Danfoss BA, BD, BB, BE, BF Data sheet

...
Data Sheet
Solenoid coils Type BA, BD, BB, BE, BF, BG, BN, BO,
BJ, BX, BY, BQ, AM, AZ, AS and AP
Solenoid coils for A and B system
Danfoss solenoid valves and coils are usually ordered separately to allow maximum exibility, enabling you to select a valve and coil combination to best suit your needs.
The Danfoss coil program consists of both the easy-to-handle Clip-On system and traditional coils with threaded fastener.
Danfoss oer a wide range of application specic coils for e.g. steam or hazardous areas. The coils are available with approvals such as EN60730-1, EEx/ATEX and UL.
Features
• Encapsulated coils with long operating life, even under extreme conditions
• Standard coils for AC or DC
• Standard coils from 12 V – 400 V, 50, 60, 50 / 60 Hz or DC
• Standard coils available with:
Cable plugsIndustrial plugsTerminal box3 core cableJunction boxConduit hub
AI247086497610en-001001
1234567891011
12
F4501
Type BQ240CS
018F4511
-40 40 °C 208 - 240V 60Hz 9.5W 16VA 230V 50H z 10W 17V A
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
Spare part no. Tambient
2
3
4
8
7
11
5
6
12
9
10
1
Country of origin
Coil type
Spare part no. (code no.)
Ambient temperature: (-40 – 40 °C = Ambient temperature range: -40 °C – 40 °C)
Supply voltage [V]
Frequency [Hz]
Power consumption [W]
Power consumption [VA]
CE marking
UL recognized coil
Raw coil number (F4501=Raw coil number 018F4501)
Point of contact
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
1 Coil identication
Technical data is printed directly on the coil:
Figure 1: Identication label
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 2
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BA024A
-40 – 40
24
-15%, 10%
50
8.517042N7508
BA048A
-40 – 40
48
-15%, 10%
50
9.518042N7510
BA115A
-40 – 40
115
-15%, 10%50918042N7512
BA230A
-40 – 40
220 – 230
-15%, 6%501222042N7501
BA240A
-40 – 40
240
-15%, 10%501020042N7502
BA400A
-40 – 40
380 – 400
-15%, 6%501222042N7504
BA024B
-40 – 40
24
-15%, 10%
60
9.519042N7520
BA115B
-40 – 40
115
-15%, 10%601223042N7522
BA220B
-40 – 40
220
-15%, 10%601121042N7523
BA012D
-40 – 4012±10%DC14–042N7550
BA024D
-40 – 4024±10%DC14–042N7551
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
Spade connector in accordance with DIN 43650 form A
Enclosure, IEC 529
IP00 with spade connector, IP20 with protective cap, IP65 with cable plug
Duty rating
Continuous
Plug type
Cable plug (042N0156)
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
2 Product specication
2.1 BA, High performance coils
Figure 2: BA, High performance coils
Features
• Cable plug enclosure:
IP00 version with DIN 43650 A spade connectorsIP20 version with protective capIP65/IP67 version with cable plug
• Nut and snap fastener included
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 1: BA, High performance coils
Table 2: Technical data
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 3
Type
L without cable plug
[mm]
L with protective cap
[mm]
L with cable plug
[mm]
Weight
[kg]
BA5471790.16
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BD024A
-40 – 40
24
-15%, 10%501529042N7597
BD230A
-40 – 40
230
-10%, 6%501428042N7591
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
Spade connector in accordance with DIN 43650 form A
Enclosure, IEC 529
IP00 with spade connector, IP20 with protective cap, IP65 with cable plug
Duty rating
Continuous
Plug type
Cable plug (042N0156)
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
2.1.1 Dimensions and weight
Figure 3: BA, High performance coils
Table 3: BA, High performance coils
2.2 BD, High performance coils
Figure 4: BD, High performance coils
Features
• Cable plug enclosure:
IP00 version with DIN 43650 A spade connectorsIP20 version with protective capIP65/IP67 version with cable plug
• Nut and snap fastener included
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 4: BD, High performance coils
Table 5: Technical data
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 4
Type
L without cable plug
[mm]
L with protective cap
[mm]
L with cable plug
[mm]
Weight
[kg]
BD5471790.16
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BB024AS
-40 – 80
24
-15%, 10%501119018F7358
BB115AS
-40 – 80
115
-15%, 10%501119018F7361
BB230AS
-40 – 80
220 – 230
-15%, 10%501119018F7351
BB240AS
-40 – 80
240
-15%, 10%501119018F7352
BB440CS
-40 – 50
380 – 400
-15%, 10%5014
24
018F7353
440
-15%, 10%601524BB024BS
-40 – 80
24
-15%, 10%601423018F7365
BB110CS
-40 – 50 110
±10%5015
28
018F7360
110
±10%6013
22
BB230CS
-40 – 50
220 – 230
±10%5016
31
018F7363
220 – 230
±10%601324BB012DS
-40 – 5012±10%DC14–018F7396
BB024DS
-40 – 5024±10%DC16–018F7397
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
2.2.1 Dimensions and weight
Figure 5: BD, High performance coils
Table 6: BD, High performance coils
2.3 BB, High performance coils
Figure 6: BB, High performance coils
Features
• Enclosure:
IP00 version with DIN 43650 A spade connectorsIP20 version with protective capIP65/IP67 version with mounted cable plug
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 7: BB, High performance coils
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 5
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
Spade connector in accordance with DIN 43650 form A
Enclosure, IEC 529
IP00 with spade connector, IP20 with protective cap, IP65 with cable plug
Duty rating
Continuous
Plug type
Cable plug (042N0156)
Type
L without cable plug
[mm]
L with protective cap
[mm]
L with cable plug
[mm]
Weight
[kg]
BB6277850.24
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BE024AS
-40 – 80
24
-15%, 10%501221018F6707
BE048AS
-40 – 80
48
-15%, 10%501120018F6709
BE115AS
-40 – 80
115
-15%, 10%501119018F6711
BE230AS
-40 – 80
220 – 230
-15%, 10%501222018F6701
BE240AS
-40 – 80
240
-15%, 10%501119018F6702
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
Table 8: Technical data
2.3.1 Dimensions and weight
Figure 7: BB, High performance coils
Table 9: BB, High performance coils
2.4 BE, High performance coils
Figure 8: BE, High performance coils
Features
• Enclosure: IP67 for moist environments with terminal box
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 10: BE, High performance coils
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 6
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BE440CS
-40 – 80
380 – 400
-15%, 10%5013
23
018F6703
440
-15%, 10%601424BE024BS
-40 – 80
24
-15%, 10%601425018F6715
BE115CS
-40 – 80 100
-15%, 10%5011
19
018F6710
115
-15%, 10%601322BE220BS
-40 – 80
220
-15%, 10%601323018F6714
BE110CS
-40 – 50
110
±10%5015
28
018F6730
-40 – 50
110
±10%6013
22
BE230CS
-40 – 50
220 – 230
±10%5017
31
018F6732
220 – 230
±10%601424BE012DS
-40 – 5012±10%DC15–018F6756
BE024DS
-40 – 5024±10%DC16–018F6757
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
1 m 3-core ying lead
Enclosure, IEC 529
IP67
Duty rating
Continuous
Type
L with terminal box
[mm]
L with 1m cable
[mm]
Weight
[kg]
BE9465
0.30
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
Table 11: Technical data
2.4.1 Dimensions and weight
Figure 9: BE, High performance coils
Table 12: BE, High performance coils
2.5 BF, High performance coils
Figure 10: BF, High performance coils
Features
• Enclosure: IP67 for moist environments with molded-in cable
• In accordance with:
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 7
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BF230AS
-40 – 80
220 – 230
-15%, 10%501222018F6251
BF240AS
-40 – 80
240
-15%, 10%501119018F6252
BF440CS
-40 – 80
380 – 400
-15%, 10%5014
24
018F6253
440
-15%, 10%601524BF024AS
-40 – 80
24
-15%, 10%501220018F6257
BF115CS
-40 – 80 100
-15%, 10%5011
19
018F6260
115
-15%, 10%601322BF220BS
-40 – 80
220
-15%, 10%601423018F6264
BF024BS
-40 – 80
24
-15%, 10%601425018F6265
BF110CS
-40 – 50 110
±10%5015
29
018F6280
110
±10%6013
23
BF230CS
-40 – 50
220 – 230
±10%5016
31
018F6282
220 – 230
±10%6014
24
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
1 m 3-core ying lead
Enclosure, IEC 529
IP67
Duty rating
Continuous
Type
L with 1m cable
[mm]
Weight
[kg]
BF670.30
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 13: BF, High performance coils
Table 14: Technical data
2.5.1 Dimensions and weight
Figure 11: BF, High performance coils
Table 15: BF, High performance coils
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 8
Type
Tambient
[°C]
Supply voltage
[V]
Voltage variation
Frequency
[Hz]
Power consumption
Code no.
[W]
[VA]
BG024AS
-40 – 80
24
-15%, 10%501121018F6807
BG110AS
-40 – 80
110
-15%, 10%501325018F6811
BG230AS
-40 – 80
220 – 230
-15%, 10%501528018F6801
BG240AS
-40 – 80
240
-15%, 10%501325018F6802
BG400AS
-40 – 80
380 – 400
-15%, 10%501529018F6803
BG024BS
-40 – 80
24
-15%, 10%601529018F6815
BG110BS
-40 – 80
110
-15%, 10%601629018F6813
BG220BS
-40 – 80
220
-15%, 10%601629018F6814
BG012DS
-40 – 5012±10%DC20–018F6856
BG024DS
-40 – 5024±10%DC16–018F6857
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
Terminal box
Enclosure, IEC 529
IP67
Duty rating
Continuous
Plug type
Terminal box
112
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
2.6 BG, High performance coils
Figure 12: BG, High performance coils
Features
• Enclosure: IP67 for moist environments with terminal box
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 16: BG, High performance coils
Table 17: Technical data
2.6.1 Dimensions and weight
Figure 13: BG, High performance coils
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 9
Type
L with terminal box
[mm]
Weight
[kg]
BG
112
0.50
Type
Tambient [°C]
Supply voltage [V]
Voltage variation
Frequency [Hz]
Power consumption
Code no.
[W]
[VA]
BN230CS
-40 – 50 220 – 230
±10%5022
24
018F7301 220 – 230
±10%6022
24
Design
In accordance with VDE 0580
Insulation of coil windings
Class H according to IEC 85
Connection
1 m 3-core
ying lead
Enclosure, IEC 529
IP67
Duty rating
Continuous
L
Solenoid coils, type BA, BD, BB, BE, BF, BG, BN, BO, BJ, BX, BY, BQ, AM, AS, AZ and AP
Table 18: BG, High performance coils
2.7 BN, High performance coils Hum-free
Figure 14: BN, High performance coils
Features
• Hum-free
• Enclosure: IP67 for moist environments with ying lead
• In accordance with:
RoHS Directive 2011/65/EULow Voltage Directive 2014/35/EU
EN60730-1EN60730-2-8
Table 19: BN, High performance coils
Table 20: Technical data
2.7.1 Dimensions and weight
Figure 15: BN, High performance coils Hum-free
© Danfoss | Climate Solutions | 2021.07 AI247086497610en-001001 | 10
Loading...
+ 21 hidden pages