Danfoss AKVA 10-n Installation guide [da]

Installation guide

Electric expansion valve

AKVA 10-n (n = 1-8)

 

 

 

 

<![if ! IE]>

<![endif]>068R9546

 

 

 

 

<![if ! IE]>

<![endif]>068R9546

 

 

 

AKVA 10 -

1, 2, 3, 4, 5, 6

7,8

 

 

 

In

⅜” (Øin = 17.2 mm)

½” (Øin = 21.3 mm)

 

 

 

Out

½” (Øout = 21.3 mm)

¾” (Øout = 26.9 mm)

 

 

 

 

 

Stainless steel

Orifice, Dyse, Düse, Orificio

 

 

 

matr. no 1.4301

 

 

 

 

 

Code no.

kW

TR

 

 

 

Best.nr.

 

 

 

Bestell-Nr.

 

 

 

 

 

N° de code

 

 

 

 

n

Núm. de código

 

 

 

 

1

068F0526

4.0

1.1

 

 

2

068F0527

6.3

1.8

 

 

3

068F0528

10.0

2.8

 

 

4

068F0529

16.0

4.5

 

 

5

068F0530

25.0

7.1

 

 

6

068F0531

40.0

11.4

 

 

7

068F0532

63.0

18.0

 

 

8

068F0533

100.0

 

 

 

© Danfoss | DCS (ms) | 2019.08

 

 

AN11938641929301-000201 | 1

Danfoss AKVA 10-n Installation guide

Ambient temperature range:

-50 °C < tamb < 50 °C -58 °F < t amb < 120 °F

Media temperature range:

-50 °C < t media < 60 °C -58 °F < t media < 140 °F

Max. Working pressure:

Ps = 42 barg / MWP = 610 psig

Max test pressure

PT = 46,2 barg / 670 psig

Max differential pressure

MOPDmax = (P1-P2) = 18 bar (260 psi)

Media R717, R744, HCFC, HFC

 

<![if ! IE]>

<![endif]>Danfoss 68F311.10

75 Nm

 

55 ft-lbs

 

55ft-

 

 

2 | AN11938641929301-000201

 

© Danfoss | DCS (ms) | 2019.08

Loading...