Danfoss DSA HOME Operating guide

Page 1
Operating Guide
DSA HOME
Please always keep the instructions close to the device!
Please read the operating instructions carefully before starting any work.
Attention! Before starting up the station, please check it for proper function and free of defects!
© Danfoss |2017.09
Original instruction
VI.MG.F1.02 | 1
Page 2
DSA HOME
0.0 Table of contents
0.0 Table of contents ................................................................................................................................................................................................................................ 2
1.0 General notes ....................................................................................................................................................................................................................................... 3
1.1 Information about Operating Instructions ........................................................................................................................................................................... 3
1.2 Applicable Documents ................................................................................................................................................................................................................ 3
1.3 Explanation of symbols ............................................................................................................................................................................................................... 3
1.4 Liability and Warranty ................................................................................................................................................................................................................... 3
1.5 Copyright Protection .................................................................................................................................................................................................................... 4
1.6 Spare parts ....................................................................................................................................................................................................................................... 4
1.7 Substation disassembly ............................................................................................................................................................................................................... 4
1.8 Disposal ............................................................................................................................................................................................................................................ 4
2.0 Safety ................................................................................................................................................................................................................................................ 5
2.1 General information ..................................................................................................................................................................................................................... 5
2.2 Responsibility of substation operator .................................................................................................................................................................................. 5
2.3 Intended use ................................................................................................................................................................................................................................... 5
2.4 Possible misuse .............................................................................................................................................................................................................................. 5
2.5 Safety work ...................................................................................................................................................................................................................................... 5
2.6 Personal protective equipment ............................................................................................................................................................................................... 6
2.7 Risks associated with the substation ..................................................................................................................................................................................... 6
2.8 Emergency stop switch .............................................................................................................................................................................................................. 7
2.9 Operators ......................................................................................................................................................................................................................................... 7
2.10 Steps to follow in the event of danger or accidents ........................................................................................................................................................ 7
2.11 Residual hazards / risk analysis ................................................................................................................................................................................................ 8
3.0 Technical data ...................................................................................................................................................................................................................................... 9
3.1 Technical information .................................................................................................................................................................................................................. 9
3.1.1 CE label ................................................................................................................................................................................................................................... 9
3.1.2 Dimensions and packaging ............................................................................................................................................................................................ 9
3.2 Symbols used in circuit diagrams ..........................................................................................................................................................................................10
4.0 Function and conguration .......................................................................................................................................................................................................... 11
4.1 Function ..........................................................................................................................................................................................................................................11
4.2 DSA HOME conguration possibilities - Primary side .................................................................................................................................................... 11
4.3 DSA HOME conguration possibilities - Heating side ...................................................................................................................................................12
4.4 DSA HOME conguration possibilities - Domestic Hot Water side ........................................................................................................................... 12
5.0 Transport, packaging and storage ..............................................................................................................................................................................................13
5.1 Transport of pallets by forklift ............................................................................................................................................................................................... 13
5.2 Transport inspection .................................................................................................................................................................................................................. 13
5.3 Packaging ......................................................................................................................................................................................................................................14
5.4 Storage ..........................................................................................................................................................................................................................................14
6.0 Installation ........................................................................................................................................................................................................................................... 14
6.1 Installation preparation ..........................................................................................................................................................................................................15
6.1.1 Primary connection ......................................................................................................................................................................................................... 15
6.1.2 Secondary connection ....................................................................................................................................................................................................15
6.1.3 Electrical connection ....................................................................................................................................................................................................... 15
6.2 Packaging / unpacking the substation .............................................................................................................................................................................. 16
6.3 Substation assembly ................................................................................................................................................................................................................ 17
6.4 Draining station ......................................................................................................................................................................................................................... 18
7.0 Commissioning ..................................................................................................................................................................................................................................19
7.1 Requirements for commissioning .......................................................................................................................................................................................19
7.2 Secondary side commissioning ........................................................................................................................................................................................... 19
7.3 Primary-side commissioning ................................................................................................................................................................................................19
7.4 Requirements for commissioning .......................................................................................................................................................................................20
7.5 Fault and Shutdown .................................................................................................................................................................................................................20
7.6 Commissioning after a failure or malfunctioning ......................................................................................................................................................... 20
8.0 Operation ...........................................................................................................................................................................................................................................20
8.1 Switching on ...............................................................................................................................................................................................................................20
8.2 Switching o ...............................................................................................................................................................................................................................20
8.3 Restarting after substation shutdown ...............................................................................................................................................................................20
8.4 Service / clean - strainer ...........................................................................................................................................................................................................21
8.5 Service / disassembly and replacement - heat exchanger ..........................................................................................................................................22
8.6 Service / Check - Safety valve and expansion vessel .....................................................................................................................................................23
9.0 Maintenance ..................................................................................................................................................................................................................................... 24
9.1 Safety warning ........................................................................................................................................................................................................................... 24
9.2 Maintenance plan (recommendations) .............................................................................................................................................................................24
9.3 Heat exchanger maintenance ..............................................................................................................................................................................................25
9.4 Maintenance validation ..........................................................................................................................................................................................................25
10.0 Troubleshooting ...................................................................................................................................................................................................................... 26
10.1 Safety ...........................................................................................................................................................................................................................................29
11.0 Spare parts .................................................................................................................................................................................................................................29
12.0 Index ................................................................................................................................................................................................................................... 30
2 | © Danfoss | 2017.09
VI.MG.F1.02
Page 3
DSA HOME
1.0 General notes
1.1 Information about Operating Instructions
This manual describes the installation, operation and maintenance of the substation. Compliance with all safety and operating instruc­tions is a prerequisite for the safe operation and proper use of the substation. In addition, regulations applicable to the eld of appli­cation of the substation, local accident prevention regulations and general safety regulations must be followed. The operating manual is part of the product and must be available at all times within the immediate vicinity of the operating area of the substation for the installation, operation, maintenance and cleaning responsible of the substation.
1.2 Applicable Documents
Individual system components - unless otherwise indicated - are components purchased from other manufacturers. All components used in the substation have been subjected to their manufacturers’ risk assessments. Declarations of conformity with current European and national legislation have been made by the manufacturers of the components. Declarations of conformity, and operation, main­tenance and repair instructions for the individual components are integral parts of the substation documentation.
1.3 Explanation of symbols
Important security and device-related information in these oper­ating instructions is marked by warning notices. The instructions must be followed to prevent accidents, personal injury or property damage.
The graphic illustrations in this manual are provided to better represent the issues described, and are not necessarily to scale and may dier slightly from the actual design of the substation. In addition to these operating instructions, operating manuals for all installed components on substation must be followed. The information contained therein - particularly with regard to safety
- must be followed!
The instructions contained in the manufacturer’s documents for security, set-up, installation, operation, maintenance, and disman­tling and disposal of the components must be followed strictly.
WARNING
This symbol indicates a danger that may result in damage to health, injury, permanent physical injury or death. Please follow the notes for working safely very carefully and take extreme care in these situations!
WARNING
Electrical hazard! This symbol indicates danger from electricity. Failure to follow safety procedures can result in severe injury or death. This work may only be performed by a trained electrician.
1.4 Liability and Warranty
All information and instructions in this manual have been compiled in accordance with applicable regulations and the current status of engineering developments as well as our many years of knowledge and experience. The actual scope of delivery may dier from the ex­planations and graphic representations of special versions described here, as a result of additional accessories / order options or latest technical changes. For questions, please contact Danfoss directly. We reserve the right to make technical changes to the product in the course of improvement of its functional properties and further development. Items such as tools and equipment that may wear out during use of the device, as well as auxiliary materials and supplies such as oils, greases and detergents, are not covered by warranty.
ATTENTION
This symbol indicates a risk that may result in damage to, or malfunction / failure of equipment if ignored.
NOTE
This symbol highlights tips and information that must be followed for the ecient and trouble-free operation of the substation.
In addition, the commitments agreed in the contract, such as the general terms and conditions and the manufacturer’s terms of deliv ery, and statutory regulations at the time the contract is concluded shall apply.
NOTE
These operating instructions should be read carefully before starting work on or with the substation, and in particular before commission­ing! The manufacturer will not accept claimsfor damage or faults arising from non-compliance with these operating instructions.
-
VI.MG.F1.02
© Danfoss |2017.09 | 3
Page 4
DSA HOME
1.5 Copyright Protection
Operating instructions must be kept condential. These are intend­ed exclusively for the persons employed on and with the substation. Transfer of the operating instructions to third parties without writ­ten approval of the manufacturer is prohibited. If such approval is required, please contact Danfoss directly. This document and any others delivered with the substation are pro­tected by copyright. Copies (whether whole or in part) are allowed only with the permission of the manufacturer. Violators will be liable to prosecution. All other rights reserved.
1.6 Spare parts
Use only original spare parts from the manufacturer. The use of non-approved spare parts will invalidate any guarantees, or service, compensation and liability claims against the manufacturer or its agents, distributors and representatives.
1.7 Substation disassembly
Clean and sort the substation parts and components in compliance with applicable health and safety and environmental regulations. Before starting disassembly:
• Switch the unit OFF and secure against being switched ON again.
• Ensure that the entire energy supply is physically separate from the substation and that stored residual power is properly discharged.
• Remove supplies and materials as well as any remaining processing materials in an environmentally friendly manner.
NOTE
Contents of this instruction – texts, drawings, images or other illus­trations are copyrighted and subject to other intellectual property rights. Any improper reuse is forbidden.
ATTENTION
Using the wrong or faulty spare parts can lead to damage, malfunction or total failure of the substation.
WARNING
Risk of injury! Stored residual power, components with sharp edges, edges and corners on and inside the substation or necessary tools can cause personal injury. Any substation removal work must there­fore be carried out only by a specialist.
1.8 Disposal
If no withdrawal or waste management agreement has been con­cluded, disassemble the dismantled components for recycling:
• Metal to scrap material
• Plastics to plastics recycling
• To dispose other components, sort by material properties
• Remove any residual media and dispose of properly media with additives (e.g. glycol) must comply with relevant legislation
Remove operating materials such as lubricants, oils, fats, cleaning agents and inhibitors from the substation in an environmentally friendly manner . In this case, use a suitable, approved container for lubricants. Mark the container with information about the content and level, and date clearly. Secure nal disposal of the materials so that improper use is excluded.
WARNING
Do not drink! Water in the installation which has not been used for a long period of time may not meet the quality standard for drinking water in certain conditions. Prevent such use and drain or dispose of water used to run the substation.
WARNING
Electrical and electronic components, lubricants and other excipi­ents must be handled by hazardous waste treatment plants and may only be disposed by approved specialist companies!
4 | © Danfoss | 2017.09
VI.MG.F1.02
Page 5
DSA HOME
2.0 Safety
This section gives an overview of all the important security aspects of optimal protection of personnel as well as of safe and trouble­free operation of the substation. In addition, these chapters include specic safety symbols in order to avert immediate safety hazards.
2.1 General information
Substation is built at the time of its development and manufactur­ing according to existing, accepted engineering standards and is safe to operate. The substation can be dangerous if used by improperly trained personnel or used improperly or by unauthorised persons. Any person authorised to work on or with the substation must read and understand the operating instructions before starting work. We recom­mend advising the operator to obtain conrmation from sta proven understanding of the instruction manual. Modications of any kind as well as additions or modications to the substation are forbidden. All substation security, warning and operating instructions must be maintained in good legible condition. Damaged labels or stickers must be replaced immediately. Specied values or ranges must be strictly adhered to.
2.2 Responsibility of substation operator
NOTE
For modication and extension activities, always consult with the substation manufacturer.
• Operating instructions must always be stored within the immediate vicinity of the substation and must be accessible at all times for installation, operation and maintenance and to cleaning sta.
• Operate the substation only if it is in a proper technical and safe operating condition.
• Check that safety devices are always kept freely accessible test them regularly.
Information about industrial safety is based on the European Union regulations valid at the time of manufacture of the substation. The operator is obliged throughout the entire lifetime of the substa­tion to conform to those safety actions designated in the current rules and regulations and to comply with those in new regulations. Outside of the European Union, the safety laws, local rules and regulations applicable to the location where the substation oper­ates must be followed.
2.3 Intended use
Operational safety is guaranteed only where the substation is used properly and in accordance with the instructions / details in this manual. A district heating substation is used to provide heat energy from the district heating utility grid by transferring heat to customer installation systems. Intended use also includes compliance with instructions for installation, operation, maintenance and cleaning.
2.4 Possible misuse
WARNING. Hazard from improper use!
Any use of the substation apart from its intended use may lead to dangerous situations.
2.5 Safety work
In addition to the safety instructions in this manual, and for sub­station safety in general, accident prevention and environmental protection regulations must be observed and followed. The opera­tor and authorised personnel are responsible for the trouble-free operation of the substation, as well as for the clear denition of re­sponsibilities for installation, operation, maintenance and cleaning of the substation. There must be no deviation from the information in the operating instructions! The operator shall also ensure that:
• Any further risks are identied in an assessment of risks arising from the special working conditions at the operations site.
• That any additional work and safety instructions resulting from the risk assessment of activities performed on the substation are described in a standard operating procedure (SOP).
Always follow local regulations as well as any existing ordinances on industrial safety and health (e.g. in Germany: BetrSichV, BGBL I 2002, 3777).
Any additional and / or other use of the substation is forbidden and considered as improper use! Any claims against the manufac­turer and / or its representative for any loss or damage as a result of improper use of the substation are excluded. The operator and / or owner shall be solely liable for any damage arising when the substation is used for any purpose other than.
Therefore:
• Use the district heating transfer station only for its intended purpose and in accordance with the information provided in this document, particularly the limitations given in the technical data.
• Avoid any further or other use of the district heating transfer station.
• It is forbidden to change, upgrade or modify the design or individual components for the purpose of changing the station’s range of usability or application.
Hazards to persons and / or the system can be prevented by fol­lowing the safety at work instructions.
VI.MG.F1.02
Failure to follow these instructions can result in mechanical or equipment failure that poses adanger to persons and goods and the entire workplace. Failure to comply with safety regulations will invalidate any warranty.
© Danfoss |2017.09 | 5
Page 6
DSA HOME
2.6 Personal protective equipment
While working on and with the substation the following must be worn at all times:
Protective clothing
is close-tting work clothing with low tensile strength and tight sleeves and without protruding parts. Its main purpose is to guard against snagging on moving machine parts. Do not wear rings, chains or other jewelry.
Protective gloves
to protect the hands from friction, abrasion, puncture or deeper injury as well as from contact with hot surfaces.
2.7 Risks associated with the substation
Protective goggles
to protect the eyes from ying parts and liquid splashes.
Safety shoes
to protect from heavy falling parts and losing traction on slippery surfaces.
Helmet
to protect against falling or ying parts and materials.
The substation has been subjected to a risk analysis based on the design and construction of the substation and in correspondence with the current state of technology. Nevertheless, risks remain! The substation can generate a hot stream of uid or steam when e.g. adrain or air vent is opened.
WARNING! Risk of injury!
Risk from liquids splashing under high pressure. Wear personal protective equipment for all operations carried out on the sub­station!
The substation operates with high electrical voltages of up to 400 V and currents of up to 25 A.
WARNING! Electrical shock hazard!
Electrical energy can cause serious injury. Damaged insulation or components can lead to serious injury or death.
• Switch OFF the main switch and secure against reconnection before performing any maintenance, cleaning or repair.
• Turn o the power switch when performing any work with the electrical system
• Do not remove any safety devices or put out of operation
WARNING! Risk of injury!
Risk from liquids splashing under high pressure. Wear personal protective equipment for all operations carried out on the sub­station!
Therefore:
• Depressurise before starting any work on the substation.
• Do not remove or alter any safety devices or put out of service.
• Do not change the default settings from the values or beyond the tolerance ranges specied in the operating manual
The substation has sharp edges and corners.
WARNING! Risk of injury!
Sharp-edged parts and sharp edges may cause abrasion to the skin. Wear protective gloves when working on the substation.
WARNING! Risk of burns!
Hot surfaces can cause serious burns. For all operations carried out on the substation always wear protective gloves!
Components inside of the station can contain automatically moving parts (pumps, actuators, etc.). The devices can be very heavy.
WARNING! Danger of crushing!
During transport or lifting of the substation, bruising can occur due to heavy weight. The substation may include electrical com­ponents (engines, transmissions) which may also cause bruising if contacted while in operation. For all operations carried out on the substation, always switch the main supply OFF and wear pro­tective clothing.
6 | © Danfoss | 2017.09
VI.MG.F1.02
Page 7
DSA HOME
2.8 Emergency stop switch
The operator shall ensure that the emergency stop switch is installed in accordance with applicable accident prevention regulations. The operator must inform operations sta about the location and opera­tion of the emergency stop switch.
2.9 Operators
The substation may be operated and maintained only by authorised, trained and instructed personnel. These personnel must receive spe cial training on potential risks. An “instructed person” is a person who has been informed of the tasks assigned to him/her and the potential hazards of improper usage and, if necessary, who has been trained and instructed in protective equipment and actions. A “professional” is a person who, because of his/her technical train­ing, knowledge, and experience, as well as his/her knowledge of the relevant provisions, can evaluate the work transferred to him/her and recognise possible dangers. If the sta do not have the knowledge required, then they must be trained. Responsibilities for operation and maintenance must be clearly dened and respected so that there is no unclear division of responsibilities in terms of safety.
2.10 Steps to follow in the event of danger or accidents
In the event of an emergency or accident, the substation must be switched OFF by immediately pressing the emergency stop switch. This can be done by opening the safety door or protective window equipped with safety switches that trigger the emergency stop func­tion when opened. Safety devices with an emergency stop function are only to be used in appropriate situations.
The substation may only be operated and maintained by persons
-
who can be expected to reliably run their work. Any operation that aects the safety of persons or the substation environment must be avoided. Persons under the inuence of drugs, alcohol or medication that aects responsiveness must not perform any work with or on the substation. When selecting personnel, the relevant country’s youth employment protection regulations as well as any occupation­specic regulations that may exist must be followed with respect to minimum age. The operator must ensure that no unauthorised persons are work­ing on or with the substation. Unauthorised persons such as visi­tors, guest etc., must not come into contact with the substation. You must maintain a reasonable safety distance. The user is obliged to immediately report any issues which occur in the substation and may aect the safety of the operator.
Safety equipment must not be used for normal shutdown of the substation. Always be prepared for accidents or re! Keep rst-aid equipment (rst-aid kit, eye wash, etc.) and a re extinguisher within the substation area. Personnel must be trained in the handling and location of safety devices, accident procedures, rst aid and rescue equipment. This results in the prevention of dangerous situations and ensures the best possible assistance in the event of an accident.
VI.MG.F1.02
© Danfoss |2017.09 | 7
Page 8
DSA HOME
2.11 Residual hazards / risk analysis
Risk place Risk type Protective aim Measure
Shut-o valves and ttings
in the station
Piping and components
in the station
Entire station Electric shock Safe contact with the station Fullment of contact protection
Entire station
Entire station
During operation, residual risk can be limited to the following al­phabetic values according to the Suva (Assessment and Reduction of risks from machines) risk assessment: B5/C4/D3/E2. The residual potential for danger arises from failure to comply with the above instructions. The assembly has been manufactured according to the explicit specications of the customer, who is responsible for com­pliance with the parameters specied and the selection of qualied operating personnel. The substation is equipped with the following warning on which the key residual risks are point out again:
Crushing during
manual operation
Burning when touched Safe contact at the station
Splashing of liquids and/or
steam at high pressure
Overheating the station
or transmitting heat to a connected system at
a temperature above
what is permissible
Manual operation of the
shut-o valves and ttings
must be safe
Controlled reduction of excess
pressure in case of fault
Turning o the heat supply
in case of failure
Due to construction, provide enough space for ergonomic
operation
Thermal insulation of pipes
and components, signs at the
station, warnings in the
operating instructions
Protection according to local
standards or legal regulations
(e.g. DIN 4747 T1 or DIN EN 12828)
Protection according to local
standards or legal regulations
(e.g. DIN 4747 T1 or DIN EN 12828)
Operation of this substation is permitted only by trained personnel after detailed study of the enclosed documentation. The system must be lled and completely vented before commissioning. Do not exceed the maximum allowable working pressure or maximum allowable operating temperature specied on the label. Any use other than the proper use is prohibited.
Risk of burns from touching or from the release of hot media (water/steam). Avoid touching the substation or wear suitable protective clothing!
Risk of crushing during assembly and operation.
Risk of electric shock. Check that the substation is disconnected before working with the electrical system.
All ange and threaded connections, ttings, electrical clamps and screw connections must be checked and tightened as necessary before lling or commissioning. Run pumps only when lled with water (no dry run!)
Before starting up the substation properly install the following (unless fully assembled in factory):
- Safety valve, drain and air vent according to EN12828 or EN806, unless local standards are available.
- Strainer in the primary ow and secondary return pipeline
- Equipotential bonding according to IEC60364-4-41:2005 (grounding / protective conductor / potential equalisation), unless local standards are available (e.g. DIN VDE 0100:540:2012-06)
8 | © Danfoss | 2017.09
VI.MG.F1.02
Page 9
DSA HOME
SUBSTATION
MANUFACTURER
ID NO./PRODUCTION DATE
CODE/TYPE
PURPOSE OFUSE
PED CATEGORY POWR SUPPLY VOLTAGE
PRIMARY SECONDARY SECONDARY SECONDARY SECONDARY
HEATING DHW
PN CLASS 16 6 10
MIN / MAX TEMPERATURE TS °C 5/130 5/90 5/60
MAX ALLOWED PRESSURE PS b ar 14,3 6 10 CAPACITY kW 65 25 40
TEMPERATURE PROGRAM °C 130-72/70-90 70-27/5-60
HEAT EXCHANGER XB06L-1-16 XB06H-1-20
FLOW m3/h 0,392/1,096 0,818/0,624 PRESSURE DROP HEX bar 0,02/0,10 0,14/0,08
MADE IN POLAND
Danfoss A/S, Nordborgvej 81, 6430 Nordborg, Denmark
1000288607/2017/29
146B8015/DSA HOME 2F-3
Heating / Domestic Hot Water
2014/68/EU Article 4.3
1 x 230V
3.0 Technical data
3.1 Technical information
Main substation information can be found on the CE label as well as in documents contained in the appendices (circuit and electrical diagram, data sheet).
3.1.1 CE label
The CE label is attached to the substation. It contains the following information:
• Manufacturer
• Serial no.
• Production date (year / calendar week)
• Substation code / Type (Name)
• Applications
• Category according to PED directive
• Power supply voltage
• PN class
• Minimum and maximum operating temperatures
• Maximum allowed pressure by maximum operating temperature
• Capacity
• Temperature programme
• Heat exchanger type
• Volumetric ow
• Pressure drop inside heat exchanger
3.1.2 Dimensions and packaging
The maximum substation delivery dimensions are 810 × 800 × 350 [mm]. The range of standard product dimensions and weights can be found in the technical datasheet.
The DSA HOME is delivered to customer on standard Euro pallet, which ensures trouble-free transport to the customer. in addition whole station is covered with foiled carton box.
max. 810
max. 350max. 800
Figure 1: DSA HOME external dimensions
VI.MG.F1.02
Figure 2: DSA HOME packaging
© Danfoss |2017.09 | 9
Page 10
DSA HOME
3.2 Symbols used in circuit diagrams
Pressure transmitter
10 | © Danfoss | 2017.09
VI.MG.F1.02
Page 11
DSA HOME
4.0 Function and conguration
4.1 Function
The DSA HOME is an indirect compact substation, where heat trans­fer from the district heating network to a secondary installation is realised via plate heat exchangers. This solution ensures hydraulic system separation.
The basic idea of heat transfer in a compact substation is connect­ing the primary side of the piping to the district heating company’s network, which supplies hot water within the appropriate parameters (such as for pressure and temperature), and the secondary piping to the customer’s installation on the other side. Network parameters may vary depending on the season and may be higher during the winter season and lower during the warmer months. Primary medium ow normally through shut-o valve and strainer, located inside primary module. In addition for pressure and temperature measure­ments, usually pressure gauge and thermometer are assembled, if it is needed according to the specication of District Heating Utility on primary ow and/or return pipe. The control valve with actuator is located on the primary supply pipe . Cooled heating water ows back through the primary return piping to the district heating network.
4.2 DSA HOME – Primary Side
Due to the dierent market requirements, the basic conguration includes only control valves with actuators located on the primary supply piping (pos. Scw, Sco). Shut o valve (G3, G4) are placed on return piping. Flat gasket connection ensures long lifetime and easy maintenance.
In the secondary circuit circulating pump transfers heated water to the heating surfaces of other installations (e.g. ventilation equip­ment, drinking water or heating installations, etc.). Several heating circuit control valves are installed to allow adjustment of secondary temperatures on specic heating circuits. If a controller with weather compensation is installed at the substation, it has the following es­sential functions:
• Measures ow temperature on the secondary side and outside temperature
• Changes the stroke of the control valve on the primary side so that it conforms to the required secondary temperature
• Limits the return temperature on the primary side to a value preset in the controller
• Switches the secondary side circulating pump(s) on and o as necessary and ensures frost protection
If required, special functions are available according to needs and designs. Refer to the instruction manual of the controller manufac­turer. All substations are oered upon request and manufactured in keeping with the customer’s special operating conditions.
Due to its xed dimensions and standardised connections it is easy to connect an additional primary module or prepare installations well before substation delivery. The composite at gasket allows for a durable and leakage-free connection. The primary side based on DN20 piping.
The DSA HOME conguration is based on micro plate heat exchanger technology. In comparison with traditional heat exchangers, it en­sures better heat transfer and reduced pressure loss. This results in alonger system life span and better reliability.
Figure 3: DSA HOME Primary side conguration
VI.MG.F1.02
© Danfoss |2017.09 | 11
Page 12
DSA HOME
4.3 DSA HOME conguration possibilities – Heating side
The heating side of the DSA HOME oers piping up to DN20, which allows the transfer of medium suitable for one family house on awall­mounted construction. The base conguration includes:
• threaded shut-o valves (pos. Z1, Z2)
• strainer (pos. F2)
• pump (pos. PO)
• surface sensor (pos. Tco)
• safety valve (pos. ZBO)
• thermomanometers (pos. TM2)
A visual parameter such as temperature and pressure can be meas­ured with a thermomanometer (pos. TM2). The safety valve (pos. ZBO) is located on the supply (4). Heating pump (pos. PO) is located on return piping, to ensure longer lifetime as working temperature is lower. Surface sensor (Tco) check temperature on supply pipe and via controller increase or reduce the ow on primary side.
4.4 DSA HOME – Domestic Hot Water side
Figure 4: DSA HOME heating conguration
The basic domestic hot water conguration includes shut-o valves (pos. G5, G6), which allows to shut o DHW circuit. The temperature sensor (pos. Tcw) connected to the controller makes it possible to keep the temperature at a requested level. Brass-threaded strainer (pos. F3) protect dirt-sensitive components such as the pump (pos. PC) and heat exchanger from impurities. Check valves (pos. G8, G9) prevent components from being damaging by backow and can prevent anon-hygienic situation. Pressure and temperature measure­ment can be made by thermomanometers.
The domestic hot water piping is prepared from a combination of stainless steel components and brass ttings. Due to the use of high performance plate in the heat exchanger and a pipe size of up to DN15, the DSA HOME is suitable for one family houses.
Figure 5: DSA HOME Domestic Hot Water conguration
12 | © Danfoss | 2017.09
VI.MG.F1.02
Page 13
DSA HOME
5.0 Transport, packaging and storage
Follow general safety rules during transport:
• Adapt transportation to local conditions
• Use only approved lifting gear and lifting equipment with adequate load capacity
• Only attach the substation to suitable anchor points and not to protruding machine parts or eyelet components. Ensure the secure t of the slings!
• Ropes and belts must be equipped with a safety hook. Do not use damaged or frayed cables. Do not fasten ropes or straps to sharp edges or corners and do not knot or twist. Always consider the centre of gravity before handling
• Never lift, pan or lower loads over people
• Always transport the substation with the utmost care and caution
• During vessel transport especially bear in mind that: insulation must not be damaged during transport or removed (especially when transporting over longer distances)
• Ensure suitable means of transport so that no deformation arises on connections or vessel
• Avoid direct contact with ferrous materials or surface destruction of stainless steel vessels
5.1 Transport of pallets by forklift
Packages mounted on pallets can be transported by forklift under the following conditions:
• The forklift must be designated according to the weight of the handling units
• Operator must be authorised (licensed) to operate the forklift
Procedure:
1. Drive the forklift with the forks between or under the tie bars of the pallet
2. Drive the forks far enough to protrude from the opposite side of the pallet
3. Make sure that the centre of gravity is between the forks and cannot tilt
4. Lift the package and start transport
WARNING! Danger to life!
When lifting, panning and lowering ,there is a risk of serious personal injury and damage from falling parts. Never stand under suspended loads!
WARNING! Danger to life!
When lifting, panning or lowering, there is a risk of serious personal injury and damage from falling parts. Never stand under suspended loads!
Follow safety rules:
• Use only approved lifting gear and lifting equipment with adequate load capacity
• Only attach the substation to suitable anchor points and not to protruding machine parts or eyelet components. Ensure the secure t of the slings!
• Ropes and belts must be equipped with a safety hook. Do not use damaged or frayed cables. Do not fasten ropes or straps to sharp edges and corners and do not knot or twist. Always consider the centre of gravity before handling
• Never lift, pan or lower loads over people
• Always transport the substation with the utmost care and caution
5.2 Transport inspection
Immediately after delivery check for completeness and any trans­portation damage. In case of externally visible transport damage, do not accept delivery or accept only conditionally. Note the extent of damage on the transport documents / bill of delivery. Initiate acom­plaint. Claim defects that are not visible immediately after detect­ing, as claims for damages can be made only within the applicable complaint periods.
VI.MG.F1.02
© Danfoss |2017.09 | 13
Page 14
DSA HOME
5.3 Packaging
Substations are delivered with dierent types of packaging. Pack­aging materials are primarily of wood, cardboard and plastics (foil, foams). Strapping is in addition. Packaging material may also include materials added to packages for moisture or frost protection (e.g. silica gel bags, antifreeze, etc.). If no agreement has been made re­garding the return of packaging material, the packaging material remains with the customer.
Our transport packaging can be returned to us, free of delivery charges, at:
WARNING!
Unpaid delivered transport packaging will not be accepted by us.
Danfoss Poland Sp. z o.o. Tuchom, ul. Tęczowa 46 80-209 Chwaszczyno
5.4 Storage
After packages have been unloaded they must be stored until assem­bly in accordance with the attached shipping marks. Machine parts and accessories packaged in separate boxes must not be unpacked.
For storage, the following rules apply:
• Dry storage. Relative humidity: up to 60%
• Ensure that packages are not stored outdoors. In addition, ensure that the storage room oor is dry during storage
• Keep out of direct sunlight. Optimal storage temperature 15 to 25 C°
• Keep dust-free
• Avoid mechanical vibrations and damage
• For long-term storage of more than three months, conservation activities should be taken In severe weather conditions, conservation must be renewed as necessary
6.0 Installation
WARNING! Risk of injury!
Improper installation and assembly can result in serious injury and / or property damage. Installation and assembly work may be performed only by qualied personnel in compliance with safety regulations.
District heating transfer stations are completely pre-piped and wired installations on a frame. All parts and components are mounted or xed to the frame. External substation connections are marked with easily understandable labels / stickers.
Secure durability of ground based on total weight of equipment (including water content). Take care that each connection is stress­free after assembly; the substation cannot be used as a xed point.
Packaging materials must be utilised in an environmentally friendly way and in accordance with the relevant waste disposal regulations.
If substation parts or components must be removed due to limited space for transport (corridors, elevators, small doors etc.), ensure that they are reassembled exactly as they were in the original place.
NOTE!
The mechanical separation of substation components through sawing, cutting, etc. of cabling and / or frame parts and piping is not permitted.
Pipe connections and tting connections can be prepared as:
• Threaded connections acc. DIN 2999 (internal / external)
• Threaded connections acc. DIN 2993/ISO 228 (external)
NOTE!
The use of pipe wrenches for nuts and bolts is not permitted. Only use a suitable spanner!
14 | © Danfoss | 2017.09
VI.MG.F1.02
Page 15
DSA HOME
6.1 Installation preparation
Substation installation should be carried out on a clean, at surface.
The DSA HOME must be assembled and mounted onto the wall with the appropriate screws and dowels found in the loose components box.
6.1.1 Primary connection
The primary connection must be made by qualied personnel in consultation with local / district heating supply companies if the installation is connected to such network. The primary supply and return must be connected to the designated devices or the substa­tion shut-o valves.
The commissioning of primary side connections to the district heat­ing network is usually done by the relevant local / district heating company.
• If substation is delivered (ordered) without a strainer on primary inlet site, make sure it is separately mounted before substation is connected to the network to protect all components from potential damage. If this requirement is not respected it may result in loss of warranty.
• After installation of substation to the network it is required to splash pipes between main strainer and substation to remove any potential particles.
NOTE!
Check the durability of wall material before installing.
6.1.2 Secondary connection
A specialised installation company connects the secondary installa­tion to the substation’s designated shut-o valve.
6.1.3 Electrical connection
Only a qualied electrician approved by a responsible electric utilities company may carry out the electrical installation of the substation in compliance with all applicable rules and regulations. The substation is completely wired and tested at the factory by default. If an outdoor sensor for substation control is ordered, this is enclosed in the loose component box and should be installed as far as this is possible on the north side of the building.
WARNING! Risk of injury!
Improper installation and assembly can result in serious injury and / or property damage. Installation and assembly work may be performed only by qualied personnel in compliance with safety regulations.
VI.MG.F1.02
© Danfoss |2017.09 | 15
Page 16
DSA HOME
6.2 Packing / unpacking the substation
The packaged product is supplied with a standard Euro pallet and is easy to transport by truck or forklift.
Remove the protective foil and unscrew the substation from the pallet.
Before moving the station, identify the handling point. The substation must not be transported with piping due to risk of damage.
16 | © Danfoss | 2017.09
VI.MG.F1.02
Page 17
DSA HOME
6.3 Substation assembly
Fix the support bracket to the wall with the attached screws.
Place the station on the support bracket and x the main frame to the wall. The substation must not be connected to the piping without screwing main frame to wall.
VI.MG.F1.02
© Danfoss |2017.09 | 17
Page 18
DSA HOME
6.4 Draining station
Locate the drain valves on the specic circuit which you would like to empty.
ATTENTION!
To drain the primary side, always close the shut-o valve on the district heating connection.
NOTE!
To drain only the substation and not the whole installation, close the shut-o valves on the substation.
If the drain pipe is not connected to the drain valve, connect the ap­propriate hose or piping in accordance with local legal regulations.
WARNING! Risk of injury or damage!
Never operate the drain valve when the outlet is directed towards you or electrical devices. Always secure all equipment so that it is not ooded by accident. Before any operation always ensure that the water has cooled suciently.
Open the drain valve and wait until the circuit concerned has emptied. Immediately after draining, close the valve.
WARNING! Risk of injury!
Even after draining, there may still be water inside the heat ex­changer and piping.
18 | © Danfoss | 2017.09
VI.MG.F1.02
Page 19
DSA HOME
7.0 Commissioning
The following actions must always be carried out only after com­missioning:
• Initial start-up of the substation (see commissioning protocol in the attached annex)
• Restarting after complex substation maintenance
• Restarting after the implementation of a new device
• Restart following a malfunction of the substation
• Restarting after shutdown or longer downtime
Installation and initial commissioning of the substation is carried out by approved employees of the manufacturer or authorised partner companies. Typically the local utility company is must be involved in work relating to heating connections. Typically the district heating utility must be involved in work relating to primary connections. Unauthorised initial start-up is not allowed.
7.1 Requirements for commissioning
In order to commission the station the following conditions must be met:
• Commissioning must be approved by the district heating utilities
• All screws and fasteners must be tightened
• Substation piping must be connected properly
• All impurities and leftover installation materials must be removed from the piping
• The station must be properly connected to electricity: the supply voltage must be applied to the main switch or circuit breaker
• The primary connection must be applied to the primary shut-o valves within the necessary parameters
Following installation, initial start-up and the execution of test runs by the manufacturer or its authorised representative, the substation is handed over to the operator. Afterwards, the substation is operated as intended in accordance with the instructions in the Operator’s Manual. Installation and commissioning of the substation can be performed by employees of the manufacturer, installers authorised by it or by a specialised installation company. In any case, the exist­ence of a fully completed commissioning protocol (see annex) is aprerequisite for maintaining a substation warranty.
• The secondary installation should be lled (including the substation) and vented (venting pumps are necessary)
• Pressurisation must be ready with the required base pressure
• Desired time programmes and additional data for controller set-up must be available
• The substation may only be put into operation when an authorised specialist from the district heating company or an expert from an installation company or an authorised specialist from the commercial oce has approved the correct condition of the whole system.
7.2 Secondary side commissioning
Before commissioning, check that all safety-related rules and regula­tions have been taken into account.
Working parameters for the substation’s plate type must match the operating parameters of the local / district heating company and the heating system. Fill the secondary installation with water accord­ing to the water quality rules. To avoid substation damage, ensure that pressure during lling does not exceed the maximum allowable working pressure. Before rst use, the secondary side must be rinsed suciently by the installation company. Check all connections for leaks and tightness. Fill the secondary installation to the required static pressure.
7.3 Primary-side commissioning
All work on the primary side of the system must be carried out in coordination with the local / district heating company by suitably qualied and trained personnel. Fill the substation by slowly open­ing the shut-o valve on the primary supply. Also slowly open the shut-o valve on the primary return. Manually adjust the electronic controller to the “valve open” position.
If the medium is water, set the ow / pressure dierential regulator or pressure regulator (if available) to the maximum ow rate according to capacity or preset dierential pressure. Than set up the pressure regulator, if there is one, to the designated value. Check all connec­tions for leaks and tightness, and retighten with the required torque if necessary.
Rinse the primary site with the district heating medium and reclose the shut-o valves. Clean the strainers and adjust the electronic controller in accordance with the designated values in the enclosed supplier instructions.
VI.MG.F1.02
© Danfoss |2017.09 | 19
Page 20
DSA HOME
7.4 Requirements for commissioning
The electronic controller is preset in the factory in accordance with the data available to us. After commissioning, the controller auto matically performs a self-test, displays a default system code and automatically goes into operating mode. Now a precise setting can be made in accordance with the controller manufacturer’s manual can be made. The manual is attached to the station.
7.5 Fault and Shutdown
The heating controller, control valve actuator and heating pump are connected to mains voltage. Therefore:
- Immediately turn o the main switch or unplug the power cable
- Close the second shut-o valves on the primary and secondary side
- A specialist company must be consulted for troubleshooting
-
WARNING! Electric shock hazard!
Leaking water can subject the entire substation to dangerous volt­age. Before starting any work, switch the power OFF and ensure that it cannot be turned back on.
7.6 Commissioning after a failure or malfunctiong
After a failure on the primary side, always contact the local or district heating company. Recommissioning is to be carried out by a special ist company.
After a failure on the secondary side contact a specialist company. Recommissioning is to be carried out by the specialist company.
8.0 Operation
The substation works in fully automatic mode. During operation, no personnel are required either in the area of the substation or within its immediate vicinity.
8.1 Switching on
To turn the substation on, follow the requirements in the “Commis­sioning” chapter 7. The substation can be turned on at the main switch of the electronic controller and will start to operate automatically.
8.2 Switching o
The substation can be turned o at the main switch of the electronic controller and will stop automatically.
WARNING! Risk of burns!
In case of leakage on the primary side, the medium may escape as steam at a temperature of more than 100°C. Danger of burns.
-
8.3 Restarting after substation shutdown
If the substation is to be turned o for a long period of time (i.e. without power) in order to save energy, then proceed with restart as for the rst commissioning. Flushing of the system is recommended.
20 | © Danfoss | 2017.09
VI.MG.F1.02
Page 21
DSA HOME
8.4 Service / clean – strainer
Before you begin cleaning, perform the actions described at point 2 (draining the system) and check that no components will collide when removing the mesh.
Secure the electrical components below strainer level with a metal sheet or foil.
Use a suitable at spanner to unscrew (counterclockwise) the cap from the strainer, remove the mesh and clean it. Before closing the strainer check the seal (for tightness and integrity). If necessary, re­place it.
WARNING! Risk of injury!
Even after draining, there may still be water inside the strainer.
VI.MG.F1.02
© Danfoss |2017.09 | 21
Page 22
DSA HOME
8.5 Service / disassembly and replacement – heat exchanger
Before you begin any activities with the heat exchanger perform the actions described at point 2 (draining the system).
Gently remove the PUR insulation by pulling it.
NOTE!
Seeger Circlip Ring Pliers must be used to remove the heat exchang­er. This tool is not provided with the substation.
Use a suitable at spanner to unscrew the piping from the heat ex­changer and heat exchanger from the backplate.
WARNING! Risk of injury!
Even after draining, there may still be water inside the heat ex­changer and piping.
After releasing the heat exchanger, push it back and front.
22 | © Danfoss | 2017.09
VI.MG.F1.02
Page 23
DSA HOME
8.6 Service / Check – Safety valve and expansion vessel
Locate the safety valves on the secondary side (these are separate on the heating and domestic hot water circuit). If the drain pipe is not connected to the safety valve, connect the appropriate hose or piping in accordance with local legal regulations.
WARNING! Risk of injury or damage!
Never operate a safety valve when the outlet is directed towards you or towards electrical devices. Always secure all equipment so that it will not be ooded by accident.
Turn the lifting handle in the direction of the arrow until you hear aclick. Then the valve must be closed tight.
NOTE!
If a valve drips constantly, it is very likely that impurities have built up in the seat. To clean the valve seat and seal, unscrew the head part.
VI.MG.F1.02
© Danfoss |2017.09 | 23
Page 24
DSA HOME
9.0 Maintnance
9.1 Safety warning
In the appendix you will nd a summary of the most important tech­nical requirements. It is recommended to hire an authorised installer for frequent maintenance.
The most important actions for main components and assemblies are summarised under section 9.2. Other instructions for components not specied in this installation manual can be found separately in the accessory box and must be observed.
WARNING! Risk of injury!
In principle work may be carried out only by qualied and specially trained personnel. Avoid loosen tight clothing (no loose sleeves, rings, etc.). Always wear the following personal protective equip­ment in the vicinity of the substation:
- Safety glasses to protect the eyes from ying parts and uids
- Safety footwear for protection against heavy falling objects and slipping on slippery surfaces
WARNING! Electrical shock hazard!
Work on electrical equipment may only be carried out by a qualied electrician in accordance with the safety regulations. Switch OFF the electrical supply before starting work and secure against reconnection.
9.2 Maintenance Plan (recommendations)
Interval Maintenance Comments
Check all connections If necessary re-tighten and / or replace seals
Every 2 months
Every 6 months
Every 12 months
Check all parameters to nominal / actual values or admissibility
Cleaning of strainers If necessary, refer to point 8.4
General visual inspection of all components
Perform a functional test of the safety valve
Perform a functional test of the electrical and elec­tronic components, switches and so on
Perform an electrical test of the safety devices Temperature monitor, sensors and / or limiters
Clean strainers
Perform a functional and usability check of all components
Perform a visual inspection of substation’s appear­ance
Control of the heat exchanger
Perform a visual inspection of the heat meter and water meter
Perform a visual inspection of the measuring devices
Perform a visual inspection of the expansion vessels
If excessive, restore proper parameters
In case of visible damage, perform a functional test and if necessary replace the component
Open the safety valve for a short period of time. Refer to point 8.6
Manually switch the pump or open and close the actuator
For example, open and close the shut-o valves
Colour (rust), insulation
In case of contamination, clean / descale (refer to point 9.3) as needed
Check legalisation period
Manometer, thermometer
Shape of vessels, tamper head, tightness of the membrane
24 | © Danfoss | 2017.09
VI.MG.F1.02
Page 25
DSA HOME
9.3 Heat exchanger maintenance
The following is a list of important activities that should be performed during maintenance. Additional information is included in the at­tached manufacturer’s instructions.
This abstract only provides information about the required steps. It is important in any case to comply with all relevant legal and tech­nical regulations and requirements pertaining to local conditions and regulations (e.g. the home owner, district heating utilities, etc.)
Fittings: In general, the ttings used are maintenance free. During mainte­nance, the functionality of hand wheels or levers should be tested in terms of ease of use by opening and closing. This will protect the ball, plates and valve seats against dirt and limescale deposits. See the manufacturer’s instructions for the most common components in Annex I.
Heat exchanger: Heat exchangers are designed for long-term use. Due to relatively high temperatures, in particular cases lime and other deposits may appear on the inner surface. In case of reduced performance, the heat exchanger should be cleaned. For detailed information, please refer to the heat exchanger instructions.
Water quality: To ensure maximum heat exchanger performance and lifetime, fol­low the Danfoss “Guideline to Water Quality for Copper Brazed Plate Heat Exchanger” – VJ.KV.D3.02 or a newer version.
9.4 Maintenance validation
Following maintenance work but before turning on the substation, please note the following:
• Check the tightness of all previously loosened threaded connections
• Verify that all previously removed components have been reinstalled correctly
• Ensure that all tools, materials and other equipment used during maintenance have been removed from the work area
• Clean up the work area, remove any spilled substances and remove any waste from material processing
• Make sure that the system and all unit safety devices are working properly again
VI.MG.F1.02
© Danfoss |2017.09 | 25
Page 26
DSA HOME
10.0 Troubleshooting
Electrical equipment which has failed and mechanical, pneumatic and hydraulic components must be serviced only by qualied personnel with the relevant specialties.
Information about all failures which cannot be eliminated through the following actions is to be forwarded to the substation manufacturer or to service partners authorised by Danfoss.
Malfunction Possible Solution Comment
Secondary water tem­perature is too low
Secondary water tem­perature is too high
Check if main switch is turn on
Lack of voltage supply
Lack of heat supply
- No primary system pressure
- Primary dierential pressure is too low
- Heating water ow is too ow
Incorrect controller setting(s) Check and correct settings Read controller’s user’s manual
Defective controller Replace controller Contact customer service
Closed shut-o valve(s) Open shut-o valves
Defective sensor Replace the sensor
Circulation pump(s) defective or not switched ON
Heating pump(s) defective or not switched ON
Balancing valve not set correctly
Circulation pump is not running at the intended speed
Defective control valve Clean or replace valve
Defective actuator or thermostat
Substation is sized incorrectly ­usually primary control valve is too big or too small
Reduced ow through heat exchanger
Outdoor sensor is placed incor­rectly
Missing voltage supply -> actua­tor is in open position
Incorrect controller setting(s) Check and correct setting(s) Read controller’s user manual
Defective sensor Replace the sensor
Defective control valve Clean or replace valve
Defective actuator or thermostat Replace actuator / thermostat
Circulation pump is not running at the intended speed
Check cabling Check fuses
Check and secure operating conditions:
- Pressure
- Flow
- Dierential pressure
Switch ON / replace circulation pump(s)
Switch ON / replace heating pump(s)
Adjust balancing valve to correct value
Increase or decrease pump speed / replace pump
Replace defective actuator or thermostat
Check dimensioning Extend / enlarge substation (calculate dimensions for new control valve and replace old one)
Clean / replace heat exchanger
Place outdoor sensor correctly
Take the system out of operation and close valve manually. After providing power supply, go back into standard mode
Increase or decrease pump speed / replace pump
Contact authorised personnel or electric utility
Contact district heating utility Adjust ow limiter settings
Check values and if necessary replace sensor
Set designated ow
Set designated ow
Contact our sales sta responsible
Read heat exchanger user’s manual
Read electronic controller user’s manual.
Check values and if necessary replace sensor
Actuator still open or thermostat / capillary defective
Set designated ow
26 | © Danfoss | 2017.09
VI.MG.F1.02
Page 27
DSA HOME
Malfunction Possible Solution Comment
Correct settings e.g.:
- Xp (proportional band)
Secondary water tem­perature oscillating or not constant
Leakage*
Risk of scalding!
Unacceptable pressure increase, constant blow up of safety valve
Pressure surges, water hammer
Incorrect controller setting(s)
Fluctuating heating water supply
- Fluctuating primary dierential pressure
- Fluctuating primary ow
Primary control valve is too large
Connection leakages ( ange / ttings, couplings)
Leakage of welds Turn o substation Contact customer service
Leaks from ttings (housing / couplings)
- Leakage of gasket heat ex­changers
- Pollution / calcication
- Pressure hammers
- Leakage of brazed or welded heat exchangers
- Pollution / calcication
- Pressure hammers
Internal leakage of the heat exchanger
Incorrect adjustment and lling pressure
Defective pressure equipment or expansion vessel
Incorrect opening pressure / di­mension or defective safety valve
Incorrect setting of pressure re­ducer / pressure relief controller
Secondary side - uctuating sup­ply temperatures
Secondary side - abruptly chang­ing operating conditions:
- Disconnection of system parts
- Closing of valves
- Pumps switching OFF
Incorrect adjustment and lling pressure
Defective pressure equipment or expansion vessel
Incorrect opening pressure / di­mension or defective safety valve
- Tn (integration time constant)
- M run (running time of the motorised control valve)
Check and secure operating conditions:
- Pressure
- Flow
- Dierential pressure
Control valve needs to be recalcu­lated, replace if necessary
Turn o substation:
- Check operating parameters and test for admissibility ( see label)
- Check connections and tighten as necessary or replace seals
Tighten connection or replace component
- Tighten bolts
- Open and clean plates
- Change seals if necessary
Replace heat exchanger Contact customer service
Test heat exchanger and replace if necessary
Check vessel and pressurisation (base pressure)
Replace component(s)
Replace safety valve
Check / correct device setting Read device user’s manual
Check control valve settings (characteristics in particular)
Check control valve settings (characteristics in particular) Check system settings / interplay of the entire system
Check vessel and pressurisation (base pressure)
Replace component(s)
Replace safety valve
Read controller’s user manual
Contact our sales sta responsible
Contact customer service
Read heat exchanger user’s manual or contact customer service
Contact customer service
Check and adjust parameters
Check and adjust parameters
*May not be applicable for some products or product variants.
VI.MG.F1.02
© Danfoss |2017.09 | 27
Page 28
DSA HOME
Malfunction Possible Solution Comment
Incorrect pump setting Check / correct setting Read pump manual
Check and correct settings of balancing components
Check ow and hydraulic setup Check if extraneous objects are inside piping
Check functionality of non-return valves (spring)
Check dimensioning Extend / enlarge substation (calculate dimensions for new control valve and replace old one)
Clean the lter (after consulting district heating plant)
Check functionality of dierential pressure controller
Replace defective actuator or thermostat
Check the functions of the con­trol valve - clean valve housing if required
Check that the controller setting is correct - see separate instruc­tions. Check the power supply. Temporary set the actuator to “manual” control - see the instructions for heating circuit, manual control
Check that the pump is receiving power and that it runs. Make sure that there is no air in the pump housing - see pump manual
Set the pump at a higher speed of rotation - see instructions for heating circuit
Read device user’s manual
Rinse the substation
Contact our sales sta responsible
Clean valve seat if required
Check values and if necessary replace sensor
Excessive noise
No heat
Missing hydraulic set-up
Flow noise (e.g. in pipes )
Loose parts inside components
System incorrectly dimensioned, e.g. primary control valve is too small
Defective control valve Clean valve
Defective pump impeller Replace pump
Strainer clogged on DH or HE side Clean strainer
Filter in district heating meter clogged
Defective dierential pressure controller
Defective sensor Replace the sensor
Defective actuator or thermostat
Defective control valve or pos­sibly dirt in the valve housing
Automatic controls incorrectly set or defective - possible power failure.
Pump out of operation
The pump rotation speed is set too low
Air in the system Vent the installation thoroughly
28 | © Danfoss | 2017.09
VI.MG.F1.02
Page 29
DSA HOME
10.1 Safety
WARNING! Risk of injury!
Improper troubleshooting can lead to serious personal injury and / or property damage. Therefore troubleshooting of malfunctions may be performed only by trained and authorised personnel!
10.2 Steps to take in the event of malfunction
In summary:
• Immediately stop the substation using the emergency stop function when there are faults that can cause immediate danger to persons, property and / or operational security.
• Switch OFF the substation when there are faults that do not pose such dangers. Additionally, interrupt the power supply to the unit and secure against reconnection.
• Immediately inform superior about fault.
• Request authorised personnel to determine the nature and extent of the disorder and the cause of the malfunction, and to repair the malfunction.
11.0 Spare parts
Use only original spare parts from the manufacturer.
WARNING!
Incorrect or faulty spare parts and / or components from other manufacturers may cause serious damage to and/or malfunction or failure of the substation.
Using non-approved spare parts will invalidate all warranty, service, damage and/or liability claims against the manufacturer or its agents, distributors and representatives.
When ordering spare parts, always specify:
• Substation type
• Serial / production number
• Part number / article number (if available)
• Quantity
• Name
• Desired shipping method (post, freight, sea, air, express)
• Shipping address
• If needed, provide a sketch or photo with remarks
Spare part orders without the above specications may not be ful­lled. In the absence of a desired shipping method, the shipping method will be at the discretion of the supplier.
In the annex, you can nd a list of the most important suppliers of purchased components, where spare parts may be requested follow­ing the expiry of the warranty. In such a case, provide the manufac­turer with comprehensive information about the used parts so that a replacement can be oered.
VI.MG.F1.02
© Danfoss |2017.09 | 29
Page 30
DSA HOME
A actuator 11, 20, 24, 26, 28 assembly 2, 8, 14, 15, 17 authorized personnel 5, 26, 29
M maintenance 2, 3, 5, 6, 7, 11, 12, 19, 24, 25 Maintenance Plan 30 malfunction 3, 4, 19, 29
B balancing valve 26
C circuit 2, 9, 10, 11, 12, 18, 19, 23, 28 circulation 12, 26 commissioning 2, 8, 15, 19, 20 component 15, 24, 27 connections 8, 11, 13, 14, 15, 19, 24, 25, 27 control valves 11 controller 11, 19, 20, 26, 27, 28
D District Heating 5, 11, 15, 18, 19, 20, 25, 26, 28 domestic hot water 2, 12 drain 4, 6, 8, 11, 12, 18, 23 drinking water 4, 11 DSA HOME 1, 2, 9, 11, 12, 15
E electrician 3, 15, 24 employees 19 EPP 22 expansion vessel 2, 23, 24, 27
F ttings 8, 12, 25, 27 at spanner 21, 22 ow noise 28
H hazard 3, 6, 20, 24 heat exchanger 2, 9, 11, 12, 22, 24, 25, 26, 27 heating supply 15 hot surfaces 6
I installation 3, 4, 5, 9, 11, 12, 14, 15, 18, 19, 24, 28 installer 24 Intended use 5
L loose components 15
O operator 2, 5, 7, 19
P packing 16 personnel 5, 7, 8, 14, 15, 19, 20, 24, 26, 29 primary connection 15, 19 protective clothing 8 protective gloves 6 pump 11, 12, 20, 24, 26, 28
R reconnection 6, 24, 29 risk 2, 3, 5, 6, 8, 13, 16
S safety rules 13 safety valve 12, 23, 24, 27 scrap 4 secondary side 11, 19, 20, 23 Seeger Circlip Ring Pliers 22 sensor 12, 15, 26, 28 service 4, 6, 26, 27, 29 spare parts 4, 29 strainer 2, 11, 12, 15, 19, 21, 24, 28 substation 2, 3, 4, 5, 6, 7, 8, 9, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 22, 24, 25, 26, 27, 28, 29
T technical requirements 12 thermometer 11, 24 transport 6, 9, 13, 14, 16 troubleshooting 20, 29
U unpacking 2, 16
V voltage 9, 19, 20, 26
W warranty 3, 5, 15, 19, 29
30 | © Danfoss | 2017.09
VI.MG.F1.02
Page 31
DSA HOME
VI.MG.F1.02
© Danfoss |2017.09 | 31
Page 32
DSA HOME
Danfoss Poland Sp. z o.o. · Tuchom, ul. Tęczowa 46 · 80-209 Chwaszczyno · POLAND Tel.: +48 58 512 91 34 · Fax: +48 58 512 91 05 · serwis@danfoss.pl · www.danfoss.com
32 | © Danfoss | 2017.09
VI.MG.F1.02
Loading...