DHP-A
DHP-A Opti
DHP-AL
DHP-AL Opti
DHP-C
DHP-H
DHP-H Opti
DHP-H Opti Pro
DHP-L
DHP-L Opti
DHP-L Opti Pro
VMBMA1002
If these instructions are not followed during installation and
service, Danfoss A/Sliability according to the applicable warranty
is not binding. Danfoss A/S retains the right to make changes to
components and specifications without prior notice.
The following documents are available for this product:
Installation instructions containing information to install and commission a heat pump installation. Supplied
•
with the heat pump on delivery.
The service instructions contain information about the heat pump’s function, accessories, fault tracing and
•
technical data. The instructions also contain tips and advice that should be followed before a heat pump
installation. It is therefore recommended that the instructions are read before installation.
The service instructions are available for download as below.
The electrical instructions that contain the wiring diagram for the heat pump intended for fault tracing and
•
service. The electrical instructions are available for download as below.
The maintenance instructions must handed over and gone through with the end customer. Supplied with the
•
heat pump on delivery.
Country specific instructions and forms are available where relevant. Supplied with the heat pump on delivery.
•
Self-adhesive decals with translation text. Must be placed on the manufacturing plate in conjunction with
•
installation. Supplied with the heat pump on delivery.
The Service instructions and Electrical instructions are available for download here:
1.2Symbols in documents
The instructions contain different warning symbols, which, together with text, indicate to the user that there are
risks involved with actions to be taken.
The symbols are displayed to the left of the text and three different symbols are used to indicate the degree of
danger:
DANGER! Indicates an immediate danger that leads to fatal or serious injury if necessary measures are not
taken.
Warning! Risk of personal injury!Indicates a possible danger that can lead to fatal or serious injury if
necessary measures are not taken.
Caution! Risk of installation damage.Indicates a possible hazard that can lead to item damage if necessary
measures are not taken.
A fourth symbol is used to give practical information or tips on how to perform a procedure.
Note! Information regarding making the handling of the installation easier or a possible operational
technical disadvantage.
1.3Symbols on decals
The following symbols can occur on decals on the different parts of the heat pump. Which symbols are used
depends on the heat pump model.
Installation instructions VMBMA1002 – 3
!
!
3
353
50
362
54
406
55
408
71
417
Warning, danger!
Read the documentation provided.
Read the documentation provided.
Warning, hazardous electrical voltage!
Warning, hot surfaces!
Electrical components
Component, normalComponent, accessory
Outdoor unit
Outdoor sensor
Hot water sensor
Warning, moving parts!
Warning, risk of crushing injury!
Drip tray
Shunt valve
Room sensor
Sensor hot-water top
Flow guard
EVU
Defrost sensor
4 – Installation instructions VMBMA1002
Pipe connections
Tap water
Heating system
Brine
Defrosting tank
Expansion tank with safety valve, brine
Bleeding
Temperature and pressure relief valve
Outdoor unit
Water heater
Installation instructions VMBMA1002 – 5
2Important information/Safety regulations
Warning! Risk of personal injury! Children are not permitted to play with the product.
Warning! As the water temperature in DHP-H Opti Pro and DHP-L Opti Pro becomes extremely hot, a
mixer valve must be installed between the cold water and hot water pipes to ensure a lower domestic hot
water temperature.Alternatively the maximum hot water temperature must be reduced in the Service
menu.
Warning! Danfoss SP (1-phase) heat pumps have a factory installed safety valve for temperature and
pressure, (10 bar 90-95°C), in accordance with the requirements in Great Britain. This valve is located in the
water tank and may not be used for any purpose other than connecting the outlet pipe.
Also note that for heat pump DHP-H Opti Pro SP and DHP-L Opti Pro SP it is imperative that the hot water
temperature is changed from default setting 95°C to 85°C.
Caution! The heat pump must be installed by authorised installation engineers and the installation must
follow the applicable local rules and regulations as well as these installation instructions.
Caution! This product is not intended for persons (including children) with reduced physical, sensory or
psychological capacity, or who do not have knowledge or experience, unless supervised or they have
received instructions on how the apparatus functions from a safety qualified person.
Caution! The heat pump must be located in a frost-free environment!
Caution! The heat pump must be placed in an area with a floor drain.
Caution! The heat pump must be located on a stable base. The floor must be able to support the gross
weight of the heat pump with filled hot water tank (see Technical data).
Caution! To prevent leaks, ensure that there are no stresses in the connecting pipes!
Caution! It is important that the heating system is bled after installation.
Caution! Bleed valves must be installed where necessary.
6 – Installation instructions VMBMA1002
Caution! The hot water tank must be equipped with an approved safety valve.
Caution! Heating systems with closed expansion tanks must also be supplied with approved pressure
gauges and safety valves.
Caution! Cold and hot water pipes and overflow pipes from safety valves must be made of heat resistant
and corrosion-resistant material, e.g. copper. The safety valve overflow pipes must have an open
connection to the drain and visibly flow into this in a frost-free environment.
Caution! The connecting pipe between the expansion tank and the safety valve must slope continuously
upwards. A continuous upwards slope means that the pipe must not slope downwards from the
horizontal at any point.
Note! If there is any risk of groundwater infiltration at wall lead-ins for brine pipes, watertight grommets
must be used.
Note! In addition to applicable local rules and regulations the installation should be carried out in a
manner that prevents vibrations from the heat pump being transmitted into the house causing noise.
2.1Refrigerant
Caution! Work on the refrigerant circuit must only be carried out by a certified engineer!
Although the heat pump cooling system (refrigerant circuit) is filled with a chlorine-free and environmentallyapproved refrigerant that will not affect the ozone layer, work on this system may only be carried out by authorized persons.
2.1.1Fire risk
The refrigerant is not combustible or explosive in normal conditions.
2.1.2Toxicity
In normal use and normal conditions the refrigerant has low toxicity. However, although the toxicity of the refrigerant is low, it can cause injury (or be highly dangerous) in abnormal circumstances or where deliberately abused.
Warning! Risk of personal injury! Spaces in which heavy vapour can collect below the level of the air must
be well ventilated.
Refrigerant vapour is heavier than air and, in enclosed spaces below the level of a door for example, and in the
event of leakage, concentrations can arise with a resultant risk of suffocation due to a lack of oxygen.
Installation instructions VMBMA1002 – 7
Warning! Risk of personal injury! Refrigerant exposed to a naked flame creates a poisonous irritating gas.
This gas can be detected by its odour even at concentrations below its permitted levels. Evacuate the area
until it has been sufficiently ventilated.
2.1.3Work on the refrigerant circuit
Caution! When repairing the refrigerant circuit, the refrigerant must not be released from the heat pump,
it must treated in the appropriate way.
Draining and refilling must only be carried out using new refrigerant (for the amount and type of refrigerant see
manufacturer’s plate) through the service valves.
Caution! All warranties from Danfoss are void if, when filling with refrigerant other than Danfoss A/S
specified refrigerant, if there has not been written notification that the new refrigerant is an approved
replacement refrigerant together with other remedies.
2.1.4Scrapping
Caution! When the heat pump is to be scrapped the refrigerant must be extracted for disposal. Local rules
and regulations related to the disposal of refrigerant must be followed.
2.2Electrical connection
Caution! Electrical installation may only be carried out by an authorized electrician and must follow
applicable local and national regulations.
Caution! The electrical installation must be carried out using permanently routed cables. It must be
possible to isolate the power supply using an all-pole circuit breaker with a minimum contact gap of 3
mm. (The maximum load for externally connected units is 2A).
DANGER! Hazardous electrical voltage! The terminal blocks are live and can be highly dangerous due to
the risk of electric shock. All power supplies must be isolated before electrical installation is started. The
heat pump is connected internally at the factory, for this reason electrical installation consists mainly of
the connection of the power supply.
2.3Commissioning
Caution! The installation may only be commissioned if the heating system and brine system have been
filled and bled. Otherwise the circulation pumps can be damaged.
8 – Installation instructions VMBMA1002
Caution! If the installation is only to be driven by an auxiliary heater during the installation, ensure that
the heating system is filled and the brine pump and compressor cannot be started. This is carried out by
setting the operating mode to AUX. HEATER.
Installation instructions VMBMA1002 – 9
110
1845 (±10)
455
596
528
300
440
40±10
1
2
610
80
4
7
8
6
5
9
3
110
1845 (±10)
455
596
528
300
440
40±10
1
2
610
80
4
7
8
6
5
9
3
3Heat pump data, dimensions and connections
3.1DHP-H, DHP-H Opti
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
3Heating system supply pipe, 22 Cu: 4-10 kW, 28 Cu: 12-16 kW
4Heating system return pipe, 22 Cu: 4-10 kW, 28 Cu: 12-16 kW
5Connection for bleed valve, 22 Cu
6Hot water line, 22 mm
7Cold water line, 22 mm
8Lead-in for supply, sensor and communication cables
9Safety valve for temperature and pressure (only applies to
certain models)
The brine pipes can be connected on either the left or right-hand sides
of the heat pump.
Figure 1.Dimensions and connections
3.2DHP-H Opti Pro
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
3Heating system supply pipe, 22 Cu: 4-10 kW, 28 Cu:
kW
5Connection for bleed valve, 22 Cu
6Hot water line, 22 mm
7Cold water line, 22 mm
8Lead-in for supply, sensor and communication cables
9Safety valve for temperature and pressure (only applies
to certain models)
The brine pipes can be connected on either the left or right-hand sides
of the heat pump.
Figure 2.Dimensions and connections
10 – Installation instructions VMBMA1002
110
1845 (±10)
455
596
528
300
440
40±10
2
1
610
80
4
786
5
3
1538 (±10)
455
596
690
40±10
110
528
300
440
1
2
610
80
3
5
4
3.3DHP-C
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
3Heating system supply pipe, 22 Cu
4Heating system return pipe, 22 Cu
5Connection for bleed valve, 22 Cu
6Hot water line, 22 mm
7Cold water line, 22 mm
8Lead-in for supply, sensor and communication cables
The brine pipes can be connected on either the left or right-hand sides
of the heat pump.
Figure 3.Dimensions and connections
3.4DHP-L, DHP-L Opti
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
3Heating system supply pipe, 22 Cu: 4-10 kW, 28 Cu:
kW
6Supply line water heater, 22 Cu
7Lead-in for supply, sensor and communication cables
The brine lines (2), (3) and return line water heater (1) can be connected
on the right or left-hand sides.
3.6DHP-A, DHP-A Opti
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
3Lead-in for supply, sensor and communication cables
4Heating system supply pipe, 22 Cu: 6-10 kW, 28 Cu: 12 kW
5Heating system return pipe, 22 Cu: 6-10 kW, 28 Cu: 12 kW
6Connection for bleed valve, 22 Cu
7Hot water line, 22 mm
8Cold water line, 22 mm
9Expansion outlet brine circuit, R25 int.
10Safety valve for temperature and pressure (only applies to
certain models)
The brine pipes can be connected on either the left or right-hand sides
of the heat pump.
Figure 5.Dimensions and connections
12 – Installation instructions VMBMA1002
3
5
6
2
11
15
14
10
12
13
17
7
16
4
89
1
1538 (±10)
455
596
690
40±10
455
690
40±10
3.7DHP-AL, DHP-AL Opti
The brine pipes can be connected on either the left or right-hand sides of the heat pump.
Figure 6.Dimensions and connections heat pump and water heater
Symbol explanation
Heat pump
1Brine in, 28 Cu5Heating system supply pipe, 22 Cu: 6-10 kW, 28 Cu: 12
kW
2Brine out, during normal operation, 28 Cu6Heating system return pipe, 22 Cu: 6-10 kW, 28 Cu: 12 kW
3Brine out during defrosting to hwh pos 8, 28 Cu7Lead-in power and sensor lead
4Return line from water heater pos 9, 28 Cu
Symbol explanation
Water heater
8Connection for brine out when defrosting from
pos 3
9Water heater, return pipe to pos 414Supply to water heater coil
10Bleed valve, at stainless steel water heater15Brine, expansion outlet when outdoor unit is positioned at
11Brine out during defrosting, 28 Cu16Lead-in sensor lead
12Hot water line, 22 mm17Safety valve for temperature and pressure (only applies to
13Cold water line, 22 mm
high level
certain models)
Installation instructions VMBMA1002 – 13
1
12
2
1175
630
405
441
342
300
120
910
3.8Outdoor unit DHP-A, DHP-AL, DHP-A Opti, DHP-AL Opti
Figure 7.Outdoor unit, dimensions and connections.
Symbol explanation
1Brine in, 28 Cu
2Brine out, 28 Cu
14 – Installation instructions VMBMA1002
4Transport, unpacking and setting-up
4.1Transporting the heat pump
Caution! During transportation or lifting of the entire heat pump, the front panel must always be installed
as it locks the other panels construction.
Caution! The heat pump must always be transported and stored in a dry area. Secure the heat pump so
that it cannot tip over during transportation.
When transporting indoors to the installation location it may be necessary to place the heat pump on its back. The
time that the heat pump is transported on its back should be as short as possible. After the heat pump has been
lifted up again it must stand upright for at least an hour before commissioning.
4.2Unpacking heat pump
4.2.1Delivery check
1.Check that there is no transport damage. The heat pump is packaged in cardboard.
2.Remove the packaging and check that the delivery contains the following components.
Safety valve 9 bar 1/2"086U236911
Safety valve 1.5 bar 1/2"086U089611
Outdoor sensor086U270111
Expansion and bleed tank086U282411
Rubber bellows for 22-28 mm hole086U342355
Flexible hose R20 L=550086U60332-
Flexible hose R25 L=550086U6034-2
Filler device DN25086U60061-
Filler device DN32086U6007-1
Dirt filter with shut-off DN20086U34271-
Dirt filter with shut-off DN25086U6005-1
Manual holder086U398811
4.3Setting-up the heat pump
4.3.1Recommended location
Part number4-10 kW12-16 kW
Caution! To avoid condensation problems for the brine lines, as short a brine line as possible is
recommended indoors.
The heat pump should be located on a stable floor, preferably made of concrete. When locating the heat pump on
a wooden floor this should be reinforced to take the weight of the heat pump including a filled water heater, see
technical data for relevant heat pump. One solution is to place a thick metal plate, at least 6mm, under the heat
pump. The metal plate should cover several joists spreading the weight of the heat pump over a larger area. If the
heat pump is being installed in a newly-built house, this has normally been taken into account during construction, and the joists where the heat pump will be located have been reinforced. Always check that this has been
carried out when installing into a newly-built house.
Installation instructions VMBMA1002 – 15
300 mm
300 mm
300 mm
10 mm
600 mm
1905
1620
Avoid positioning the heat pump in a corner as the surrounding walls may amplify its noise. It is also important to
adjust the heat pump using the adjustable feet so that it is horizontal to the base.
4.3.2Space requirement
Caution! The heat pump must not be enclosed as the temperature inside the cabinet becomes extremely
high.
To facilitate the installation and subsequent testing and maintenance there must be sufficient free space around
the heat pump in accordance with the following image:
4.3.3Setting up
Note! The heat pump has feet that can be adjusted to compensate for irregularities in the surface on
which it is sitting. If the surface is so irregular that the feet cannot compensate for it, the installation
engineer must remedy this.
Note! It is recommended that the condensation drain is installed from the drip tray’s drain pipe by lying
the heat pump down. The drain pipe opens through a hole in the base plate and has a Ø10 mm hose
connection.
Note! If the heat pump has been laid down it is recommended that it stands upright for at least an hour
before commissioning.
4.3.4Removing the front cover
Caution! Do not damage the electrical wiring for the display when the front cover is removed!
16 – Installation instructions VMBMA1002
1
2
3
To install the heat pump the front cover must be removed.
Figure 8.Removing the front cover
1.Press against the front cover and turn the catch 90° degrees anti-clockwise to release the front cover.
2.Tilt the front cover outwards.
3.Lift the front cover upwards to remove it from the heat pump.
4.4Setting-up the outdoor unit
Note! Applies to DHP-A.
4.4.1Recommended location
When positioning the outdoor unit, note the following:
Caution! When the outdoor unit is defrosting, water will drip straight down under the unit. The area
around the outdoor unit must therefore be properly drained in order to take the water (approximately 2
litres per defrost).
Caution! The outdoor unit’s adjustable stand must be positioned on a secure base such as wooden
sleepers, paving slabs or cast footings.
Note! The outdoor unit does not have to be positioned in any specific direction.
Note! Noise is produced from the outdoor unit when the fan is in operation, remember this when
positioning to reduce disturbance in your own home as well as to any neighbours.
Installation instructions VMBMA1002 – 17
300 mm
300 mm
300 mm
1500 mm
1
1
2
3
4.4.2Space requirement
Figure 9.Necessary service space for outdoor unit.
4.4.3Unpacking
The outdoor unit is packed and delivered in a crate.
1.Start by unpacking the unit from the crate.
2.Check that the delivery is complete, it must contain the outdoor unit, front cover, cover as well as a disassembled stand including necessary screws, nuts and washers.
4.4.4Installation
4.4.4.1 Assembling the stand
Assemble the stand
1.Screw the two horizontal struts together (2) using the two ends (1) as illustrated below. Use 10 x M6x10
screws. The curved edges of the horizontal struts must be facing inwards.
Figure 10.Assembling the stand
Symbol explanation
1Ends
2Strut
3Feet
2.Screw the adjustable feet (3) into the holes under the ends.
4.4.4.2 Preparing the outdoor unit
While the outdoor unit remains on the pallet it should be prepared for placing on the stand. Carry out the following:
18 – Installation instructions VMBMA1002
1.There are three M6x20 screws on the lower edge of the outdoor unit. Unscrew them so that 2-3 mm of the
thread remains. Use a torx TX25 screwdriver, or equivalent.
Caution! Do not lift the outdoor unit by its side panels when it is to be raised or moved.
2.Raise the outdoor unit.
3.Remove the side plates. They are held in place by clamps and so are removed by pulling outwards.
4.Remove all four screwed lifting eyes. Use a 13 mm wrench, or equivalent.
4.4.4.3 Assembling the outdoor unit on the stand
1.Lift the outdoor unit into the place on the stand.
2.Screw the outdoor unit onto the stand. Use 4 x M6x20 screws. It may be necessary to push and pull the
stand slightly in order to get the screw holes to align.
Caution! When filling the brine system the outdoor unit must be bled using the bleed screws on
the connecting pipes inside the side covers. We recommend that you return to this instruction after
the brine system has been filled.
3.Reinstall the side panels.
4.4.4.4 Assembling the defrost sensor
Figure 11.Hook the defroster sensor mounting into place
1.Slide the mounting for the defroster sensor into the hole on the reverse of the outdoor unit until the cover
hooks into place on the edge.
2.Take out the defrosting sensor from the electrical connection box. Thread out the sensor through a suitable
lead-in.
3.Route the defroster sensor connection cable through the cable lead-in to the mounting.
4.Secure the defroster sensor at the bottom of the mounting using a cable tie.
4.4.4.5 Assembling the front cover
1.Hook the lower edge of the front cover onto at least one of the three screws in the bottom edge of the
stand.
2.Secure the upper edge of the front panel temporarily in the centre hole. Use 1 x M6x15 torx TX25.
3.Align all the three screws in the lower edge.
4.Screw the three screws in the lower edge fully. Use a torx TX25 screwdriver, or equivalent.
Installation instructions VMBMA1002 – 19
5.Secure the front panel's upper edge with the 2 x remaining M6x15 torx TX25, see figure below.
Figure 12.Secure the cover
4.4.4.6 Install the cover
1.Hook the cover at the front edge on the front cover.
Figure 13.Hook the front cover into place
1.Secure the cover using a screw on each side. Use 2 x cross head screws.
If the cover does not align with the side cover plates it may be necessary to drill new 3 mm holes:
Mark for the new holes
•
Lift off the cover
•
Drill the holes
•
Install and screw the cover into place
•
Figure 14.Screw the front cover into place
20 – Installation instructions VMBMA1002
4.4.4.7 Install cover
1.Hook the cover onto the stand.
Figure 15.Hook the cover onto the stand.
Installation instructions VMBMA1002 – 21
5Piping installation
Warning! As the water temperature in DHP-H Opti Pro and DHP-L Opti Pro becomes extremely hot, a
mixer valve must be installed between the cold water and hot water pipes to ensure a lower domestic hot
water temperature.Alternatively the maximum hot water temperature must be reduced in the Service
menu.
Warning! Danfoss SP (1-phase) heat pumps have a factory installed safety valve for temperature and
pressure, (10 bar 90-95°C), in accordance with the requirements in Great Britain. This valve is located in the
water tank and may not be used for any purpose other than connecting the outlet pipe.
Also note that for heat pump DHP-H Opti Pro SP and DHP-L Opti Pro SP it is imperative that the hot water
temperature is changed from default setting 95°C to 85°C.
Caution! Piping installation must be carried out in accordance with applicable local rules and regulations.
The hot water tank must be equipped with an approved safety valve.
Caution! To prevent leaks, ensure that there are no stresses in the connecting pipes!
Caution! It is important that the heating system is bled after installation. Bleed valves must be installed
where necessary.
Note! Ensure that the pipe installation is carried out in accordance with the dimensions and connection
diagrams.
Note! Configure the heat pump for the desired system solution in the SERVICE\ADD. HEATER\EXTERNAL
ADDITION menu.
5.1Safety valves
Caution! Radiator systems with a closed expansion tank must also be equipped with an approved
pressure gauge and safety valve, minimum DN 20, 1.5 bar opening pressure, or according to country
specific requirements.
Caution! Cold and hot water pipes and overflow pipes from safety valves must be made of heat resistant
and corrosion-resistant material, e.g. copper. The safety valve overflow pipes must have an open
connection to the drain and visibly flow into this in a frost-free environment.
Caution! The connecting pipe between the expansion tank and the safety valve must slope continuously
upwards. A continuous upwards slope means that the pipe must not slope downwards from the
horizontal at any point.
22 – Installation instructions VMBMA1002
5.2Connection heat transfer fluid
5.2.1System solution 1
In system solution 1 the heat pump can produce both heating and hot water with the compressor and the integrated auxiliary heater. Production of heating and hot water cannot occur at the same time because the exchange
valve for heating/hot water is positioned after the auxiliary heater.
The integrated auxiliary heater carries out peak heating charging (antilegionella function) in those operating
modes that permit auxiliary heat.
For system solution 1, select the factory setting in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXTERNAL AUX. HEATER = 0 (Off)
REV.V. HOT WATER = INT
5.2.1.1 Example system solution 1
System solution for DHP-H, DHP-H Opti, DHP-H Opti Pro, DHP-C, DHP-A, DHP-A Opti.
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
126Safety valve for temperature and pressure (only
applies to certain models)
Figure 16.Example system solution 1
Installation instructions VMBMA1002 – 23
5.2.1.2 Example system solution 1
System solution for DHP-L, DHP-L Opti
Figure 17.Example system solution 1
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
18Water heater
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
126Safety valve for temperature and pressure (only
applies to certain models)
24 – Installation instructions VMBMA1002
5.2.1.3 Example system solution 1
System solution for DHP-L Opti Pro.
Figure 18.Example system solution 1
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
18Water heater
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
126Safety valve for temperature and pressure
(only applies to certain models)
5.2.1.4 Example system solution 1
System solution for DHP-AL, DHP-AL Opti.
Figure 19.Example system solution 1
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
17Water heater (DHP-AL)
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
126Safety valve for temperature and pressure
(only applies to certain models)
Installation instructions VMBMA1002 – 25
5.2.2System solution 2
In system solution 2, the heat pump can produce both heat and hot water and an external auxiliary heater (oil
boiler, electric boiler, district heating or similar) supports heat production but not hot water production. The
exchange valve for heating/hot water is located ahead of the external auxiliary heater, which allows the production of heating and hot water at the same time.
The integrated auxiliary heater can be used for heating and hot water production as well as for antilegionella. The
values of the integrals, A2 and A3 are used to select if the external auxiliary heater is to step in before or after the
integrated electrical auxiliary heater.
The heat pump control computer also controls an additional shunt located after the external addition.
For system solution 2, select in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXT.AUX.HEATER = ON
REV.V. HOT WATER = INT
5.2.2.1 Example system solution 2
System solution for DHP-H, DHP-H Opti, DHP-H Opti Pro, DHP-C, DHP-A, DHP-A Opti.
Figure 20.Example system solution 2
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
36Circulation pump
51Supply line sensor, moved out from heat pump
72Additional shunt
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure (only
applies to certain models)
26 – Installation instructions VMBMA1002
5.2.2.2 Example system solution 2
System solution for DHP-L, DHP-L Opti.
Figure 21.Example system solution 2
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
18Water heater
36Circulation pump
51Supply line sensor, moved out from heat pump
72Additional shunt
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure (only
applies to certain models)
Installation instructions VMBMA1002 – 27
5.2.2.3 Example system solution 2
System solution 2 for DHP-L Opti Pro.
Figure 22.Example system solution 2
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
18Water heater
36Circulation pump
51Supply line sensor, moved out from heat pump
72Additional shunt
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure (only applies
to certain models)
28 – Installation instructions VMBMA1002
5.2.2.4 Example system solution 2
System solution for DHP-AL, DHP-AL Opti.
Figure 23.Example system solution 2
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
17Water heater (DHP-AL)
36Circulation pump
51Supply line sensor, moved out from heat pump
72Additional shunt
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure (only
applies to certain models)
5.2.3System solution 3
In system solution 3, the heat pump can produce both heat and hot water and an external auxiliary heater (oil
boiler, district heating or similar) supports heat and hot water production and can support antilegionella. The
exchange valve for heating/hot water is located after the external auxiliary heater, which prevents the production
of heating and hot water at the same time.
The integrated auxiliary heater can be used for heating and hot water production as well as for antilegionella.
The parameter "TOPH.AUX” is used to determine if the external or internal auxiliary heater produces antilegionella.
The values of the integrals, A2 and A3 are used to select if the external auxiliary heater is to step in before or after
the integrated electrical auxiliary heater.
The heat pump control computer also controls an additional shunt located after the external addition.
For system solution 3, select in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXT.AUX.HEATER = ON
REV.V. HOT WATER = EXT
Installation instructions VMBMA1002 – 29
5.2.3.1 Example system solution 3
System solution for DHP-H, DHP-H Opti, DHP-C, DHP-A, DHP-A Opti.
Figure 24.Example system solution 3
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
36Circulation pump
51Supply line sensor, moved out from heat pump
72Additional shunt
77Reversing valve
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure (only
applies to certain models)
30 – Installation instructions VMBMA1002
5.2.3.2 Example system solution 3
System solution for DHP-L, DHP-L Opti.
Figure 25.Example system solution 3
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
18Water heater
36Circulation pump
51Supply line sensor, moved out from heat
pump
72Additional shunt
77Reversing valve
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure
(only applies to certain models)
Installation instructions VMBMA1002 – 31
5.2.3.3 Example system solution 3
System solution for DHP-AL, DHP-AL Opti.
Figure 26.Example system solution 3
Symbol explanation
1Heat pump
10Supply line
11Return line
12Cold water
13Hot-water
17Water heater (DHP-AL)
36Circulation pump
51Supply line sensor, moved out from heat
pump
72Additional shunt
77Reversing valve
80Shut-off valve
83Non-return valve
85Venting valve
86Safety valve expansion heating system
87Safety valve cold water 9 bar
89Vacuum valve
91Strainer
96Flexible hose
113Expansion heating system
117External auxiliary heater
126Safety valve for temperature and pressure
(only applies to certain models)
5.2.4Connecting cold and hot water lines
1.Connect the cold water and hot water pipes with all the necessary components according to the connection diagram for the relevant system.
5.2.5Connecting the heating system supply and return lines
For information on how flexible hoses should be installed, see Flexible hoses.
1.Connect the supply pipe with a flexible hose connection and with all the necessary components.
2.Connect the return pipe with a flexible hose connection and with all the necessary components including a
filter.
3.Insulate the supply and return lines.
4.Connect the bleed valve to the outlet (22mm Cu) on the top of the heat pump.
1Brine in
2Brine out
3Shut-off valve (part of the filler cock)
4Dirt valve
5Safety valve (1.5 bar)
6Bleed and expansion tank
Figure 27.General connection diagram brine lines
5.3.2Connection brine DHP-C
7Shut-off valve
Figure 28.General connection diagram brine lines
5.3.3Connection brine DHP-A, DHP-A Opti
If the outdoor unit is installed higher than the heat pump a pressure tank with safety valve must be connected to
the outlet for bleeding.
If the outdoor unit is installed at the same level or lower than the heat pump, the accompanying plastic vessel can
be used. The upper part of the outdoor unit must then not exceed the fluid level in the vessel.
Figure 29.General connection diagram, brine
lines
Symbol explanation
1Brine in
2Brine out
3Shut-off valve (part of the filler cock)
4Strainer
5Safety valve (1.5 bar)
6Bleed and expansion tank
7Shut-off valve
Symbol explanation
1Brine in
2Brine out
3Shut-off valve (part of the filler cock)
4Strainer
5Safety valve (1.5 bar)
6Bleed and expansion tank
7Shut-off valve
8Pressure tank
Installation instructions VMBMA1002 – 33
1
2
3
33
3 4 3
1
6
8
7
5
11
2
12
5
10
9
5.3.3.1 Connection brine Outdoor unit DHP-A, DHP-A Opti
Symbol explanation
1Brine out
2Brine in
3Flexible hoses
Figure 30.General connection diagram, brine lines
5.3.4Connecting brine DHP-AL, DHP-AL Opti
If the outdoor unit is installed higher than the heat pump a pressure tank with safety valve must be connected to
the outlet for bleeding.
If the outdoor unit is installed at the same level or lower than the heat pump, the accompanying plastic vessel can
be used. The upper part of the outdoor unit must then not exceed the fluid level in the vessel.
Figure 31.General connection diagram, brine lines
Symbol explanation
1Brine in
2Brine out
3Shut-off valve (part of the filler cock)
4Strainer (part of the filler cock)
5Safety valve (1.5 bar)
6Bleed and expansion tank
5.3.5Drilling holes for brine pipes
Caution! Ensure that the holes for the insert pipes are positioned so that there is room for the other
installations.
Caution! The brine pipes shall have separate lead-ins. If the wall lead-ins are below the highest ground
water level watertight lead-ins must be used.
34 – Installation instructions VMBMA1002
7Shut-off valve
8Pressure tank
9Outdoor unit
10Flexible hoses
11Bleed valve
12Moved out supply line sensor, brine
1
1
2
3
3
4
The brine pipes must be insulated from the heat pump, through the walls and outside the house all the way to the
collector so as to avoid condensation and prevent heat loss.
If the brine pipes are to be routed above ground, drill holes in the walls for them.
If the brine pipes are to be routed below ground see the instructions below.
Symbol explanation
1Insert pipe
2Brine pipe
3Mortar
4Sealant
Figure 32.Making holes
1.Drill holes in the wall for the insert pipes (1) for the brine pipes. Follow the dimension and connection diagrams. If there is any risk of groundwater infiltration at brine pipe lead-ins, watertight grommets must be
used.
2.Position the insert pipes (1) in the holes sloping downwards. The inclination must be at least 1cm every
30cm. Cut them at an angle (as illustrated) so that rain water cannot get into the pipes.
3.Insert the brine pipes (2) into the insert pipes in the installation room.
4.Fill in the holes around the lines with mortar (3).
5.Ensure that the brine pipes (2) are centred in the insert pipes (1) so that the insulation is distributed equally
on all sides.
6.Seal the insert pipes (1) with a suitable sealant (foam) (4).
5.3.6Installing brine pipes
1.Determine to which side the brine pipes are to be connected.
2.Route the out pipe for brine in through the corresponding hole (with rubber collar) in the heat pump side.
3.Install all necessary components on the pipe. Remember to install the filler cock with the filter cover
upwards.
4.Route the pipe for brine out through the corresponding hole (with rubber collar) in the heat pump side.
Caution! When the brine lines are connected to the right for DHP-A, the brine out line must be routed
over the brine pump, under the compressor’s vacuum pipe and under the condenser’s flexible hose, see
figure below.
Installation instructions VMBMA1002 – 35
Figure 33.The brine's supply line
1.Install the out pipe with all the accompanying components.
2.Install the expansion tank with the safety valve.
3.Fit both brine pipes with anti-diffusion insulation running all the way from the heat pump to the lead-in in
the wall. The brine pipes running outside the house to the collector can be buried, however they must be
well insulated.
Caution! Applies to DHP-A:Bear in mind that the outdoor unit may move during defrosts, use
flexible hoses to connect the pipes from the heat pump and pipes on the outdoor unit.
5.3.7Connection to outdoor unit
Connection for the brine circuit from the heat pump to the outdoor unit can be carried out using pipes or hoses.
Depending on what connection is selected and what diameter the connection has, there is a maximum length that
the connection may be. The maximum lengths in the table below are based on ethylene glycol (which is mixed to
anti-freeze protection down to -32±1°C) at 0°C.
Table 1.Max coil length between heat pump and outdoor unit
DHP-A, DHP-ALExt.avail.
press.
SizekPaCu22
63034
86321
105011 *
12435 *
Calculated maximum coil length between the HP and outdoor unit, in metres
Øi = 20.0
(2 x 17)
(2 x 10.5)
(2 x 5.5)
(2 x 2.5)
Cu28
Øi = 25.6
133
(2 x 66.5)
98
(2 x 49)
47
(2 x 23.5)
26
(2 x 13)
PEM DN 25
Øi = 21.0
48
(2 x 24)
30
(2 x 15)
13 *
(2 x 6.5)
8 *
(2 x 4)
PEM DN 32
Øi = 28.0
173
(2 x 86.5)
150
(2 x 75)
78
(2 x 39)
44
(2 x 22)
*) Not recommended because of high liquid speeds with risk of corrosion/noise problems.
5.4Noise information
5.4.1Flexible hoses
Caution! The press sleeves may never be used as a counterhold when tightening connections.
All pipes should be routed in such a way that vibrations cannot be transmitted from the heat pump through the
piping and out into the building. This also applies to the expansion pipe. We recommend that flexible hoses are
36 – Installation instructions VMBMA1002
used for all pipe connections to avoid the transmission of vibrations. Flexible hoses are available to purchase as
accessories. The figures below show how appropriate and inappropriate installations look using this type of hose.
To avoid noise caused by pipe mounting, a rubber-coated pipe clamp should be used to prevent the transmission
of vibrations. However, installation should not be too rigid and the pipe clamp must not be too tight.
Figure 34.Do not twist the flexible hoses as they are installed. At threaded connections, use a counterhold spanner
Figure 35.Cut the hose to the correct length to avoid excess bowing-out or stretching at bends.
Figure 36.Cut the hose to the correct length to avoid excess bowing-out or stretching and offset the ends so that the
hose is installed completely straight.
Figure 37.Use fixed pipe bends to avoid excess stress on bends next to connections
Installation instructions VMBMA1002 – 37
123
5
7
6
4
8
9
121110
6Electrical Installation
DANGER! Electrical voltage! The terminal blocks are live and can be highly dangerous due to the risk of
electric shock. All power supplies must be isolated before electrical installation is started. The heat pump
is connected internally at the factory, for this reason electrical installation consists mainly of the
connection of the power supply.
Caution! Electrical installation may only be carried out by an authorized electrician and must follow
applicable local and national regulations.
Caution! The electrical installation must be carried out using permanently routed cables. It must be
possible to isolate the power supply using an all-pole circuit breaker with a minimum contact gap of 3
mm. (The maximum load for externally connected units is 2A).
6.1Electrical components
Figure 38.The location of the components on
the electrical panel
1Terminal block (applies to the expansion card)
2Terminal block (applies to DHP-A)
3Defrost card (applies to DHP-A)
4Terminal block
5Space for Danfoss Online
6Warning decal
7Space for expansion card
8Motor protection for compressor
9Automatic fuses
10Resetting overheating protection
11Control computer
12Soft starter card
4 kW6 kW8 kW10 kW12 kW16 kW
400V, 3-NA
230V, 1-NA
168/101/102/163101/162/20
201/252/32
3
251/322/40
3
3
161/162/20
251/322/40
3
3
161/162/20
321/402/50
3
3
161/202/25
321/402/50
3
3
201/202/25
-
3
DHP-C
6 kW8 kW10 kW4 H5 H7 H
400V, 3-NA
101/162/20
3
161/162/20
3
161/162/20
3
101/162/20
3
161/162/20
3
161/162/20
3
38 – Installation instructions VMBMA1002
21
43
65
N3 3L1 PE5 1L1 1L2 1L32L1 2L2 2L3 PE1
DHP-A, DHP-A Opti, DHP-AL, DHP-AL Opti
6 kW8 kW10 kW12 kW
400V, 3-NA
230V, 1-NA
101/162/203/204/
255/256/30
251/322/40
7
3
161/162/203/204/
255/256/30
251/322/40
1.Heat pump with 3 kW immersion heater (1-N 1.5 kW).
2.Heat pump with 6 kW immersion heater (1-N 3 kW).
3.Heat pump with 9 kW immersion heater (1-N 4.5 kW).
4.Heat pump with 12 kW immersion heater and shut off compressor
5.Heat pump with 15 kW immersion heater and shut off compressor
6.Heat pump with 12 kW immersion heater
7.Heat pump with 15 kW immersion heater
8.Fuse phase L1 (size 4 has 1-phase compressor)
6.3Connecting external supply voltage
7
3
161/162/203/204/
255/306/35
321/402/50
7
3
161/202/253/254/
255/306/35
321/402/50
7
3
DANGER! Electrical voltage! The power cable may only be connected to the terminal block intended for
this purpose. No other terminal blocks may be used!
1.Route the power cable through the opening in the top panel of the heat pump to the terminal blocks.
2.Connect the power cable as follows.
6.3.1Connection 400 V, 3-N
Incoming cable
Circuit-breakerTerminal block heat pump
Figure 39.Connection 400V 3N
Installation instructions VMBMA1002 – 39
21
43
1L1 N2 PE1
21
43
2L1,
2L2
N3 PE42L1,
2L1
H
2/3 x H
305 306
6.3.2Connection 230 V, 1-N
Incoming 230V heat pump
Incoming 230V immersion heater
6.3.3Connection 230 V, 3-P
See country specific electrical instructions.
Circuit-breakerTerminal block heat pump
Figure 40.Connection 230V 1N
6.4Position and connect outdoor sensors
Position the outdoor sensor on the north or north west side of the house.
•
For higher buildings, the sensor should be positioned between the second and third storeys. Its location must
•
not be completely protected from the wind but not in a direct draft. The outdoor sensor should not be placed
on reflective panel walls.
The sensor must be positioned at least 1 m from openings in the walls that emit hot air.
•
If the sensor cable is connected through a pipe, the pipe must be sealed so that the sensor is not affected by
•
outgoing air.
Recommended location
Unsuitable location
The outdoor sensor is connected by a two core cable. A maximum cable length of 50 m applies for a cross section
of 0.75 mm2. For greater lengths a cross section of 1.5 mm2 is used, up to a maximum of 120 m.
Then connect the sensor to the heat pump’s control system.
Figure 41.Connection outdoor sensor
40 – Installation instructions VMBMA1002
N/220
211
213
104
218
386
387
125
N/220
126
N/220
127
PE
220/N
211
213
283
104
218
386
387
125
4
5
7
8
9
1
2
3
6
311
312
325
326
1
2
6.5Connect outdoor unit, DHP-A, DHP-AL
Caution! The power cable may only be connected to the terminal block intended for this purpose. No
other terminal blocks may be used!
1.Route the power cable through the opening in the top panel of the heat pump to the terminal blocks.
2.Connect the power cable to the terminal block.
Outdoor unitHeat pumpSymbol explanation
1Neutral
2Fan high speed
3Fan low speed
4Motor protection fan
5Defrost sensor
6Accessories
7Heating, drip tray
8Heating cable
9Accessories
Figure 42.Connection outdoor unit
6.6Connect temperature sensor hot water, DHP-L
Sensor for hot water and hot water peak from external water heater is connected in the following way to DHP-L,
DHP-L Opti, DHP-L Opti Pro.
Symbol explanation
1.Sensor hot-water
2.Sensor hot-water top
Figure 43.Connection temperature sensor hot water
6.7Changing the language in the control computer
If necessary, change the language in the control computer menu system
1.Ensure that the main circuit breaker is on.
2.Open the INFORMATION menu.
3.Change language in the control computer menu INFORMATION -> LANGUAGE - ENGLISH, select language
with + or -.
Installation instructions VMBMA1002 – 41
6.8Selection of system solution and connection of external aux. heater
Note! Configure the heat pump for the desired system solution in the SERVICE\ADD. HEATER\EXTERNAL
ADDITION menu.
Also see section Piping installation and Menyinformation.
6.8.1System solution 1
The heat pump is delivered configured for system solution 1.
6.8.2System solution 2
Note! If necessary the external components must be fused using accessory 086U9685 FUSE TO EXTERNAL
COMPONENT according to the installation instructions supplied with the accessory. The tables below give
the components referred to.
For system solution 2, select the following in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXT.AUX.HEATER = ON
•
REV.V. HOT WATER = INT
•
For DHP-H, DHP-H Opti, DHP-H Opti Pro, DHP-C the electrical connection for system solution 2 must be carried out
according to the following table:
Table 2.Electrical connection
ComponentConnection
Internal auxiliary
heater
External auxiliary
heater
Additional shuntTerminal block, 215/216
Internal exchange
valve
I/O-card, output for 6 kW (normal connection)
I/O-card, output for 3 kW, connected and fused with 086U9685
I/O-card, 214 (normal connection)
For DHP-L, DHP-L Opti, DHP-L Opti Pro the electrical connection for system solution 2 must be carried out according to the following table:
Table 3.Electrical connection
ComponentConnection
Internal auxiliary
heater
External auxiliary
heater
Additional shuntTerminal block, 215/216
Internal exchange
valve
I/O-card, output for 6 kW (normal connection)
Terminal block 210, connected and fused with 086U9685
I/O-card, 214 (normal connection)
For DHP-A, DHP-A Opti, DHP-AL, DHP-AL Opti the electrical connection for system solution 2 must be carried out
according to the following table:
42 – Installation instructions VMBMA1002
Table 4.Electrical connection
ComponentConnection
Internal auxiliary heater I/O-card, output for 3 kW and 6 kW as well as Defrost card, output for 6 kW (normal connections)
External auxiliary heater Defrost card; 283, connected and fused with 086U9685
Note! If necessary the external components must be fused using accessory 086U9685 FUSE TO EXTERNAL
COMPONENT according to the installation instructions supplied with the accessory. The tables below give
the components referred to.
For system solution 3, select the following in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXT.AUX.HEATER = ON
•
REV.V. HOT WATER = EXT
•
For DHP-H, DHP-H Opti, DHP-C the electrical connection for system solution 3 must be carried out according to the
following table
Table 5.Electrical connection
ComponentConnection
Internal auxiliary
heater
External auxiliary
heater
Additional shuntTerminal block, 215/216
External exchange
valve
I/O-card, output for 6 kW (normal connection)
I/O-card, output for 3 kW, connected and fused with 086U9685
I/O-card, 214 kW, connected and fused with 086U9685
For DHP-L, DHP-L Opti the electrical connection for system solution 3 must be carried out according to the following table:
Table 6.Electrical connection
ComponentConnection
Internal auxiliary
heater
External auxiliary
heater
Additional shuntTerminal block, 215/216
External exchange
valve
I/O-card, output for 6 kW (normal connection)
Terminal block 210, connected and fused with 086U9685
I/O-card, 214 kW, connected and fused with 086U9685
For DHP-A, DHP-A Opti, DHP-AL, DHP-AL Opti the electrical connection for system solution 3 must be carried out
according to the following table:
Installation instructions VMBMA1002 – 43
Table 7.Electrical connection
ComponentConnection
Internal auxiliary heater I/O-card, output for 3 kW and 6 kW as well as Defrost card, output for 6 kW (normal connections)
External auxiliary heater Defrost card; 283, connected and fused with 086U9685
Additional shuntTerminal block, 215/216
External exchange
valve
For system solution 3, the heat pump's integrated exchange valve must be limited in open mode to the heating
system.
To limit the direction of flow for the exchange valve for the heating system, carry out the following steps:
1.Check that the main circuit breaker is on.
2.Open the SERVICE menu by pressing and holding the left button in for five seconds.
3.Open the control computer menu SERVICE -> MANUAL TEST.
4.Set the value for MANUAL TEST to 1.
5.Set the value for REV.V. HOT WATER to 0.
6.Wait at least 15 seconds, disconnect the quick connector at the exchange valve.
7.Set the value for MANUAL TEST back to 0.
8.Connect the external exchange valve cables according to the tables above.
9.Move the supply line sensor out to the position shown in the diagram for System solution 3.
I/O-card, 214 kW, connected and fused with 086U9685
6.9Changing the number of auxiliary heating power stages
Caution! Setting the maximum permitted number of power stages for the auxiliary heating must be
carried out.
1.Ensure that the main circuit breaker is on.
2.Open the SERVICE menu by pressing and holding in for five seconds.
3.Change the number of auxiliary heating power stages in the control system's menu SERVICE -> AUX.HEAT > MAXSTEP, select the number of stages using + and -.
44 – Installation instructions VMBMA1002
2
1
3
ROOM
NO HEAT DEMAND
OPERAT. AUTO
20°C
7Menu information
Menu description regards software with version 1.3.
The heat pump has an integrated control system which automatically calculates the heat demand in the house to
ensure that the correct amount of heat is produced and emitted where necessary.
The control panel is operated using a keypad and information is shown in a display and by an indicator.
Note! The information in the display and menus will vary depending on the heat pump model and
connected accessories.
1.Keypad
2.Indicator
3.Display
+ Plus sign used to scroll up a menu and increase the values.
- Minus sign used to scroll down a menu and reduce the values.
> Right arrow used to select a value or open a menu.
< Left arrow to cancel selection or exit a menu.
The indicator at the bottom of the control panel has three modes:
Not lit, means that the heat pump is not powered.
•
When the green light shines continuously, the heat pump has power and is ready to produce heat or hot
•
water.
Flashing green, means an active alarm.
•
Caution! During a service that consists of replacing the display card, all heat pump settings are reset to
factory settings. Therefore note current settings before replacement.
The control system is divided into the following two main menus:
INFORMATION
•
SERVICE
•
The INFORMATION menu is opened by pressing the left or right buttons.
For installation and service, the SERVICE menu is used, which is opened by pressing the left button for
at least five seconds.
Installation instructions VMBMA1002 – 45
8INFORMATION menu
Open the menu by pressing the left or right button. The menu also shows history and operating times.
Note! The menu information below describes all possible parameters. The parameters that appear in the
display vary depending on the selections made in menus (e.g. type of heat pump) and on the connected
hardware (e.g. expansion card and defrost card).
Table 8.Used to change the heat pump's operating modes and to adjust the heat curve.
MenuSub menuSub menuSub menu
INFORMATION
OPERAT.
HEAT CURVE
HEAT CURVE 2 (if shunt group is activated)
TEMPERATURE
OPERAT. TIME
ØCANCEL
Ø
AUTO
HEAT PUMP
AUX. HEATER
HOT WATER
MANUAL TEST
CURVE
MIN
MAX
CURVE 5
CURVE 0
CURVE -5
HEAT STOP
REDUCTION
TANK TEMP
OVERCHARGE
ROOM FACTOR
POOL
POOL HYSTERESIS
CURVE
MIN
MAX
OUTDOOR
ROOM
SYSTEM SUPPLY
SUPPLY LINE
RETURN LINE
BUFFER TANK
HOT WATER
INTEGRAL
BRINE IN
BRINE OUT
POOL
COOLING
SHUNT GROUP
2ND HEAT CIR.
CURRENT
46 – Installation instructions VMBMA1002
MenuSub menuSub menuSub menu
HEAT PUMP
AUX. HEAT 1
AUX. HEAT 2
AUX. HEAT 3
HOT WATER
COOLING
ACT COOLING
DEFROST
DEFROSTS
BETW. 2 DEFR
TIME LAST DEFR
FAN H OFF AT
DEFROST CURVE
MANUAL DEFR
LANGUAGE
SVENSKA
ENGLISH
DEUTSCH
NEDERLANDS
FRANÇAIS
ESPAÑOL
ITALIANO
NORSK
DANSK
SUOMI
EESTI
POLSKI
ČEŠTINA
8.1Sub-menu OPERAT.
Table 9.Used to select operating mode.
Menu selectionMeaningFactory setting
(OFF)
AUTOAutomatic operation with both heat pump and auxiliary heater permitted. If the
HEAT PUMPOperation with only heat pump permitted.
AUX. HEATEROperation with only auxiliary heater permitted.-
HOT WATEROperation with heat pump for hot water production and auxiliary heater during
MANUAL TESTOnly displayed when the value for MANUAL TEST is set to 2 in
The installation is fully switched off. This mode is also used to acknowledge certain alarms.
CANCEL = starting point, no changes made.
To select OFF as operating mode, press the minus sign once to scroll down one
step and press the right arrow once.
number of power stages for auxiliary heating are set to zero (SERVICE -> AUX.
HEATER -> MAX STEP) only AUTO or OFF can be selected as operating mode.
peak heating charging (anti-legionella function).
The SERVICE menu. Outputs that control components are activated manually.
-
-
-
Note! No peak heating charging (anti-legionella function) with
only heat pump operation.
-
-
Installation instructions VMBMA1002 – 47
8.2Sub-menu HEAT CURVE
Table 10.Used to change settings for the heat curve.
Menu selectionMeaningFactory setting
CURVECalculated supply temperature at 0°C outdoor temperature. Shown
as a graphic curve. The curve will be limited by the set values of MIN
and MAX.
MINMinimum permitted supply temperature, if the temperature for heat
stop has been reached and the heat pump has stopped.
MAXMaximum calculated setpoint value of the supply temperature.55°C
CURVE +5Local increase or reduction of CURVE at an outdoor temperature of
+5°C. Shown in the graph for CURVE.
CURVE 0Local increase or reduction of CURVE at an outdoor temperature of
0°C. Shown in the graph for CURVE.
CURVE -5Local increase or reduction of CURVE at an outdoor temperature of
-5°C. Shown in the graph for CURVE.
HEAT STOPMaximum outdoor temperature when heat production is permitted.
If HEAT STOP applies, the outdoor temperature must drop 3°C below
the setting before HEAT STOP stops.
REDUCTIONOnly appears if the tariff control function has been activated. Lower-
ing set room temperature. Active at 10 kΩ connection at EVU input.
TANK TEMPDisplayed if buffer tank is active. Charges the buffer tank to the set
temperature. AUTO setting charges the tank to the supply line setpoint value.
OVERCHARGEDisplayed if the buffer tank is active and TANK TEMP is set to AUTO.
Charges the buffer tank to supply line setpoint value + the value of
OVERCHARGE.
ROOM FACTOROnly displayed if an accessory Room temperature sensor is installed.
Determines how great an impact the room temperature is to have
when calculating the supply temperature. For under floor heating it
is recommended that ROOM FACTOR is set to 1, 2 or 3. For radiator
heating it is recommended that ROOM FACTOR is set to 2, 3 or 4.
POOLOnly appears if POOL is selected. The temperature in the pool is con-
trolled by a separate sensor regardless of the heating and hot water
system.
POOL HYSTERESISOnly appears if POOL is selected. The difference between the desired
charge value (adjustable) and actual value to the pool sensor. Pool
hysteresis does not affect the integral value.
40°C
(for under floor heating 30°C)
(range: 22°C / 56°C)
10°C
(range: 10°C / 50°C)
(for under floor heating 45°C)
(range: 40°C / 85°C)
0°C
(range: -5°C / 5°C)
0°C
(range: -5°C / 5°C)
0°C
(range: -5°C / 5°C)
17°C
(range: 0°C / 40°C)
2°C
(range: 1°C / 10°C)
AUTO
(range: 30°C / 55°C)
0°C
(range: 0°C / 5°C)
2
(range: 0 / 4)
(0 = no impact,
4 = very large impact)
20°C
(range: 5°C /40°C)
2°C
(range: 1°C / 10°C)
8.3Sub-menu HEAT CURVE 2
Only appears if shunt group sensor is connected and activated in menu SERVICE -> INSTALLATION -> SYSTEM ->
SHUNT GROUP.
Table 11.Used to change settings for heat curve 2.
Menu selectionMeaningFactory setting
CURVE 2Calculated shunt group temperature at 0°C outdoor temperature. Shown as a
graphic curve. The curve will be limited by the set values of MIN and MAX.
MINMinimum permitted shunt group temperature, if the temperature for heat stop
has not been reached.
MAXMaximum permitted shunt group temperature.55°C
48 – Installation instructions VMBMA1002
40°C
(range: 22°C / 56°C)
10°C
(range: 10°C / 50°C)
(range: 15°C / 70°C)
8.4Sub-menu TEMPERATURE
The history of different temperature measurements can be viewed by pressing the right arrow key. The graph
shows the last 60 measurement points for the set time interval (SERVICE -> INSTALLATION -> LOG TIME). In the
event of an alarm, history stops being logged until the alarm is reset by changing the operating mode to OFF.
Table 12.Used to indicate the prevailing temperatures, history and set/calculated values.
Menu selectionMeaningFactory setting
OUTDOORShows the actual outdoor temperature.-
ROOMShows the actual set temperature.-
SYSTEM SUPPLYDisplays system supply temperature at the buffer tank system.-
SUPPLY LINEShows the actual supply temperature. The calculated supply temperature to
the heating system group is within brackets.
During hot water production in operating mode AUX. HEATER the value for
HOT WATER STOP + 10° is shown within brackets.
RETURN LINEShows the actual return temperature. The stop temperature, MAX RETURN is
within brackets.
BUFFER TANKIndicates the buffer tank temperature, if activated.-
HOT WATERIndicates actual hot water temperature, if activated.-
INTEGRALShows the actual calculated value for integral.-
BRINE INShows the actual temperature for brine in.-
BRINE OUTShows the actual temperature for brine out.-
POOLOnly appears if POOL is selected. Shows the actual pool temperature.
The set pool temperature is shown in brackets.
COOLINGIndicates temperature.
SHUNT GROUPOnly appears if SHUNT GROUP is selected. Shows the actual supply tempera-
ture. The calculated supply temperature to the shunt group is within brackets.
2ND HEAT CIR.Shows the temperature of the second heating circuit if installed by the buffer
tank system.
CURRENTOnly appears if CURRENT LIMITER is selected. Shows the actual current con-
sumption. The set value for MAX CURRENT is shown in brackets.
-
-
-
-
-
8.5Sub-menu OPERAT.TIME
Table 13.Used to show the operating time for each component. Time given in hours.
Menu selectionMeaningFactory setting
HEAT PUMPCompressor operating time for both heating and hot water production.-
AUX. HEATEROperating time of auxiliary heater.-
HOT WATEROperating time for hot water with compressor.-
8.6Sub-menu DEFROST
Table 14.Used to obtain information about defrosting settings and to make defrosting settings.
Menu selectionMeaningFactory setting
DEFROSTSTotal number of defrosts carried out.-
BETW. 2 DEFRThe operating time of the compressor in minutes between the
TIME LAST DEFRThe operating time of the compressor in minutes since last
-
two last defrosts.
-
defrost.
Installation instructions VMBMA1002 – 49
Menu selectionMeaningFactory setting
FAN H OFF ATHigh speed is deactivated at this temperature and low speed is
DEFROST CURVEUsed to change the angle of the defrost curve using + or–
MANUAL DEFRUsed to perform a manual defrost. Started using + or -.0
8.7Sub-menu LANGUAGE
Table 15.Used to set the language of the menu system.
Menu selection
SVENSKA
ENGLISH
DEUTSCH
NEDERLANDS
FRANÇAIS
ESPAÑOL
ITALIANO
NORSK
DANSK
SUOMI
EESTI
POLSKI
ČEŠTINA
activated.
(Change the start temperature for defrost).
12°C
(range: 10°C / 20°C)
-10°C
(range: -13°C / -7°C)
(range: 0 / 1)
50 – Installation instructions VMBMA1002
9SERVICE menu
The SERVICE menu is for use during installation and service to optimise and adjust the operation of the heat pump.
Open the menu by pressing the left button for five seconds.
Note! The menu information below describes all possible parameters. The parameters that appear in the
display vary depending on the selections made in menus (e.g. type of heat pump) and on the connected
hardware (e.g. expansion card and defrost card).
Table 16.Used to change the heat pump's default settings.
MenuSub menuSub menuSub menuSub menu
SERVICE
HOT WATER
HEAT PUMP
AUX. HEATER
MANUAL TEST
START
HOT WATER TIME
HEATING TIME
TOPH. INTERVAL
TOPH. TIME
TOPH.STOP
INFL. H.W SENSOR
WEIGHT HOT WATER
INTEGRAL A1
HYSTERESIS
MAX RETURN
START INTERVAL
ALARM BRINE
PRESS. PIPE
OUTDOOR STOP
SHUNT TIME
SHUNT COOLING
MAX STEP
INTEGRAL A2
HYSTERESIS
MAX STEP
MAX CURRENT
HOT WATER STOP
DELAY AFTER EVU
EXT.AUX.HEATER
EXT.AUX.HEATER
INTEGRAL A3
TURN OFF DELAY
REV.V. HOT WATER
TOPH. AUX
Installation instructions VMBMA1002 – 51
MenuSub menuSub menuSub menuSub menu
MANUAL TEST
HEAT PUMP
BRINE PUMP
CIRC. PUMP
REV.V. HOT WATER
SHUNT
SYSTEM SHUNT
HGW-SHUNT
AUX. HEAT 1
AUX. HEAT 2
AUX. HEAT 3
EXT.AUX.HEATER
EXT. CIRC. PUMP
SHUNT DEFR
FAN L
FAN H
EXT. AUX. HEATER
ALARM
SHUNT COOLING
SHUNT GROUP
2ND H.C SHUNT
PASSIVE COOLING
ACT COOLING
REV. V. POOL
0-10V
INSTALLATION
SYSTEM
HEAT SOURCE
GROUND OR ROCK
AIR
(BRINE SOLUTION
DIRECT EVAP.)
COOLING
PASSIVE COOLING
(Ø
EXTERNAL
INTEGRATED IN HP)
ACT COOLING
(Ø
EXTERNAL)
ROOM SENSOR
POOL
SHUNT GROUP
BUFFER TANK
BUFFER TANK
SYSTEM SHUNT
2ND H.C SHUNT
ADDITION
OPTIMUM
HGW
0-10V
(Ø
EXT. AUX. HEATER)
FLOW SENSOR
CURRENT LIMITER
PHASE FAULT
(Ø
PHASE READING)
52 – Installation instructions VMBMA1002
MenuSub menuSub menuSub menuSub menu
SERVICE TIME
FACTORY SET
CANCEL
RADIATOR
FLOOR
RESET OPER. TIME
SENSOR CALIBRATION
OUTDOOR
SUPPLY LINE
RETURN LINE
HOT WATER
BRINE IN
BRINE OUT
DEFR SENSOR
POOL
SHUNT GROUP
HGW TEMPERATURE
BUFFER TANK
2ND HEAT CIR.
SYSTEM SUPPLY
EXTERNAL FACTOR
VERSION
DISPLAY
I/O-CARD
LOG TIME
BRINE TIME ON
BRINE TIME OFF
DEFROST
DEFR CURVE 0
DEFR CURVE -XX
DEFR TEMPERATURE
STOP DEFR
BELOW 5°C DEFR
MIN TIME DEFR
FAN START
FAN STOP
DEFR SENSOR
OPTIMUM
TEMP DIFF CIRC.
TEMP DIFF BRINE
START FLOW CIRC.
START FLOW BRINE
CONST. FL. CIRC:
CONST. FL. BRINE
MIN FLOW CIRC.
MAX H.W CHARGE HW
MIN CHARGE. HW
HGW
HGW TEMPERATURE
TEMPERATURE DIFF
HOT WATER DIFF
HOT WATER TO RAD
MAX TEMPERATURE
START HGW
INITIALIZING HGW
INTEGRAL DELAY
HGW-SHUNT TIME
HGW INT. BOUND.
HGW INTEGRAL
PULSE WIDTH
Installation instructions VMBMA1002 – 53
9.1Sub-menu HOT WATER
Table 17.Used to change the settings for hot water production.
Menu selectionMeaningFactory setting
STARTStart temperature for hot water production. Shows the actual
weighted hot water temperature and the value within brackets
indicates the start temperature. ( = no hot water production)
HOT WATER TIMETime for hot water production during combined hot water and
heating demand, in minutes.
TOPH. TIMETime in hours that the legionella demand is to be fulfilled for
legionella operation to be considered complete.
HEATING TIMETime for hot water production during combined heating and hot
water demand, in minutes.
TOPH. INTERVALTime interval between peak heating chargings (anti-legionella
function) in days. Operating mode that permits auxiliary heater
must be selected.
TOPH. STOPStop temperature for peak heat charging. Operating mode that
permits auxiliary heater must be selected.
INFL. H.W SENSOR.Water heater sensor’s influence compared with the peak sensor’s at
start of water heating.
WEIGHT HOT WATERThe calculated value of the hot water sensor directed towards the
peak sensor.
(range: , 30°C / 55°C)
20M
(range: 5M / 40M)
0M
(range: 1M / 10M
20M
(range: 5M / 40M)
7D
(range: , 1D / 90D)
60°C
(range: 50°C / 65°C)
65%
(range: 0% / 100%)
-
9.2Sub-menu HEAT PUMP
Table 18.Used to change the heat pump's operating settings.
Menu selectionMeaningFactory setting
INTEGRAL A1The integral’s value for starting the heat pump. See Important
parameters for more information.
HYSTERESISIf the difference between the actual supply temperature and the
calculated supply temperature is too great either the integral
value is set to start value A1 (the heat pump starts) or the value
is set to 0 (stops the heat pump).
MAX RETURNStop temperature at high return from the heating system.55°C
START INTERVALMinimum time interval between two heat pump starts in
minutes.
ALARM BRINEGives an alarm when the outgoing brine temperature falls
below the set value.
PRESS. PIPESensor on the compressor’s hot gas line. The value within brack-
ets indicates maximum permitted temperature. If this value is
exceeded, the compressor will stop and start again as soon as
the temperature has dropped. No alarm shown in the display,
however, a square is shown in the left, lower corner of the display.
OUTDOOR STOPDisplayed only if AIR is selected. Lowest outdoor temperature
when the outdoor sensor stops the compressor and heating or
hot water are instead produced by the auxiliary heater.
-60°min
(range: -250°min / -5°min)
10°C
(range: 1°C / 15°C)
(range: 30°C / 70°C)
20M
(range: 10M / 30M)
(range: , -14°C / 10°C)
140°C
-20°C
(range: -20°C / -1°C)
54 – Installation instructions VMBMA1002
Menu selectionMeaningFactory setting
SHUNT TIMETime in seconds. Indicates how often the shunt is to adjust its
opening.
SHUNT COOLINGThe cooling shunt works towards the set temperature.18°C
9.3Sub-menu AUX. HEATER
Table 19.Used to change the heat pump stages’ operating settings.
Menu selectionMeaningFactory setting
MAX STEP
INTEGRAL A2Two conditions must be fulfilled in order to start the auxiliary heater:
HYSTERESISIf the difference between the actual supply temperature and the cal-
MAX CURRENTRefers to main fuse in the unit, in amperes20
HOT WATER STOPStop temperature for hot water during AUX. HEATER. The value is
DELAY AFTER EVUTime in minutes. Indicates how many minutes after EVU are to pass
EXT.AUX.HEATER
Maximum number of permitted steps for auxiliary heating. = no
auxiliary heating permitted (Means that only AUTO or HEAT PUMP
can be selected.)
the integral’s value to start must be less than integral A2, and the
supply temperature must be 2°C lower than the calculated temperature. See Important parametersfor more information.
culated supply temperature is too great (see Important parameters),
either the integral value is set to start value A2 (starts the auxiliary
heater) or to 0 (stops the auxiliary heater ).
read off by the hot water sensor.
before the auxiliary heater may be activated.
Menu selectionMeaning
EXT.AUX.HEATERIndicates whether an external
INTEGRAL A3Indicates the value of the integral
TURN OFF DELAYIndicates how long the external
REV.V. HOT WATERIndicates whether the exchange
TOPH. AUXIndicates whether the external
auxiliary heater is installed in the
system.
when external auxiliary heater is
connected.
auxiliary heater must continue to
be active after its demand is no
longer needed.
valve for hot water is located
before or after the external auxiliary heater. (Determines whether
the external auxiliary heater may
produce hot water.)
auxiliary heater can be used for
anti-legionella. The exchange
valve must be positioned after
the external auxiliary heater.
60S
(range: 10S / 99S
(range: 0°C / 30°C)
(range: , 1, 2, 3, 4, 5, +4,
+5)
-600
(range: -50 / -990)
20°C
(range: 5°C / 30°C)
(range: 16 / 35)
60°C
(range: 50°C / 65°C)
30M
(range: 0M / 120M)
/ ON
-300
(range: -990 / INTEGRAL A1
- 10)
0M
(range: 0M / 180M)
INT / EXT
/ ON
Installation instructions VMBMA1002 – 55
9.4Sub-menu MANUAL TEST
Table 20.Used to manually test and test operate the heat pump’s components or signal outputs.
Menu selectionMeaningFactory setting
MANUAL TEST0 = deactivate manual test
1 = activate manual test
2 = activate manual test with option of navigating from the SERVICE menu
to check that the temperatures rise for example.
HEAT PUMP0 = stop heat pump
1 = start heat pump
-
-
Note! The heat pump cannot be started in the event of an
active alarm.
BRINE PUMP0 = stop the brine pump
1 = start the brine pump
CIRC. PUMP0 = stop the circulation pump
1 = start the circulation pump
REV.V. HOT WATER0 = heating mode for the exchange valve
1 = hot water mode for the exchange valve
SHUNT- = closes shunt
0 = shunt unaffected
+ = opens shunt
SYSTEM SHUNT- = closes shunt
0 = shunt unaffected
+ = opens shunt
HGW-SHUNT- = closes shunt
0 = shunt unaffected
+ = opens shunt
AUX. HEAT 10 = stop aux. heater step 1
1 = start aux. heater step 1
AUX. HEAT 20 = stop aux. heater step 2
1 = start aux. heater step 2
AUX. HEAT 30 = stop aux. heater step 3
1 = start aux. heater step 3
EXT.AUX.HEATER0 = stop external auxiliary heater
1 = start external auxiliary heater
EXT.CIRC. PUMP0 = stop circulation pump
1 = start circulation pump
SHUNT DEFR- = opens flow from defrosting tank
0 = shunt unaffected
+ = closes flow from defrosting tank
FAN L0 = stop fan
1 = start fan at low speed
FAN H0 = stop fan
1 = start fan at high speed
EXT. AUX. HEATER0 = 0V on plinth 283
1 = control voltage 230V on plinth 283
ALARM0 = stop signal on output External alarm
1 = start signal on output External alarm
SHUNT COOLING- = closes shunt
0 = shunt unaffected
+ = opens shunt
SHUNT GROUP- = closes shunt
0 = shunt unaffected
+ = opens shunt
-
-
-
Only at buffer tank
-
-
-
56 – Installation instructions VMBMA1002
Menu selectionMeaningFactory setting
2ND H.C SHUNT- = closes shunt
0 = shunt unaffected
+ = opens shunt
PASSIVE COOLING0= stop passive cooling
1= start passive cooling
COOLING A0= stop active cooling
1= start active cooling
REV. V. POOL0 = normal mode for the exchange valve
1 = pool mode for the exchange valve
0-10VUsed for circulation pumps at BUFFER TANK.-
Only at buffer tank
-
Installation instructions VMBMA1002 – 57
9.5Sub-menu INSTALLATION
Table 21.Used for settings that are set during installation.
Menu selection MeaningFactory setting
SYSTEMSub menu SERVICE -> INSTALLATION -> SYSTEM:
Note! The menu selection in the SYSTEM menu varies depending on the selected
values. Tip: start in the top menu and work downwards.
Menu selectionMeaning
HEAT SOURCEGROUND OR ROCK
COOLINGPASSIVE COOLING
POOL
SHUNT GROUP
BUFFER TANK (See sepa-
rate instruction for buffer
tank)
ADDITIONOPTIMUM
OUTSIDE AIR
(BRINE SOLUTION, DIRECT EVAP.)
(, EXTERNAL, INTEGRATED IN HP)
COOLING A
(, EXTERNAL)
ROOM SENSOR
(, ON)
, ON
, ON
BUFFER TANK
SYSTEM SHUNT
2ND H.C SHUNT
(, ON)
HGW
(, ON)
0-10V
(, EXT. AUX. HEATER)
FLOW SENSOR
(
, ON)
CURRENT LIMITER
, ON)
(
PHASE FAULT
, PHASE READING)
(
SERVICE TIME
Note! Only used for test operation. The heat
pump counts 60 times as fast, which means that
the waiting times are eliminated during test
operation.
0 = deactivates SERVICE TIME
1 = activates SERVICE TIME, which speeds up the control system’s integral calculation and start delay by 60 times.
58 – Installation instructions VMBMA1002
-
Menu selection MeaningFactory setting
FACTORY SETCANCEL = starting point, no changes made.
RADIATOR = reset factory settings for radiator system
FLOOR = reset factory settings for under floor heating
RESET OPER.
TIME
SENSOR CALIBRATION
VERSIONShows the software version which is stored on the display card
LOG TIMETime interval between collection points of temperature history
BRINE TIME ONThe brine pump starts the set number of seconds before the
BRINE TIME OFFThe brine pump stops the set number of seconds after the com-
0 = no reset of operating times
1 = reset of operating times to zero
Following sensors can be found in the installation:
OUTDOOR
SUPPLY LINE
RETURN LINE
HOT WATER
BRINE IN
BRINE OUT
DEFR SENSOR
POOL
SHUNT GROUP
HGW TEMPERATURE
BUFFER TANK
2ND HEAT CIR.
SYSTEM SUPPLY
EXTERNAL FACTOR Affects sensors that are installed inside the
heat pump.
respectively the I/O-card.
DISPLAY: V X.X
I/O-CARD: V X.X
in minutes. The history graphs always show the 60 last collection points, which means that the graphs can display history
from 1 hour up to 60 hours ago.
(The function is not active if there is an active alarm).
The menu applies to DHP-A, DHP-AL with defrost card and only appears if OUTDOOR AIR in SERVICE -> INSTALLATION -> SYSTEM -> HEAT SOURCE menu is selected.
Table 22.Used to change settings for outdoor unit defrost.
Menu selectionMeaningFactory setting
DEFR CURVE 0Used to set the temperature of the heat pump’s brine return at
which defrosting should start, at 0°C outdoor temperature, using +
or -.
The graph can be changed up or down at 0°C outdoor temperature
in the display. See Important parameters for more information.
DEFR CURVE -xxUsed to set the temperature at which the heat pump's brine return
is to start a defrost, at the set outdoor temperature for OUTDOOR
STOP, using +or-.
The setting is made by reducing the OUTDOOR STOP value by this
value.
The number of degrees shown after DEFR CURVE in the display is
the set value for OUTDOOR STOP. The combined temperature is
shown in the top right corner of the display.
The graph can be changed up or down at the outdoor temperature
OUTDOOR STOP in the display. See Important parameters for more
information.
DEFR TEMPERATURE
STOP DEFRThe temperature that the Brine In sensor must reach to complete a
BELOW 5°C DEFRSafety defrosting occurs when the outdoor temperature has been
MIN TIME DEFRMinimum time between two defrosts in minutes.45M
FAN STARTThe fan starts when the temperature on the brine in sensor to the
FAN STOPThe fan stops when the temperature on the brine in sensor to the
DEFR SENSORShows the actual temperature of the incoming air to the outdoor
The temperature shunted to the outdoor unit during a defrost.15°C
defrost.
below 5°C for a set number of days, shunts +20°C for 10 minutes.
heat pump reaches the set value.
If FAN START is set to ON, the fans starts and stops at the same time
as the compressor and the FAN STOP parameter is inactive.
The menu applies to Opti with speed controlled circulation pumps and only appears if ON in SERVICE -> INSTALLATION -> SYSTEM -> ADDITION -> OPTIMUM menu is selected.
Table 23.Used to change the circulations pumps’ operating settings.
Menu selectionMeaningFactory setting
TEMP DIFF CIRC.Desired temperature difference between supply and return line
for the heating system.
TEMP DIFF BRINEDesired temperature difference between supply and return line
for the brine system.
60 – Installation instructions VMBMA1002
8°C
(range: , 0°C / 15°C)
3°C
(range: , 0°C / 15°C)
Menu selectionMeaningFactory setting
START FLOW CIRC.Speed control of the heating system’s circulation pump in Volts.
Higher voltage gives a greater circulation pump speed, which
gives a lower temperature difference. A low voltage gives a
greater difference.
3 - 10 = Manually adjustable speed, where 3 is low voltage and
10 is high voltage.
START FLOW BRINESpeed control of the brine system’s circulation pump in Volts.
Higher voltage gives a greater brine pump speed, which gives a
lower temperature difference. A low voltage gives a greater difference.
3 - 10 = Manually adjustable speed, where 3 is low voltage and
10 is high voltage.
CONST. FL. CIRC.
CONST. FL. BRINE
MIN FLOW CIRC.Lowest permitted voltage (speed) of the circulation pump’s flow
MAX H.W CHARGE HWHighest supply temperature during water heating.55°C
MIN CHARGE. HWLowest desired supply temperature during water heating.50°C
If TEMP DIFF CIRC is set to the flow is continuous with this
value in the heating system. Value indicated in Volts.
If TEMP DIFF BRINE is set to the flow is continuous with this
value in the brine system. Value indicated in Volts.
in the heating system. If there is no heat demand, there may still
be a demand to read in the temperatures for the sensors in the
system and the circulation pump therefore must be run.
7V
(range: 3V / 10V)
10V
(range: 3V / 10V)
7V
(range: 3V / 10V)
10V
(range: 3V / 10V)
3V
(range: 3V / 10V)
(range: 45°C / 65°C)
(range: 30°C / 65°C)
9.8Sub-menu HGW
The menu applies to the Opti Pro-modelswith de-superheater and only appears if ON in SERVICE -> INSTALLATION
-> SYSTEM -> ADDITION -> HGW menu is selected.
Table 24.Used to change the de-superheater’s operating settings.
Menu selectionMeaningFactory setting
HGW TEMP.Shows the HGW sensor after the de-superheater (the supply tempera-
TEMP DIFFDesired difference between the HGW sensor and water heater’s start
HOT WATER DIFF.Shows actual difference between the HGW sensor and water heater’s
HOT WATER TO RAD. If there is a heat demand, the HGW shunt switches to the heating sys-
MAX TEMP.Max temperature of the water in the water heater. The temperature is
ture to water heater) in °C.
sensor.
start sensor.
tem when the weighted value is greater than the total of the START
temperature for hot water and this value. Example: 40°+3K = at a temperature of 43°C in the water heater, the shunt switches to the heating
system.
measured on the peak sensor in the water heater.
Note! Domestic hot water can have this temperature,
which can mean that an external mixer valve may be
required.
-
20K
(range: 15K / 35K)
-
3K
(range: 1K / 10K)
95°C
(range: 60°C / 100°C)
START HGWThe number of seconds the HGW shunt is to open at HGW start is the
starting point of shunt opening. The opening time for the HGW shunt
from fully closed to fully open towards the water heater is 30 seconds.
INITIALIZING HGWThe time in seconds before control of HGW shunt starts after HGW start. 60S
7S
(range: 0S / 30S)
(range: 10S / 90S)
Installation instructions VMBMA1002 – 61
Menu selectionMeaningFactory setting
INTEGRAL DELAYDelay of integral calculation in seconds after the integral value for HGW
has been reached.
HGW-SHUNT TIMEThe time that the signal is active to open or close the HGW shunt com-
pletely.
HGW INT. BOUND.Integral value (parameter) for HGW.60
HGW INTEGRALShows the actual value for the HGW integral. Plus indicates that the
shunt opens towards the water heater and minus indicates that the
shunt opens towards the heating system.
PULSE WIDTHHow long the plus or minus signal to the shunt is to be high when the
HGW integral has been reached.
10S
(range: 5S / 120S)
35S
(range: 15S / 60S)
(range: 10 / 120)
-
0.25S
(range: 0.20S / 1.00S)
62 – Installation instructions VMBMA1002
10Commissioning
10.1Filling the water heater and heating system
1.Fill the water heater with cold water by opening the filler valve that is on the valve pipe.
2.Bleed by opening one of the hot water taps.
3.Then fill the water heater coil and the heating system with water through the filling valve to a pressure of
approx. 1 bar.
10.2Bleed the heating system
1.Open all radiator valves fully.
2.Bleed all radiators.
3.Refill the heating system to a pressure of approximately 1 bar.
4.Repeat the procedure until all air has been removed.
5.Leave the radiator valves fully open.
10.3Filling the brine system
Caution! Before filling the brine system, the electrical installation must be completed so that it is possible
to operate the brine pump.
Caution! Before filling the brine system for DHP-A, DHP-AL, the water heater MUST be filled.
Note! Always check local rules and regulations before using anti-freeze.
Note! Anti-freeze with corrosion protection additives must be used and mixed to achieve frost protection
down to -15°C for DHP-H, DHP-L and DHP-C..
Note! Use only ethylene glycol as anti freeze for DHP-A and DHP-AL, mixed to achieve frost protection
down to -32±1°C.
10.3.1Calculated volume DHP-H, -C, -L
The volume of the brine system is calculated as follows:
Heat pump (exchanger and piping) approximately 2 litres
•
Expansion tank approximately 3 litres
•
Collector (single pipe): PEM 40 approximately 1.0 litre/m; PEM 32 approximately 0.6 litre/m; Cu 28 approxi-
•
mately 0.5 litre/m
10.3.2Calculated volume DHP-A, -AL
The volume of the brine system is calculated as follows:
Heat pump (exchanger, pipe and outer jacket) approximately 47 litres
•
Expansion tank approximately 3 litres
•
Outdoor unit approximately 7 litres
•
Collector (single pipe): 28 mm pipe approx. 0.5 litre/m
•
Installation instructions VMBMA1002 – 63
10.3.3Filler cock
467
35
1
2
3
456 7
8
9
10
11
12
When the filler cock is installed on the return pipe, remember to turn the strainer cover upwards in order to minimise the amount of air that gets into the brine system when cleaning the filter.
1Brine in
2Brine out
3Shut-off valve (part of the filler cock)
4Shut-off valve (part of the filler cock)
5Shut-off valve (part of the filler cock)
6Strainer (part of the filler cock)
7Shut-off valve (part of the filler cock)
8Safety valve 1.5 bar
9Bleed and expansion tank
10Shut-off valve
11External pump
12External container
64 – Installation instructions VMBMA1002
1.Set the heat pump operating mode to "OFF" in the control computer menu INFORMATION -> OPERAT.
2.Mix water and anti-freeze in the correct proportions in an external container (12). Note that each pack must
be well mixed.
3.Check that the freezing point of the mixture is reached using a refractometer (-15°C for DHP-H, DHPC andDHP-L), (-32±1°C for DHP-A, DHP-AL).
4.Fill the system with the mixture using an external pump (11) which can bleed the brine pipes. Connect the
pressure side of the pump to the filler connection at valve (5).
5.For DHP-A, DHP-AL: open the defroster shunt in the control computer menu SERVICE -> MANUAL TEST ->
SHUNT DEFR, set the value to -.
6.Close valve (4).
7.Open valves (5) and (10).
8.Connect a transparent hose (3) that opens out into the external container (12).
9.Open valve (3).
10.Start the external pump (11) and fill the brine pipes.
11.Start the brine pump manually in the control computer menu SERVICE -> MANUAL TEST -> BRINEPUMP, set
the value to 1.
12.Run the brine pump and the external pump (11) in series until fluid, clear of air, comes out of the return
hose from the valve (3).
13.Stop the brine pump in the control computer menu SERVICE -> MANUAL TEST -> BRINEPUMP, set the value
to 0, at the same time leave the external pump running.
14.Open valve (4) with the external pump running to eliminate the air between the valves (3) and (5).
15.Close valve (3) and pressurise the system using the external pump.
Caution! Max 150kpa (1.5 bar)
16.Close valve (5).
17.For DHP-A, DHP-AL: close the defroster shunt in the control computer menu SERVICE -> MANUAL TEST ->
SHUNT DEFR, set the value to 0.
18.Stop the external pump (11) and disconnect the filling equipment.
19.Install insulation on the filler cock.
10.4Bleed the brine circuit
Note! When topping up, the brine pump must be running.
1.Start the brine pump in the control system's menu SERVICE -> MANUAL TEST -> BRINEPUMP, set the value
to 1.
2.Check that the level in the bleed tank (9) is stabilised.
3.Dismantle the safety valve (8) on the bleed tank.
4.Top up with brine to 2/3 of the tank through the connection on which the safety valve (8) was installed.
5.Leave the brine pump running so that that the air in the system collects in the bleed tank.
6.As air separates in the bleed tank the fluid level drops, top up as in step 4.
7.Reinstall the valve (8) when all air has been removed from the system.
8.Open valve (8) and release any overpressure. The fluid level should not fall below 2/3 of the height of the
tank.
9.Check that valve (3) is closed.
10.Stop the brine pump in the control system's menu SERVICE -> MANUAL TEST -> BRINEPUMP, set the value
to 0.
11.Switch to the desired operating mode if the heating system has been filled and bled.
Collect any excess brine in a plastic container for topping up the system if necessary (leave it with the customer).
10.5Bleed the outdoor unit
If the outdoor unit is installed higher than the heat pump with a pressurised brine system, the outdoor unit must
be bled using the bleed screws (1) on the connection pipes. The side covers of the outdoor unit must be removed
to access the bleed screws.
Installation instructions VMBMA1002 – 65
1
Symbol explanation
1Bleed screws
Figure 46.Location of bleed screws
If the outdoor unit is installed at the same level or lower than the heat pump it is recommended that the brine
circuit in the outdoor unit is also bled. After bleeding, the side panels and decor front panel must be installed.
10.6Start up
Note! Read the safety instructions!
Caution! The installation may only be commissioned if the heating system, water heater and brine system
have been filled and bled. Otherwise the circulation pumps can be damaged.
Caution! Any alarms that may occur in connection with the installation must be fault-traced.
Caution! If the installation is only to operate using an auxiliary heater during the installation, ensure that
the heating system is filled and bled and that the compressor cannot be started. This is carried out by
setting the operating mode to INFORMATION --> OPERAT.--> AUX. HEATER
Caution! For heat pumps DHP-H Opti Pro SP and DHP-L Opti Pro SP (1-phase) it is imperative that the hot
water temperature changes from default setting 95 °C to 85 °C.
10.6.1Installation checklist
Before manual test operation, the following points must be checked to ensure that they have been correctly carried out:
Piping installation
•
Electrical Installation
•
10.6.1.1 Piping installation, heating system
Pipe connections in accordance with the connection diagram
•
Flexible hoses on the supply and return lines
•
Pipe insulation
•
66 – Installation instructions VMBMA1002
Strainer on return line
•
The heating system has been bled
•
All radiator valves fully open
•
Expansion tank heating system (not included in the delivery)
•
Safety valve for expansion tank (not included in the delivery)
•
Filler cock heating system (not included in the delivery)
•
Leakage inspection
•
If a an external water heater is installed, also check:
Reversing valve
•
Safety valve for cold water (9 bar)
•
10.6.1.2 Electrical Installation
Circuit-breaker
•
Fuse protection
•
Direction of rotation of the compressor
•
Coolant pump
•
For DHP-A, outdoor unit
•
For DHP-A, defrost sensor
•
Positioning of the outdoor sensor
•
Control computer settings
•
If a an external water heater is installed, also check:
Reversing valve
•
10.6.1.3 Brine system
Expansion/bleed tank on the return pipe
•
Safety valve for expansion tank
•
Filler cock on the return pipe
•
Insulation in the outside wall lead-in
•
Other brine pipe insulation
•
Bleeding brine
•
Leakage inspection
•
10.6.2Manual test
Test operate and at the same time check the function of the components.
10.6.2.1 Activate MANUAL TEST
1.Ensure that the main circuit breaker is on.
2.Select operating mode , in the menu INFORMATION -> OPERAT.->
3.Open the SERVICE menu by pressing and holding < in for five seconds.
4.Set the value for MANUAL TEST to 2.
Note! Set MANUAL TEST to 2 to navigate away from the menu during ongoing test operation.
Installation instructions VMBMA1002 – 67
10.6.2.2 Test the brine pump
1.Start the brine pump by setting the value BRINE PUMP to 1.
2.Check that the brine pump is running by:
listening
•
putting a hand on the pump
•
checking that the level in the expansion tank is stable. If the level is not stable there is air in the system.
•
listen for air
•
3.If the pump does not start automatically, perform manual start.
4.If there is air in the brine system, bleed the system.
5.Stop the brine pump by setting the value to 0.
10.6.2.3 Test the circulation pump
1.Start the heating system circulation pump by setting the value CIRC. PUMP to 1.
2.Check that the circulation pump is running by carrying out the following:
Listen
•
Place a hand on the pump
•
Listen for air
•
3.If the pump does not start, see Starting circulation pumps manually.
4.If there is air in the heating system, bleed the system, see Bleed the heating system.
5.Stop the circulation pump by setting the value to 0.
10.6.2.4 Test the exchange valve
1.Activate the 3-way valve by setting the value REV.V. HOT WATER to 1.
2.Check that the indicator on the exchange valve's upper side changes position.
3.If the indicator does not change position, perform fault tracing.
10.6.2.5 Test the compressor
1.Start the circulation pump by setting the value CIRC.PUMP to 1.
2.Start the heat pump compressor by setting the value HEAT PUMP to 1. At the same time as the value is set
to 1 for HEAT PUMP the brine pump starts.
Warning! Risk of burn injury, the pressure pipe on the compressor can get up to 70-80 degrees in
temperature after operating for a while!
3.Check that:
the compressor is running in the right direction by putting a hand on the pressure pipe before the com-
•
pressor starts, the pipe is then cold. Feel again after a short while to ensure the pressure pipe becomes
properly hot.
it sounds normal and there is no noise.
•
4.If the pipe does not get hot, or if the compressor sounds abnormal, perform fault tracing according to the
service instructions.
5.Stop the compressor by setting the value to 0.
6.Stop the brine pump by setting the value to 0.
7.Stop the circulation pump by setting the value to 0.
10.6.2.6 Testing the auxiliary heating power stages
1.Start the circulation pump by setting the value CIRC. PUMP to 1
2.Start the first auxiliary heating power stage by setting the value ADD.HEAT 1 to 1.
68 – Installation instructions VMBMA1002
1
3.Check that the auxiliary heater step works by exiting the MANUAL TEST menu and entering the INFORMATION -> TEMPERATURE -> SUPPLY LINE menu and check that the temperature rises.
4.Return to the menu MANUAL TEST and stop AUX. HEAT 1 by setting the value back to 0.
5.Repeat the steps in AUX. HEAT 1 for AUX. HEAT 2 and AUX. HEAT 3.
6.Stop the circulation pump by setting the value to 0.
10.6.2.7 Test the outdoor unit for DHP-A, -AL
1.Start the defroster shunt by setting the value SHUNT DEFR to -(minus). Check that the shunt motor is drawing current.
2.Start the fan at low speed by setting the FAN L value to 1. Check that the fan runs at low speed.
3.Start the fan at high speed by setting the FAN H value to 1. Check that the fan runs at high speed.
10.6.2.8 Exit test operation
Set the value for MANUAL TEST to 0.
10.7Commissioning
10.7.1Starting circulation pumps manually
If any of the circulation pumps do not start, it may need to be helped as follows:
Figure 47.Location of the bleed screw
Caution! When bleeding the circulation pumps, water can come into contact with electrical components.
Therefore, protect the electric panel against water.
1.Open and remove the bleed screw on the front of the pump. Ensure to catch the water that runs out when
the screw is removed.
2.Insert a flat blade screwdriver and turn it in the direction of rotation of the pump (clockwise).
3.Reinstall the bleed screw with its rubber seal.
10.7.2Adaptation to the heating system
Adjust the heat pump settings to the applicable heating system, for instance an underfloor heating or radiator
system. The delta temperature must be at least 8°C above the heat pump. The delta temperature should be 3–5°C
for the brine system. If one of the ΔT is not reached, the flow of the circulation pumps may need adjusting depending on the applicable heating system.
Installation instructions VMBMA1002 – 69
10.7.2.1 Noise check
During transportation and installation there is a certain risk that the heat pump can be damaged, components
may move or get bent and this can cause noise. Because of this it is important to check the heat pump when it has
been installed and is ready to be commissioned to ensure that everything is in order. The heat pump should be
tested in both heating and hot water modes to ensure that there is no abnormal noise. While doing this, check
that there is no abnormal noise in other parts of the house.
Noise is produced from the outdoor unit when the fan is in operation, check during that manual operation that
there is no disturbance in your own home as well as to any neighbours. A noise kit is available for purchase for the
outdoor unit for DHP-A 10 and 12 if it is necessary to reduce the noise.
10.7.2.2 Select operating mode
Set the heat pump to the desired operating mode in the menu INFORMATION -> OPERAT. If necessary, set certain
parameters in the control system, such as ROOM and CURVE.
10.7.3Installing the front cover
Caution! Take care not to damage the front cover or display cables!
1.Hook on the lower edge of the front cover.
2.Carefully press the front cover’s upper edge towards the heat pump.
3.Turn the catch in the top panel 90 degrees clockwise.
10.7.4After start up
Note! Remember that it takes time for the heat pump to heat a cold house. It is best to let the heat pump
work at its own pace and NOT raise or alter any values in the control system to try to heat it up more
rapidly.
Caution! If there is an alarm in conjunction with commissioning it usually means that there is air in the
system.
10.8Trimming the heating system
To obtain a heating system balance and obtain an even and comfortable indoor temperature, you must adjust
your heating system according to the example below.
Note! Adjust the heating system during the winter to obtain the greatest possible output.
Note! Trimming must be carried out over a few days as the inertia in the heating system causes the indoor
temperature to change slowly.
1.Choose one of the house’s rooms as a reference room for the indoor temperature, where the highest temperature is required, 20-21°C.
2.Place a thermometer in the room.
3.Open all the heating system’s radiator valves fully.
4.Leave the heat pump’s ROOM value set at 20°C. See Setting ROOM values for more information.
5.Note the temperature in the reference room at different points in time over a 24 hour period.
70 – Installation instructions VMBMA1002
6.Adjust the ROOM value so that the reference room reaches your required indoor temperature of 20-21°C.
Remember that other rooms will have different temperatures during trimming, but these are adjusted later.
7.If the ROOM value must be adjusted more than 3°C upwards or downwards the CURVE value must be adjusted instead. See Adjusting CURVE values for more information.
8.If the indoor temperature varies several degrees despite trimming, a specific part of the heat curve may
need adjusting. Check at what outdoor temperature the variation is greatest and adjust the curve at the
corresponding value (CURVE 5, CURVE 0, CURVE -5). See Adjusting a specific part of the heat curve for more
information.
9.When the reference room has an even temperature of 20-21°C over a 24 hour period, you can adjust the
radiator valves in the other rooms so that their indoor temperatures are the same temperature or lower
than the reference room.
10.9Customer information
After commissioning is complete, the customer must be informed about their new heat pump installation. Below
is a checklist regarding the information that the installer must give the customer:
The model of the heat pump that has been installed
•
Run through the User manual and show what it contains
•
Describe the various operating modes and what they mean
•
Describe the most common alarms and corrective actions
•
Demonstrate how to navigate the control system and which settings the customer can set themselves
•
Demonstrate how to view history and operating times
•
Show the pipe installation and go through the periodic maintenance actions that the customers must be
•
aware of:
o
check the recommended pressure on the manometers
o
fill the heating system
o
exercise safety valves
o
clean strainers
Explain how the customer can tune their existing heating system according to the instructions in the User
•
manual
The applicable warranties
•
Where the customer is to turn for servicing
•
Finally, fill in the references at the back of the Maintenance instructions.
•
Installation instructions VMBMA1002 – 71
VMBMA1002