Fact sheet
Akva Lux II
Fully insulated instantaneous water heater for low-temperature district heating
district heating
Mieszkaniowy węzeł cieplny do bezpośrednich systemów centralnego ogrzewania
oraz przygotowania ciepłej wody użytkowej.
Application
Akva Lux II is a fully insulated instantaneous
water heater featuring high performance. It
meets the future energy demands for low
energy consumption and very low standby
heat losses. It is especially suitable for large
villas with for instance several bathrooms
or jacuzzi and for the large family, for which
an exceptionally large amount of water is
required. The Akva Lux II is also very suiable for small apartment houses with 2-4
apartments.
Construction
The Akva Lux II water heater is prefabricated
with a brazed, highly efficient Danfoss plate
heat exchanger for domestic hot water
production, a domestic hot water controller
Danfoss PTC2+P, as well as a Danfoss FJVR
thermostat for control of the bypass/
circulation temperature. A circulation set
and a safety set is available as optional
equipment.
Design
The Akva Lux II is designed for wall-mounting
and much importance has been assigned
to a user-friendly and easily accessible
placement of all system components,
including the controllers. The Akva Lux II is
fully insulated in an EPP insulation box and
can be supplied with a white-lacquered
cover in modern design.
Bypass (thermostatic circulation)
The water heater is supplied with a
thermostatically controlled bypass,
which ensures that hot water is produced
immediately, when tapping starts.
The bypass temperature is set with due
consideration of the best possible DHW
comfort and economy.
Domestic hot water recirculation
The water heater is prepared for domestic
hot water circulation. If the household piping
includes hot water recirculation the water
heater must be connected to the hot water
recirculation system and a circulation pump
and a non-return valve must be mounted
on the circulation pipe and a safety valve
must be mounted in the DCW inlet. The
pump must be installed so that it pumps
towards the water heater. Domestic hot
water recirculation ensures that hot water
is available at the tapping point without
waiting time and waste of water. The
circulation temperature is set independently
of the set DHW temperature. This ensures
the best possible DHW comfort, very low
standby losses and thus a very good district
heating economy.
Heat exchanger for DHW heating
The water heater is based on a brazed, highly
efficient plate heat exchanger type XB 06H1 26 or XB 06H-1 40, which is controlled by a
thermostatic and pressure controlled DHW
controller, Danfoss PTC2+P with integrated
differential pressure controller and energy
saving function, which ensures that the
heat exchanger is cold during standby. After
completion of the tapping process, the
controller immediately blocks the district
heating flow, to avoid standby, so the losses
and to protect the heat-
exchanger from the formation of lime scale
and growth of bacteria. The heat exchanger
is cold during standby, so the heat loss is
very low. The integrated differential pressure
controller compensates for variations in
supply temperature and varying differential
pressure and thereby ensures a constant hot
water temperature at all times.
Service and maintenance
The water heater is very service-friendly
and easy to install. It is mounted on the wall
and as all pipes are placed in pipe bracket
distance, it is possible to establish a nice
piping.
FEATURES AND BENEFITS
• Prepared for low-temperature
district heating
• Fully insulated and very
low heat losses
• Cold heat exchanger during
standby, - no standby losses
• DHW controller PTC2+P with
integrated differential pressure
controller and energy saving function
• Pipes and heat exchanger made
of stainless steel, connections
with EPDM gaskets.
• Minimized risk of lime scale
and bacteria formation
• Capacity: up to 53 kW DHW
www.danfoss.com
Material
Size
Scale
Projection
E
D
C
B
A
87
6
5
4
3
2
1
General tolerance accuracy
CIRCUIT DIAGRAM EXAMPLE
DCW
DHW
Design specications:
Nominal pressure (prim/sec.): PN 16 / PN 16
Max. supply temperature: 120 °C
DCW static pressure: pmin = 2.0 bar
Min. ΔP: See capacity examples
Brazing material (HEX): Copper
Weight excl. cover:
XB06H-1 26 = 8 kg
XB06H-1 40 = 9 kg
Insulation: EPP λ 0.039
Cover: White-lacquered steel
Dimensions (mm):
Insulated: H 463 × W 306 × D 190
Insulated with cover: H 463 × W 310 × D 210
Connections sizes:
DH, DHW, DCW: G ¾“ ET (ext. thread)
Circulation: R ½“ ET (ext. thread)
DH
supply
2. Danfoss, copper brazed plate heat exchanger in stainless
steel AISI 316, type XB 06H-1 26 or XB 06H-1 40.
38. Domestic hot water controller Danfoss PTC2+P with energy saving
function (= cold heat exchanger during standby).
40. By-pass/circulation thermostat Danfoss FJVR.
----------------------------------------------------------------------------------
DHW circulation:
A. Connection of capillary tube from Danfoss FJVR acting as by-pass
(standard function).
B. Connection of capillary tube from Danfoss FJVR acting as circulation
thermostat.
C. Connection of circulation hose. Circulation set for control
change from bypass to DHW recirculation is not part of the delivery and
must be ordered seperately.
For systems with DHW recirculation the water heater must be supplied with
circulation pump, non-return valve and safety valve mounted in the cold
water supply.
DH
return
Connections:
200
145,5
1. Domestic cold water (DCW)
2. Domestic hot water (DHW)
3. District heating (DH) supply
4. District heating (DH) return
5. Circulation
Code N o’s:
403
463
306
60 80 60
40
190
Akva Lux II water
heater with heat
Insulated* Code no.:
exchanger type:
XB 06H-1 26
XB 06H-1 40
* Akva Lux II is fully insulated and available with out w/o white cover.
w/o cover 004U8243
w. cover 004U8245
w/o cover 004U8244
w. cover 004U8246
Options:
Cover H 410 x W 310 x D 210 mm
Circulation set for mounting on site
Safety valve set
DHW: CAPACITY EXAMPLES, 10°C / 45°C
capacity
DHW
[kW]
Plate heat
exchanger
Supply flow
primary
[°C]
Return flow
primary
[°C]
DHW
tap load
[l/min]
32.3 XB 06H-1 26 55 21.8 13.16 0.28 840
32.3 XB 06H-1 26 60 18.9 13.16 0.18 680
32.3 XB 06H-1 40 55 19.0 13.16 0.19 770
32.3 XB 06H-1 40 60 17.0 13.16 0.13 650
41.0 XB 06H-1 26 60 20.4 16.86 0.31 900
41.0 XB 06H-1 26 70 16.8 16.86 0.17 670
53.0 XB 06H-1 40 60 19.1 21.84 0.39 1127
53.0 XB 06H-1 40 70 15.7 21.84 0.25 850
Danfoss Redan A/S · District Heating · Omega 7, Søften · DK-8382 Hinnerup · Denmark
Tel.: +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.com · www.redan.danfoss.dk
© Danfoss | DHS-SRMT/ PL | 2016. 10
Pressure loss*
primary
[bar]
Flow rate
primary
[l/h]
VL.GP.G3.02