C62L-EZ-F Evaporator Micro Plate Heat Exchanger
21%
lower hold-up volume enables significant reduction in refrigerant charge
C62L-EZ-F
Danf already on order pro All trademarks in this material are property of the respec
Micro Plate Heat Exchanger (MPHE)
63 [2.5”]
H1Q4
H4Q1
525 [20.7”]
118 [4.6”]
INTRODUCTION The C62L-EZ-F is an evaporator optimized for R32 for use in high-efficiency chillers with capacities of 20 – 90 kW.
KEY FEATURES - Improved heat transfer - equals higher efficiency chillers
TECHNICAL DATA
n = NUMBER OF PLATES
The Z-pattern channel plate technology pushes the performance of heat exchangers to the limits by fully mixing the liquid and gas refrigerant through a “zigzag” flow, which increases the heat transfer coefficient. At the same time, inheriting from the dimple features, C62L-EZ-F reduces the water side pressure drop and the amount of material used. In the reversible mode of the chiller as a condenser, C62L-EZ-F also has outstanding performance.
To meet demands for higher seasonal efficiency, the C62L-EZ-F is designed to work efficiently and increase comfort in modern buildings without increasing the carbon footprint. Helping chillers perform more efficiently, it reduces both energy costs and environmental impact.
The low hold-up volume reduces the system refrigerant charge and offers valuable savings.
- Reduced water side pressure drop - equals higher efficiency chillers
- Minimal hold-up volume - equals less refrigerant charge
- Smaller footprint - enables more compact chillers
- High heat transfer and minimal refrigerant charge - equals a reduced CO₂ footprint
Min. working temperature: -196 °C Max. working temperature: 200 °C Max. working pressure: 49 bar (refrigerant side) / 25 bar (water side) Hold-up volume: Q1-Q2/ Q3-Q4 (l): 0.098×n/2 / 0.078×(n-2)/2 Weight (kg): 2.92+0.15xn Max. no. of plates: 140
470 [18.5”]
11+1.84*NoP [0.43+0.072*NoP”]
H2Q3
H3Q2
STANDARD MATERIALS
STANDARD CONNECTIONS
THIRD-PARTY APPROVALS
ACCESSORIES – STUD BOLTS
CORRESPONDING CONDENSERS
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
2 | AI313331150438en-000101 © Danfoss | DCS (ms) | 2019.07
vided that such alterations can be made without subsequential changes being necessary eady agreed.
Cover plates: AISI 304L Plates: AISI 316L Connections: AISI 304L Brazing filler: Pure copper
Other material combinations are available on request. Please contact your Danfoss sales representative for more information.
Standard connections as below are optimzed for this product as an evaporator in chiller systems. For other connections, please contact your Danfoss representative, (Internal threaded, R thread (BSPT), NPT and Victaulic are also available).
Q3 (Refrigerant inlet): soldering 3/8”, ½”, 5/8”, ¾” or 7/8” Q4 (Refrigerant outlet): soldering ½”, 5/8”, 3/4” , 7/8”, 1 1/8”, 1 3/8” or 1 ½” Q1-Q2 (Water side): External threaded G ½”, G 3/4”, G 1”, G 1 ¼” or G 1 ½”
Europe: Pressure Equipment Directive (PED). America: Underwriters Laboratory Inc (UL). The third party approvals stated are standard for all our products. For details of other existing approvals or to discuss how we can meet your local needs, please contact yourDanfoss representative.
Stud bolts and feet on front and/or back cover plates for mounting support are available upon request. Contact your Danfoss sales representative for further information.
A corresponding Micro Plate heat exchanger for condenser duties (C62L-CX) is also available.
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.