Danfoss AKS 3000 Data sheet

Data Sheet
Pressure transmitter Type AKS 3000
For A/C and refrigeration
AKS 3000 is a series of absolute transmitters with high-level signal conditioned current output, developed to meet demands in A/C and refrigeration applications.
AKS 3000 utilizes the proved piezoresistive measuring principle, which has been used for decades in Danfoss pressure transmitters.The pressure reference is a sealed gauge. This means that atmospheric pressure variations have no inuence on regulating accuracy. A must in accurate low pressure regulation.
All materials in contact with the refrigerant and materials for the housing are AISI 316L stainless steel. No soft gaskets, all environmental sealings are made through laser weldings only.
AKS 3000 has a 4 – 20 mA output, and is available with spade terminals for EN 175301-803 plug.
AI190386421543en-000501
Pressure transmitter, AKS 3000
Features
Designed to meet A/C and refrigeration application demands without compromising control accuracy concerning:
Tough environment
• Vibration
• Shock during operation and transport
• Humidity and ice formation
• Temperature variations
• Corrosive media like ammonia gases and salt mist
Convenient performance
• 4 – 20 mA signal
• 1% typical accuracy
• 0.5% typical linearity
• Prepared for high pressure refrigerants Bar code for tracing of calibration data
Convenient performance
• Compact design
• Max. working pressure 33 bar <P< 100 bar
• Digitally temperature compensation Optimized accuracy at -10 °C and 20 °C for suction line installations.
1
4 -18NPT, G 3⁄8 A, G1⁄2 Aor female 7⁄16-20 UNF ensures tight pressure connection
• All laser welded AISI 316L stainless steel enclosure
• No soft seals
• Enclosure: IP65
• For use in ATEX zone 2 explosive atmospheres
• UL approved
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 2
Pressure transmitter, AKS 3000
Applications
• Fan speed control
• High pressure control
• Compressor capacity control
• Evaporator pressure detection
• Oil pressure control
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 3
Type code
A1
EN 175301-803-A
pg 9
Ambient temperature 4 - 20 mA output
-40 – 85 °C
Electrical connection 4 - 20 mA output
Pin 1: + supply Pin 2: ÷ supply
Pin 3: Not used
Connected to transmitter housing
Pressure Connection
1
4
- 18 NPT
G
3
8 A ISO 228/1
G
1
2 A
7
16
- 20 UNF Female Weight [kg]
plug
cable
L [mm]16212016.5
0.15
0.20
Pressure transmitter, AKS 3000
Product specication
Thermal sensitivity
• AKS 3000 is calibrated to limit ambient temperature inuence on the regulating accuracy.
• Pressure transmitters to be used at low temperature conditions, e.g. in suction lines, are calibrated at -10 °C and 20 °C.
• In this way control accuracy is optimized in a temperature range of -30 °C – 40 °C.
• Pressure transmitters for general use, e.g. at normal room temperature, are calibrated at 20 °C and 60 °C.
• In this way control accuracy is optimized in a temperature range of 0 °C – 80 °C.
Electrical connection
Table 1: Electrical connection, Two-wire, 4 – 20 mA
Dimensions and weight
Figure 1: Dimensions
NOTE:
All dimensions in millimeters
Table 2: Dimensions and weight
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 4
Operating range
[bar] (e)
Max. working
pressure PB [bar]
Calibration at [°C]
Code no.
EN 175301-803 plug
G
3
8 A
G
1
2 A
1
4 - 18 NPT
7
16 - 20UNF Female
-1 – 6
33
-10 / 20
060G1040––
060G1321
-1 – 933–
060G1895
060G1051
060G1007
(1)
-1 – 12
33
060G1058
060G1896
060G1052
060G1323
-1 – 20
50
060G1049
060G1053
060G1010
0 – 18
50
20 / 60
––060G1068
060G1325
0 – 25
50
060G1041
060G1608
(1)
060G1080
060G1019
0 – 3060––060G1081
060G1327
0 – 40
100
060G1066––
060G1328
0 – 60
100
060G3631
060G1083
Features
Descriptions
Accuracy
±1% FS (typ.) / ±2% FS (max.)
Non-linearity
< ±0.5% FS
Hysteresis and repeatability
≤ ±0.1% FS
Thermal zero point shift
≤ ±0.2% FS/10K (typ.) ≤ ±0.4% FS/10K (max.)
Thermal sensitivity (span) shift
≤ ±0.2% FS/10K (typ.) ≤ ±0.4% FS/10K (max.)
Response time
< 4 ms
Max. operating pressure
See Table 3: Ordering
Features
Descriptions
Rated output signal
4 – 20 mA
Supply voltage, [UB] (polarity protected)
9 – 32 V DC
Supply voltage dependency
< 0.2% FS/10 V
Output limitation
22.4 mA (typ.)
Power-up time
< 50 ms
Max. load, [RL]
RL
UB 9V
0.02A
[Ω]
Sensor operating temperature range
Normal
-40 – 85 °C
ATEX Zone 2
-10 – 85 °C
Media temperature range
- 40 – 85 °C
Compensated temperature range
≤ 16 bar
LP: -30 – 40 °C HP: 0 – 80 °C
> 16 bar
Transport temperature range
-50 – 85 °C
EMC - Emmission
EN 61000-6-3
EMC - Immunity
Electrostatic discharge Air
8 kV
EN 61000-6-2
Contact
4 kV
EN 61000-6-2
RF
eld
10 V/m, 26 MHz – 1 GHz
EN 61000-6-2
conducted
3 Vrms, 150 kHz – 30 MHz
EN 61000-6-2
Transient burst
4 kV (CM), Clamp
EN 61000-6-2
surge
1 kV (CM,DM) at Rg = 42 Ω
EN 61000-6-2
Insulation resistance
> 100 MΩ at 500 V DC
Pressure transmitter, AKS 3000
Ordering
Table 3: Ordering
(1)
(1)
Calibrated as absolute pressure range:
Calibrated as absolute pressure range: 060G1007: 0 – 10 bar (abs)
060G1007: 0 – 10 bar (abs) 060G1608: 0 – 25 bar (abs)
060G1608: 0 – 25 bar (abs)
Ordering standard
Table 4: Performance
Table 5: Electrical specications
Table 6: Environmental conditions
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 5
Vibration stability
Sinusoidal
20 g, 25 Hz – 2 kHz
IEC 60068-2-6
Random
7,5 grms, 5 Hz – 1 kHz
IEC 60068-2-34, IEC 60068-2-36
Shock resistance
Shock
500 g / 1 ms
IEC 60068-2-27
Free fall
1 m
IEC 60068-2-32
Enclosure
IP65 (IEC 60529)
Zone 2 applications
EN60079-0; EN60079-15
Features
Description
AKS products can be used in end user applications employing the following ammable refrigerants: A3: R290, R600, R600a, R1270 A2L: R32, R444B, R452A/B, R454A/B/C, R455A, R1234zyef
IEC/EN 60335-2-89 (commercial refrigerating appliances) IEC/EN 60335-2-40 (electrical heat pumps, air-onditioners)
Features
Descriptions
Electrical connection
EN 175301-803 plug
Wetted parts, material
EN10088-1-1.4404 (AISI 316L)
Housing material
EN10088-1-1.4404 (AISI 316L)
Weight
0.15 kg
Refrigerants
DR3, DR55, DR7, HDR110, L40, R1234yf, R1234ze, R1270, R1290, R134a, R22, R227, R23, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R413A, R417A, R422A, R422D, R427A, R438A, R444B, R447A, R448A, R449A, R449B, R450A, R452A, R454B, R502, R507, R513A, R600, R600a, R717 (NH3), R744 (CO2), R1270
Pressure transmitter, AKS 3000
Explosive atmospheres
Table 7: Explosive atmospheres
The products for ATEX Zone 2 are applicable in refrigeration applications employing any ammable refrigerants classied as IIA – please, refer to AKS installation guide. In ATEX Zone 2 applications at low temperatures cable and
plug must be protected against impact.
Table 8: Flammable refrigerants
For other products not ATEX Zone 2 assessed, an ignition risk assessment has been conducted with reference to IEC/EN 60335-2-89 (commercial refrigerating appliances) and IEC/EN 60335-2-40 (electrical heat pumps, air­conditioners).
For countries where safety standards are not an indispensable part of the safety system, Danfoss recommends the installer to seek a third-party approval of the system containing ammable refrigerant. Note: Please, follow specic selection criteria stated in the data sheet for these particular refrigerants.
Mechanical characteristics
Table 9: Mechanical characteristics
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 6
File name
Document type
Document topic
Approval authority
UL E227388
Explosive - Safety Certicate
Hazardous Locations
UL
UL E31024
Electrical - Safety Certicate
UL
UL E311982
Electrical - Safety Certicate
UL
064G9615.06
EU Declaration
ATEX/EMCD/RoHS
Danfoss
060G9688.00
Manufacturers Declaration
Danfoss
0F18477.5123467890YTN
Pressure - Safety Certicate
CRN
TSSA
060R3160.00
Manufacturers Declaration
China RoHS
Danfoss
064R9402.00
Manufacturers Declaration
PED
Danfoss
E494625
Electrical - Safety Certicate
UL
1786330
Explosive - Safety Certicate
CSA
Pressure transmitter, AKS 3000
Certicates, declarations and approvals
The list contains all certicates, declarations, and approvals for this product type. Individual code number may have some or all of these approvals, and certain local approvals may not appear on the list.
Some approvals may change over time. You can check the most current status at danfoss.com or contact your local Danfoss representative if you have any questions.
Table 10: Certicates, declarations and approvals
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 7
Online support
Danfoss oers a wide range of support along with our products, including digital product information, software, mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related—no matter where you are in the world or what area of the cooling industry you work in. Get quick access to essential information like product specs, code numbers, technical documentation, certications, accessories, and more. Start browsing at store.danfoss.com.
Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to our ocial collection of data sheets, certicates and declarations, manuals and guides, 3D models and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specically designed to help engineers, installers, service technicians, and wholesalers better understand the products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support
Local Danfoss websites are the main sources for help and information about our company and products. Find product availability, get the latest regional news, or connect with a nearby expert—all in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | Climate Solutions | 2021.02 AI190386421543en-000501 | 8