• For the initial charge, the compressor must not run.
• Charge refrigerant as close as possible to the nominal system charge.
• This initial charging operation must be done in liquid phase between the condenser outlet and the lter drier.
If needed, a complement of charge can be done before evaporator, in liquid phase while compressor is running by
slowly throttling liquid in.
Never bypass safety low pressure switch.
For more detailed information see “Recommended refrigerant system charging practice“ AP000086421422.
Dielectric strength and insulation resistance tests
Several tests have been performed on each compressor at the factory between each phase and ground.
• Dielectric strength test is done with a high potential voltage (hi-pot) of 2Un +1000V AC at least, and leakage
current must be less than 5 mA.
• Insulation resistance is measured with a 500 V DC megohm tester and must be higher than 1 megohm.
Recommendations:
• Additional dielectric test is not recommended as it may reduce motor lifetime. Nevertheless, if such as test is
necessary, it must be performed at a lower voltage.
• Insulation resistance test can be done.
• The presence of refrigerant around the motor windings will result in lower resistance values to ground and higher
leakage current readings. Such readings do not indicate a faulty compressor. To prevent this, the system can be
rst operated briey to distribute refrigerant.
Do not use a megohm meter nor apply power to the compressor while it is under vacuum as this may cause
internal damage.
Commissioning
Preliminary check
Check electrical power supply:
• Phase order: Reverse rotation is obvious if the compressor do not build up pressure and sound level is abnormal
high. For DSH090-184 compressors equipped with internal reverse vent valve which can protect compressor
without damage within duration below 24h. For more details refer to section Phase sequence and reverse rotation
protection.
For DSH240 to DSH600 compressors equipped with an electronic module, reverse rotation will be automatically
detected. For more details refer to section Motor protection.
• Voltage and voltage unbalance within tolerance: For more details refer to section Motor voltage.
Scroll compressors, DSH090 to DSH600 | Application
Initial start-up
• Surface sump heaters must be energized at least 6 hours in advance to remove refrigerant.
• A quicker start-up is possible by “jogging” the compressor to evacuate refrigerant. Start the compressor for 1
second, then wait for 1 to 2 minutes. After 3 or 4 jogs the compressor can be started. This operation must be
repeated for each compressor individually.
System monitoring
The system must be monitored after initial startup for a minimum of 60 minutes to ensure proper operating
characteristics such as:
• Correct superheat and subcooling.
• Current draw of individual compressors within acceptable values (max operating current).
• No abnormal vibrations and noise.
• Correct oil level.
If Oil Top-up is needed, it must be done while the compressor is idle. Use the schrader connector or any other
accessible connector on the compressor suction line. Always use original Danfoss POE oil 160SZ from new cans. For
more detailed information see “Lubricants lling in instructions for Danfoss Commercial Compressors”
AP000086435866.
Dismantle and disposal
Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its
Danfoss scroll compressors DSH can be ordered in either industrial packs or in single packs. Please use the code
numbers from below tables for ordering.
Compressors DSH090 to DSH184 are delivered with exible grommets.
For compressors DSH240 to DSH600 use in single applications, exible grommets are available as accessory kit
8156138.
Single pack
Compressors compatible R454B, R452B and R410A
Figure 69: Single pack
Table 41: Single pack compressors compatible R454B, R452B and R410A
(1)
(1)
Electronic motor protection, module located in terminal box.
Electronic motor protection, module located in terminal box.
Mounting kit for DSH240-295-381-485 single compressor applications : Ref 8156138
Mounting kit for DSH240-295-381-485 single compressor applications : Ref 8156138
Danfoss oers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related—no matter where
you are in the world or what area of the cooling industry you work in. Get quick access to essential
information like product specs, code numbers, technical documentation, certications, accessories,
and more.
Start browsing at store.danfoss.com.
Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to
our ocial collection of data sheets, certicates and declarations, manuals and guides, 3D models
and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support
Local Danfoss websites are the main sources for help and information about our company and
products. Find product availability, get the latest regional news, or connect with a nearby expert—all
in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
Coolselector®2 - nd the best components for you HVAC/R system
Coolselector®2 makes it easy for engineers, consultants, and designers to nd and order the best
components for refrigeration and air conditioning systems. Run calculations based on your operating
conditions and then choose the best setup for your system design.
Download Coolselector®2 for free at coolselector.danfoss.com.
Ref Tools – essential tools for HVACR professionals
Get the guidance, support, information, and tools you need—on the job and in eld. Ref Tools is a
free, powerful app that contains essential tools every air conditioning and refrigeration technician
needs in their digital toolbelt.
Download Ref Tools for free at coolapps.danfoss.com
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other
technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download,
shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order conrmation. Danfoss cannot accept any
responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to
products ordered but not delivered provided that such alterations can be made without changes to form, t or function of the product. All trademarks in this material
are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.