LIMITED WARRANTY
The DS-5C is warranted against defects in workmanship and materials for two years from date of sale.
This warranty does not apply to damage resulting from accident, misuse, or alteration nor where connected
voltage is more than 5% above the configured operating voltage, nor to equipment improperly installed or
wired or maintained in violation of this Owner’s Manual. No other written or oral warranty applies. No
employee, agent, dealer or other person is authorized to give any warranties on behalf of DANFOSS.
CAUTION: Read all instructions carefully before installation.
Save this Installation Manual for future reference.
DS-5C
Units returned for warranty repair cannot be modified from shipped condition and leads must
protrude a minimum of 6 inches from the base conduit hub. Repair costs of a modified unit will be
quoted as the unit must be returned to the original, unmodified condition prior to return shipping. The
customer shall be responsible for all costs incurred in the removal and/or reinstallation and shipping of the
product for repairs. Within the limitations of this warranty, inoperative units should be returned, freight
prepaid, to DANFOSS, and we will repair or replace, at our option, at no charge to you with return freight
paid by DANFOSS to destinations within the U.S. and Canada. It is agreed that such repair or
replacement is the exclusive remedy available from DANFOSS and that DANFOSS IS NOT
RESPONSIBLE FOR DAMAGES OF ANY KIND, INCLUDING INCIDENTAL AND CONSEQUENTIAL
DAMAGE. Some states do not allow the exclusion or limitation of incidental or consequential damages so
the above exclusion may not apply to you. The warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
Input: 100-277 VAC +/- 5%, 47-63 Hz
Control: 2 x 277 VAC @ 30A
Operating Temp: -40°C to +85°C
DANFOSS ELECTRIC HEATING DIVISION
Toronto, Ontario, Canada
TOLL FREE: 866-676-8062
PHONE: 905-285-2050
FAX: 905-285-2055
Visit us on the Internet at: www.LX.Danfoss.com
CM
L
US
C
D
I
S
E
T
Intertek
RAIN/SNOW SENSOR CONTROLLER
INSTALLATION MANUAL
INDICATOR
OFF
POWER
ENCLOSURE TYPE 3R
RAIN/SNOW SENSOR CONTROLLER
DS−5C
DANGER
CONFORMS TO UL STD 508
CERTIFIED TO CAN/CSA STD C22.2 NO. 14
INPUT
100−277V AC 0.15 A 50/60 Hz
CONTROL
2 x 30 A 277V AC, 20 A 28V DC
WARNING: THIS UNIT MAY BE SUPPLIED BY MORE THAN ONE BREAKER
AVERTISSEMENT: IL PEUT Y AVOIR UN CIRCUIT SECONDAIRE SOUS TENSION
ACTIVATED
L
Intertek
3175102
CONTROL SWITCH
MANUAL ON
AUTOMATIC
STANDBY/RESET
CM
USC
I
D
S
E
T
Need Indoor Monitoring &
Control? Take a Look at the
DANFOSS CDP-2
Simple Installation & Operation at a Competitive Price
Approved CS-xxx Interface Cable Is Also Available
Visit www.goase.com for more information
Danfoss Electric Heating Division Toronto, Ontario, Canada

General Safety Instructions
1. THIS UNIT SHOULD BE INSTALLED, OPENED, AND REPAIRED BY QUALIFIED PERSONNEL
ONLY!
CETTE UNITÉ DEVRAIT ÊTRE INSTALLÉE, OUVERTE, ET RÉPARÉE PAR LE PERSONNEL
QUALIFIÉ SEULEMENT!
2. To avoid shock hazard do not open the front cover with power connected to the DS-5C or any
controlled equipment.
Pour éviter la décharge électrique déconnectez toute la puissance avant d'ouvrir la couverture du DS-
5C.
Selecting a Mounting Location for the DS-5C
The interleaved grid on the top of the DS-5C is the precipitation or “moisture" sensor. The brass cylinder
protruding from the bottom of the enclosure is the temperature sensor. For reliable rain and snow detection
the unit must be mounted in a location that exposes the moisture sensor to a clear view of the sky. The unit
should not be mounted directly under eaves or overhangs. It should not be mounted so close to the ground
that it may become buried in snow. For proper temperature detection the DS-5C must be mounted
outdoors, away from furnace vents, dryer vents, and other sources of heat. Note that, when powered, the
DS-5C moisture grid will always remain hot. This is normal. This allows the sensor to continuously melt
snow and evaporate both rain and snow from the grid.
The DS-5C can be mounted by screwing the base conduit hub onto an appropriate size free-standing
conduit or by using the mounting holes in each corner of the enclosure.
DO NOT DRILL HOLES THROUGH THE ENCLOSURE FOR MOUNTING!
Ne Font Pas Les Trous De Foret Par La Boîte Pour Le Support!
This can allow water into the enclosure causing a potential shock hazard. It is recommended that a
weatherproof junction box be mounted below the DS-5C for termination of the power and load pigtails to
the building wiring.
Use Care When Replacing the Front Cover. Do Not Pinch the Gasket or Overtighten the Screws.
CONTROL/MONITOR JACK
CONFIGURATION SWITCH
TEMPERATURE ADJUST
DELAY OFF ADJUST
SENSITIVITY ADJUST
LOAD1 LOAD2
ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES
Toujours Suivre Les Codes Électriques Locaux Et Nationaux
GRID JACK
2
INPUT POWER
SWITCH JACK
External Control/Monitor Operation
Pin Color Function
1 White GND/Common
2 Red Deice On Mon A
3 Orange Deice On Mon B
4 Black Manual On
5 Green Standby/Reset
monitor relay. This relay, rated at 24 VAC/VDC @ 400 mA, 10W maximum, will close with the load relays
and can be used to externally monitor activation of the sensor. This terminal block is also the connection
point for connecting a CDP-2. Use only tinned, stranded, shielded cable for a reliable connection.
The DS-5C provides external control/monitor capability. Cable
rated 300V up to 18 AWG can be connected to TB2 to access this
feature. Connecting Black (4) to White (1) will activate the
“Manual On” function. Connecting Green (5) to White (1) will
activate the “Standby/Reset” function. See the “Manual Override
Switch Function” for a description of these modes. The
Red/Orange (2/3) leads are connected to an internal low power
Power & Activation Indicator
A green lamp shines through a lens on the cover of the DS-5C to indicate operational status. If this lamp is
OFF the DS-5C is not receiving power. If this lamp is steady ON the DS-5C is powered but not triggered.
If this lamp is FLASHING the DS-5C is powered on and triggered, the main relays are closed, and attached
equipment should be activated. Note that, even though snow or rain may have stopped, the DS-5C
indicator will continue to flash during the Delay-Off drying cycle.
Moisture Grid Maintenance & Replacement
It is recommended that the DS-5C be powered down and the grid wiped clean with clear water at least
once every 4 months. Heavy deposits may be removed using a non-metallic scouring pad (Scotch-BriteTM
or equivalent.) However, after a number of years, the corrosive elements left behind when water is
evaporated out of the moisture grid will eventually damage the grid rings. The moisture grid can be easily
replaced by ordering and installing an MG-5 “Moisture Grid Assembly” and following the procedure below:
THIS PROCEDURE SHOULD ONLY BE PERFORMED BY QUALIFIED PERSONNEL!
CE PROCÉDÉ DEVRAIT SEULEMENT ÊTRE EXÉCUTÉ PAR LE PERSONNEL QUALIFIÉ!
Open all power and load breakers connected to the DS-5C. Open the front cover and remove the cable
connector from the Grid Jack. While holding the reducing bushing, unscrew and remove the old moisture
grid. Pass the new moisture grid connector through the top hole and screw the assembly into the reducing
bushing. Tighten the grid hand tight plus ¼ turn. Connect the new cable to the Grid Jack. Confirm that the
four connector pins are properly aligned with the jack. Close the front cover, confirming that the front cover
gasket is properly sealed. Reapply power.
Use Care When Replacing the Front Cover. Do Not Pinch the Gasket or Overtighten the Screws.
Preseason Snow Detection Testing
It is always a good idea to test the operation of the DS-5C prior to the winter season. Procure some clean
water and, if the outdoor temperature is above the trigger point, a can of spray component cooler (Radio
Shack Part #64-4321 or equivalent.) Clean the moisture grid following the procedure outlined above and
allow it to dry. Apply power to the DS-5C, drip some of the water onto the moisture grid, then spray the
temperature sensor protruding from the base of the enclosure with the component cooler. Once the
temperature sensor has reached the trigger point with water still present on the grid the DS-5C will activate.
The user should hear the internal control relays close and see the green lamp blink. Proper operation has
been confirmed. Allow the grid to dry completely. To clear the Delay-Off timer place the override switch
into “Standby/Reset”, and then back to the “Automatic” position.
7