Instructions
Stepper output module
AK-XM 208C
080Z0023
AK-XM 208C
-20°< tamb |
< 55°C° |
Listed |
|
|
|
|
4VR5 |
|
|
|
|||
-0°F < tamb |
< 130°F |
|
|
|
||
UL file: E357029 |
|
|
|
|||
0 - 95% RH, non condensing |
|
|
|
|||
Class 2 or LPS in accordance with NEC. |
|
|
||||
IP10 / VBG4 |
|
|
||||
For supply connections, use 16 AWG or |
|
|
||||
Controller supply = 5 VA |
|
|
||||
larger wires rated for at least 90°C (194°F). |
|
|||||
Valve supply = 7.8 VA + valves. |
|
|||||
Use copper conducters only. |
|
|
||||
Class II construction |
|
|
||||
|
|
|
|
|||
4 x stepper valve output |
|
|
|
|
||
8 x AI |
|
Separate power supply to AK-XM 208C: |
|
|
||
|
|
Valve data |
|
|||
|
|
24 V a.c. / d.c. +/- 20% |
|
|
||
|
|
|
Type |
P |
||
The terminals "+" and "-" |
xx VA |
|
||||
|
|
|
||||
xx = Eg: 7.8 + (4 x 1.3) = 13 VA |
AK-PS 075 |
ETS 12.5 - ETS 400 |
1.3 VA |
|||
must not be earthed. |
||||||
xx = Eg: 7.8 + (4 x 5.1) = 28.2 VA |
AK-PS 150 |
KVS 15 - KVS 42 |
|
|||
|
|
|
||||
|
|
|
|
CCMT 2 - CCMT 8 |
|
|
|
|
|
|
CCM 10 - CCM 40 |
|
|
|
|
Max. 10 V |
|
CTR 20 |
|
|
|
|
|
|
CCMT 16 - CCMT 42 |
5.1 VA |
5 VA
Output:
24 V d.c.
20-500 step/s
Imax. = 325 mA RMS / valve
∑ Pout = max. 21 VA
L = max. 30 m. (Filter AKA 211 must not be used.)
The connection to the valve must not be broken using a relay
RI8PS802 09-2018
Point
Terminal 17: |
12 V |
|||
Terminal18: |
5 V |
|||
Terminal 19,20 : |
|
|
|
|
|
|
|
|
The screen on the pressure transmitter cables must only be connected at the end of the module.
OPEN = Green = valve opens
CLOSE = Green = valve closes
Red flash = valve error / connection error
|
|
|
|
1 |
25 |
26 |
27 |
28 |
|
|
|
Step / |
2 |
29 |
30 |
31 |
32 |
|
|
CCM / CCMT |
Termi- |
|||||
|
|
3 |
33 |
34 |
35 |
36 |
||
|
|
|
nal |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
37 |
38 |
39 |
40 |
|
|
|
ETS |
|
|
|
|
|
|
|
|
CCM / CCMT |
|
|
|
|
|
|
|
|
CTR |
|
White |
Black |
Red |
Green |
|
Signal |
Signal |
KVS 15 |
|
|
|
|
|
|
|
type |
KVS 42-54 |
|
|
|
|
|
|
|
|
|
|
|
|
||
S (sensor) |
S1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pt 1000 ohm/0°C |
S2 |
Pt 1000 |
|
|
|
|
|
|
|
Saux1 |
|
|
|
|
|
|
|
|
Saux2 |
|
|
|
|
|
|
|
|
SSA |
|
|
|
|
|
|
|
|
SdA |
|
|
|
|
|
|
|
P (pressure) |
|
|
|
|
|
|
|
|
AKS 32R |
|
|
|
|
|
|
|
|
AKS 2050 |
|
AKS 32R |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P0A |
AKS 2050 |
|
|
|
|
|
|
|
P0B |
MBS 8250 |
|
|
|
|
|
|
|
PcA |
-1 - xx bar |
|
|
(Controller) |
|
|
|
|
PcB |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AKS 32 |
Paux |
AKS 32 |
|
|
|
|
|
|
|
|
-1 - zz bar |
|
|
|
|
|
|
|
|
Signal |
|
Signal type / |
Module |
Point |
Terminal |
|
|
|
|
|
Active at |
|
|
|
U (voltage) |
|
|
1 (AI 1) |
1 |
- 2 |
|
|
2 (AI 2) |
3 |
- 4 |
|
|
|
|
|||
|
... |
0 - 5 V |
3 (AI 3) |
5 |
- 6 |
|
0 - 10 V |
4 (AI 4) |
7 |
- 8 |
|
|
|
|
|||
|
|
|
5 (AI 5) |
9 - 10 |
|
|
|
|
6 (AI 6) |
11 |
- 12 |
On/Off |
Ext. |
Active at: |
7 (AI 7) |
13 |
- 14 |
|
|
|
|||
|
Main |
8 (AI 8) |
15 |
- 16 |
|
|
|
||||
|
switch |
Closed |
Valve |
|
|
|
|
|
|
||
|
Day/ |
/ |
9 (Step 1) |
25 |
- 28 |
|
Open |
||||
|
Night |
10 (Step 2) |
29 |
- 32 |
|
|
|
||||
|
|
|
|||
|
Door |
|
11 (Step 3) |
33 |
- 36 |
|
|
|
12 (Step 4) |
37 |
- 40 |
|
|
|
The Product contains electrical components |
|
|
|
|
|
And may not be disposed together with domestic waste. |
||
|
|
|
Equipment must be separate collected with Electrical and Elec- |
||
|
|
|
tronic waste. According to Local and currently valid legislation. |
<![endif]>ADAP-KOOL®
2 |
Instructions RI8PS802 © Danfoss 09/2018 |
AK-XM 208C |