Danfoss C62-CX Data sheet

Data sheet
Micro Plate Heat Exchanger
Xperience increased savings with new asymmetric heat exchangers
52%
Signicant reduction in refrigerant and smaller C0 compared with a traditional BPHE
footprint,
2
ra.danfoss.com
C62-CX Asymmetric Chiller Condenser Micro Plate Heat Exchanger
H1 H4
H1 H4
H2 H3
H2 H3
Principle of asymmetric channels
525
20.7"
470
18. 5"
Q4 Q1
Q4 Q1
Q3 Q2
Q3 Q2
Unique channel plate pattern
Introduction
Key features
Technical data
n = number of plates
max. No. Of plates: 150
Standard materials
Connections
Third-party approvals
63/2.5"
118 /4. 6"
A
20/0.79” 25/0.98” 29/1.1”
Asymmetric braze joints
Condenser function
The C62-CX is a condenser with asymmetric design optimised for use in chillers with capacities of Rt 6-31 (20-110 kW). The innovative Micro Plate technology and the asymmetric channel geometries, with different designs on the refrigerant and water sides, improve heat transfer, reduce the amount of material used and minimise pressure losses on the water side.
To meet demands for higher seasonal efficiency, the C62-CX is designed to work efficiently and increase comfor t in modern buildings without increasing the carbon footprint. Helping water-cooled chillers perform more efficiently, it reduces both energy consumption and environmental impact. The low hold-up volume reduces the system refrigerant charge and offers valuable savings.
Minimal refrigerant hold-up volume: Smaller refrigerant charge
High heat transfer: For a more efficient chiller
Minimal pressure losses on secondary side: Less pump power
Smaller footprint: Enabling more compact chiller
Reduced CO
Model A (mm/inch)
C62-CX 9.5+1.74xn / 0.37+0.07xn
footprint: Environmentally friendly with high heat transfer and minimal refrigerant charge.
2
Min/Max. working
temperature
-196 °C (-320 °F) /
200 °C (390 °F)
Max. working
pressure
30 bar / 435 psi
Hold-up volume
Q1-Q2 / Q3-Q4
(l): 0.092xn/2 / 0.07x(n-2)/2
3
): 0.003xn/2 / 0.002xn/2
(ft
Weight
2.45kg+0.138xn /
5.41lb+0.32xn
Cover plates: AISI 304L Plates: AISI 316L Connections: AISI 304L Brazing filler: Pure copper Other material combinations are available on request. Please contact your Danfoss sales representative for more information.
Q3 (Refrigerant outlet): solder 3/8” to 7/8” Q4 (Refrigerant inlet): solder 1/2” to 1 3/8” Q1-Q2 (Water side): threaded external 1” or 1 1/4”
For other connections, please contact your Danfoss representative.
Europe: Pressure Equipment Directive (PED). America: Underwriters Laboratory Inc (UL). The third-party approvals stated are standard for all our products. For details of other existing approvals or to discuss how we can meet your local needs, please contact your Danfoss representative.
Accessories – stud bolts
DKQB.PD.310.S1.02 © Danfoss | RC-MDP (sw) | 2014.11
Stud bolts on front and/or back cover plates for mounting support are available on request. Contact your Danfoss sales representative for further information.
Loading...