Danfoss C62-CX Data sheet

Danfoss C62-CX Data sheet

Data sheet

Micro Plate Heat Exchanger

Xperience increased savings with new asymmetric heat exchangers

C62-CX Chiller Condenser

52%

Significant reduction in refrigerant and smaller C02 footprint, compared with a traditional BPHE

ra.danfoss.com

C62-CX Asymmetric Chiller Condenser

Micro Plate Heat Exchanger

Q4

Q1

H1

H4

525

20.7"

470

18.5"

Principle of asymmetric channels

Unique channel plate pattern

Q3

Q2

 

H2

H3

 

 

 

63/2.5"

 

20/0.79”

 

 

 

 

 

25/0.98”

 

 

 

 

 

 

 

 

 

 

 

118/4.6"

A

29/1.1”

 

 

 

 

 

Asymmetric braze joints

Condenser function

Introduction

The C62-CX is a condenser with asymmetric design optimised for use in chillers with capacities of Rt 6-31 (20-110 kW). The innovative Micro

 

Plate technology and the asymmetric channel geometries, with different designs on the refrigerant and water sides, improve heat transfer,

 

reduce the amount of material used and minimise pressure losses on the water side.

 

To meet demands for higher seasonal efficiency, the C62-CX is designed to work efficiently and increase comfort in modern buildings

 

without increasing the carbon footprint. Helping water-cooled chillers perform more efficiently, it reduces both energy consumption and

 

environmental impact. The low hold-up volume reduces the system refrigerant charge and offers valuable savings.

 

 

 

Key features

Minimal refrigerant hold-up volume: Smaller refrigerant charge

 

High heat transfer: For a more efficient chiller

 

Minimal pressure losses on secondary side: Less pump power

 

Smaller footprint: Enabling more compact chiller

 

Reduced CO2 footprint: Environmentally friendly with high heat transfer and minimal refrigerant charge.

Technical data

 

 

 

 

 

 

 

Model

A (mm/inch)

Min/Max. working

Max. working

Hold-up volume

Weight

n = number of plates

 

temperature

pressure

Q1-Q2 / Q3-Q4

max. No. Of plates: 150

 

 

 

 

 

 

 

-196 °C (-320 °F)

 

(l): 0.092xn/2 / 0.07x(n-2)/2

2.45kg+0.138xn

 

 

 

 

 

 

C62-CX

9.5+1.74xn / 0.37+0.07xn

 

/

30 bar / 435 psi

/

 

 

(ft3): 0.003xn/2 / 0.002xn/2

 

 

 

 

200 °C (390 °F)

 

5.41lb+0.32xn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

Cover plates: AISI 304L

 

Plates: AISI 316L

 

 

 

materials

Connections: AISI 304L

 

Brazing filler: Pure copper

 

 

 

Other material combinations are available on request. Please contact your Danfoss sales representative for more information.

 

 

 

 

 

 

Connections

Q3 (Refrigerant outlet): solder 3/8” to 7/8”

 

 

 

 

 

Q4 (Refrigerant inlet): solder 1/2” to 1 3/8”

 

 

 

 

 

Q1-Q2 (Water side): threaded external 1” or 1 1/4”

 

 

 

For other connections, please contact your Danfoss representative.

Third-party

Europe: Pressure Equipment Directive (PED). America: Underwriters Laboratory Inc (UL). The third-party approvals stated are standard for all our

approvals

products. For details of other existing approvals or to discuss how we can meet your local needs, please contact your Danfoss representative.

 

 

 

Accessories

Stud bolts on front and/or back cover plates for mounting support are available on request. Contact your Danfoss sales representative

– stud bolts

for further information.

 

 

 

DKQB.PD.310.S1.02

© Danfoss | RC-MDP (sw) | 2014.11

Loading...