Danfoss Compact 28 VX-FI, Compact 28 HWP, Compact 28 HWS Operating guide

OperatingGuide
TermixCompact28VX-FI/HWP/HWS

1.0TableofContents

1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotes–general............................................3
4.0Mounting........................................................4
4.1MountingtheCompactstation..................................4
4.3Electricalconnections.............................................13
5.0Design.............................................................14
5.1Design...............................................................14
5.2Schematicdiagram................................................15
6.0Controls..........................................................18
6.1Heatingcircuit......................................................18
6.2Other.................................................................22
6.3Maintenance........................................................24
7.0Troubleshooting..............................................25
7.1Troubleshootingingeneral......................................25
7.2TroubleshootingHE...............................................26
7.3Disposal.............................................................28
8.0Declaration......................................................31
8.1Declarationofconformity........................................31
©Danfoss|2019.04VI.LZ.J2.02/LUK42365|1
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

2.0Functionaldescription

Districtheatingsubstationforindirectheating.
Spaceheating
TheT ermixCompact28VX-FIisaheatexchangerunitforthe productionofheatinginlargebuildingssuchassportscentres, schools,blocksofflatsetc.Itcanbeusedforconnectiontoindirect districtheatinginplaceswherethedistrictheatingplantrequiresa hydraulicbreakontheplantside.Itisalsosuitableforconversion todistrictheatingwhenthesecondaryheatingsystemissuitable tobeingconnectedtodirectdistrictheatingorwhenaparticularly effectivesecurityagainstleakageintheheatingsystemisrequired. Itispossibletoconnectahot-watertank.
Efficientheatexchanger
Thesubstationisfittedwithanefficientplateheatexchanger, whichensuresthemostfavourableheatextractionandachieves optimumcomfortandoperatingeconomy.
Severalvariants
TermixCompact28VX-FIisbuiltwithaheatexchangerforspace heating,flowcontroller,pump,electronicregulationoftheheating circuitaswellasadirectoutletforahotwatertank.Theelectronic controllerisfactorypre-set.Electricalcomponentsarepre-wired, andtheunitisequippedwithaplugfor230Va.c. Itisrecommendedthatdynamicbalancingvalvesareinstalledin thebuilding’srisersintheheatsupplyandontheheatingsystem’s returnlineimmediatelybeforetheunit.
TermixCompact28VX-FIisproducedinstandardconstructions:
VXwithheatexchangerforindirectheating.
VXwithheatexchangerforindirectheatingandintegrated tankregulation.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which makesthissolutionhighlyflexible.Atthesametime,bothspace andtimearesavedwheninstalling.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Reliableandeasytoinstall
TermixCompact28VX-FIisoperationallyreliable.Aqualityproduct manufacturedinDenmark,whichiseasytoinstallandquickly commissioned.
2|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|3
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

4.0Mounting

4.1MountingtheCompactstation

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Tankflowline(TFL)
6.Tankreturnline(TRL)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Connectionsizes:
DH+HE: TFL+TRL:
Dimensions(mm):
Withinsulation:
Weight(approx.):60kg
G1”(int.thread) G¾”(int.thread)
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
H890xW905xD400
4|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
Removethefront.
Removeotherblocks.
Attachthemountingrailtothewall.
Liftthestation.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|5
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
Mountthestationonthemountingrail.
Attachthestationtothewallintheholesonthemountingplate.
Installthesafetyvalve.
Installballvalves.
MountblockA(CifitistheMagnapump)ontheleft-handsideof thepump.AttachblockEtoblockA/C,andattachittothepipe abovethepumpbyclickingitinplace.
6|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
MountblockB(DifitistheMagnapump)ontheright-handsideof thepump.
MountblockF(GforVM2valve).Theblockishingedandcanbe drawnaroundthevalve.AttachtheblocktoblockB/DandE.
MountblockJandHaroundthevalveforthetankcontrol.
Mountthefrontcover.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|7
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
Keyholeformounting.
8|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
4.1.2Pipeconnectionsup
Removethetopblock.
Removethepipeplugsatthetopofthestation.
RemoveU-clamps.
Removepipes.Anglesandteesareturnedsothatpipescanbe installedfromabove.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|9
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
Installthepipes.Districtheatingsupplypipestobeinterchanged.
FitU-clamps.
Fitthepipeplugsatthebottomofthestation.
Fitthetopblock.
10|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

4.2Start-up

Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe system,theballvalvemustfirstbeclosed,theplugremovedand asupplyhoseconnected.Onre-openingtheballvalve,system fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe observedclosely.Theexpansionvesselissuppliedpre-pressurised to0.5bar.Thepre-pressurerequiredateachsubstationwill dependonsystemhead(thedistancebetweenthelowestand highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure approximately1-2barhigherthanthepre-pressuresetting.The ballvalveisthenclosed,thehoseremovedandtheplugputback in.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
0–50,5
5–101,0
10–15
15–202,0
1,5
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconfirmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderfloorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|11
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderfloorheatingcontroller.Thepumpmustbestoppedif allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
12|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

4.3Electricalconnections

Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording to60364-4-41:2007andIEC60364-5-54:2011. Bondingpointonthemountingplatebelowrightcornermarked withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|13
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

5.0Design

5.1Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
F
Electroniccontroller
4
Safetyvalve,HE
9
Strainer
14|©Danfoss|2019.04
10
Circulatorpump
14
Sensorpocket,energymeter
20
Filling/drainvalve
25
Pressuregaugewithballvalve
26
Pressuregauge,HE 27AActuator,HE 48
Airvent,manual
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

5.2Schematicdiagram

5.2.1SchematicdiagramTermixCompact28VX-FI
DH
Supply
DH
Return
TRL
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
E
Hotwatertankwithcoil
F
Electroniccontroller
L
Borderofdelivery
1
Ballvalve
2
Singlecheckvalve
4
Safetyvalve
9
Strainer
10
Circulatorpump
11
Domestichotwaterpump
14
Sensorpocket,energymeter
16
Outdoorsensor
18
Thermometer
19
Surfacesensor
20
Filling/drainvalve
23
Ballvalve
24
Deliveredloosewithunit
HE Supply
HE Return
TFL
25
Pressuregaugewithballvalve
26
Pressuregauge
27
Actuator
29
2-waymotorizedvalve
30
Flowcontrollerwithintegratedcontrolvalve
31
Differentialpressurecontroller
44
Immersionsensor
48
Airvent,manual
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|15
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
5.2.2SchematicdiagramT ermixCompact28VX-FIHWP
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
5.2.3SchematicdiagramT ermixCompact28VX-FIHWS
HE Supply
HE Return
DHW
HWC
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
HE Supply
HE Return
DHW
HWC
DCW
16|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
Schematicdescription
A
Heatexchanger,HE
E
Hotwatertankwithcoil
F
Electroniccontroller
L
Borderofdelivery
1
Ballvalve
2
Singlecheckvalve
4
Safetyvalve
9
Strainer
10
Circulatorpump
DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn TFL: TRL: DHW: HWC: DCW:
5.2.4Technicalparameters
Nominalpressure: Max.DHsupplytemperature: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
Tankflowline Tankreturnline Domestichotwater Hotwatercirculation Domesticcoldwater
PN16 110°C Copper
11
Domestichotwaterpump
13
Chargingpump
14
Sensorpocket,energymeter
16
Outdoorsensor
18
Thermometer
19
Surfacesensor
20
Filling/drainvalve
24
Deliveredloosewithunit
25
Pressuregaugewithballvalve
26
Pressuregauge
27
Actuator
29
2-waymotorizedvalve
30
Flowcontrollerwithintegratedcontrolvalve
44
Immersionsensor
48
Airvent,manual
69
On/offvalve
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|17
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

6.0Controls

6.1Heatingcircuit

6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingflowcontrollerwithintegratedcontrol valve.Thecontrollercloseswhensetmax.flowisexceededand canbeusedincombinationwithDanfosselectricalactuatorswith orwithoutsafetyfunction.Springreturnmotorcanbeusedas safetyfunctionbypowerfailure.
18|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point controls.Spring-returnactuatorscanbeusedtoprovidesafety shut-offintheeventofpowerfailure.
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith manufacturer´sinstructions. Wheretheroomtemperatureiscontrolledbyradiatorthermostats, itisrecommendedthatthermostatsbesetforminimum temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|19
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
6.1.6Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating liquidsinheatingsystemswithvariableflows,internallycontrolled withthreeproportionalpressurecurvesandthreeconstant pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids inheatingsystemswithvariableflowswhereyouwanttooptimise thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
6.1.7GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastflash) CP=Constantpressure(slowflash)
20|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
6.1.8HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|21
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

6.2Other

6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
6.2.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
22|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
6.2.3Fittingpiece
Thesubstationisequippedwithafittingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater onthesystem.
2:Loosennuts
Loosenthenutsonthefittingpiece.
3:Removefittingpiece
Removethefittingpieceandreplaceitwiththeenergymeter.Do notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|23
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

6.3Maintenance

Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
24|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

7.0Troubleshooting

7.1Troubleshootingingeneral

Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|25
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

7.2TroubleshootingHE

ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
DHsupplytemperaturetoolow.
(radiatorcircuit).
ThefilterintheenergymeteronDHcircuit clogged.
Defectiveorwronglyadjusteddifferential pressurecontroller.
Sensordefective–orpossiblydirtinthe valvehousing.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
Thepumpissetattoolowspeedof rotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperatureadjusted toolow.
Defectiveradiatorvalves.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongsettingofautomaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongplacement/fittingofoutdoor temperaturesensor.
Strainerclogged.Cleangate/strainer.
Cleangate/strainer(s).
Cleanthefilter(afterconsultingtheDH plantoperator).
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Setthepumpathigherspeedofrotation.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Adjustaccordingtoinstructions.
Check–replace.
Adjust/installbalancingvalves.
Checkpipedimensions.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Callautomaticcontrolsmanufactureror replacetheregulator.
Replacethermostat–orsensoronly.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Callinautomaticcontrolsmanufactureror replacecontroller.
Replacethermostat–orsensoronly.
Adjustlocationofoutdoortemperature sensor.
26|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
ToohighDHreturntemperature.
Noiseinsystem.
Heatloadtoohigh.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Thesystemissinglepipeloop.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Defectiveorincorrectlysetradiatorvalve(s). Singlepipeloopsystemsrequirespecial one-piperadiatorvalves.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Defectivemotorizedvalve,sensoror automaticcontroller.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Defectivemotorizedvalve,sensoror electroniccontroller.
Increasetotalheatingsurface.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Ventthesystem.
Check–set/replace.
Check–cleanout.
Check–replace.
Check–replace.
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|27
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

7.3Disposal

Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
28|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
29|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS
30|©Danfoss|2019.04
VI.LZ.J2.02/LUK42365
OperatingGuideT ermixCompact28VX-FI/HWP/HWS

8.0Declaration

8.1Declarationofconformity

Category0withelectricalequipment
VI.LZ.J2.02/LUK42365
©Danfoss|2019.04|31