Danfoss DEVIpipeguard Ex Data sheet

Hazardous areas (ATEX)
Data Sheet
DEVIpipeguard Ex
DEVIpipeguard™ Ex
The DEVIpipeguard™ Ex self-limiting cable will keep your pipe system protected from freezing during cold temperatures and can also be used for maintaining constant temperatures for dierent liquids. The DEVIpipeguard™ Ex is approved for hazardous areas.
The self-limiting capability of the cable ensures that the output of the cable increases or decreases according to ambient temperature. The cables can be installed directly on the pipe system.
Benets:
• High chemical resistance
• Can be cut to length on site
• Can be used in hazardous areas
• UV resistant
• Moisture proof
Standard compliance:
• EN60079-0:2009, EN60079-31:2009 and EN60079-30-1:2007
Certicates:
h EPS 14 ATEX1743 U
Type
Operation voltage
Cable dimensions
Cable length on drum
Outer sheath
Bus wire
Max. permissible use temperature (powered)
Max. permissible use temperature (unpowered)
Min. bending radius
Min. installation temp. -45° C
Max. surface temperature 80° C (T6)
Classication
Value
230 V~
14.1 x 5.8 mm.
305 m
Black, TPE-O
Cu nickel plated, 2 x 1.23 mm
65° C
80° C
25 mm
II 2G Ex e IIC Gb
II 2D Ex tb IIIC Db
Types
Item no. Type Otput Max. installation length* EAN no.
98300675 DEVIpipeguard™ Ex 20 20 W/m @ 10° C 109 m @ 10° C and 16A 5703466208045
98300676 DEVIpipeguard™ Ex 30 30 W/m @ 10° C 83 m @ 10° C and 16A 5703466208052
98300679 DEVIpipeguard™ Ex 40 40 W/m @ 10° C 57 m @ 10° C and 16A 5703466208069
*With a 16A circuit breaker To prevent moisture from damaging the cable during storage, the ends must be seale. RCD of 30 mA is required, max. 500 m of cable per RCD.
Construction
Outer sheath
Screen
Insulation
Self limiting heating element
Bus wires
Accessories and spare parts on page 93
60
VDIWY302
Produced by Danfoss © 07/2015
Loading...