These operating instructions can be used for all AKD 5000
Series frequency converters with software version 1.6x.
The software version number can be seen from parameter 624.
175ZA871.12
Safety
MG.50.R3.02 -
3
The voltage of the frequency converter
is dangerous whenever the equipment
is connected to mains. Incorrect
installation of the motor or the frequency converter
may cause damage to the equipment, serious
personal injury or death.
Consequently, the instructions in this manual,
as well as national and local rules and safety
regulations, must be complied with.
■Safety regulations
1. The frequency converter must be disconnected
from mains if repair work is to be carried out. Check
that the mains supply has been disconnected
and that the necessary time has passed before
removing motor and mains plugs.
2. The [STOP/RESET] key on the control panel of
the frequency converter does not disconnect
the equipment from mains and is thus n
be used as a safety switch.
3. Correct protective earthing of the equipment
must be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included
in the factory setting. If this function is desired,
set parameter 128 to data value ETR trip or
data value ETR warning.
N
ote: The function is initialised at 1.16 x rated
motor current and rated motor frequency. For
the North American market: The ETR functions
provide class 20 motor overload protection
in accordance with NEC.
6. Do n
7. Please note that the frequency converter has more
ot remove the plugs for the motor and main
supply while the frequency converter is connected
to mains. Check that the mains supply has been
disconnected and that the necessary time has
expired before removing motor and mains plugs.
voltage inputs than L1, L2 and L3, when loadsharing
(linking of DC intermediate circuit) and external 24 V
DC have been installed. Check that all voltage inputs
have been disconnected and that the necessary
time has passed before repair work is commenced.
ot to
AKD 5000
■Warning against unintended start
1. The motor can be brought to a stop by
means of digital commands, bus commands,
references or a local stop, while the frequency
converter is connected to mains.
If personal safety considerations make it necessary
to ensure that no unintended start occurs, t
stop functions are not sufficient.
2. While parameters are being changed, the
motor may start. Consequently, t
[STOP/RESET] must always be activated, following
which data can be modified.
3. A motor that has been stopped may start if faults
occur in the electronics of the frequency converter,
or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
he stop key
hese
4
MG.50.R3.02 -
AKD 5000
Warning:
It can be extremely dangerous to touch the electrical parts
even when the mains supply has been disconnected.
Also ensure that other voltage inputs are disconnected
from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been
removed before servicing the drive.
195NA300.10
Safety
MG.50.R3.02 -
5
AKD 5000
■Quick Setup
■Introduction to Quick Setup
This Quick Setup will guide you through EMC correct
installation of the frequency converter by connecting
power, motor and control wiring (fig. 1). Start/stop
ofmotoristobedonewiththeswitch.
Fig. 1
■1. Mechanical Installation
AKD 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free
air passage of 1
200-240 V must have 20 cm).
Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Place
the frequency converter on the wall. Tighten up all four screws.
All the below listed measurements are in mm
0 cm above and below the frequency converter (5016-5062 380-500 V and 5008-5027
NOTE: The terminals are detachable on AKD 5001-5006, 200-240 V and AKD 5001-5011, 380-500 V
Connect the mains supply to the mains terminals L1, L2, L3 of the frequency converter and to the earth
connection (fig. 5-8). Cable relief fitting is placed on the wall for Bookstyle units. Mount screened motor
cable to the motor terminals U, V, W, PE of the frequency converter. Make sure, the screen is connected
electrically to the drive.
Fig. 6
C
ompact IP 20 and IP 54
5001 - 5011 380 - 500 V
5001 - 5006 200 - 240 V
Fig. 7
C
ompact IP 20
5016 - 5062 380 - 500 V
5008 - 5027 200 - 240 V
Quick
Setup
MG.50.R3.02 -
7
■3. Electrical installation, control leads
Use a screw driver to remove the front cover
under the control panel.
NOTE: The terminals are detachable. Connect a
jumber between terminals 12 and 27 (Fig. 10)
Mount screened cable to external start/stop of
control terminals 12 and 18.
AKD 5000
Fig. 10
■4. Programming
The frequency converter is programmed over
the control panel.
Press the QUICK MENU button. The Quick Menu
appears in the display. You choose parameters by
means of arrow up and arrow down. Press the
CHANGE DATA button to change parameter value.
Data values are changed using the up and down
arrows. Press the left or right buttons to move the
cursor. Press OK to save your parameter setting.
Set the desired language in parameter 001. You
have six possibilities: English, German, French,
Danish, Spanish and Italian.
Set the motor parameters according to the motorplate:
Motor power
Motor voltage
Motor frequency
Motor current
Rated motor speed
Press the START button to start the motor. Set motor
speed in Parameter 003. Check if the direction of
rotations is as shown in the display. It can be changed
by swapping two phases of the motor cable.
Press the STOP button to stop the motor.
■AKD Lon card
Requirements:
AKD 2800 must have software version (par
624) 1.32 or higher
AKD 5000 must have software version (par
624) 1.52 or higher
8
Fig. 11
Select total or reduced Automatic Motor Adaption
(AMA) in Parameter 107. For further description of
AMA, see section Automatic Motor Adaption, AMA.
Press the START button to start the Automatic
Motor Adaption (AMA).
Press the DISPLAY/STATUS button to leave
the Quick Menu.
The AKD Lon card is RS485 based and must connect
to an RS485 Adap-Kool Lon network.
The card can be ordered as build-in with the AKD5000
and comes in an external box for the AKD2800.
MG.50.R3.02 -
AKD 5000
AKD Lon connections:
The Lon card has two connections.
AKD-Connections:
Lon card terminals1
(Red +24V)
(White or Yellow
A 6-pole connector (only 1-4 is used) that connects
to the AKD. Connections are as follows:
2
3
(Black Com)
(Green TX+, RX+)
TX-, RX-)
AKD terminals126939 or 2068
The 3-pole connector for the Lon Communication:
Lon card terminals123
Adap-Kool LonABShield
Connect the Adap-Kool Lon network to the removable
3-postion connector. Be careful to route the network
wires away from the AC power and motor wires.
Commissioning
Upon power up the lower red LED of the double LED’s,
next to the Lon connectors will initially be flashing red.
1. Set AKD address in parameter 500 in
the AKD (1 to 60)
2. Wait for about 1 min until the red LED goes
off. (card initialisation)
3. Press one of the service pin buttons
4. Wait for about 2 minutes (upload of
parameters to gateway)
5. Perform a "Net configuration" upload in AKM
and you should now find the AKD. Perform a
"AKC description" upload in AKM
6. Go to menu AKC -> Controllers in AKM and
youshouldfindtheAKD
4
Quick
Setup
MG.50.R3.02 -
9
AKD 5000
■Introduction
These Operating Instructions are a tool intended for persons who are to install, operate and program the
AKD 5000 Series.
When reading these Operating Instructions, you will come across different symbols that require special
attention.
The symbols used are the following:
Indicates a general warning
NB!:
Indicates something to be noted by the reader
Indicates a high-voltage warning
10
MG.50.R3.02 -
■Ordering form AKD 5000 Series - Typecode
AKD 5000
Introduction
MG.50.R3.02 -
11
AKD 5000
■General technical dat a
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-500 V units ................................................................ 3 x 380/400/415/440/460/500 V ±10%
Supply frequency ......................................................................................................................... 48/62 Hz +/- 1%
AKD 5001-5011, 380-500 V and AKD 5001-5006, 200-240 V ............................... ±2.0% of rated supply voltage
AKD 5016-5062, 380-500 V and AKD 5008-5027, 200-240 V ............................... ±1.5% of rated supply voltage
True Power factor (λ) ...................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos φ) .............................................................................................. near unity (>0.98)
No. of switchings on supply input L1, L2, L3 .......................................................................... approx. 1 time/min.
See the section on special conditions in the Design Guide
AKD output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency .................................................................................................................. 0-132 Hz, 0-1000 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-500 V units ............................................................... 380/400/415/440/460/480/500 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times .................................................................................................................................... 0.05-3600 sec.
Torque characteristics:
Starting torque, AKD 5001-5027, 200-240 V and AKD 5001-5062, 380-500 V ............................. 160% for 1 min.
Starting torque ............................................................................................................................ 180% for 0.5 sec.
Overload torque, AKD 5001-5027, 200-240 V and AKD 5001-5062, 380-500 V .......................................... 160%
Arresting torque at 0 rpm (closed loop) ......................................................................................................... 100%
The torque characteristics given are for the frequency converter at the high overload torque level
(160%). At the normal overload torque (110%), the values are lower.
Control card, digital inputs:
Number of programmable digital inputs ................................................................................................................ 8
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
........................................................................................................................................ 2 k
i
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV).
In addition, the digital inputs can be isolated from the other terminals on t
he control card by
connecting an external 24 V DC supply and opening switch 4.
Control card, analogue inputs:
No. of programmable analogue voltage inputs/thermistor inputs .......................................................................... 2
Voltage level ........................................................................................................................ 0 - ±10 V DC (scalable)
Input resistance, R
...................................................................................................................................... 10 k
i
No. of programmable analogue current inputs ..................................................................................................... 1
Current range .................................................................................................................... 0/4 - ±20 mA (scalable)
Resolution .......................................................................................................................................... 10 bit + sign
12
MG.50.R3.02 -
AKD 5000
Accuracy on input .......................................................................................................... Max. error 1% of full scale
Scanning time per input ............................................................................................................................. 3 msec.
Max. frequency on terminal 17 ...................................................................................................................... 5 kHz
Max. frequency on terminals 29, 32, 33 ...................................................................... 20 kHz (PNP open collector)
Max. frequency on terminals 29, 32, 33 ..................................................................................... 65 kHz (Push-pull)
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
Scanning time per input ............................................................................................................................. 3 msec.
Resolution .......................................................................................................................................... 10 bit + sign
Accuracy (100-1 kHz), terminals 17, 29, 33 ............................................................... Max. error: 0.5% of full scale
Accuracy (1-65 kHz), terminals 29, 33 ....................................................................... Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse/encoder inputs are galvanically isolated from the supply voltage
(PELV). In addition, pulse and encoder inputs can be isolated from the other terminals on the control
card by connecting an external 24 V DC supply and opening switch 4.
See section on Control cables.
........................................................................................................................................ 2 k
i
Control card, digital/pulse and analogue outputs:
No. of programmable digital and analogue outputs .............................................................................................. 2
Voltage level at digital/pulse output ...................................................................................................... 0 - 24 V DC
Minimum load to ground (terminal 39) at digital/pulse output ....................................................................... 600
Frequency ranges (digital output used as pulse output) ............................................................................ 0-32 kHz
Current range at analogue output ........................................................................................................ 0/4 - 20 mA
Maximum load to ground (terminal 39) at analogue output ........................................................................... 500
Accuracy of analogue output ..................................................................................... Max. error: 1.5% of full scale
Resolution on analogue output. ....................................................................................................................... 8 bit
Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the
supply voltage (PELV), as well as other inputs and outputs.
Voltage range ....................................................................................... 24 V DC ±15% (max. 37 V DC for 10 sec.)
Max. voltage ripple ..................................................................................................................................... 2 V DC
Power consumption .............................................................................. 15 W - 50 W (50 W for start-up, 20 msec.)
Min. pre-fuse ............................................................................................................................................... 6 Amp
Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.
Cable lengths, cross-sections and connectors:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable AKD 5011 380-500 V ................................................................... 100 m
Max. brake cable length, screened cable ........................................................................................................ 20 m
Max. loadsharing cable length, screened cable ..................................... 25 m from frequency converter to DC bar.
Max. cable cross-section for motor, brake and loadsharing, see next section
Max. cable cross-section for 24 V external DC supply .............................................................. 4.0 mm
Max. cross-section for control cables ....................................................................................... 1.5 mm
Max. cross-section for serial communication ............................................................................ 1.5 mm
If UL/cUL is to be complied with, cable with temperature class 60/75°C must be used
(AKD 5001-5062 380-500 V and AKD 5001-5027 200-240 V).
2
/10 AWG
2
/16 AWG
2
/16 AWG
Accuracy of display readout (parameters 009-012):
Motor current [6] 0-140% load ............................................................... Max. error: ±2.0% of rated output current
Torque % [7], -100 - 140% load ...................................................................... Max. error: ±5% of rated motor size
Output [8], power HP [9], 0-90% load ................................................................... Max. error: ±5% of rated output
Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
..................................................................................................... >1500 rpm: max. error of 0.1% of actual speed
Torque control accuracy (open loop) ................................................ 0- 150 rpm: max. error ±20% of rated torque
................................................................................................... 150-1500 rpm: max. error ±10% of rated torque
........................................................................................................ >1500 rpm: max. error ±20% of rated torque
Torque control accuracy (speed feedback) ............................................................. Max. error ±5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
14
MG.50.R3.02 -
AKD 5000
Externals:
Enclosure ............................................................................................................................................. IP 20, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ................................................................................ 93 % (IEC 68-2-3) for storage/transport
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Ambient temperature IP 20 (high overload torque 160%) ....................... Max. 45°C (24-hour average max. 40°C)
Ambient temperature IP 20 (normal overload torque 110%) .................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (high overload torque 160%) ....................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (normal overload torque 110%) .................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 20/54 AKD 5011 500 V .................................... Max. 40°C (24-hour average max. 35°C)
Derating for high ambient temperature, see the Design Guide
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ..................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
Derating for high air altitude, see the Design Guide
EMC standards applied, Emission .............................................................. EN 50081-1/2, EN 61800-3, EN 55011
EMC standards applied, Immunity .......................... EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, VDE 0160/1990.12
See section on special conditions in the Design Guide.
AKD 5000 Series protection:
• Electronic motor thermal protection against overload.
• Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature
reaches 90°C for IP 20. For IP 54, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C.
• The frequency converter is protected against short-circuiting on motor terminals U, V, W.
• The frequency converter is protected against earth fault on motor terminals U, V, W.
• Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if
the intermediate circuit voltage gets too high or too low.
• If a motor phase is missing, the frequency converter cuts out.
• If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
• If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.
data
Technical
MG.50.R3.02 -
15
■Electrical data
■Compact,Mainssupply3x200-240V
AKD 5000
According to international requirementsAAAAKKKKDDDDttttyyyyppppeeee555500000000111155550000000022225
55500000000333
Output currentIN[A] 3.75.47.810.612.515.2
I
(60 s) [A] 5.98.612.5172024.3
MAX
Output (240 V)SN[kVA] 1.52.23.24.45.26.3
Ty pi ca l s ha f t out pu tPN[kW] 0.751.11.52.23.03.7
Ty pi ca l s ha f t out pu tPN[HP]11.52345
Max. cable cross-section to motor,
brake and loadsharing [mm2]/[AWG]2)
Rated input current(200 V)I
Max. cable
cross-section power [mm2]/[AWG]2)
L,N
4/104/104/104/104/104/10
[A] 3.44.87.19.511.514.5
4/104/104/104/104/104/10
Max. pre-fuses[-]/UL1)[A] 16/1016/1016/1525/2025/2535/30
Efficiency
Weight IP 20 EB
Compact
3)
0.950.950.950.950.950.95
[kg] 888101010
Weight IP 54 Compact[kg] 11.511.511.513.513.513.5
Power loss at
max. load.
Enclosure
[W] 587695126172194
IP 20/
IP54
IP 20/
IP54
IP 20/
IP54
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
35
55500000000444
IP 20/
IP54
45
55500000000555
IP 20/
IP54
55
55500000000666
IP 20/
IP54
6
16
MG.50.R3.02 -
■Compact,Mainssupply3x200-240V
AKD 5000
According to international requirementsAAAAKKKKDDDDttttyyyyppppeeee5
Output (240 V)SN[kVA]1013192530
Ty pi ca l s ha f t out pu tPN[kW]5.57.5111518.5
Ty pi ca l s ha f t out pu tPN[HP]7.510152025
Max. cable cross-section to motor,IP 5416/616/635/235/250/0
brake and loadsharing [mm
2
Min. cable cross-section to motor,
brake and loadsharing
4)
[mm2/AWG]
Rated input current(200 V) I
2)5)
/AWG]
L,N
IP 2016/635/235/235/250/0
2)
10/810/810/810/816/6
[A]3246617388
Max. cable cross-section,IP 5416/616/635/235/250/0
power [mm
0.950.950.950.950.95
Weight IP 20 EB[kg]2125273436
Weight IP 54[kg]3840535556
Power loss at max. load.
-highoverloadtorque
(160 %)
-normaloverload
torque (110 %)
Enclosure
[W]
[W]
340426626833994
42654578310421243
IP 20/
IP 54
IP 20/
IP 54
15
55500001111666
IP 20/
IP 54
65
55500002222222
IP 20/
IP 54
25
55500002222777
IP 20/
IP 54
7
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20.
Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
6. If UL/cUL is to be complied with, Ferraz Shawmut type Y85443, Danfoss ordering no. 612Z1182 must be used.
MG.50.R3.02 -
data
Technical
17
■Compact,Mainssupply3x380-500V
AKD 5000
According to international requirementsAAAAKKKKDDDDttttyyyyppppeeee555500000000111155550000000022225
SN[kVA] (441-500 V)18.824.229.4
Typical shaft outputPN[kW]111518.5
Typical shaft outputPN[HP]152025
Max. cable cross-section to motor,IP 5416/616/616/6
brake and loadsharing [mm2]/[AWG]
2) 4)
IP 2016/616/635/2
Min. cable cross-section to motor,
brake and loadsharing [mm2]/[AWG]10/810/810/8
Rated input currentI
[A] (380 V)3237.544
L,N
I
[A] (460 V)27.63441
L,N
Max. cable cross-section,IP 5416/616/616/6
power [mm2]/[AWG]IP 2016/616/635/2
Max. pre-fuses[-]/UL1)[A]63/4063/5063/60
Pre-fuse SMPS[-]/UL5)[A]4.0/4.04.0/4.04.0/4.0
Efficiency0.960.960.96
Weight IP 20 EB[kg]212227
Weight IP 54[kg]414142
Power loss at max. load.
-highoverloadtorque
(160 %)
- normal overload
torque (110 %)
Enclosure
[W]
[W]
419559655
559655768
IP
20/IP54IP20/IP54IP20/IP54
25
55500002222777
7
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20.
Always comply with national and local regulations on min. cable cross-section.
5. If UL/cUL is to be complied with, Ferraz shawmut type FA Y85443, Danfoss ordering no. 612Z1182 must be used.
20
MG.50.R3.02 -
Compact, Mains supply 3 x 380 - 500 V
AKD 5000
According to international requirementsAAAAKKKKDDDDttttyyyyppppeeee5
Weight IP 20 EB[kg]28414243
Weight IP 54[kg]54565660
Power loss at max. load.
- high overload torque
(160 %)
-normaloverload
torque (110 %)
Enclosure
[W]
[W]
768106512751571
1065127515711851
IP
20/IP54IP20/IP54IP20/IP54IP20/IP54
25
55500005555222
4.0/
4.0
25
55500006666222
55
75 @
500 V
75
100 @
500 V
45
55 @
500 V
60
75 @
500 V
4.0/4.0
2
data
Technical
1. For type of fuse see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20.
Always comply with national and local regulations on min. cable cross-section.
5. Aluminium cables with cross-section above 35 mm
2
must be connected by use of a AI-Cu connector.
6. If UL/cUL is to be complied with, Ferraz shawmut type FA Y85443, Danfoss ordering no. 612Z1182 must be used.
MG.50.R3.02 -
21
AKD 5000
■Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
AKDBussmannSIBALittel fuseFerraz-Shawmut
5001KTN-R105017906-010KLN-R10ATM-R10 or A2K-10R
5002KTN-R105017906-010KLN-R10ATM-R10 or A2K-10R
5003KTN-R255017906-016KLN-R15ATM-R15 or A2K-15R
5004KTN-R205017906-020KLN-R20ATM-R20 or A2K-20R
5005KTN-R255017906-025KLN-R25ATM-R25 or A2K-25R
5006KTN-R305012406-032KLN-R30ATM-R30 or A2K-30R
5008KTN-R505014006-050KLN-R50A2K-50R
5011KTN-R605014006-063KLN-R60A2K-60R
5016KTN-R855014006-080KLN-R80A2K-80R
5022KTN-R1252028220-125KLN-R125A2K-125R
5027KTN-R1252028220-125KLN-R125A2K-125R
380-500 V
BussmannSIBALittel fuseFerraz-Shawmut
5001KTS-R65017906-006KLS-R6ATM-R6 or A6K-6R
5002KTS-R65017906-006KLS-R6ATM-R6 or A6K-6R
5003KTS-R105017906-010KLS-R10ATM-R10 or A6K-10R
5004KTS-R105017906-010KLS-R10ATM-R10 or A6K-10R
5005KTS-R155017906-016KLS-R16ATM-R16 or A6K-16R
5006KTS-R205017906-020KLS-R20ATM-R20 or A6K-20R
5008KTS-R255017906-025KLS-R25ATM-R25 or A6K-25R
5011KTS-R305012406-032KLS-R30A6K-30R
5016KTS-R405012406-040KLS-R40A6K-40R
5022KTS-R505014006-050KLS-R50A6K-50R
5027KTS-R605014006-063KLS-R60A6K-60R
5032KTS-R802028220-100KLS-R80A6K-180R
5042KTS-R1002028220-125KLS-R100A6K-100R
5052KTS-R1252028220-125KLS-R125A6K-125R
5062KTS-R1502028220-160KLS-R150A6K-150R
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
(symmetrical), 500 V maximum.
rms
22
MG.50.R3.02 -
■Mechanical dimensions
All the below listed measurements are in mm.
Compact IP 20
5001 - 5003 200 - 240 V
5001 - 5005 380 - 500 V
5004 - 5006 200 - 240 V
5006 - 5011 380 - 500 V
5008 200 - 240 V
5016 - 5022 380 - 500 V
5011 - 5016 200 - 240 V
5027 - 5032 380 - 500 V
5022 - 5027 200 - 240 V
5042 - 5062 380 - 500 V
Compact IP 54
5001 - 5003 200 - 240 V
5001 - 5005 380 - 500 V
5004 - 5006 200 - 240 V
5006 - 5011 380 - 500 V
5008 - 5011 200 - 240 V
5016 - 5027 380 - 500 V
5016 - 5027 200 - 240 V
5032 - 5062 380 - 500 V
AKD 5000
ABCDabab/beType
395220160384200100C
395220200384200100C
560242260540200200D
700242260680200200D
800308296780270200D
46028219585260258100F
53028219585330258100F
81035028070560326200F
94040028070690375200F
ab: Minimum space above enclosure
be: Minimum space below enclosure
1: Only above enclosure (ab) IP 00 when built in a Rittal cabinet.
■Mechanical dimensions, cont.
Type C, IP20Type D, IP20
data
Technical
MG.50.R3.02 -
23
Typ e F, I P54
AKD 5000
24
MG.50.R3.02 -
■Mechanical installation
AKD 5000
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The frequency converter must be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the minimum distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be
ensured that the ambient temperature does not rise
above the max. temperature stated for the frequency
converter and that the 24-hour average temperature is
not exceeded . The max. temperature and 24-hour
average can be seen from the General Technical Data.
If the ambient temperature is in the range of 45°C-55°
C, derating of the frequency converter will become
relevant, see Derating for ambient temperature.
The service life of the frequency converter will
be reduced if derating for ambient temperature
is not taken into account.
Installation on a plane, vertical surface (no spacers)
Installation on a plane, vertical surface (no spacers)
AKD 5032-5052, 200-240 V225Installation on a plane, vertical surface (no spacers)
26
MG.50.R3.02 -
AKD 5000
■Electrical installation
The voltage on the frequency converter is
dangerous when the unit is connected to
mains. Incorrect installation of the motor or
the frequency converter may lead to material damage
or serious injury or it may be fatal. Consequently, the
instructions in this manual as well as national and local
rules and safety regulations must be complied with.
Touching the electrical parts may be fatal, even after
the mains supply has been disconnected.
Using AKD 5001-5006, 200-240 V and 380-500
V: wait at least 4 minutes.
Using AKD 5008-5052, 200-240 V: wait
at least 15 minutes.
Using AKD 5008-5500, 380-500 V: wait
at least 15 minutes.
NB!:
It is the user’s or certified electrician’s
responsibility to ensure correct earthing and
protection in accordance with applicable
national and local norms and standards.
■Electrical installation, power cables
Compact IP 20
AKD 5001-5006, 200-240 V
AKD 5001-5011, 380-500 V
AKD 5001-5011, 550-600
MG.50.R3.02 -
V
Installation
27
AKD 5000
Compact IP 54
AKD 5001-5006, 200-240 V
AKD 5001-5011, 380-500 V
28
MG.50.R3.02 -
AKD 5000
Compact IP 20 / IP 54
AKD 5001-5006 200-240 V
AKD 5001-5011 380-500 V
Compact IP 20
AKD 5008-5027 200-240 V
AKD 5016-5062 380-500 V
MG.50.R3.02 -
Installation
29
Loading...
+ 94 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.