The Series 45 product family........................................................................................................................................................9
Load sensing open circuit system............................................................................................................................................11
Servo Control Orifice.....................................................................................................................................................................12
Servo Control Orifice Principle.............................................................................................................................................12
Servo Control Orifice Performance.................................................................................................................................... 13
LS control with bleed orifice............................................................................................................................................17
Integral PC function............................................................................................................................................................18
Load sensing system characteristics............................................................................................................................ 18
Electric Controls..............................................................................................................................................................................18
Electric Proportional Controls (EPC)...................................................................................................................................18
Electric Proportional Control Principle........................................................................................................................18
Electric Proportional Control Response/Recovery..................................................................................................19
Electric Proportional Control Characteristic – Normally Closed.........................................................................20
Electric Proportional Control Characteristic – Normally Open...........................................................................21
Electric On-Off Controls..........................................................................................................................................................23
Electric On-Off Control Principle....................................................................................................................................23
Electric On-Off Control Response/Recovery..............................................................................................................24
Electric On-Off Control Performance vs. Ambient Temperature Characteristic...........................................24
Electric On-Off Control Characteristic – Normally Closed.................................................................................... 25
Electric On/Off Control Characteristic – Normally Open.......................................................................................26
Electric dump valve PC/LS controls....................................................................................................................................27
Electric Torque Limiting Control Principle................................................................................................................. 28
Electronic Torque Limiting Control Characteristic..................................................................................................29
Fan Drive Control (FDC)..........................................................................................................................................................29
Fan Drive Control Principle .............................................................................................................................................31
Fan Drive Control System Characteristics.................................................................................................................. 31
Unintended Applications for Fan Drive Control Systems.....................................................................................32
Fan Drive Control characteristic - Normally Closed ...............................................................................................32
Solenoid data – Normally closed...................................................................................................................................33
Fan Drive Control configuration....................................................................................................................................35
NC Fan Drive Control 3D Views......................................................................................................................................35
Example Circuit #1....................................................................................................................................................................40
Example Circuit #2....................................................................................................................................................................41
Case pressure............................................................................................................................................................................. 43
Duty cycle and pump life.......................................................................................................................................................44
Speed, flow, and inlet pressure............................................................................................................................................45
Understanding and minimizing system noise............................................................................................................... 50
Understanding and minimizing system instability...................................................................................................... 50
LS System Over-Signaling......................................................................................................................................................50
Order Code.......................................................................................................................................................................................53
Load Sensing Control with Bleed Orifice /Pressure Compensated........................................................................ 67
Electric Controls..............................................................................................................................................................................68
Solenoid Data - Normally Closed........................................................................................................................................ 68
Solenoid Data - Normally Open...........................................................................................................................................68
Normally Closed Electric On/Off with Pressure Compensation Controls.............................................................69
Normally Open Electric On/Off with Pressure Compensation Controls............................................................... 69
Normally Closed Electric Proportional with Pressure Compensation Controls................................................. 71
Normally Open Electric Proportional with Pressure Compensation Controls....................................................72
Normally Closed Fan Drive Control....................................................................................................................................73
Front Mounting Flange - SAE-B two bolt.........................................................................................................................80
Auxiliary Mounting Pad - Running Cover...................................................................................................................82
Electric solenoid, left side.................................................................................................................................................83
Fan drive control..................................................................................................................................................................83
Order code........................................................................................................................................................................................86
Load Sensing Control with Bleed Orifice /Pressure Compensated........................................................................ 98
Electric Controls..............................................................................................................................................................................99
Solenoid Data - Normally Closed......................................................................................................................................100
Solenoid Data - Normally Open........................................................................................................................................ 100
Normally Closed Electric On/Off with Pressure Compensation Controls.......................................................... 100
Normally Open Electric On/Off with Pressure Compensation Controls.............................................................101
Normally Closed Electric Proportional Controls with PC and LS Compensation............................................102
Normally Open Electric Proportional Controls with PC and LS Compensation...............................................104
Front Mounting Flange - SAE-B two bolt.......................................................................................................................110
Auxiliary Mounting Pad - Running Cover.................................................................................................................112
Electric Solenoid, Left Side..................................................................................................................................................112
Electric Solenoid, Right Side...............................................................................................................................................112
Order code..................................................................................................................................................................................... 115
Load sensing Control with Bleed Orifice/ Pressure Compensated...................................................................... 134
Electric Controls........................................................................................................................................................................... 135
Solenoid Data - Normally Closed......................................................................................................................................135
Solenoid Data - Normally Open........................................................................................................................................ 135
Fan Drive Control Solenoid Data - Normally Closed..................................................................................................136
Normally Closed Electric On/Off with Pressure Compensation Controls.......................................................... 136
Normally Open Electric On/Off with Pressure Compensation Controls.............................................................137
Normally Closed Electric Proportional with Pressure Compensation Controls...............................................138
Normally Open Electric Proportional with Pressure Compensation Controls................................................. 139
Normally Closed Electric Torque Limiting Control with Pressure Compensation Controls........................141
Normally Closed Fan Drive Control ................................................................................................................................ 142
Right Fan Drive Control........................................................................................................................................................148
Right Angle Sensor Position Installation Dimensions...............................................................................................151
Front Mounting Flange........................................................................................................................................................152
Order code..................................................................................................................................................................................... 160
Load Sensing Control with Bleed Orifice/Pressure Compensated.......................................................................170
Electric Controls........................................................................................................................................................................... 171
Solenoid Data - Normally Closed......................................................................................................................................172
Solenoid Data - Normally Open........................................................................................................................................ 172
Fan Drive Control Solenoid Data - Normally Closed..................................................................................................172
Normally Closed Electric On/Off with Pressure Compensation Controls.......................................................... 172
Normally Open Electric On/Off with Pressure Compensation Controls.............................................................173
Normally Closed Electric Proportional with Pressure Compensation Controls...............................................174
Normally Open Electric Proportional with Pressure Compensation Controls................................................. 175
Normally Closed Electric Torque Limiting Control with Pressure Compensation Controls........................177
Right Fan Drive Control........................................................................................................................................................181
Right Angle Sensor Position Installation Dimensions...............................................................................................184
Front Mounting Flange........................................................................................................................................................185
Order code..................................................................................................................................................................................... 191
Load Sensing Control with Bleed Orifice/Pressure Compensated.......................................................................203
Electric Controls........................................................................................................................................................................... 204
Solenoid Data - Normally Closed......................................................................................................................................205
Solenoid Data - Normally Open........................................................................................................................................ 205
Normally Closed Electric On/Off with Pressure Compensation Controls.......................................................... 205
Normally Open Electric On/Off with Pressure Compensation Controls.............................................................206
Normally Closed Electric Proportional with Pressure Compensation Controls...............................................207
Normally Open Electric Proportional with Pressure Compensation Controls................................................. 209
Normally Closed Electric Torque Limiting Control with Pressure Compensation Controls........................210
Front Mounting Flange........................................................................................................................................................218
Series 45 is a complete family of high performance variable displacement, axial piston pumps. Each frame
is designed to exceed the demanding work function requirements of the mobile equipment marketplace.
Each frame within the Series 45 family is uniquely designed to optimize performance, size, and cost.
The series 45 family of open circuit, variable piston pumps, offers a range of displacements from 25 to 147
cm³/rev [1.53 to 8.97 in3/rev]. With maximum speeds up to 3600 rpm and continuous operating
pressures up to 310 bar [4495 psi], product selection is easily tailored to the flow and pressure
requirements of individual applications.
Frame EE100B1006.10245028805003104495400580064.7245.0SAE C 4-
E130B1307.93220026005003104495400580075.5286.0SAE C 4-
E147C1478.97210024755002603770350507581.5308.7SAE C 4-
3
3
in
min
(rpm)
Max.Min.Cont.Max.
-1
min
(rpm)
-1
min
(rpm)
-1
barpsibarpsiUS
(at rated speed)
l/minFlange
gal/min
Load sensing open circuit system
The pump receives fluid directly from the reservoir through the inlet line. A screen in the inlet line
protects the pump from large contaminants. The pump outlet feeds directional control valves such as
PVG-32’s, hydraulic integrated circuits (HIC), and other types of control valves. The PVG valve directs
pump flow to cylinders, motors and other work functions. A heat exchanger cools the fluid returning
from the valve. A filter cleans the fluid before it returns to the reservoir.
Flow in the circuit determines the speed of the actuators. The position of the PVG valve determines the
flow demand. A hydraulic pressure signal (LS signal) communicates demand to the pump control. The
pump control monitors the pressure differential between pump outlet and the LS signal, and regulates
servo pressure to control the swashplate angle. Swashplate angle determines pump flow.
Actuator load determines system pressure. The pump control monitors system pressure and will decrease
the swashplate angle to reduce flow if system pressure reaches the PC setting. A secondary system relief
valve in the PVG valve acts as a back-up to control system pressure.
Danfoss | January 2022BC152886483703en-001201 | 11
P109124
K2 Frame Series 45
open circuit axial
piston pump with
load sensing control
Reservoir
Filter
Heat exchanger
System pressur e
Servo pressur e
Actuator pressur e
Load sense pressur e
Actuator retur n
Suction / case drain /
system retur n
Double-ac ting cylinder
Bi-directional
gear moto r
PVG 32
mulit-sec tion
load
sensing
contro l
valve
Technical Information
Series 45 Pumps
General Information
Pictorial circuit diagram
Servo Control Orifice
Servo Control Orifice Principle
Series 45 controls offer an optional servo control orifice (not available with Pressure Compensation only
Controls) available to aid in tuning system performance. The optional servo control orifice restricts flow
to and from the servo system in the pump, effectively pacing the motion of the servo system.
Input Speed=1800rpm, Temperature=49°C, PC Setting=210Bar, LS Setting=20Bar
1.0mm Servo
Control Orifice
0.8mm Servo
Control Orifice
Without Servo
Control Orifice
0
50
100
150
200
250
System Pressure (bar)
Time
Relative Servo Control Orifice Performance
Generic LS Response and Recovery
Input Speed = 1800rpm, Temperature=49 C, PC Setting=310Bar, LS Setting=30Bar
0.8mm Servo
Control Orifice
1.0mm Servo
Control Orifice
Without Servo
Control Orifice
P108 665E
Technical Information
Series 45 Pumps
General Information
Servo Control Orifice Performance
The use of the Servo Control Orifice will provide additional pacing to the pump, while the response of the
pump to pressure spikes remains unaffected. The Pressure Compensation Function response and
recovery, as well as the Load Sense Function response and recovery are shown below, and outline the
relative impact in response and recovery of the Servo Control Orifices. Note that these graphs are meant
as a generic comparison only, and that unique effects on response and recovery behavior for each
specific frame are shown later in this section.
Danfoss | January 2022BC152886483703en-001201 | 13
0
0
Q max
Pressure
Fl
ow
P101 166E
PC setting
Technical Information
Series 45 Pumps
General Information
We recommend that systems experiencing instability use a Servo Control Orifice. Start with the largest
size orifice available, and work down to the smaller size until the system is satisfactorily tuned. All FanDrive systems should start with a 0.8mm Servo Control Orifice if possible. Systems including motors are
more likely to require the Servo Control Orifice option.
Pacing Factor
Use of a Servo Control Orifice adds a pacing factor to each Series 45 Frame, impacting the behavior of the
pumps reactivity. This pacing factor can be multiplied by the specific Frame/Displacement/Control
selection’s response and recovery times, to determine the final paced response and recovery times.
Unique response and recovery times can be found in each frame-specific chapter, in the desired control
section. The paced response and recovery relationship is shown below.
Pacing Factors are unique to each orifice size, and can impact each frame differently. Below are the
Pacing Factors for each Servo Control Orifice Size by frame.
FramePacing Factors - Servo Control Orifice
1.0 mm Servo Control Orifice0.8 mm Servo Control Orifice
PC ResponsePC RecoveryLS ResponseLS RecoveryPC ResponsePC RecoveryLS ResponseLS Recovery
PC Response from 160 bar to 210 bar, PC Recovery from 210 bar to 160 bar at 1800 rpm: LS Response from 230 bar to 30 bar, LS Recovery from 30 bar
to 230 bar at 1800 rpm.
**
** PC Response from 160 bar to 210 bar, PC Recovery from 210 bar to 160 bar at 1800 rpm: LS Response from 160 bar to 20 bar, LS Recovery from 20
bar to 160 bar at 1800 rpm.
Hydraulic Controls
*
*
**
**
1
(No Effect)
2.32.02.01
2.32.02.03.22.62.6
2.32.02.03.22.62.6
2.32.32.33.73.13.1
2.32.32.33.73.13.1
(No Effect)
3.22.62.6
Pressure compensated controls
Operation
The PC control maintains constant system pressure in the hydraulic circuit by varying the output flow of
the pump. Used with a closed center control valve, the pump remains in high pressure standby mode at
the PC setting with zero flow until the function is actuated. This condition is often called a dead head
condition.
Once the closed center valve is opened, the PC control senses the immediate drop in system pressure
and increases pump flow by increasing the swashplate angle. The pump continues to increase flow until
system pressure reaches the PC setting. If system pressure exceeds the PC setting, the PC control reduces
the swashplate angle to maintain system pressure by reducing flow. The PC control continues to monitor
system pressure and changes swashplate angle to match the output flow with the work function
pressure requirements.
If the demand for flow exceeds the capacity of the pump, the PC control directs the pump to maximum
displacement. In this condition, actual system pressure depends on the actuator load.
Each section includes control schematic diagrams, setting ranges, and response / recovery times for each
control available. Response is the time (in milliseconds) for the pump to reach zero displacement when
commanded by the control. Recovery is the time (in milliseconds) for the pump to reach full displacement
when commanded by the control. Actual times can vary depending on application conditions.
Warning
A relief valve is required to be installed in the pump outlet for additional system protection. Failure to
install a relief valve may lead to system damage and/or injury.
Pressure compensated system characteristics
Constant pressure and variable flow
•
High pressure standby mode when flow is not needed
•
System flow adjusts to meet system requirements
•
Single pump can provide flow to multiple work functions
•
Quick response to system flow and pressure requirements
•
Typical applications for pressure compensated systems
Constant force cylinders (bailers, compactors, refuse trucks)
•
On/off fan drives
•
Drill rigs
•
Sweepers
•
Trenchers
•
Remote pressure compensated controls
The remote PC control is a two-stage control that allows multiple PC settings. Remote PC controls are
commonly used in applications requiring low and high pressure PC operation.
Danfoss | January 2022BC152886483703en-001201 | 15
0
0
Q max
Pressure
Fl
ow
P101 969E
PC setting
Remote PC setting
P101 966
W
Technical Information
Series 45 Pumps
General Information
Typical operating curve
Closed center circuit with remote PC
The remote PC control uses a pilot line connected to an external hydraulic valve. The external valve
changes pressure in the pilot line, causing the PC control to operate at a lower pressure. When the pilot
line is vented to reservoir, the pump maintains pressure at the load sense setting. When pilot flow is
blocked, the pump maintains pressure at the PC setting. An on-off solenoid valve can be used in the pilot
line to create a low-pressure standby mode. A proportional solenoid valve, coupled with a
microprocessor control, can produce an infinite range of operating pressures between the low pressure
standby setting and the PC setting.
Warning
A relief valve is required to be installed in the pump outlet for additional system protection. Failure to
install a relief valve may lead to system damage and/or injury.
Each section includes control schematic diagrams, setting ranges, and response / recovery times for each
control available. Response is the time (in milliseconds) for the pump to reach zero displacement when
commanded by the control. Recovery is the time (in milliseconds) for the pump to reach full displacement
when commanded by the control. Actual times can vary depending on application conditions.
Size the external valve and plumbing for a pilot flow of 3.8 l/min [1 US gal/min].
Remote pressure compensated system characteristics
Constant pressure and variable flow
•
High or low pressure standby mode when flow is not needed
•
System flow adjusts to meet system requirements
•
Single pump can provide flow to multiple work functions
•
Quick response to system flow and pressure requirements
Typical applications for remote pressure compensated systems
Modulating fan drives
•
Anti-stall control with engine speed feedback
•
Front wheel assist
•
Road rollers
•
Combine harvesters
•
Wood chippers
•
Load sensing controls
Operation
The LS control matches system requirements for both pressure and flow in the circuit regardless of the
working pressure. Used with a closed center control valve, the pump remains in low-pressure standby
mode with zero flow until the valve is opened. The LS setting determines standby pressure.
Typical operating curve
Load sensing circuit
Most load sensing systems use parallel, closed center, control valves with special porting that allows the
highest work function pressure (LS signal) to feed back to the LS control. Margin pressure is the difference
between system pressure and the LS signal pressure. The LS control monitors margin pressure to read
system demand. A drop in margin pressure means the system needs more flow. A rise in margin pressure
tells the LS control to decrease flow.
LS control with bleed orifice
The load sense signal line requires a bleed orifice to prevent high-pressure lockup of the pump control.
Most load-sensing control valves include this orifice. An optional internal bleed orifice is available, for use
with control valves that do not internally bleed the LS signal to tank.
Danfoss | January 2022BC152886483703en-001201 | 17
W
Technical Information
Series 45 Pumps
General Information
Electric Controls
Integral PC function
The LS control also performs as a PC control, decreasing pump flow when system pressure reaches the PC
setting. The pressure compensating function has priority over the load sensing function.
Warning
A relief valve is required to be installed in the pump outlet for additional system protection. Failure to
install a relief valve may lead to system damage and/or injury.
Load sensing system characteristics
Variable pressure and flow
•
Low pressure standby mode when flow is not needed
•
System flow adjusted to meet system requirements
•
Lower torque requirements during engine start-up
•
Single pump can supply flow and regulate pressure for multiple circuits
•
Quick response to system flow and pressure requirements
•
Electric Proportional Controls (EPC)
PLUS+1® Compliance
All Series 45 Electric controls have met and passed the Danfoss PLUS+1® compliance standard testing,
and as such, this Series 45 control is PLUS+1® compliant. PLUS+1® compliance blocks are available on the
Danfoss website, within the PLUS+1® Guide section.
Electric Proportional Control Principle
The Electric Proportional Control consists of a proportional solenoid integrated into a Remote Pressure
Compensated control. This control allows the pump to be operated at any pressure limit between the
Load Sense and Pressure Compensation settings by varying the current sent to the solenoid.
Reference individual frame sections for the margin (LS) setting vs low pressure standby relationship.
Electric proportional controls have a unique relationship between margin (LS) setting and low pressure
standby. This relationship is available in the electric proportional controls section for each frame.
For fan-drive systems, and systems with motors, use a minimum 15bar LS setting to enhance system
stability. As the LS setting is reduced, the risk for system instability may be increased. A 20bar LS setting is
recommended as a starting point for all new applications.
Electric Proportional Control Response/Recovery
S45 Electric Proportional Controls require the use of a servo control orifice, and are available with two
possible servo control orifice options. The servo control orifice is used to enhance system stability, as well
as dampen the pump reactiveness. A smaller orifice diameter will add dampening to the pump
reactiveness, while a larger orifice will allow quicker pump reaction. Fan-Drive applications, as well as
systems with the pump supplying motors, are recommended to use the 0.8mm diameter orifice to
enhance system stability.
Module “G” Options for Electric Proportional Controls
Frame“E” - 0.8mm Orifice“F” - 1.0mm Orifice
All Frames
••
Specific Electric Proportional Control Response/Recovery times are shown for the available servo control
orifice options in the control section within each specific frame section. These times represent the
response from 100bar to 200bar, and recovery from 200bar to 100bar. As the upper pressure approaches
the PC setting, the PC function will begin to assist in clipping pressure overshoots during the pump’s
response, and will decrease the response times of the pump to equal those of the PC response.
Electric Proportional Control Pressure vs. Flow Characteristic
The Electric Proportional Controls continuous duty operating temperature range is shown below; this
guideline should be followed as well as the maximum current limitations. Note that rated voltage refers
to either a 12V or 24V coil. Under high temperature conditions, current required to operate the solenoid
increases.
Danfoss | January 2022BC152886483703en-001201 | 19
50
60
70
80
90
100
-40
100
Percent of Rated Voltage (%)
Ambient Temperature (°C)
P108 415E
-30
-20
-10
0
60
80
10
20
30
40
50
70
90
110
120
Operating Range
0
50
100
150
200
250
300
350
System Pressure (Bar)
0
0.2
0.4
0.6
0.8
1
Current proportion I/I max
310 Bar PC, 10 Bar LS
310 Bar PC, 20 Bar LS
310 Bar PC, 30 Bar LS
260 Bar PC, 20 Bar LS
210 Bar PC, 20 Bar LS
P108 657E
Technical Information
Series 45 Pumps
General Information
Continuous Duty Operating Temperature
Electric Proportional Control Characteristic – Normally Closed
When an electric current is sent to the Normally Closed configuration control, the pump pressure
decreases proportional to an increase in current. When the load in the system changes, the pump will
adjust its displacement to maintain the pressure demanded by the controlling current. This control is
especially useful for fan-drives, due to the direct relationship between fan-speed and pump pressure.
Due to the nature of Electric Proportional Controls, the relationship between current and pump pressure
is unique for each individual PC/LS pressure setting combination. The relationship between different PC
settings and different LS settings on the Pressure vs. Current Characteristic curve are shown below. The
hydraulic schematic for the Normally Closed Electric Proportional control is shown below as well.
Maximum Current1800 mA920 mA
Inrush Current1700 mA800 mA
Technical Information
Series 45 Pumps
General Information
Solenoid Data – Normally Closed (continued)
Voltage12V24V
Coil Resistance @ 20°C [70°F]7.1 Ω28.5 Ω
PWM Range200-300 Hz
PWM Frequency (preferred)250 Hz
IP Rating (IEC 60529 | DIN 40050-9)IP67IP67
IP Rating (IEC 60529 | DIN 40050-9) with mating connectorIP69KIP69K
Operating TemperatureConsistent with Pump Limits:
-40°C (-40°F) to 104°C (220°F)
The available Normally Closed Electric Proportional Controls for the Series 45 are shown below. The
allowable Pressure Compensator (PC) and Load Sense (LS) pressure settings are provided for each frame
in their respective sections.
Electric Proportional Controls Options – Normally ClosedFrame
CodeDescriptionLK
AHElectric Proportional Pressure Control w/Pressure Comp. (NC,
12VDC) Left
ALElectric Proportional Pressure Control w/Pressure Comp. (NC,
24VDC) Left
AVElectric Proportional Pressure Control w/Pressure Comp. (NC,
12VDC) Right
AKElectric Proportional Pressure Control w/Pressure Comp. (NC,
24VDC) Right
BHElectric Proportional Pressure Control w/Pressure Comp. (NC,
12VDC) [>280 bar] Left
BLElectric Proportional Pressure Control w/Pressure Comp. (NC,
24VDC) [>280 bar] Left
BMElectric Proportional Pressure Control w/Pressure Comp. (NC,
12VDC) [>280 bar] Right
BKElectric Proportional Pressure Control w/Pressure Comp. (NC,
24VDC) [>280 bar] Right
EMElectric Proportional Pressure Control w/Pressure Comp. (NC,
12VDC)
ENElectric Proportional Pressure Control w/Pressure Comp. (NC,
4. K2 Frame electric controls are limited only for Left orientation and up to 260 Bar
Electric Proportional Control Characteristic – Normally Open
When an electric current is sent to the normally open configuration control, the pump pressure increases
proportional to an increase in current. When the load in the system changes, the pump will adjust its
displacement to maintain the pressure demanded by the controlling current. This control is especially
useful for fan-drives, due to the direct relationship between fan-speed and pump pressure.
Due to the nature of Electric Proportional Controls, the relationship between current and pump pressure
is unique for each individual PC/LS pressure setting combination. The relationship between different PC
Danfoss | January 2022BC152886483703en-001201 | 21
0
50
100
150
200
250
300
350
System Pressure (Bar)
0
0.2
0.4
0.6
0.8
1
260 Bar PC, 20 Bar LS
210 Bar PC, 20 Bar LS
310 Bar PC, 20 Bar LS
310 Bar PC, 30 Bar LS
310 Bar PC, 10 Bar LS
P108 658E
Current proportion I/I max
Technical Information
Series 45 Pumps
General Information
settings and different LS settings on the Pressure vs. Current Characteristic curve are shown below. The
hydraulic schematic for the Normally Open Electric Proportional control is shown below as well.
Operating Pressure vs. Input Current (N.O. EPC)
Solenoid Data – Normally Open
Voltage12V24V
Maximum Current1500 mA665 mA
Inrush Current1700 mA800 mA
Coil Resistance @ 20°C [70°F]7.1 Ω28.5 Ω
PWM Range200-300 Hz
PWM Frequency (preferred)250 Hz
IP Rating (IEC 60529 | DIN 40050-9)IP67IP67
IP Rating (IEC 60529 | DIN 40050-9) with mating connectorIP69KIP69K
Operating TemperatureConsistent with Pump Limits:
-40°C (-40°F) to 104°C (220°F)
The available Normally Open Electric Proportional Controls for the Series 45 are shown below. The
allowable Pressure Compensator (PC) and Load Sense (LS) pressure settings are provided for each frame
in their respective sections. Note that for Electric Proportional Controls, the Load Sense setting describes
the Low Pressure Standby value, not margin.
Electric Proportional Controls Options – Normally OpenFrame
CodeDescriptionLK
AXElectric Proportional Pressure Control w/Pressure Comp. (NO,
12VDC) Left
CLElectric Proportional Pressure Control w/Pressure Comp. (NO,
24VDC) Left
AWElectric Proportional Pressure Control w/Pressure Comp. (NO,
12VDC) Right
CKElectric Proportional Pressure Control w/Pressure Comp. (NO,
24VDC) Right
BXElectric Proportional Pressure Control w/Pressure Comp. (NO,
4. K2 Frame electric controls are limited only for Left orientation and up to 260 Bar
Electric On-Off Controls
•••
•••
•••
PLUS+1 Compliance
All Series 45 Electric controls have met and passed the Danfoss PLUS+1 compliance standard testing, and
as such, this Series 45 control is PLUS+1 compliant. PLUS+1 compliance blocks are available on the
Danfoss website, within the PLUS+1 Guide section.
Electric On-Off Control Principle
The Electric On/Off Control consists of an On/Off solenoid integrated into a Remote Pressure
Compensated control. This control allows the pump to be operated at either the Load Sense pressure
setting when “On”, or the Pressure Compensation pressure setting when “Off”.
Danfoss | January 2022BC152886483703en-001201 | 23
Technical Information
Series 45 Pumps
General Information
For fan-drive systems, and systems with motors, use a minimum 15bar LS setting to enhance system
stability. As the LS setting is reduced, the risk for system instability may be increased. A 20bar LS setting is
recommended as a starting point for all new applications.
Electric On-Off Control Response/Recovery
S45 Electric On/Off Controls are available with two servo control orifice options, as well as without an
orifice. The servo control orifice is used to enhance system stability, as well as dampen the pump
reactiveness. A smaller orifice diameter will add dampening to the pump reactiveness, while a larger
orifice will allow quicker pump reaction.
Module “G” Options for Electric On/Off Controls
Frame“E” - 0.8mm Orifice“F” - 1.0mm Orifice“N” - No Orifice
All Frames
•••
Specific Electric On/Off Control Response/Recovery times are shown for the available servo control orifice
options in the control section within each specific frame section. These times represent the response
from 75% of rated continuous pressure to 100% of rated continuous pressure, and recovery from 100% of
rated continuous pressure to 75% of rated continuous pressure for N.C. configuration per SAE J745 (viceversa for N.O). As the system pressure approaches the PC setting, the PC function will begin to assist in
clipping pressure overshoots during the pump’s response, and will decrease the response times of the
pump to equal those of the PC response.
Electric On-Off Control Performance vs. Ambient Temperature Characteristic
The Electric On/Off Controls continuous duty operating temperature range is shown below; this guideline
should be followed as well as the maximum current limitations. Note that rated voltage refers to either a
12V or 24V coil. Under high temperature conditions the PWM duty cycle to operate the solenoid
increases.
Electric On-Off Control Characteristic – Normally Closed
The normally closed configuration On/Off control directs the pump to its Pressure Compensation
pressure setting when no current is applied. When the required electric current is sent to the normally
closed configuration control the pump pressure decreases to the Low-Pressure Standby setting. This
control does not have Load Sense functionality, but rather acts as a Pressure Compensation control when
not energized, or is directed to its low-pressure standby when energized. This control is especially useful
for machine startups, as the pump can be directed to its Low-Pressure Standby setting during startup to
reduce the load on engine starters.
The available Normally Closed Electric On/Off Controls for the Series 45 are shown below. The allowable
Pressure Compensator (PC) and Load Sense (LS) pressure settings are provided for each frame in their
respective sections.
Electric On/Off Controls Options – Normally ClosedFrame
CodeDescriptionLK
ARElectric On/Off Pressure Control w/Pressure Comp. (NC,12VDC)
Left
CRElectric On/Off Pressure Control w/Pressure Comp. (NC,24VDC)
Left
AGElectric On/Off Pressure Control w/Pressure Comp. (NC,12VDC)
Right
AYElectric On/Off Pressure Control w/Pressure Comp. (NC,24VDC)
Right
BRElectric On/Off Pressure Control w/Pressure Comp. (NC,12VDC)
[>280 bar] Left
DRElectric On/Off Pressure Control w/Pressure Comp. (NC,24VDC)
[>280 bar] Left
BEElectric On/Off Pressure Control w/Pressure Comp. (NC,12VDC)
[>280 bar] Right
BGElectric On/Off Pressure Control w/Pressure Comp. (NC,24VDC)
[>280 bar] Right
EBElectric On/Off Pressure Control w/Pressure Comp. (NC,12VDC)
EEElectric On/Off Pressure Control w/Pressure Comp. (NC,24VDC)
4. K2 Frame electric controls are limited only for Left orientation and up to 260 Bar
Electric On/Off Control Characteristic – Normally Open
The Normally Open configuration On/Off control directs the pump to its Low-Pressure Standby setting
when no current is applied. When the required electric current (end current) is sent to the Normally Open
configuration control, the pump pressure increases to the Pressure Compensation pressure setting. This
control does not have Load Sense functionality, but rather acts as a Pressure Compensation control when
energized, or is directed to its Low-Pressure Standby when de-energized. This control is especially useful
for machine startups, as the pump can be directed to its Low Pressure Standby setting during startup to
reduce the load on engine starters.
Solenoid Data – Normally Open
Voltage12V24V
Maximum Current1500 mA665 mA
Inrush Current1700 mA800 mA
Coil Resistance @ 20°C [70°F]7.1 Ω28.5 Ω
PWM Range200-300 Hz
PWM Frequency (preferred)250 Hz
IP Rating (IEC 60529 | DIN 40050-9)IP67IP67
IP Rating (IEC 60529 | DIN 40050-9) with mating connectorIP69KIP69K
Operating TemperatureConsistent with Pump Limits:
-40°C (-40°F) to 104°C (220°F)
The available Normally Open Electric On/Off Controls for the Series 45 Frame E are shown below, with the
allowable Pressure Compensator (PC) pressure range provided for each control. All Electric On/Off
Controls are available with the 10-40bar Load Sense (LS) setting range.
Electric On/Off Controls Options – Normally OpenFrame
CodeDescriptionLK
ANElectric On/Off Pressure Control w/Pressure Comp. (NO,12VDC)
Left
CNElectric On/Off Pressure Control w/Pressure Comp. (NO,24VDC)
Left
AFElectric On/Off Pressure Control w/Pressure Comp. (NO,12VDC)
Right
ATElectric On/Off Pressure Control w/Pressure Comp. (NO,24VDC)
Right
BNElectric On/Off Pressure Control w/Pressure Comp. (NO,12VDC)
[>280 bar] Left
DNElectric On/Off Pressure Control w/Pressure Comp. (NO,24VDC)
[>280 bar] Left
BFElectric On/Off Pressure Control w/Pressure Comp. (NO,12VDC)
[>280 bar] Right
DFElectric On/Off Pressure Control w/Pressure Comp. (NO,24VDC)
[>280 bar] Right
EAElectric On/Off Pressure Control w/Pressure Comp. (NO,12VDC)
EGElectric On/Off Pressure Control w/Pressure Comp. (NO,24VDC)
4. K2 Frame electric controls are limited only for Left orientation and up to 260 Bar
Electric dump valve PC/LS controls
The electric dump valve pressure-compensated/load sense control allows the pump to operate as a
PC/LS type control under normal operating conditions. The solenoid dump valve overrides the LS control,
allowing the pump to operate in a Low-Pressure Standby mode. This function provides reduced
horsepower and torque loss in certain situations. It may be particularly useful to reduce loads on a system
during engine start.
When closed, the solenoid valve allows the control to act as a PC/LS control. When open, the solenoid
valve allows flow from the incoming load sense pressure to dump to case. This reduces the pressure in
the LS spring cavity, shifting the LS spool, and allows the pump to de-stroke to the Low-Pressure Standby
condition. This control is for applications needing a PC/LS control with the ability to switch to LowPressure Standby electronically. The solenoid valve is available in a normally closed and open
configuration.
For high cycling or power management applications, ensure to limit margin pressures to 60 bar or less for
optimal control component life.
Refer to LS System Over-Signaling on page 50 for more details.
Electric Dump Control (frames E, F and J)
Electronic Torque Limiting Controls (ETL)
PLUS+1 Compliance
All controls for this product have met and passed the Danfoss PLUS+1® compliance standard testing, and
as such, this product control is PLUS+1® Compliant. PLUS+1® compliance blocks (software) are available
on the Danfoss website, |
Danfoss | January 2022BC152886483703en-001201 | 27
ETL load sense
connection port
P108779
S
M2
X
B
(ETL Signal
Port)
Technical Information
Series 45 Pumps
General Information
Electric Torque Limiting Control Principle
The Electronic Torque Limiting control consists of a normally closed proportional relief valve (PRV)
integrated into a Pressure Compensated/Load Sensing control. This control operates as a PC/LS control,
with the additional ability to limit load sense pressure using the integrated PRV by varying the current to
the solenoid. When combined with an angle sensor, this control allows for a PC/LS control with electronic
torque limiting.
J-frame pump with integrated ETL control
Pump torque consumption is a function of pump outlet pressure, pump displacement, and pump
mechanical efficiency. When pump mechanical efficiency is considered constant, the pump torque can
be limited when pump displacement is known and pump pressure is controlled. As pump displacement
increases, the pump outlet pressure can be limited using the PRV to result in a constant torque limit.
Pump outlet pressure is equal to the load sense pressure, which is limited with the PRV, plus the margin
pressure setting of the pump.
The Electronic Torque Limiting control allows users to limit pump torque consumption electronically by
combining a pressure limiting PRV and angle sensor. This torque limit can be changed with varying
engine speeds (as shown in the Electronic Torque Limiting graph below), allowing the use of full engine
torque at all engine speeds and increasing machine productivity. A microcontroller is required to store
engine torque vs speed, receive the pump angle sensor signal, and then calculate and output the pump
outlet pressure limit. The basic torque limiting control logic for a single engine speed is shown below.
Danfoss offers a PLUS+1 subsystem application block for the Electronic Torque Limiting control option in
combination with keyed MC012-112 microcontroller hardware. The part number for the keyed
MC012-112 microcontroller is 11157484. Refer to graph Operating Pressure vs. Input Current (N.C. EPC) on
page 20 for pressure vs. current information.
All Series 45 Electric controls have met and passed the Danfoss PLUS+1 compliance standard testing, and
as such, this Series 45 control is PLUS+1 compliant. PLUS+1 compliance blocks (software) are available on
the Danfoss website, within the PLUS+1 Guide section.
Danfoss | January 2022BC152886483703en-001201 | 29
The Fan Drive Control is a unique electrically actuated pressure control solution that consists of a
normally closed proportional solenoid and one dual diameter spool sliding in the control housing.
System pressure acts on an area between the two spool diameters of the spool lands. This hydraulic force
is balanced with forces of springs and the solenoid when the spool is in the metering position. When no
current is sent to the solenoid it operates the pump at or below the PC setting which is adjusted
mechanically with the adjustor screw and lock nut. Increasing the control current proportionally reduces
the pump's outlet pressure until a minimum standby pressure is reached.
Control Block 12V and 24V
The minimum system pressure is given by swashplate moments of the pump and by servo system
leakages which produce a pressure drop across the control. In addition, fan motor type and fan inertia
impact minimum system pressure.
The Normally Closed Fan Drive Control coupled with a microprocessor allows the pump to operate at an
infinite range of operating pressures between a minimum system pressure and PC setting.
Warning
A relief valve is required to be installed in the pump outlet for additional system protection. Failure to
install a relief valve may lead to system damage and/or injury.
Warning
The Fan Drive Control is intended for fan drive systems only! Use in other systems could result in system
component damage or unintended machine movement. The Fan Drive Control is not intended to serve
at the primary system pressure relief. Loss of the input signal to this control will cause the pump to
produce maximum flow.
Fan Drive Control System Characteristics
•
Constant pressure and variable flow
•
High or low system pressure mode based on fan cooling demand
Danfoss | January 2022BC152886483703en-001201 | 31
P109029
0
50
100
150
200
250
300
350
0100200300400500600700800
PC310barPC260barPC210barPC140barPC100bar
Solenoid Input Current (mA)
Pump Outlet Pressure (bar)
Technical Information
Series 45 Pumps
General Information
Unintended Applications for Fan Drive Control Systems
•
Applications with frequent PC events (system pressure overshoots)
•
Adjustable Load Sensing systems
Fan Drive Control Cross Section
Fan Drive Control characteristic - Normally Closed
When an electric current is sent to the Normally Closed Fan Drive Control, pump outlet pressure
decreases proportionally to the increase in currentt. When the load in the system changes, the pump will
adjust its displacement to maintain the pressure demanded by the controlling current. This predictable
control is especially useful for fan-drive systems, due to the direct relationship between fan-speed and
pump pressure. Due to the nature of the Fan Drive Control, the relationship between current and pump
pressure is unique for each individual PC pressure setting combination. The relationship between pump
outlet pressure and control input current (for a 24V coil) is shown for various PC settings below. The
hydraulic schematic for the Normally Closed Fan Drive Control is shown below as well.
Pump Outlet Pressure vs. control input current 24V Normally closed FDC (at 100Hz PWM)
Pump Outlet Pressure vs. control input current 12V Normally closed FDC (at 100Hz PWM)
Attaining remarkably low system pressures is possible with the Fan Drive Control. The minimum system
pressure is greatly dependent on individual system parameters such as fan motor type and fan size. This
feature is highly desirable in low cooling demand conditions to keep fan speed as slow as possible.
Virtually eliminated control deadband increases controllability and reduces power loss. Control current
resolution is greatly improved.
Danfoss | January 2022BC152886483703en-001201 | 33
Solenoid data – Normally closed
Solenoid Data – Normally Closed
Connector on solenoidDeutsch DT04-2P
Mating Connector (not included)Deutsch DT06-2S
12V24V
Technical Information
Series 45 Pumps
General Information
Solenoid Data – Normally Closed (continued)
12V24V
Identification by color of nutBlackBlue
Nominal current1650 mA840 mA
Maximum Control Current1800 mA920 mA
Environmental ratingIP67 without mating connector,
IP69K with mating connector
Maximum output driver current2.0 Amps
PLUS+1 dither frequencyNot recommended
Useable PWM Frequency Range50-200 Hz
Recommended PWM Frequency200 Hz
Nominal Resistance at 20°C3.66 Ω14.2 Ω
Inductivity (pin at stroke end)33 mH140 mH
Minimum voltage9.5 Vdc19.0 Vdc
Maximum power17.9 Watts18.1 Watts
The Fan Drive Control is designed as a current driven control. It requires a PWM- input signal.
The available Normally Closed Fan Drive Controls for Series 45 are shown below. The allowable Pressure
Compensator (PC) pressure settings are provided for each frame.
C module—Control
Fan Drive Control OptionsFrame
CodeDescriptionLKK2JFE
SAFan Drive Control (12Vdc), 100-210 Bar, Left•••
SBFan Drive Control (24Vdc), 100-210 Bar, Left•••
SCFan Drive Control (12Vdc), 220-310 Bar, Left•••
SDFan Drive Control (24Vdc), 220-310 Bar, Left•••
SEFan Drive Control (12Vdc), 100-210 Bar, Right••
SFFan Drive Control (24Vdc), 100-210 Bar, Right••
SGFan Drive Control (12Vdc), 220-310 Bar, Right••
SHFan Drive Control (24Vdc), 220-310 Bar, Right••
G module options—Choke Orifice
Fan Drive Control optionsChoke Orifice size
G0.8 mm (0.031 in)
F1.0 mm (0.039 in
Angle Sensor
H module options—Gain Orifice
Fan Drive Control optionsGain Orifice Size
E1.2 mm (0.047 in)
NC Fan Drive Control 3D Views
LeftRight
PLUS+1 Compliance
The Electric Angle Sensor has met and passed the Danfoss PLUS+1 compliance standard testing, and as
such, this Angle Sensor is PLUS+1 compliant. PLUS+1 compliance blocks are available on the Danfoss
website, within the PLUS+1 Guide section.
Danfoss | January 2022BC152886483703en-001201 | 35
Swashplate
AMR Sensor
Magnet Carrier
Deutsch Plug
P108788
Technical Information
Series 45 Pumps
General Information
Angle Sensor Principle
The Series 45 Angle Sensor option allows users to measure the angle of pump displacement. The angle
sensor is an electronic sensor mounted to the housing of the pump, which reads the pump stroke angle
based on the swashplate position. Interfacing with the angle sensor is achieved through a 4-pin Deutsch
DTM04-4P receptacle attached to a flexible connection cable (for a mating connector, use Deutsch® plug
DTM06-4S). The sensor is mounted to the pump within an aluminum housing to prevent magnetic
interference.
Angle Sensor Characteristics
The angle sensor package incorporates two sensor signals (primary & secondary), within a single sensor
housing. This allows for improved accuracy and troubleshooting. For the ‘Angle Sensor – Right’ order
code in the K module, the sensor is positioned according to the following conventions:
When looking at the input shaft with the control on the ‘top’ side, the angle sensor will be viewed on the
right hand side. This convention is true for both Clockwise and Counter-clockwise rotation J & F-Frames.
This sensor location yields a unique voltage versus swashplate angle characteristic curve which is the
same for both Clockwise and Counter-clockwise rotation J & F-frames. Although each pair of curves will
be unique for individual pumps, a general example of what to expect is provided below for J & F units
with the ‘Right’ angle sensor position.
Danfoss | January 2022BC152886483703en-001201 | 37
The location convention for the E-Frame angle sensor is different from that of the J & F-Frame due to a
difference in design of the endcap and servo systems. When looking at the input shaft, the angle sensor
will be positioned on the same side as the outlet port of the endcap. The outlet port of the endcap is
always the smaller of the inlet and outlet ports, indicated below. This is the ‘right side’ order code
location, even though it appears on the left hand side from a frontal view.
P108821
36
[1.42]
E Frame Angle Sensor Position
Outlet Port
36
[1.42]
59.4
[2.34]
126.9
[5.0]
120
[4.72]
Approximate
Wire Length
131.5
[5.18]
Technical Information
Series 45 Pumps
General Information
Clockwise rotation E-frames appear with the control on the top side in this view. Counter-clockwise
rotation E-Frames appear with the control on the bottom side in this view.
This sensor location yields a unique voltage versus swashplate angle characteristic curve which is
different for Clockwise and Counter-clockwise rotation E-frames. Although each pair of curves will be
unique for individual pumps, a general example of what to expect is provided below for both Clockwise
and Counter-clockwise rotation units with the Right angle sensor position.
Danfoss | January 2022BC152886483703en-001201 | 39
Technical Information
Series 45 Pumps
General Information
Angle sensor electrical specifications
Electrical specifications
DescriptionMinimumTypicalMaximumUnitNote
Supply (V+)4.7555.25VdcSensor is ratiometric in the voltage range
Supply protection——28VdcSensor will switch off above 5.5 V
Supply current drawn—2225mASensor supply at 5 V
Output short circuit current (VDD to SIG
1/2 and GND to SIG 1/2)
Resolution—0.03—degree11 bit output channel
Hysteresis————Design of sensor eliminates any mechanical hysteresis
Environment temperature range-40 (-40)80 (176)104 (220)°C (°F)If temperature limits are exceeded, the sensor will
Operating temperature range20 (68)50 (122)95 (203)°C (°F)Temperature of oil
Storage temperature-40 (-40)—125 (257)°C (°F)—
Refresh rate of the sensor——100μsInternal ADC refresh rate
——7.5mAAdditional 7.5 mA for each sensor signal, total sensor
7.5x2+22=37 mA typical for FSO
function at a reduced level of performance
Angle Sensor Calibration
Charge Pump Circuits
A 2-point calibration of the sensor is recommended, with points measured at pump standby, and
maximum pump stroke. Maximum pump stroke can be achieved when the pump input shaft is not being
turned, as Series 45 pumps are biased to maximum displacement. In some cases the pump may need to
be turned momentarily to ensure the pump is in the maximum displacement position; this can be
achieved through a momentary switching of the engine starter on/off.
Angle Sensor Functionality
The Series 45 angle sensor option is intended for functionality such as electronic torque limiting, duty
cycle measurement, troubleshooting, etc. The angle sensor is PLUS+1 compliant with an available
hardware compliance block.
Angle Sensor Intended Functionality:
•
Electronic Torque Limiting
•
Duty Cycle Recording
•
Troubleshooting
Angle Sensor Unsupported Functionality:
•
Displacement/Flow Control
This section includes two general circuits for providing charge pressure to Series 45 pumps.
Example Circuit #1
Example Circuit #1 shows a generic open circuit charging layout.
In applications where the Series 45 pump does not have the required inlet pressure available, an external
charge pump may be used to increase the inlet pressure to an acceptable level. Scenarios in which this
may occur include a layout with the pump above the reservoir, high altitude conditions, etc.
For circuit type #1, follow these recommendations:
Size the charge pump so that its flow is 10 to 20% greater than the Series 45 flow rate at worst case
•
conditions
Include a relief valve or check valve, as shown, between the charge pump and S45 pump with an
•
initial pressure setting of up to 10 bar; if aeration at the inlet of the S45 pump is still present, increase
the relief/cracking pressure up to 20 bar (maximum).
Generic open circuit
Example Circuit #2
Example Circuit #2 shows a semi-closed circuit charging layout.
In applications where the Series 45 pump does not have the required inlet pressure available, an external
charge pump may be used to increase the inlet pressure to an acceptable level. Scenarios in which this
may occur include a layout with the pump above the reservoir, high altitude conditions, etc.
For circuit type #2, follow these recommendations:
Determine if the work function ever consumes more flow than it expels (for example: double acting
•
or single acting cylinders). If so, determine the maximum flow differential in/out of the work function.
Size the charge pump so that its flow is 10-20% of the Series 45 pump flow at worst case conditions,
•
and increase this size by any work function flow differential which may occur.
An inline oil cooler may be required for this type of circuit.
•
Include an oil filter after the oil cooler; this ensures that any sediment in the oil cooler that may be
•
dislodged due to vibration or any other reason is caught in the filter.
Include a relief valve or check valve between the charge pump and S45 pump with an initial pressure
•
setting of up to 10 bar; if aeration at the inlet of the S45 pump is still present, increase the relief/
cracking pressure up to 20 bar (maximum).
Danfoss | January 2022BC152886483703en-001201 | 41
P108 642E
Charge Pump
Flow = Qp*10% to 20%
+ work function flow differential
Series 45 Pump
Flow = Qp
Relief Valve or
Check Valve
Set to 10 bar
If the work function ever
consumes more flow than it
expels under certain
conditions, this flow must be
added to the charge pump size
To Work Function
Work Function
Oil Filter
Oil Cooler
Technical Information
Series 45 Pumps
General Information
Semi-closed circuit
Operating parameters
Fluids
Ratings and performance data for Series 45 products are based on operating with premium hydraulic
fluids containing oxidation, rust, and foam inhibitors. These include premium turbine oils, API CD engine
oils per SAE J183, M2C33F or G automatic transmission fluids (ATF), Dexron II (ATF) meeting Allison C-3 or
Caterpillar T0‑2 requirements, and certain specialty agricultural tractor fluids. For more information on
hydraulic fluid selection, see Danfoss publication BC152886484524 Hydraulic Fluids and Lubricants,
Technical Information, and 520L0465 Experience with Biodegradable Hydraulic Fluids, Technical
Information.
Viscosity
Fluid viscosity limits
Conditionmm2/s (cSt)SUS
ν min.continuous958
intermittent6.447
ν max.continuous110500
intermittent (cold start)10004700
Maintain fluid viscosity within the recommended range for maximum efficiency and pump life.
Minimum Viscosity – This should only occur during brief occasions of maximum ambient temperature and
severe duty cycle operation.
Maximum Viscosity – This should only occur at cold start. Pump performance will be reduced. Limit
speeds until the system warms up.
Temperature
Oil temperature limits are defined at the pump's case drain. As a rule of thumb, under steady state
conditions the case drain temperature is approximately 20 - 25 degrees Centegrade higher than the
pump's inlet oil temperature.
Continuous82° C [180° F]
Maximum Intermittent104° C [220° F]
- 40° C [- 40° F]
Frame L, K, J, F, & E Maximum Temperature limits are based on material properties. Don't exceed it.
Measure temperature at the case drain of the pump.
K2 Frame Temperature Limits
Minimum
(intermittent, cold start)
Continuous104° C [219° F]
Maximum Intermittent115° C [239° F]
- 40° C [- 40° F]
Frame K2 Maximum temperature limits are higher than other frame sizes & based on improved
swashplate bearing material capabilities. Continuous operation at the Maximum Intermittent
Temperature is possible with K2 if fluid viscosity requirements are maintained. Minimum temperature for
all frame sizes relates to the physical properties of the component materials. Cold oil will not affect the
durability of the pump components. However, it may affect the ability of the pump to provide flow and
transmit power.
Ensure fluid temperature and viscosity limits are concurrently satisfied.
Inlet pressure
Inlet pressure limits
Minimum
(continuous)
Minimum
(cold start)
0.8 bar absolute [6.7 in. Hg vac.]
(at reduced maximum speed)
0.5 bar absolute [15.1 in. Hg vac.]
Maintain inlet pressure within the limits shown in the table. Refer to Inlet pressure vs. speed charts for
each displacement.
Case pressure
Case pressure limits
Maximum
(continuous)
Intermittent
(cold start)
0.5 bar [7 psi] above inlet
2 bar [29 psi] above inlet
Maintain case pressure within the limits shown in the table. The housing must always be filled with
hydraulic fluid.
Caution
Operating outside of inlet and case pressure limits will damage the pump. To minimize this risk, use full
size inlet and case drain plumbing, and limit line lengths.
Danfoss | January 2022BC152886483703en-001201 | 43
Technical Information
Series 45 Pumps
General Information
Pressure ratings
The specification tables in each section give maximum pressure ratings for each displacement. Not all
displacements within a given frame operate under the same pressure limits. Definitions of the operating
pressure limits appear below.
Continuous working pressure is the average, regularly occurring operating pressure. Operating at or below
this pressure should yield satisfactory product life. For all applications, the load should move below this
pressure. This corresponds to the maximum allowable PC setting.
Maximum (peak) working pressure is the highest intermittent pressure allowed. Maximum machine load
should never exceed this pressure, and pressure overshoots should not exceed this pressure. *See Duty
cycle and pump life.
Speed ratings
The specification tables in each section give minimum, maximum, and rated speeds for each
displacement. Not all displacements within a given frame operate under the same speed limits.
Definitions of these speed limits appear below.
Rated speed is the fastest recommended operating speed at full displacement and 1 bar abs. [0 in Hg vac]
inlet pressure. Operating at or below this speed should yield satisfactory product life.
Maximum speed is the highest recommended operating speed at full power conditions. Operating at or
beyond maximum speed requires positive inlet pressure and/or a reduction of pump outlet flow. Refer to
Inlet pressure vs. speed charts for each displacement.
Minimum speed is the lowest operating speed allowed. Operating below this speed will not yield
satisfactory performance.
Duty cycle and pump life
Knowing the operating conditions of your application is the best way to ensure proper pump selection.
With accurate duty cycle information, your Danfoss representative can assist in calculating expected
pump life.
Inlet pressure vs. speed charts in each section show the relationship between speed, flow, and inlet
pressure for each displacement. Use these charts to ensure your application operates within the
prescribed range.
The charts define the area of inlet pressures and speeds allowed for a given displacement. Operating at
lower displacements allows greater speed or lower inlet pressure.
Sample inlet pressure vs. speed chart
Operating limit at 80% displacement
Operating limit at 90% displacement
Operating limit at 100% displacement
Danfoss | January 2022BC152886483703en-001201 | 45
Technical Information
Series 45 Pumps
General Information
Design parameters
Installation
Series 45 pumps may be installed in any position. To optimize inlet conditions, install the pump at an
elevation below the minimum reservoir fluid level. Design inlet plumbing to maintain inlet pressure
within prescribed limits (see Inlet pressure limits)
Fill the pump housing and inlet line with clean fluid during installation. Connect the case drain line to the
uppermost drain port (L1 or L2) to keep the housing full during operation.
To allow unrestricted flow to the reservoir, use a dedicated drain line. Connect it below the minimum
reservoir fluid level and as far away from the reservoir outlet as possible. Use plumbing adequate to
maintain case pressure within prescribed limits (see Case pressure limits, ).
Filtration
To prevent damage to the pump, including premature wear, fluid entering the pump inlet must be free of
contaminants. Series 45 pumps require system filtration capable of maintaining fluid cleanliness at ISO
4406-1999 class 22/18/13 or better.
Danfoss does not recommend suction line filtration. Suction line filtration can cause high inlet vacuum,
which limits pump operating speed. Instead we recommend a 125 µm (150 mesh) screen in the reservoir
covering the pump inlet. This protects the pump from coarse particle ingestion.
Return line filtration is the preferred method for open circuit systems. Consider these factors when
selecting a system filter:
Cleanliness specifications
•
Contaminant ingression rates
•
Flow capacity
•
Desired maintenance interval
•
Typically, a filter with a beta ratio of β10 = 10 is adequate. However, because each system is unique, only
a thorough testing and evaluation program can fully validate the filtration system. For more information,
see Danfoss publication BC152886482150 Design Guidelines for Hydraulic Fluid Cleanliness.
Reservoir
The reservoir provides clean fluid, dissipates heat, and removes entrained air from the hydraulic fluid. It
allows for fluid volume changes associated with fluid expansion and cylinder differential volumes.
Minimum reservoir capacity depends on the volume needed to perform these functions. Typically, a
capacity of one to three times the pump flow (per minute) is satisfactory.
Locate the reservoir outlet (suction line) near the bottom, allowing clearance for settling foreign particles.
Place the reservoir inlet (return lines) below the lowest expected fluid level, as far away from the outlet as
possible.
Fluid velocity
Choose piping sizes and configurations sufficient to maintain optimum fluid velocity, and minimize
pressure drops. This reduces noise, pressure drops, and overheating. It maximizes system life and
performance.
Recommended fluid velocities
System lines6 to 9 m/sec [20 to 30 ft/sec]
Suction line1 to 2 m/sec [4 to 6 ft/sec]
Case drain3 to 5 m/sec [10 to 15 ft/sec]
Q = flow (l/min)
A = area (mm²)
Velocity = (16.67•Q)/A (m/sec)
US units
Q = flow (US gal/min)
A = area (in²)
Velocity = (0.321•Q)/A (ft/sec)
Shaft loads
Series 45 pumps have tapered roller bearings capable of accepting external radial and thrust (axial) loads.
The external radial shaft load limits are a function of the load position, orientation, and the operating
conditions of the pump.
The maximum allowable radial load (Re) is based on the maximum external moment (Me) and the
distance (L) from the mounting flange to the load. Compute radial loads using the formula below. Tables
in each section give maximum external moment (Me) and thrust (axial) load (Tin , T
) limits for each
out
pump frame size and displacement.
Radial load formula
Me = Re•L
L = Distance from mounting flange to point of load
Me = Maximum external moment
Re = Maximum radial side load
Shaft load orientation
Bearing life
All shaft loads affect bearing life. In applications where external shaft loads can not be avoided, maximize
bearing life by orientating the load between the 30° and 330° positions, as shown. Tapered input shafts or
Danfoss | January 2022BC152886483703en-001201 | 47
clamp-type couplings are recommended for applications with radial shaft loads.
mounting flange
L1
L2
Center of Gravity (CG)
pump 1
Center of Gravity (CG)
pump 2
P101 081E
Technical Information
Series 45 Pumps
General Information
Mounting flange loads
Adding auxiliary pumps and/or subjecting pumps to high shock loads may overload the pump mounting
flange. Tables in each section give allowable continuous and shock load moments for each frame size.
Applications with loads outside allowable limits require additional pump support.
Shock load moment (MS) is the result of an instantaneous jolt to the system.
•
Continuous load moments (Mc) are generated by the typical vibratory movement of the application.
•
Estimating overhung load moments
Use the equations below to estimate the overhung load moments for multiple pump mounting. See
installation drawings in each section to find the distance from the mounting flange to the center of
gravity for each frame size. Refer to the technical specifications in each section to find pump weight.
Overhung load example
Shock load formula
Ms = Gs•K•(W1•L1+W2•L2+...Wn•Ln)
Continuous load formula
Mc = Gc•K•(W1•L1+W2•L2+...Wn•Ln)
SI units
Ms = Shock load moment (N•m)
Mc = Continuous (vibratory) load moment (N•m)
Gs = Acceleration due to external shock (G’s)
Gc = Acceleration due to continuous vibration (G’s)
K = Conversion factor = 0.00981
Wn = Mass of nth pump (kg)
Ln = Distance from mounting flange to nth pump CG (mm)
US units
Ms = Shock load moment (lbf•in)
Mc = Continuous (vibratory) load moment (lbf•in)
Gs = Acceleration due to external shock (G’s)
Gc = Acceleration due to continuous vibration (G’s)
K = Conversion factor = 1
Wn = Weight of nth pump (lb)
Ln = Distance from mounting flange to nth pump CG (in)
Auxiliary mounting pads
Auxiliary mounting pads are available for all radial ported Series 45 pumps. Since the auxiliary pad
operates under case pressure, use an O-ring to seal the auxiliary pump mounting flange to the pad. Oil
from the main pump case lubricates the drive coupling.
All mounting pads meet SAE J744 Specifications.
•
The combination of auxiliary shaft torque and main pump torque must not exceed the maximum
•
pump input shaft rating. Tables in each section give input shaft torque ratings for each frame size.
Applications subject to severe vibratory or shock loading may require additional support to prevent
•
mounting flange damage. Tables in each section give allowable continuous and shock load moments
for each frame size.
The drawing and table below give mating pump dimensions for each size mount. Refer to installation
•
drawings in each section for auxiliary mounting pad dimensions.
Mating pump specifications
Dimensions
SAE ASAE BSAE C
P82.55
[3.250]
B6.35
[0.250]
C12.70
[0.500]
D58.20
[2.290]
E15.00
[0.590]
F13.50
[0.530]
101.60
[4.000]
9.65
[0.380]
15.20
[0.600]
53.10
[2.090]
17.50
[0.690]
14.20
[0.560]
127.00
[5.000]
12.70
[0.500]
23.37
[0.920]
55.60
[2.190]
30.50
[1.200]
18.30
[0.720]
Input shaft torque ratings
Input shaft tables in each section give maximum torque ratings for available input shafts. Ensure that
Danfoss | January 2022BC152886483703en-001201 | 49
your application respects these limits.
C
P
Margin
= P
System
- P
Load Sense
Margin Pressure
Technical Information
Series 45 Pumps
General Information
Maximum torque ratings are based on shaft strength. Do not exceed them.
Coupling arrangements that are not oil-flooded provide a reduced torque rating. Contact your Danfoss
representative for proper torque ratings if your application involves non oil-flooded couplings.
Danfoss recommends mating splines adhere to ANSI B92.1-Class 6e. Danfoss external splines are class 5
fillet root side fit. Tolerance classes 5 and 6e have the same minimum effective space width and
maximum effective tooth thickness limits to ensure interchangeability between mating parts. Tables in
each section give full spline dimensions and data.
Understanding and minimizing system noise
Charts in each section give sound levels for each frame size and displacement. Sound level data are
collected at various operating speeds and pressures in a semi-anechoic chamber. Many factors contribute
to the overall noise level of any application. Below is some information to help understand the nature of
noise in fluid power systems, and some suggestions to help minimize it.
Noise is transmitted in fluid power systems in two ways: as fluid borne noise, and structure borne noise.
Fluid-borne noise (pressure ripple or pulsation) is created as pumping elements discharge oil into the
pump outlet. It is affected by the compressibility of the oil, and the pump’s ability to transition pumping
elements from high to low pressure. Pulsations travel through the hydraulic lines at the speed of sound
(about 1400 m/s [4600 ft/sec] in oil) until there is a change (such as an elbow) in the line. Thus, amplitude
varies with overall line length and position.
Structure-borne noise is transmitted wherever the pump casing connects to the rest of the system. The
way system components respond to excitation depends on their size, form, material, and mounting.
System lines and pump mounting can amplify pump noise. Follow these suggestions to help minimize
noise in your application:
Use flexible hoses.
•
Limit system line length.
•
If possible, optimize system line position to minimize noise.
•
If you must use steel plumbing, clamp the lines.
•
If you add additional support, use rubber mounts.
•
Test for resonants in the operating range, if possible avoid them.
•
Understanding and minimizing system instability
Knowing the operating conditions and system setup of your application is the best way to ensure a stable
system. All fan-drive circuits should use a choke orifice to ensure system stability. With accurate system
information, your Danfoss representative can assist you in the selection of a servo control orifice.
LS System Over-Signaling
To optimize the life and performance of Series 45 products using Load Sensing controls, it is important to
ensure the margin pressure signal at the pump’s control is conditioned in a way which does not damage
the control’s internal components.
Caution
Excessive component wear may occur when margin pressures > 60 bar are imposed on the LS spool.
Reduce margin pressures to 60 bar or less.
Margin pressure defines the physical movement of the LS spool and subsequent modulation of pump
flow to the system and is defined by:
LS System Over-Signaling results when the actual margin pressure magnitude exceeds the minimum
pressure required to shift the LS spool. It is important to limit excessive margin pressures in transient
system conditions to ensure satisfactory control component life.
For more information on LS System Over-signaling please contact your Danfoss Representative.
Use these equations to help select the right pump size, displacement and power requirements for your
application
Danfoss | January 2022BC152886483703en-001201 | 51
P109073
Tapered roller
bearin g
Input shaf t
Shaft seal
Slipper
Slipper retainer
Piston
Cylinder block
Block spring
Valve plate
Servo piston
Endcap
(axial ported)
Swashplate
Bias spring
LS spool
PC spool
LS adjustment
PC adjustment
LS control
Tapered roller
bearing
Technical Information
Series 45 Pumps
Frame K2
Design
Series 45 Frame K2 pumps have a single servo piston design with a cradle-type swashplate set in
polymer-coated journal bearings. A bias spring and internal forces increase swashplate angle. The servo
piston decreases swashplate angle. Nine reciprocating pistons displace fluid from the pump inlet to the
pump outlet as the cylinder block rotates on the pump input shaft. The block spring holds the piston
slippers to the swashplate via the slipper retainer. The cylinder block rides on a bi-metal valve plate
optimized for high volumetric efficiency and low noise. Tapered roller bearings support the input shaft
and a viton lip-seal protects against shaft leaks.
An adjustable one spool (PC only, not shown) or two spool (LS and remote PC) control senses system
pressure and load pressure (LS controls). The control ports system pressure to the servo piston, adjusting
swashplate angle to control pump output flow.
comp. (NO,24VDC), Left
SAFan drive control (12Vdc),100-210 Bar, Left•••••
SBFan drive control (24Vdc),100-210 Bar, Left•••••
SCFan drive control (12Vdc),220-260 Bar, Left•••••
SDFan drive control (24Vdc),220-260 Bar, Left•••••
•••••
•••••
•••••
•••••
•••••
•••••
•••••
•••••
•••••
D PC setting (2 digit code, 10 bar increments)
Example25 = 250 bar (3625 psi)
10–26100 to 260 bar [1450 to 3771 psi]•••••
25C100-260 bar [1450-3770 psi]
30C100-260 bar [1450-3770 psi]
38C100-260 bar [1450-3770 psi]
40C100-260 bar [1450-3770 bar]
45C100-260 bar [1450-3770 bar]
Threshold Control [mA] (20 bar LS setting, oil temp X)00
End Current [mA] (260/310 bar PC setting, oil temp X)1000/1100500/550
L2
S
L1
B
X
Technical Information
Series 45 Pumps
Frame K2
Normally Closed Electric On/Off with Pressure Compensation Controls
1
Voltage
Threshold Control [mA] (20 bar LS setting, oil temp X)00
End Current [mA] (260/310 bar PC setting, oil temp X)1000/1100500/550
1
Without servo control orifice
12V24V
For fan-drive systems, and systems with motors, select an LS setting no less than 15 bar to enhance
system stability. As the LS setting is reduced, the risk for system instability may be increased. A 20 bar LS
setting is recommended as a starting point for all new applications.
Schematic
BOutlet
SInlet
L1, L2Case drain
XLoad sense port
LS setting range
Modelbarpsi
All10 - 40[145 - 580]
PC setting range
FrameAR (12V)CR (24V)
25C100-260 bar [1450-3770] psi100-260 bar [1450-3770] psi
30C
38C
40C
45C
Normally Open Electric On/Off with Pressure Compensation Controls
Danfoss | January 2022BC152886483703en-001201 | 69
L2
S
L1
B
X
Technical Information
Series 45 Pumps
Frame K2
Response/Recovery times (continued)
(msec)Response
38C49138
40C49138
45C49138
1
Response and recovery times are calculated without servo control orifice
1
Recovery
For fan-drive systems, and systems with motors, select an LS setting no less than 15 bar to enhance
system stability. As the LS setting is reduced, the risk for system instability may be increased. A 20 bar LS
setting is recommended as a starting point for all new applications.
For fan-drive systems, and systems with motors, select an LS setting no less than15 bar to enhance
system stability. As the LS setting is reduced, the risk for system instability may be increased. A 20 bar LS
setting is recommended as a starting point for all new applications.
Electric proportional controls have a unique relationship between margin (LS) setting and low pressure
standby. See the graph below for this relationship.
Frames E, F, J, K2 Electric Proportional Control
Low Pressure Standby
P109193
Technical Information
Series 45 Pumps
Frame K2
PC setting range
FrameAX (12V)CL (24V)
25C100-260 bar [1450-3770] psi100-260 bar [1450-3770] psi
30C
38C
40C
45C
For fan-drive systems, and systems with motors, select an LS setting no less than15 bar to enhance
system stability. As the LS setting is reduced, the risk for system instability may be increased. A 20 bar LS
setting is recommended as a starting point for all new applications.
Electric proportional controls have a unique relationship between margin (LS) setting and low pressure
standby. See the graph below for this relationship.
Danfoss | January 2022BC152886483703en-001201 | 75
P109081
33
33
S
B
S
B
33
33
30.2
58.7
52.4
26.2
Technical Information
Series 45 Pumps
Frame K2
Installation Drawings
Axial Ported Endcap
CodeDescriptionPort
SSystem port (inlet), CW rotation shownO-ring boss per ISO 6149-1, M48x2-6H or M42x2-6H
Ø 31.8 (Axial endcaps) or Ø 38.1 (Radial endcaps)Split flange per ISO 6162-1, M10x1.5-6H 18 full thread
depth (Axial) or M12x1.75-6H 22.5 full thread depth
(Radial)
BSystem port (outlet), CW rotation shown O-ring boss per ISO 6149-1, M33x2-6H or M27x2-6H
Ø 25.4 - Split flange per ISO 6162-1, M10x1.5-6H 18
full thread depth
K2 Frame open circuit pumps are available with an optional adjustable displacement limiter. This
adjustable stop limits the pump’s maximum displacement.
Series 45 Frame L and K pumps have a single servo piston design with a cradle-type swashplate set in
polymer-coated journal bearings. A bias spring and internal forces increase swashplate angle. The servo
piston decreases swashplate angle. Nine reciprocating pistons displace fluid from the pump inlet to the
pump outlet as the cylinder block rotates on the pump input shaft. The block spring holds the piston
slippers to the swashplate via the slipper retainer. The cylinder block rides on a bi-metal valve plate
optimized for high volumetric efficiency and low noise. Tapered roller bearings support the input shaft
and a viton lip-seal protects against shaft leaks.
An adjustable one spool (PC only, not shown) or two spool (LS and remote PC) control senses system
pressure and load pressure (LS controls). The control ports system pressure to the servo piston, adjusting
swashplate angle to control pump output flow.
Danfoss | January 2022BC152886483703en-001201 | 87
Technical Information
Series 45 Pumps
Frames L and K
E Load sensing setting (2 digit code, 1 bar increments)
Example20 = 20 bar (290 psi)
12–3612 to 36 bar [174 to 522 psi]••••
NNNot applicable (pressure compensated
only controls)
••••
F Not used
L FrameK Frame
025C030D038C045D
NNNot applicable••••
G Servo Control Orifice
NNone (standard)••••
E0.8 mm diameter - Electrical proportional
controls only
F1.0 mm dismeter - Electrical proportional
controls only
J0.8 mm diameter - All other controls••••
K1.0 mm dismeter - All other controls••••
••••
••••
H Gain Orifice
31.0 mm diameter••••
J Input Shaft
C213 tooth, 16/32 pitch
C315 tooth, 16/32 pitch
K10.875 inch straight keyed
K20.875 inch straight keyed (long)
T11.0 inch Taper
Auxiliary Mount/Endcap Style
Auxiliary
Description
NoneAxialO-Ring Boss O-Ring Boss Inlet - SAE O-Ring boss port (1.875 inch
NoneAxialSplit FlangeSplit Flange
NoneAxialSplit FlangeSplit Flange
Endcap Style Inlet Porting Outlet
Porting
Endcap DescriptionCode
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Left Side
Inlet - Code 61 Split Flange Port 4 Bolt
(1.25 inch port 0.4375 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Left Side
Inlet - Code 61 Split Flange Port 4 Bolt
(1.25 inch port M10 threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port M10 threads)
Control - Left Side
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port 0.5 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port M12 threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port M10 threads)
Control - Right Side
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port 0.5 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Right Side
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port 0.5 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Right Side
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port 0.5 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port M12 threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port M10 threads)
Control - Right Side
Danfoss | January 2022BC152886483703en-001201 | 89
Technical Information
Series 45 Pumps
Frames L and K
Auxiliary Mount/Endcap Style (continued)
SAE-BB, 15
teeth
SAE-BB, 15
teeth
RadialO-Ring Boss O-Ring Boss
RadialSplit Flange Split Flange
J Input Shaft/Auxiliary Mount/Endcap
Available Combinations
L FrameK Frame
025C030D038C045D
*
C2AG
*
C2BG
*
C2BK
*
C2NF
**
C2NG
**
C2NK
**
C2NM
**
C2NP
*
C2NR
*
C2RG
*
C2TG
*
C3AG
**
C3AK
*
C3BG
*
C3NF
**
C3NG
**
C3NK
*
C3RG
*
PLB or AAA Displacement limiter options only
**
KNB Displacement limiter options only
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
Inlet - SAE O-Ring boss port (1.875 inch
threads)
Outlet - SAE O-Ring boss port (1.3125 inch
threads)
Control - Right Side
Inlet - Code 61 Split Flange Port 4 Bolt (1.5
inch port 0.5 inch threads)
Outlet - Code 61 Split Flange Port 4 Bolt (1
inch port 0.375 inch threads)
Control - Right Side
Flow and power data valid at 49°C [120°F] and viscosity of 17.8 mm²/sec [88 SUS].
The chart above shows allowable inlet pressure and speed at various displacements. Greater speeds and
lower inlet pressures are possible at reduced displacement. Operating outside of acceptable limits
reduces pump life.
Danfoss | January 2022BC152886483703en-001201 | 93
The Efficiency chart shows allowable inlet pressure and speed at various displacements. Greater speeds
and lower inlet pressures are possible at reduced displacement. Operating outside of acceptable limits
reduces pump life.
Noise
dB(A)210 bar [3045 psi]
L30D6670
1800 min-1 (rpm)Rated Speed
Input power vs. speed
Flow vs. speed
Efficiency
Inlet pressure vs. speed
Noise
0
25
50
75
100
125
05001000150020002500
0
5
10
15
20
25
30
Flow (l/min)
Speed min ( rpm)
-1
Flow (US gal/min)
0
10
20
30
40
50
60
05001000150020002500
0
10
20
30
40
50
60
70
80
Power (kW)
Speed min ( rpm)
-1
Power (hp)
260 bar [3770 psi
]
140
bar [2
030
psi]
50
55
60
65
70
75
80
85
90
95
100
0
500
10001500
2000
2500
3000
Efficiency (%)
Input Speed (rpm)
System Pressure: 260 Bar - Inlet Press ure: 1. 0 Bar abs - Inlet Temperature: 49C
Flow and power data valid at 49°C [120°F] and viscosity of 17.8 mm²/sec [88 SUS].
The chart above shows allowable inlet pressure and speed at various displacements. Greater speeds and
lower inlet pressures are possible at reduced displacement. Operating outside of acceptable limits
reduces pump life.
Flow and power data valid at 49°C [120°F] and viscosity of 17.8 mm²/sec [88 SUS].
The chart above shows allowable inlet pressure and speed at various displacements. Greater speeds and
lower inlet pressures are possible at reduced displacement. Operating outside of acceptable limits
reduces pump life.