Danfoss AKV 15, AKV 20 Data sheet

Data Sheet
Electric expansion valve Type AKV 15 and AKV 20
For liquid injection into evaporators
AKV are electrically operated expansion valves designed for refrigerating plants.
The AKV valves are normally controlled by a controller from Danfoss’ range of ADAP- KOOL controllers.
The AKV valves are supplied as a component programme, as follows:
• Separate coil with terminal box or cable
• Spare parts in the form upper part, orice and
lter
Valve capacity is indicated with a number forming part of the type designation. The number represents the size of the orice of the valve in question. A valve with orice 3 will for example be designated AKV 15-3. The orice assembly is replaceable.
Features:
• Refrigerants: R134a, R22, R23, R404A, R407A, R407C, R407F, R407H, R410A, R422B, R422D, R438A, R448A, R449A, R449B, R450A, R452A, R463A, R507, R513A, R513B, R515A, R515B, R744.
• For a complete list of approved refrigerants, visit https://store.danfoss.com/ and search for individual code numbers, where refrigerants are listed as part of technical data.
• The valve requires no adjustment
• Wide regulation range Replaceable orice assembly
• Both expansion valve and solenoid valve
• Wide range of AC and DC coils
®
AI251586497622en-001301
AK-CC 550 case controller
AK-CC 750 case controller
EKC 315A superheat controller
DML/DMSC Eliminator® hermetic l‐
ter drier
Electric expansion valve, Type AKV 15 and AKV 20
Portfolio overview
Related products
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.05 AI251586497622en-001301 | 2
0
6
12
18
Electric expansion valve, Type AKV 15 and AKV 20
Function
Figure 1: Function
The valve capacity is regulated by means of pulse-width modulation. Within a period of six seconds a voltage signal from the controller will be transmitted to and removed from the valve coil. This makes the valve open and close for the ow of refrigerant.
The relation between this opening and closing time indicates the actual capacity. If there is an intense need for refrigeration, the valve will remain open for almost all six seconds of the period. If the required amount of refrigeration is modest, the valve will only stay open during a fraction of the period.
The amount of refrigeration needed is determined by the controller. When no refrigeration is required, the valve will remain closed and thus function as a solenoid valve.
© Danfoss | Climate Solutions | 2021.05 AI251586497622en-001301 | 3
Valve type
AKV 15
AKV 20
Tolerance of coil voltage (coil dependent)
10 / - 15%
10 / - 15%
Enclosure to IEC 529
Max. IP67
Max. IP67
Working principle
Pulse Width Modulation (PWM)
Recommended period of time
6 sec.
6 sec.
Capacity (R404A/R507)
14 – 85 kW / 3.98 – 24.17 ton
56 – 530 kW / 15.92 – 150.70 ton
Regulation range (Capacity range)
10 – 100%
10 – 100%
Connection
Solder
Solder or weld
Evaporating temperature
- 50 – 60 °C / -58 – 140 °F
- 40 – 60 °C / -104 – 140 °F
Ambient temperature (coil dependent)
- 40 – 50 °C / -104 – 122 °F
- 40 – 50 °C / -104 – 122 °F
MOPD (Max. Opening Pressure Dierential)
22 bar / 319 psig
18 bar / 261 psig
Filter, replaceable
External 100 μm
External 100 μm
Max. working pressure
AKV 15-1 – 15-4: 46 barg / 667 psig
AKV 20-1 – 20-5: 28 barg / 406 psig
.FW
Valve
type
Rated capacity
(1)
kv val‐ ue[m3/h]
Connections Solder ODF
R22
R134a
R407C
R404A/ R507
R407A
R410A
R744
Inlet ×
out‐
let[in]
Inlet ×
outlet
[mm]
Multipack
Code no.
[kW]
[TR]
[kW]
[TR]
[kW]
[TR]
[kW]
[TR]
[kW]
[TR]
[kW]
[TR]
[kW]
[TR]
AKV 15-1
25.7
7.3
19.9
5.66
27.1
7.72
18.1
5.14
25.4
7.23
30.1
8.56
32.7
9.3
0.25
¾ × ¾-068F5000
25.7
7.3
19.9
5.66
27.1
7.72
18.1
5.14
25.4
7.23
30.1
8.56
32.7
9.3
0.25
-
18 ×
18
068F5001
25.7
7.3
19.9
5.66
27.1
7.72
18.1
5.14
25.4
7.23
30.1
8.56
32.7
9.3
0.25
¾ × ¾-068F5035
(2)
AKV 15-2
41.1
11.7
31.8
9.03
43.3
12.3
28.9
8.23
40.6
11.6
48.1
13.7
52.4
14.9
0.4
¾ × ¾-068F5005
41.1
11.7
31.8
9.03
43.3
12.3
28.9
8.23
40.6
11.6
48.1
13.7
52.4
14.9
0.4
-
18 ×
18
068F5006
41.1
11.7
31.8
9.03
43.3
12.3
28.9
8.23
40.6
11.6
48.1
13.7
52.4
14.9
0.4
¾ × ¾-068F5036
(2)
AKV 15-3
64.5
18.3
49.9
14.1
68.1
19.4
45.4
12.9
63.8
18.1
75.7
21.5
82.6
23.5
0.63
⁷⁄₈ × ⁷⁄₈-068F5010
64.5
18.3
49.9
14.1
68.1
19.4
45.4
12.9
63.8
18.1
75.7
21.5
82.6
23.5
0.63
⁷⁄₈ × ⁷⁄₈-068F5037
(2)
AKV 15-4
1022978.6
22.3
107
30.5
71.9
20.5
101
28.6
120
34.1
131
37.2
1
1
1
8 ×
1
1
8
-
068F5015
1022978.6
22.3
107
30.5
71.9
20.5
101
28.6
120
34.1
131
37.21-
28 ×
28
068F5016
1022978.6
22.3
107
30.5
71.9
20.5
101
28.6
120
34.1
131
37.2
1
1
1
8 ×
1
1
8
-
068F5038
(2)
Electric expansion valve, Type AKV 15 and AKV 20
Product specication
Technical data
Table 2: Technical data
Filter
Figure 2: Filter
On plants using AKV 15 or AKV 20 a lter must be mounted in front of AKV 15 and AKV 20.
Capacity
Table 3: AKV 15
© Danfoss | Climate Solutions | 2021.05 AI251586497622en-001301 | 4