Underfloor heating with
heated screed as liquid
or cement screed
Basic heating systems
Advantages
Underfloor heating, with its low supply temperature, has many advantages. It runs maintenancefree, is energy saving and ensures comfortable
room temperatures.
Rooms with underfloor heating allow greater
freedom for interior design. The Danfoss FH pipes
enclosed in cement or liquid screed give off
The Danfoss underfloor heating systems with
heated screed - Basic heating systems - are low
temperature underfloor heating systems suitable
for all new buildings. They can be installed in all
rooms and floors of blocks of flats or in business
premises.
The grey Danfoss composite pipes are installed,
according to worked out distances, using
BasicClip, BasicGrip or BasicRail on insulation
panels giving the pipe lay-out. The water flowing
though the composite or PE-RT pipes gently
warms the screed which works as heating
element. It is possible to lay all common floor
• Low energy saving temperature
• Cost eective, no additional costs
• 100% impervious to air, no heat exchanger
necessary
• Comfortable, clean and healthy air
• Greater freedom of interior design, more living
space for whole family
• Maintenance-free
comfortable warmth without any drafts, - creating
a dustfree, hygenic environment.
coverings on top of Danfoss underfloor heating,
except perhaps heavy exotic carpets or special
engineered wood flooring which would need
extra calculations when planning the system.
Since low water temperatures are required to
achieve the required room temperatures, Danfoss
underfloor heating systems are ideal for use with
boilers, solar energy and heat pumps. This means
that producers of energy saving heat will find an
ideal partner in underfloor heating.
Relevant standards for
underfloor heating
The following regulations and EN Standards
should be observed when planning and installing
floor heating:
EN 1991 Action on structures
EN 1264 Underfloor Heating, Systems and
Components
DIN 4109 Sound Insulation in the Building
Industry
ISO EN 140-8 Measurement of sound insulation
in buildings and building elements
EN 13813 Screed Material and Floor Screeds
Local building regulations.
Professional information on interface co-ordination
when planning heated underfloor construction
(ref: BVF).
For underfloor heating the EN 1264, part 4
standards are applicable.
Three Danfoss basic constructions are possible:
A, B and C.
They meet the minimum insulation requirements
in relation to use and position in the house.
Minimum thermal
resistance of insulation
under floor heating
systems from EN 1264,
part4
BasicRail
ConstructionABC
Heated room
below
Thermal
resistance
(m K/W)
* When groundwater table is < 5 m this value should be raised!
The composite pipes are clipped onto the BasicRail
self-adhesive clip rails at regular distances.
The maximum of 2 m between the clip rails should
only be applied when using cement screed.
When using liquid screed a maximum distance of
1m should be observed. Because of the fluid
consistency of liquid screed it could run under
the pipes and can push them upwards.
0.751.2 51.2 51.52
Unheated or
occasionally
heated room
below or
room on
ground floor*
Outside air temperature below construction
Design
outside
temperature
Td > 0° C
In accordance with EN 1264 Danfoss FH pipes
should be laid more than
• 50 mm away from vertical construction, such as
walls
• 200 mm from chimneys and open re places,
open and walled-up shafts, as well as lift shafts
Design
outside
temperature
0° C > Td ≥ -5° C
Design
outside
temperature
-5° C > Td ≥ -15° C
BasicClip
BasicGrip
The BasicClip System is a tacker system where the
pipes are tacked onto the insulation with u-shaped
tacker pins. The insulation overlap panels are
supplied as 2 x 1 m pre-folded panels. The foil
clad panels give a perfect grip for the barbs in
the EPS and under the foil.
The grid pattern on the panel foil is 50 mm which
allows the different laying distances to be kept :
100 and 150 mm for Edge Zones, and 200, 250
and 300 mm for Comfort Zones.
Any additional insulation should be laid under
the BasicClip overlap panels.
The BasicGrip panel system consists of deeply
drawn foil with studs that allow perfect laying of
pipes.
With their size of 1 x 1 m, the panels are easy to
lay and can be installed by just one person.
The panels can be cut with the usual cutter knife.
The studded panels facilitate correct pipe
distances. Laying the pipes diagonally is possible
without additional grips. It is safe to walk on the
strong foam studded panels.
When using the BasicGrip panel without thermal
insulation the deeply drawn foil is correspondingly
thicker.
The laying distance is calculated in multiples of
50 mm, so that possible pipe distances in the
Edge Zone are 100 and 150 mm and in the
Comfort Zone 200, 250 and 300 mm are achieved.
Any additional insulation should be laid under
the BasicGrip panels.
BasicClip insulation overlap panels are available
in 2 variations:
• with 35 mm thermal and impact sound
insulation EPS
• with 20 mm thermal and impact sound
insulation EPS
For optimum installation of the system an
expansion profile is available to overcome
expansion gaps and door thresholds.
The system is suitable for liquid (CAF) and
cement screeds (CT).
BasicGrip panels are available in 3 variations:
• with 35 mm thermal and impact sound
insulation EPS
• with 11 mm thermal insulation EPS
• without insulation
For optimum installation of the system, the
following additional products are on offer:
• An expansion prole to overcome expansion
gaps and door thresholds
• Door and manifold panels with varying
insulation thickness
• PE –String to seal perimeter insulation when
using liquid screed
The system is suitable for liquid (CAF) and
cement screeds (CT).
The individual components of the overlap
insulation panels are bonded and consist of the
Continuous sound impact insulation also has to
be installed.
following layers:
• Bonded multi-layer foil with 5 cm grids to
facilitate exact pipe laying
• A thermal and impact sound insulation layer
made of polystyrene
What type of insulation is used, depends on the
type of floor and the building. If the concrete is
even and free of other installations, a single layer
of insulation is sucient. In 90% of all new
buildings heating, sanitation and electrical
services are installed which require double layer
insulation.
For height adjustment, thermal insulation, e.g.
EPS 035 DEO 20 mm is laid between the pipe
channels and gaps around the pipes are filled
with Danfoss Dry Levelling Compound.
Finally, the Basic insulation overlap panels are
installed. The surface of these 2 m2 (1 + 1 m2
foldable) insulation panels are very strong, safe
to walk on, and form a very good surface for
BasicClip and BasicRail heating systems.
The strong foil is a technically perfect base for
cement and liquid screeds.
A: Floor construction above rooms of equal use/ temperature; Minimum thermal resistance
R
= 0.75 m2K/W
min
Construction with insulation panels 20/35 mm plus additional insulation:
Insulation panels 20/35 mm
R = 0.44 m2K/W; R = 0.77 m2K/W
2020202035353535mm
++++++++
EPS DEO λ =0.040 W/mK20-mm
EPS DEO λ=0.035 W/mK20-mm
PUR λ=0.030 W/mK20-mm
PUR λ =0.025 W/mK20-mm
Total thermal resistance R0.941.011. 111.270.770.77 0.77 0.77 m K/W
Total insulation thickness4040404035353535mm
B: Floor construction above occasionally or permanently unheated rooms, cellars or ground-
floor (ground water table > 5 m); minimum thermal resistance R
= 1.25 m2 K/W
min
Construction with insulation panels 20/35 mm plus additional insulation :
Insulation 20/35 mm
R = 0.44 m2K/W; R = 0.77 m2K/W
2020202035353535mm
++++++++
EPS DEO λ = 0.040 W/mK4020mm
EPS DEO λ = 0.035 W/mK3020mm
PUR λ = 0 .030 W/mK3020mm
PUR λ = 0.025 W/mK3020mm
Total thermal resistance R1.4 4 1. 301.441.6 41.271.341.431.57 m K/W
Total insulation thickness6050505055555555mm
C: Construction for floors against outside air; minimum thermal resistance R
= 2.0 m2 K/W
min
Construction with insulation panels 20/35 mm plus additional insulation:
Insulation 20/35 mm
R = 0.44 m2K/W; R = 0.77 m2K/W
2020202035353535mm
++++++++
EPS DEO λ = 0.040 W/mK7050mm
EPS DEO λ = 0.035 W/mK6050mm
PUR λ = 0 .030 W/mK5040mm
PUR λ = 0.025 W/mK4040mm
Total thermal resistance R2 .192 .162 .112.04 2.022.22.12.37 m K/W
Other combinations are possible to achieve
certain built-up heights. The following table
indicates the thermal resistance of the different
insulations, dependent on their thickness.
EPS 045 DESEPS 040 DEOEPS 035 DEOPUR λ = 0.03
Thickness
[mm]
100.22100.25100.29100.33100.40
]
150.33150.38150.43150.50150.60
200.44200.50200. 57200.67200.80
250.56250.63250.71250.83251. 00
300. 67300.75300.86301.00301. 20
350.78350.88351.0 0351.17351. 40
400.89401. 00401 .14401. 33401. 60
451. 00451.13451. 29451. 50451. 80
501 .11501. 25501.43501.67502.00
551.2 2551. 38551. 57551.8 3552.20
601. 33601. 50601.7 1602.00602.40
651. 44651. 63651. 86652 .17652.60
701. 56701.75702.00702.33702.80
751.67751. 88752 .14752.50753.00
801.78802.00802.29802.67803.20
851. 89852.13852.43852.83853.40
902.00902.25902.57903.00903.60
952 .11952.38952.71953 .17953.80
1002.221002.501002.861003.3310 04.00
1052.331052.631053.001053.5010 54.20
1102.4411 02.7511 03.141103.6711 04.40
1152.561152.881153.291153.831154.60
1202.671203.001203.431204.001204.80
1252.781253.131253.571254.171255.00
1302.891303.251303 .7113 04. 331305.20
1353.001353.381353.861354.501355.40
1403. 111403.5014 04.0014 04.671405.60
1453.221453.631454 .141454.831455.80
1503. 331503.751504.2915 05.0015 06.00
1553.441553.881554.431555 .171556.20
1603.5616 04.0016 04.5716 05.331606.40
1653.671654.131654.711655.501656.60
1703.781704.251704.8617 05.6717 06.80
1753.8917 54.3817 55.001755.831757. 00
1804.0018 04.5018 05.141806.001807. 2 0
1854. 1118 54.631855.291856 .1718 57. 4 0
1904.221904.751905.431906. 331907. 6 0
1954.331954.8819 55.571956.5019 57. 80
2004.442005.002005.712006.672008.00
R
insulation
[m K/W ]
Thickness
[mm]
R
[m K/W ]
insulation
Thickness
[mm]
The final layer should always be the Basic
insulation overlap panels 20/35 mm to guarantee
a stable base for further installation.
The Basic Perimeter insulation 150 mm consists of
8 mm PE-Foam. The double-sided adhesive tape
on the back allows it to be easily attached to the
wall. The adhesive tape on the room side of the
foil attaches the perimeter insulation to the
insulation panels.
In accordance with EN 1264 the perimeter
insulation can be compressed by 5 mm and thus,
When using liquid screed the insulation joints
should be taped over to accept screed with a
very thin consistency.
The heating circuits are laid in meander form,
which is an advantage when first installing the
pipes in the edge zones of the room (Edge Zone)
and then taking them to the centre of the room
(Comfort Zone): the warmer temperatures of the
heating circuit arrive at the outer zones (higher
floor temperature), and the cooled down water
heats the central zone (lower floor temperature).
together with the insulation panels, forms the
required tank for the screed as well as thermal
and sound bridges.
When using a double layer of insulation, the
additional insulation should be laid first. Should
their thickness exceed 5 cm, the perimeter
insulation is installed on top of the additional
insulation.
To achieve higher output around the edges or in
front of windows, you can lay the pipes in double
pattern.
Please see recommended layout patterns in
Danfoss application sheets.
The Danfoss wet systems BasicGrip and BasicClip
are laid in spiral form.
The Danfoss composite pipe is laid in spiral form
starting from the edge, leading to the centre of
the room. The pipe distance is twice that of the
calculated pipe spacing. The pipe is then led out
of the centre between the installed pipes.
The advantage is that pipes of higher temperature are next to those of lower temperature, thus
producing an even surface temperature (higher
output).
Edge Zone: if a higher heat output is required,
the pipes in the Edge Zone (up to 1 m from wall)
can be laid closer, thus producing a higher
surface temperature.