Danfoss AK-XM 208C Installation guide

Danfoss AK-XM 208C Installation guide

Instructions

Stepper output module

AK-XM 208C

080Z0023

AK-XM 208C

-20°< tamb

< 55°C°

Listed

 

 

 

4VR5

 

 

 

-0°F < tamb

< 130°F

 

 

 

UL file: E357029

 

 

 

0 - 95% RH, non condensing

 

 

 

Class 2 or LPS in accordance with NEC.

 

 

IP10 / VBG4

 

 

For supply connections, use 16 AWG or

 

 

Controller supply = 5 VA

 

 

larger wires rated for at least 90°C (194°F).

 

Valve supply = 7.8 VA + valves.

 

Use copper conducters only.

 

 

Class II construction

 

 

 

 

 

 

4 x stepper valve output

 

 

 

 

8 x AI

 

Separate power supply to AK-XM 208C:

 

 

 

 

Valve data

 

 

 

24 V a.c. / d.c. +/- 20%

 

 

 

 

 

Type

P

The terminals "+" and "-"

xx VA

 

 

 

 

xx = Eg: 7.8 + (4 x 1.3) = 13 VA

AK-PS 075

ETS 12.5 - ETS 400

1.3 VA

must not be earthed.

xx = Eg: 7.8 + (4 x 5.1) = 28.2 VA

AK-PS 150

KVS 15 - KVS 42

 

 

 

 

 

 

 

 

CCMT 2 - CCMT 8

 

 

 

 

 

CCM 10 - CCM 40

 

 

 

Max. 10 V

 

CTR 20

 

 

 

 

 

CCMT 16 - CCMT 42

5.1 VA

5 VA

Output:

24 V d.c.

20-500 step/s

Imax. = 325 mA RMS / valve

∑ Pout = max. 21 VA

L = max. 30 m. (Filter AKA 211 must not be used.)

The connection to the valve must not be broken using a relay

RI8PS802    09-2018

Point

Terminal 17:

12 V

Terminal18:

5 V

Terminal 19,20 :

 

 

 

 

 

 

 

 

The screen on the pressure transmitter cables must only be connected at the end of the module.

OPEN = Green = valve opens

CLOSE = Green = valve closes

Red flash = valve error / connection error

 

 

 

 

1

25

26

27

28

 

 

 

Step /

2

29

30

31

32

 

 

CCM / CCMT

Termi-

 

 

3

33

34

35

36

 

 

 

nal

 

 

 

 

 

 

 

 

 

 

 

 

4

37

38

39

40

 

 

 

ETS

 

 

 

 

 

 

 

 

CCM / CCMT

 

 

 

 

 

 

 

CTR

 

White

Black

Red

Green

 

Signal

Signal

KVS 15

 

 

 

 

 

 

type

KVS 42-54

 

 

 

 

 

 

 

 

 

 

 

S (sensor)

S1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pt 1000 ohm/0°C

S2

Pt 1000

 

 

 

 

 

 

 

Saux1

 

 

 

 

 

 

 

Saux2

 

 

 

 

 

 

 

 

SSA

 

 

 

 

 

 

 

 

SdA

 

 

 

 

 

 

 

P (pressure)

 

 

 

 

 

 

 

 

AKS 32R

 

 

 

 

 

 

 

 

AKS 2050

 

AKS 32R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P0A

AKS 2050

 

 

 

 

 

 

 

P0B

MBS 8250

 

 

 

 

 

 

 

PcA

-1 - xx bar

 

 

(Controller)

 

 

 

 

PcB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AKS 32

Paux

AKS 32

 

 

 

 

 

 

 

 

-1 - zz bar

 

 

 

 

 

 

 

 

Signal

 

Signal type /

Module

Point

Terminal

 

 

 

 

Active at

 

 

 

U (voltage)

 

 

1 (AI 1)

1

- 2

 

 

2 (AI 2)

3

- 4

 

 

 

 

...

0 - 5 V

3 (AI 3)

5

- 6

 

0 - 10 V

4 (AI 4)

7

- 8

 

 

 

 

 

 

5 (AI 5)

9 - 10

 

 

 

6 (AI 6)

11

- 12

On/Off

Ext.

Active at:

7 (AI 7)

13

- 14

 

 

 

 

Main

8 (AI 8)

15

- 16

 

 

 

switch

Closed

Valve

 

 

 

 

 

 

 

Day/

/

9 (Step 1)

25

- 28

 

Open

 

Night

10 (Step 2)

29

- 32

 

 

 

 

 

 

Door

 

11 (Step 3)

33

- 36

 

 

 

12 (Step 4)

37

- 40

 

 

 

The Product contains electrical components

 

 

 

 

 

And may not be disposed together with domestic waste.

 

 

 

Equipment must be separate collected with Electrical and Elec-

 

 

 

tronic waste. According to Local and currently valid legislation.

<![if ! IE]>

<![endif]>ADAP-KOOL®

2

Instructions  RI8PS802  ©  Danfoss  09/2018

  AK-XM 208C