Danfoss DEVIhotwatt 45, DEVIhotwatt 70 Data sheet

6. Pipe tracing
Data Sheet
DEVIhotwatt™
DEVIhotwatt™ 45 (B), DEVIhotwatt™ 55 (B), DEVIhotwatt™ 70 (B)
The DEVIhotwatt™ is a self-limiting heating cable that is used for temperature maintenance of hot water supply and other fluids that need to maintain a certain temperature.
The self-limiting capability of the cable ensures that the output of the cable increase or decrease according to ambient temperature.
DEVIhotwatt™ ensures hot water in all taps and savings when circulation of the whole pipe system is unnecessary. All self-limiting heating cables must be over-temperature protected by a thermostat, as the output will decrease, but never be zero, and be protected by a RCD with a maximum trip current of 30 mA.
The cable is not approved for use in drinking water.
Benefits:
Cut to length on site
PVC free
Standard compliance:
• DIN VDE 0254: 1994-06
Approvals:
Type
Nominal voltage 230 V AC
Nominal output (min-max) : DEVIhotwatt™ 45 DEVIhotwatt™ 55 DEVIhotwatt™ 70
Outer sheath: DEVIhotwatt™ 45 DEVIhotwatt™ 55 DEVIhotwatt™ 70
Maximum permissible use temperature
Minimum installation temperature -5 °C
Cable dimensions 11,8 mm × 5,8 mm
Minimum braid coverage 70% Maximum resistance protective braid 18,2 Ω/Km
Bending Ø, min. 50 mm (Ø to the inside of the tape)
IP Class IPX7
Value
7 W/m @ 45 °C (6,5-9,5 W/m @ 45 °C)
9 W/m @ 55 °C (8,5-13,0 W/m @ 55 °C)
12 W/m @ 70 °C (11,3-15,2 W/m @ 70 °C)
100 °C, unpowered
Types DEVIhotwatt™ 45
Item no. Length
98300955 Drum, 300 m 300 m 1 7 W/m 5703466109144 98300718 Cut-to-length - - 7 W/m 5703466195925
Min-max length per
drum
Number of length
allowed on drum, max
Nominal
output @ 45 °C
Black, TPE
Green, TPE
Red, TPE
80 °C, powered
EAN no.
Types DEVIhotwatt™ 55
Item no. Length
98300958 Drum, 100 m 100 m 1 9 W/m 5703466177204 98300957 Drum, 300 m 300 m 1 9 W/m 5703435005613 98300956 Cut-to-length - - 9 W/m 5703466193389
Min-max length per
drum
Number of length
allowed on drum, max
Nominal
output @ 55 °C
Types DEVIhotwatt™ 70
Item no. Length
98300959 Drum, 300 m 300 m 1 12 W/m 5703466109151 98300964 Cut-to-length - - 12 W/m 5703466193396
Min-max length per
drum
Number of length
allowed on drum, max
Nominal
output @ 70 °C
Produced by Danfoss ©AI3195354 42520e n-010104
EAN no.
EAN no.
Maximum heating circuit length on a pipe, with circuit breaker with C-characteristic
DEVIhotwatt™ 45
Switch on
temperature
20 °C 10,3 153 231 231 231 231 12,5 108 173 188 188 188 19,5 99 146 146 146 146
10 °C 11,6 144 230 231 231 231 13,5 102 164 188 188 188 21 71 113 142 146 146
-10 °C 14,3 129 203 231 231 231 15,5 93 148 185 188 188 24 45 72 90 113 143
-25 °C 16,3 119 191 231 231 231 17 86 138 173 188 188 26,3 37 64 80 103 133
10 A 16 A 20 A 25 A 32 A 10 A 16 A 20 A 25 A 32 A 10 A 16 A 20 A 25 A 32 A
Power W/m
Power W/m
DEVIhotwatt™ 55
DEVIhotwatt™ 70
Power W/m
Power output characteristic
Output of heating cable installed and measured on a pipe.
W/m
35
30
DEVIhotwatt™ 70
DEVIhotwatt™ 55
25
DEVIhotwatt™ 45
20
15
12 W/m
Construction
Overjacket
10
9 W/m
7 W/m
5
5 10 15 20 25 30 35 40 45 50 55 60 65 70
°C
Nickel plated copper bus wires
Radiation Cross-Linked Semiconductive Heating Matrix
Radiation Cross-Linked Primary Dielectric Insulation
Screen
Insulation
Self limiting heating element
Bus wires, 1,25 mm²
Tinned copper braid
Polyolefin over jacket
Produced by Danfoss ©AI3195354 42520e n-010104