Installation Guide
Electrically Operated Expansion Valve
Types AKV 10- n (n= 1 – 7)
Refrigerants:
R744 , R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss.
068 R9514
3
/8 in. (10 mm)
1
/2 in. (12 mm)
1
/2 in. (12 mm)
5
/8 in. (16 mm)
Max. working pressure:
AKV 10 (n=1 - 6) PS/MWP = 52 barg (753 psig)
AKV 10 n=7 PS/MWP = 42 barg (610 psig)
Max. test pressure: Pe = 60 barg (869 psig)
Max. dierential pressure: MOPD = P
Media temperatur range:
t
-50 °C (-58 °F)
media
60 °C (140 °F)
t
media
- P2 =18 bar (260 psi)
1
Ambient temperatur range:
t
Min. -50 °C (-58 °F)
amb
Max. 50 °C (120 °F)
t
amb
068 R9514
AKV 10-1, AKV 10-2,
AKV 10-3, AKV 10-4,
AKV 10-5, AKV 10-6
c 75 73
d 67 75
AK V 10-7
max. 150 °C (300 °F)
Min. 5% Ag
© Danfoss A/S (AC-MCI sw) 2013-04 DKRCC.PI.VA1.A5.53 / 520H7550 1
Clip-on coil
(en-gb) Do not insulate
(da) Må ikke isoleres
(de) Nicht isolieren
(fr) Ne pas isoler
(es) No encerrar
paraevitar condensación
45 Nm
Warning
Never switch on power to the coil when
the coil is dismounted from the valve.
Otherwise the coil may be damaged and
there is risk of injuries and burns.
en-gb da de fr es
The gasket must
be exchanged,
if the valve is
dismantled
Pakningen
skal skiftes,
hvis ventilen
adskilles
Bei Zerlegung des
Ventils muß die
Dichtung ausgewechselt werden.
Changer le joint
chaque fois
que la vanne est
démontée
Es preciso
cambiar la junta
si se desmonta
la válvula