GB
Installation And User Instructions
Devimat™ Warm Floor System
Installation Instructions
User Guide
Trouble Shooter
1
Existing Floor
Wooden Floors
Concrete Floors
In all above situations, the fl oor temperature must be controlled with a DEVI fl oor sensor and
™
550 thermostat/timer, or Devireg™ 130 thermostat.
Devireg
Maximum load per m
100 W/m
150 W/m
2
2
2
INSTALLATION: KEY POINTS
•
Before laying the mat the fl oor sensor (in controller box) MUST be installed. The
sensor is fi tted into a tube (in mat box) which should be laid 20-30cm across
the fl oor under the mat between a cable loop.
• Before laying check the continuity of the cable, it should match the Ohm rating
™
on the Devimat
label with a tolerance of -5 to +10% and check the insulation
resistance which should read infi nity.
• To install the mat simply cut and turn the mat. The heating cable must NOT be
cut or subjected to strain around the area of the coupling, only the blue and
black cables can be cut to suit.
• When installing more than one mat, all ‘cold tails’ (blue/black wires) must be taken
back to the connection point/controller, DO NOT wire one mat to another.
• After laying the adhesive the heating mat must be checked once again for continuity and insulation resistance, then connected by an authorised electrician.
• The blue central core is NEUTRAL and the black central core is LIVE. The outer
surrounding copper wire is the earth screen and should be connected to earth.
™
• A fl exible adhesive is required when installing the devimat
product.
• Installation on new concrete fl oors should not be carried out for approxi-
mately 30 days to ensure thorough drying out.
Devimat™ specifi cations
Cable
Type
Voltage
Effect
Dimension (W x H)
Cold tails
DTIF
Twin conductor with screen
230 V AC
100 W/m² to 150 W/m²
460 mm x 3 - 3.5 mm
4.0 m, 1.0 mm² plus screen
Connections
Live - Black
Neutral - Blue
Earth - Screen
2
Installing the Devimat
1. Draw up a plan of the room and
calculate the free fl oor area.
Use the plan to work out how to
lay the mat evenly across the
fl oor and show the location of the
cold tail (where the mat starts),
fl oor sensor and connection box.
The Devimat
obstructions and close fl oor fi tting objects like pipes,
baths and cupboards. It is acceptable to lay the
devimat under suspended cupboards and wash
basins.
2. Mark the positions of the fl oor fi tting objects that
will be installed once the fl oor is fi nished, so
when laying the mat these can be avoided.
3. Each mat is supplied with a piece of 10mm
fl exible tubing (only one tube is required for each
thermostat), this is for the fl oor sensor, so that in
the unlikely event that the sensor fails, it can be
4. The existing fl oor
should be prepared as normally
required for tiling, this may
include cleaning and
removing all loose particles,
removing any sharp
protrusions that may cause
damage to the heating wire,
priming the fl oor surface and
bracing a timber fl oor with WBP
ply-for professional guidance refer to your adhesive
manufacturers recommendations.
™
should laid avoiding all fl oor
™
easily removed and
replaced without lifting the fl oor.
In some situations a small channel may have to be
made in the fl oor to accommodate the tubing. If so,
cut a channel from the thermostat position
approximately 20-30cm across the fl oor.
It is important that the
channel is positioned such
that it lays between two
heating wires and not across
them and not above heating
pipes below the fl oor. The
end of the tubing in the fl oor
is sealed with tape to prevent
adhesive entering the tube.
3
5. Before laying the mat should be tested-see page 7.
Remove the plastic outer and place the cold tail of
the mat at the connection point. The Devimat™ has
a self-adhesive backing, lay this to the fl oor and roll
the mat out, if necessary the mat can be laid with
the cable face down. In situations where the mat
has to be turned over it can be secured using
Devipins, hot glue gun (taking care not to damage
the heating cable), staple gun or double sided tape.
™
6. When the Devimat
reaches
the end of the run, simply
cut the grey mesh (NOT THE
RED CABLE) and turn the mat,
positioning the next piece
beside the fi rst. When cutting
and turning the mat ensure there is a 50mm
gap between the cable loops. To avoid risk
of damage at later stage do not lay the mat
where objects will be put onto or fi xed to the
fl oor.
7. If required, the cable can be removed from
the mesh and loops formed manually, but ensure
the cables are spaced the same distance as those
on the mat.
• The devimat™ must NOT be installed
across two or more rooms
• The heating cables (RED CABLE) must
not touch or cross each other.
• The heating cables (RED CABLE) must
not be CUT.
• All the red heating cable must be within
the fl oor.
4