Danfoss DSA HOME Fact sheet

Fact Sheet
DSA HOME
District heating substation up to 25 / 40 kW
1)
FEATURES AND BENEFITS
• Substation with high efficiency brazed plate heat exchangers for one family houses, made from acid-proof stainless steel
• Wall-mounted construction
• Suitable for new buildings as well as renovation projects
• Small, lightweight, compact construction
• Electronic controllers for heating and domestic hot water systems
• Fast and reliable delivery
• Fast and easy installation
• Danfoss substations and heat exchangers are manufactured according to European Pressure Directive PED 2014/68/EU
Application
The DSA HOME is designed for use in high-parameter district heating net­works. Suitable for heating single hous­es. It provides an alternative solution to an oil or gas boiler. The DSA Home is designed for heating or heating and domestic hot water. The wall-mounted construction saves space needed for installation and servicing.
Flexibility
The new DSA HOME is offered as 1- or 2- circuit module. In addition, primary modules (including ball valves, strainers, differential pressure regulators and heat meters) can be ordered as accessories. Primary modules can be connected to either the right or the left side, without any modification to the construction.
Construction / Installation
The DSA HOME is designed as a wall­mounted station. Each station is equipped with micro plate heat ex­changers manufactured by Danfoss, which significantly increase substation performance and lifetime. All compo­nents are placed at the front of the sta­tion, which makes it very easy to access them during maintenance or servicing. Due to the Euro-pallet size, it is possi­ble to transport the DSA HOME with a small van. The mounting equipment significantly reduces the time required to mount the substation to the wall. The standard station layout means that the piping can easily be prepared in the room where the substation is to be installed before the substation is deliv­ered, which reduces the time between delivery and start-up. Piping prepared with automatic welding machines ensures the highest possible welding quality.
Equipment
The DSA HOME offers a wide variety of additional accessories, such as substa­tion cover or primary modules. It can deliver with neither with ECL310 with communication functionality or with ECL110 .
Information needed for a quotation
• Heat capacities
• Temperature programme
• Permissible pressure losses in the heat exchangers / substations
• Primary pressure difference available
• Pressure losses in secondary circuits
• Flow-through hot water circulation
• Other information about other required components
1) Maximum capacity is determined by temperature, allowable pressure drops and local regulations.
www.danfoss.com
CIRCUIT DIAGRAM – EXAMPLE
G3, G4 Shut-off valve Scw Control valve DHW Sco Control valve HE Z1 Shut-off valve TM2 Thermomanometer F2 Strainer PO Heating pump Tco Temp. sensor HE ZBO Safety valve HE Tcw Temp. sensor DHW G6 Shut-off valve G9 Check valve ZBW Safety valve DHW F3 Strainer G5 Shut-off valve G8 Check valve PC Circulation pump G7 Shut-off valve FQ1 Watermeter ZUZ Refilling valve W Elastic Hose G1 Shut-off valve TM1 Thermomanometer F1 Strainer DPV dP controller LC Heatmeter
Technical paremeters
Primary side
Maximum temperature: 130 °C Nominal pressure: PN 16 Diameter (threaded): DN 20
Heating
Maximum temperature: 100 °C Nominal pressure: PN 6 Diameter (threaded): DN 20
Domestic Hot Water
Maximum temperature: 90 °C Nominal pressure: PN 10 Diameter (threaded): DN 15 / 15
Max dimensions (mm)
Width / Height / Depth (1F): 500 / 810 / 350 mm Width / Height / Depth (2F): 800 / 810 / 350 mm
Weight (incl. packing)
1-circuit station: max. 24 kg 2-circuit station: max. 35 kg
SPECIFICATION
Typ e
DSA HOME 1F-1 DSA HOME 1F-2 DSA HOME 1F-3 DSA HOME 2F-1 DSA HOME 2F-2 DSA HOME 2F-3 DSA HOME 2F-4
Capacity [kW] Control valve Heat exchanger
HE
DHW HE DHW HE DHW HE DHW
– – – –
25
40
1
800
2
VS 2 DN15 / 1,0
6 5 3 4
7
800
AVTQ 15 / 1,6
VM 2
XB06L-1-16
DN15/2,5
XB06H-1-20
Additional accessories and options:
- Primary side module (which may include ball valves, strainer, differen­tial pressure controller, heat meter, thermometers and manometers)
Connections:
1. District Heating Supply
1
2. District Heating Return
3. Heating Supply
4. Heating Return
5. Domestic Hot Water
6. Domestic Cold Water
7. Circulation
2
Pump
UPM3AUTO
15-70
– –
UPM3
DHW 15-20
Controller
ECL110
ECL310
ECL110
ECL310
© Danfoss | DHS-SMTL/ PL | 2018 .10
VL.MG.L1.02