Danfoss DEVIpipeguard 30, DEVIpipeguard 60 Data sheet

DEVIpipeguard™ Industry
Data Sheet
DEVIpipeguard™ 30 Industry, DEVIpipeguard™ 60 Industry
DEVIpipeguard™ Industry is a self-limiting heating cable that is mainly used for frost protection of pipes and for temperature maintenance in applications up to 120 °C powered or 190 °C unpowered cable.
The cable allows steam cleaning in pipes. The heating element, the insulation and the outer jacket of DEVIpipeguard™ Industry are made of fluoropolymers.
Fluoropolymer outer jacket offers increased protection against chemicals (oil and fuel) and abrasion.
A temperature-dependent resistance element between two parallel-guided copper conductors regulates and limits the heat output of the heating cable. This power setting takes place at every point of the heating cable, according to the ambient temperature prevailing there.
If the temperature rises, the power of the cable is reduced. This self-limiting prevents overheating of the cable, even if it is overlaid. The heating cable can be cut off at desired length by the parallel current supply. This simplifies planning and installation. All self­limiting heating cables must be over-temperature protected by a thermostat, as the output will decrease, but never be zero.
The installation of a thermostat is recommended.
The cable is not approved for use in drinking water.
Benefits:
Cut to length on site
PVC free
Standard compliance:
Approvals:
Type
Nominal voltage 230 V AC (max. 254 V AC)
Nominal output (min-max): DEVIpipeguard™ 30 Industry DEVIpipeguard™ 60 Industry
Maximum permissible use temperature
Temperature rating conform IEC 60079-30
Minimum installation and switched on temperature -5 °C
Cable dimensions 11,8 x 5,8 mm
Outer sheath Red, Fluorpolymer
Minimum braid coverage 70 %
Maximum resistance protective braid 18,2 Ω/Km
Bending Ø, min. 50 mm (Ø to the inside of the tape)
IP Class IPX7
Value
30 W/m @ 10 °C (30-39 W/m @ 10 °C)
60 W/m @ 10 °C (54-72 W/m @ 10 °C)
120 °C, powered
190 °C, unpowered
DEVIpipeguard™ 30 Industry – T3 (max 200°C) DEVIpipeguard™ 60 Industry – T2 (max 300°C)
Types DEVIpipeguard™ 30 Industry
Item no. Length
00109025 Drum, 270 m 270-330 m 1 30 W/m 5703466195673 98300673 Cut-to-length 1 m - 30 W/m 5703466197257
Min-max length per
drum
Number of length
allowed on drum, max
Nominal
output @ 10 °C
EAN no.
Types DEVIpipeguard™ 60 Industry
Item no. Length
00109027 Drum, 270 m 270-330 m 1 60 W/m 5703466163498 98300674 Cut-to-length 1 m - 60 W/m 5703466197264
Min-max length per
drum
Number of length
allowed on drum, max
Nominal
output @ 10 °C
Produced by Danfoss ©AI239086497888en-010104
EAN no.
Maximum heating circuit length on a pipe, with circuit breaker with C-characteristic
DEVIpipeguard™ 30 Industry
Switch on
temperature
10 A 16 A 20 A 25 A 32 A 10 A 16 A 20 A 25 A 32 A
Power W/m
Power W/m
DEVIpipeguard™ 60 Industry
30 °C 25,5 65 104 130 133 133 52,4 36 58 73 75 75 20 °C 27,7 61 98 122 133 133 56,2 34 55 69 75 75
10 °C 30,0 58 92 115 133 133 60,0 32 52 65 75 75
0 °C 32,3 54 87 109 133 133 63,8 31 49 61 75 75
-10 °C 34,5 52 83 103 129 133 67,6 29 47 58 73 75
-20 °C 36,8 49 79 98 123 133 71,4 28 45 56 70 75
-30 °C 39,0 47 75 94 117 133 75,2 27 43 53 67 75
Power output characteristic
Output of heating cable installed and measured on a pipe.
W/m
80
70
60
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
DEVIpipeguard™ 30 Industry
DEVIpipeguard™ 60 Industry
Pipe temperature (°C)
Accessories
Item no. EAN no. Type Description Image
Connection kit for DEVI-
00109007
5703466167397
pipeguard 30/60 Industry (PT-30/60) heating cables
Connection kit for DEVI-
00109026 5703466135778
pipeguard 30/60 Industry (PT-30/60) heating cables
Polyester box ABSC for
19400167 5703435002858
DEVIiceguard™ and
DEVIpipeguard™
19405851 5703435002964 Bracket Fitting for connection of housing (19400167) to pipes
11010410 5703435031001 Insulation introduction
With clamping block for the connection of cold lead and
heating cable, shrink end-cap, shrink tubes, bitumen
gaskets and ferrules.
For mounting in connection box with screw connections.
With cable gland M20x1,5 with locknut, shrink end-cap,
shrink tubes, bitumen gasket and ferrules.
For SLC (DEVIiceguard, DEVIpipeguard)
With mounting plate M20 60x60x1 mm AISI304;
Cable gland U17 M20x1,5; Cable gland M25
19805076 5703435003053
Tape aluminium
38 mm x 50 m
Self-adhesive, with 2-colour warning label, max. 75 °C
Produced by Danfoss ©AI239086497888en-010104