Data sheet
Temperature sensor
AKS 12
Pt 1000 temperature sensor.
The sensor can be used for temperature logging
on monitoring in conjunction with EKC
controllers in the following areas:
• Refrigeration
• Air conditioning
• Heating
The sensor comes adjusted and complies with
the requirements to tolerance in EN 60751,
class B.
Features • Temperature range -40 – 100 °C
• The sensors are adjusted and comply with the
requirements to tolerance in EN 60751, class B
© Danfoss | DCS (im) | 2019.08
IC.PD.P30.X3.03 | 1
Technical data
Nominal resistance 1000 ohm at 0 °C
Measuring accuracy Class B
Temperature range -40 – 100 °C
Cable material PVC, 2 x 0.22 mm
Sensor tube 18/8 stainless steel
Time constant 15 seconds
Enclosure IP67
AMP-Plug (selected
sensors only)
AMP ital mod 2,
housing 280 358,
Crimp contact 280 708-2
R (Typ.)
[Ohm]
Temp.
[°C]
Temp.
[°F]
1117 30 86
1078 20 68
2
1039 10 50
1000 0 32
961 -10 14
922 -20 -4
882 -30 -22
Ordering
Cabel resistance @ 20 °C:
PVC 2 x 0.22 mm² (Resistance per conductor R1 = 78.2 Ohm/km)
The constant conductor resistance: R = 2 x R1
The total resistance in the sensor circuit is therefore: R + RTD
Typ e Cable Packing Qty. Code no.
1 084N0036
30 084N0035
30 084N0038
1 084N0046
30 084N0037
1 084N0045
AKS 12
1.5 m
3.5 m 30 084N0039
5.5 m
5.5 m with AMP-Plug
8.5 m 30 084N0041