MG.28.J1.62 - VLT is a registered Danfoss trademark
3
■Danish
AKD 2800 Quick Setup
■Generel advarsel
MeddenneQuickSetupkandui5trinforetageen
hurtig EMC rigtig installering af frekvens-omformeren.
Betjeningsvejledningen, der også er vedlagt,
viser andre installationseksempler og beskriver
alle funktioner i detaljer.
Læs s ikkerhedsvejledning på næste side
før du begynder montagen.
■Mekanisk montage
AKD 2800 frekvensomformere tillader side om
side montering på væg. Den nødvendige køling
kræver, at luften har 10 cm fri passage over
og under frekvensomformeren.
Bor huller efter de angivne mål som angivet i Mekaniskemål. Bemærk forskellen i apparatspændinger ne.
Efterspænd alle fire skruer.
Monter afkoblingspladen til p owerledningerne
og jordskruen (klemme 95).
■Elmontage, styreledninger
Fjern frontdækslet under betje ningspanelet. Sæt
en lus mellem klemme 12 og 27.
■Programmering
Foretag programmeringen på betjeningspanelet.
Tryk [QUICK MENU] for at komme ind i quick menue n.
Her kan du vælge parameter ved hjælp af [+]
og [-]. Ved at trykke [CHANGE DATA] kan du
ændre parameterværdi.
Ændringer programmeres med [+] og [-].
En ændret parameterindstilling afsluttes m ed
[CHANGE DATA].
En ændring af en parameterværdi gemmes
automatisk efter netafbrydelse.
Hvis displayet viser tre prikker til højre betyder det,
at parameterværdien har flere end tre cifre.
For at se værdien skal [CHANGE DATA] aktiveres.
Tryk på [QUICK MENU]:
Indstil motorparametrene, som står på
motorens typeskilt:
Tilslut nettet til frekvensomformerens netklemmer 91,
92, 93 samt jordforbindelsen til klemme 95.
Monter skærmet kabel fra motor til frekvensomformerens motorklemme r U , V, W. Skærmen
slutter i skærmtilslutning.
4
Aktivér AMT:
Automatisk motortilpasn.parameter 107
Indstil referenceområde.
Min. reference, Ref
MIN
Max. reference, Ref
Indstil rampetider
MG.28.J1.62 - VLT is a registered Danfoss trademark
MAX
parameter 204
parameter 205
AKD 2800 Quick Setup
Rampe op tid [s]parameter 207
Rampe ned tid [s]parameter 208
I parameter 002 Lokal/fjernbetjent kan betjeningen
af frekvensomformeren vælges til Fjernbetjent
[0], dvs. via styreklemmerne eller Lokal [1],
dvs. via betjeningsenheden.
Indstil betjeningssted til Lokal [1].
Lokal-/fjernbetjent = Lokal [1] Par. 002
Indstil motorens hastighed ved at stille
på Lokal reference.
Lokal reference Parameter 003
■Motorstart
Tryk [Start] for at starte motoren.
Indstil m otorens hastighed ved at stille på
parameter 003 Lokal reference.
Check om motorakslens omløbsretning drejer med
uret. Hvis ikke, byt to vilkårlige faser på motorkablet.
Tryk [STOP/RESET] for at stoppe motoren.
Tryk på [QUICK MENU] for at komme tilbage
til display-mode.
[QUICK MENU] + [+] tasterne skal trykkes samtidig
for at give ad g ang t il samtlige parametre.
skal sikres imod overbelastning ifølge gældende
lokale og nationale bestemmelser.
4. Lækstrømmen til jord er højere end 3,5 mA.
5. Beskyttelse mod overbelastning af motorer
er ikke indeholdt i fabriksindstillingen. Hvis
funktionen ønskes, indstilles parameter 128
Termisk motorbeskyttelse på dataværdi ETR
Trip eller ETR Advarsel.
6. Kontrollér at netforsyningen er afbrudt inden
du fjerner motor- og netstikkene.
Danish
■Advarsel mod uønsket start
Motoren kan bringes til stop med digital
kommandoer, b uskommandoer, referencer
eller lokalt stop, mens frekvensomformeren
er tilsluttet netforsyning. Hvis personsikkerhed
kræver, at der ikke må forekomme utilsigtet start,
vil disse stop ikke være tilstrækkelige.
Under programmering af parametre kan der
forekomme motorstart. Aktiver derfor altid stoptasten
[STOP/RESET], hvorefter data kan ændres.
En stoppet motor kan starte, hvis der opstår fejl
i frekvensomformerens elektronik, eller hvis en
midlertidig overbelastning, en fejl i forsynings nettet
eller en fejl i motortilslutningen ophører.
■Sikkerhedsvejledning
Frekvensomformerens spænding er
livsfarlig, når den er til sluttet netforsyningen.
Ukorrekt montering af motoren eller
frekvensomformeren kan forårsage beskadigelse af
materiel, alvorlig personskade eller død.
Overhold derfor anvisningerne i denne Quick
Setup samt lokale og nationale reglementer
og sikkerhedsbestemmelser.
Det kan være forbundet med livs fare at berøre
de elektriske dele, også efter at netforsyningen
er koblet fra: vent mindst 4 min.
1. Netforsyningen til frekvensomformeren skal være
koblet fra i forbindelse med reparationsarbejde.
2. Tasten [STOP/RESET] på frekvens-omformerens
betjeningspanel afbryder ikke netfor-syningen og
må derfor ikke benyttes som sikk erhedsafbryder.
3. Apparatet skal forbindes korrekt til jord, brugeren
skal sikres imod forsyningsspænding, og motoren
MG.28.J1.62 - VLT is a registered Danfoss trademark
5
AKD 2800 Quick Setup
AKD 2803–2815 200–240 V
AKD 2805–2815 380–480 V
AKD 2822 200–240 V
AKD 2840 200–240 V
AKD 2855–2875 380–480 V
AKD 2822–2840 380–480 V
AKD 2880–2882 380–480 V
6
MG.28.J1.62 - VLT is a registered Danfoss trademark
■English
AKD 2800 Quick Setup
■General warning
Using this Quick Setup, you can carry out quick and
EMC-correct installation of the frequency converter
in five steps. The Operating Instructions, which are
also enclosed, give other examples of installation
and describe all functions in detail.
Read the safety instructions on the next
page before installing the unit.
■Mechanical Installation
AKD 2800 frequency converters allow side-by-side
installation. Because of the need for cooling, there
must be 10 cm free air passage above and below
the frequency converter. Drill holes in accordance
with the measurements given in section Mechanicaldimensions. Retighten all four screws.
■Electrical Installation, control cables
Remove the front cover underneath the control panel.
Place a jumper between terminals 12 and 27.
■Programming
Carry out programming on the control panel. Press the
[QUICK MENU] key to enter the Quick menu. In this
menu, parameters can be selected by means of the [+]
and [-] keys. The parameter values can be changed by
pressing [CHANGE DATA]. Changes are programmed
using the [+] and [-] keys. Finish the change of a
parameter setting by pressing [CHANGE DATA]. A
change of parameter v alues is saved automatically after
a mains failure. If the display shows three dots at the
right, the parameter value has more than three digits.
In order to see the value, activate [CHANGE DATA].
Press [QUICK MENU]: Set the motor parameters
that are on the nameplate of the motor:
Motor power [kW]parameter 102
Motor voltage [V]parameter 103
Motor frequency [Hz]parameter 104
Motor current [A]parameter 105
Rated motor speedparameter 106
English
Fit the dec oupling plate to the power cables and
the earth screw (terminal 95).
■Electrical Installation, power
Please note that the power terminals can be removed.
Connect mains to the mains terminals of the frequency
converter, i.e. 91, 92, 93 and the earth connection to
terminal 95. Fit a screened/armoured cable from the
motor to the motor terminals of the frequency converter,
i.e. U, V, W. The screen ends in a screen connector.
MG.28.J1.62 - VLT is a registered Danfoss trademark
Activate AMT:
Automatic motor tuningparameter 107
Set reference range
Min. reference, Ref
Max. reference, Ref
MIN
MAX
parameter 204
parameter 205
Ramp-up time [s]parameter 207
Ramp-down time [s]parameter 208
In parameter 002 Local/remote control, the frequency
converter mode can be selected as Remote
7
AKD 2800 Quick Setup
operation [0], i.e. via the control terminals, or
Local [1], i.e. via the control unit.
Set the control location to Local [1].
Local/remote operation = Lo cal [1] Par. 002
Set the motor speed by adjusting the
Local reference
Local reference Parameter 003
■Safety regulations
The voltage of the frequency converter
can be fatal whenever it is connected to
mains. Incorrect installation of the motor or
the frequency converter may lead to damage to the
equipment, serious personal injury or death.
Consequently, the provisions of this Quick Setup,
as well as national and local rules and safety
regulations, must be complied with.
Touching the electrical parts may be fatal, e ven
after the equipment has been disconnected from
mains: wait at least 4 min.
1. The mains supply to the frequency converter must
be disconnected if repair work is to be carried out.
2. The [STOP/RESET] key on the control panel of the
frequency converter does not disconnect the mains
supply and is thus not to b e used as a safety switch.
3. Correct protective earthing of the unit must be
established, the user must be protected against
supply voltage, and the motor must be protected
against overload in accordance with applicable
national and local regulations.
4. The earth leakage current is higher than 3.5 mA.
5. Protection against motor overload is not included
in the factory setting. If this function is required,
set parameter 128 Motor thermal protection to
data value ETR Trip or ETR Warning.
6. Check that the mains supply has been disconnected
before removing the motor and mains plugs.
■Motor start
Press [Start] to start the motor. Set the mo tor speed
by adjusting parameter 003 Local reference.
Check whether the direction of rotation of the motor
shaft is clockwise. If not, exchange any two phases
on the motor cable. Press [STOP/RESET] to stop the
motor. Press [QUICK MENU] to return to display mode.
[QUICK MENU] + [+] keys must be pressed
simultaneously to give access to all parameters.
■Warning against unintended start
The motor can be b rought to a stop
by means of digital commands, bus
commands, references or local stop,
while the frequency converter is connected to
mains. If personal safety considerations make
it necessary to ensure that no unintended start
occurs, these stops are not sufficient.
While parameters are being programmed, the
motor may start. Consequently, the stop key
[STOP/RESET] must always be activated, following
which data can be modified.
A motor that has been stopped may start if fault s
occur in the electronics of the frequency converter, or
if a tempo rary ov erload, a fault in the supply mains
or a fault in the motor connection ceases.
8
MG.28.J1.62 - VLT is a registered Danfoss trademark
AKD 2800 Quick Setup
AKD 2803–2815 200–240 V
AKD 2805–2815 380–480 V
AKD 2822 200–240 V
AKD 2840 200–240 V
AKD 2855–2875 380–480 V
English
AKD 2822–2840 380–480 V
AKD 2880–2882 380–480 V
MG.28.J1.62 - VLT is a registered Danfoss trademark
9
■German
AKD 2800 Quick Setup
■Allgemeine Warnung
Die vorliegende Kurzanleitung zur Schnellinbetriebnahme ermöglicht es dem Anwender, in fünf Schritten
eine schnelle, EMV-gemäße Installation des Frequenzumrichters vorzunehmen. Die Betriebsanleitung ebenfalls als Anlage beigefügt - enthält weitere Installationsbeispiele und beschreibt alle Funktionen im Detail.
Vor Beginn der Montage arbeiten
unbedingt die Sicherheitshinweise auf
nächster Seite lesen!
Motor und Motorklemmen U, V und W des
Frequenzumrichters durch ein abgeschirmtes Kabel
verbinden. Die Abschirmung endet im Schirmanschluß.
■Elektrische Montage; Steuerleitungen
Frontabdeckung unter dem Bedienfeld entfernen. Eine
Drahtbrücke zwischen Klemme 12 und 27 setzen.
■Programmierung
Am Bedienfeld die Programmierung vornehmen.
■Mechanische Montage
Frequenzumrichter der Serie AKD 2800 können seitlich
nebeneinander angebracht werden. Wandmontage ist
möglich. Um ausreichend Kühlung zu ge währleisten,
ist ein Freiraum von mindestens 10 cm jeweils über und
unter dem Gerät erforderlich und sicherzustellen.
Die notwendigen Bohrungen gemäß den in
Sektion Mechanische Abmessungen angegebenen
Maßen ausführen. Beachten Sie bitte die
unterschiedlichen Gerätespannungen.
Alle vier Schrauben nachziehen.
Abschaltplatte für die Stromleitungen und
Erdungsschraube (Klemme 95) montieren.
[QUICK MENU] drücken, um in das Schnellkonfigurationsmenü zu gelangen.
Die Parameter können mit Hilfe von [+] und [-] gewählt
werden. Durch Betätigen von [CHANGE DATA] kann
der jeweilige Parameterwert geändert werden.
Änderungen werden mit [+] und [-] programmiert.
Die Änderung einer Parametereinstellung jewei
mit [CHANGE DATA] beenden.
Änderungen von Parameterwerten werden nach
einem N etzausfall automatisch gespeichert.
Wenn rechts im Display drei Punkte erscheinen,
bedeutet dies, daß der Parameterwert mehr als
dreistellig ist. Um den Wert anzusehen, m
[CHANGE DATA] betätigt werden.
[QUICK MENU] drücken:
ls
uß
■Elektrische Montage; Leistung
Beachten Sie, d aß die Stromklemmen abnehmbar sind.
Netzverbindung zu den Netzklemmen 91, 92
und 9’3 des Frequenzumrichters sowie Erdung
zu Klemme 95 herstellen.
10
MG.28.J1.62 - VLT is a registered Danfoss trademark
Motorparameter gemäß den Typenschilddaten einstellen
In Parameter 002 Ort-/Fernsteuerung kann zur
Bedienung des Frequenzumrichters Fern [0], d.h.
AKD 2800 Quick Setup
über die Steuerklemmen, oder Ort [1], d.h. über
die Bedieneinheit, gewählt werden.
Ortsteuerung auf Ort [1] einstellen
Ortsteuerung = Ort [1] Par. 002
Motordrehzahl durch Einstellen von
Sollwert einstellen
Ort Sollwert Parame te r 003
■Motorstart
[START] betätigen, um den Motor anzulassen.
Motordrehzahl durch Einstellen von Parameter
003 Ort Sollwert einstellen.
Prüfen Sie, ob der Drehsinn der Motorwelle
Rechtslauf ist. Falls nicht, einfach zwei beliebige
Motorkabelphasen vertauschen.
Zum Anhalten des Motors [STOP/RESET] drücken.
Um in den Displaymodus zurückzugelangen,
[QUICK MENU] drücken.
Die Tasten [QUICK MENU] + [+] gleichzeitig drücken,
um Zugang zu sämtlichen Parametern zu erhalten.
Ort
■Sicherheitshinweise
Der Frequenzumrichter steht bei
Netzanschluß unter lebensgefährlicher
Spannung. Durch unsachgemäße
Installation des Motors oder des F reque nzumrichters
können ein Ausfall des Gerätes, schwere
Personenschäden oder sogar tödliche Verletzungen
verursacht werden.
Befolgen Sie daher stets die Anweisungen in
dieser Kurzanleitung sowie die jeweils gültigen
nationalen bzw. internationalen Vorschriften und
Sicherheitsbestimmungen.
Das Berühren spannungeführender Teile - auch nach
der Trennung vom Netz - kann lebensgefährlich
sein. M indestens 4 Minuten warten!
1. Bei Reparaturarbeiten muß die Netzversorgung
des Frequenzumrichters abgeschaltet s ein.
2. Die Taste [STOP/RESET] auf dem Bedienfeld
des Frequenzumrichters unterbricht die
Netzversorgung nicht und darf deshalb nicht a ls
Sicherheitsabschaltung benutzt werden.
3. Es ist dafür Sorge zu tragen, daß gemäß
den örtlichen und nationalen Vorschriften eine
ordnungsgemäße Erdung des Gerätes erfolgt, der
Anwender gegen Leitungsspannung geschü tzt und
der Motor gegen Überlastung abgesichert ist.
4. Der Ableitstrom gegen Erde ist höher als 3,4 mA.
5. Ein Überlastungsschutz des Motors ist in
der Werkseinstellung nicht enthalten. Wenn
diese Funktion gewüncht wird, Parameter 128
Thermischer Motorschutz auf den D atenwe rt ETR
Abschaltung oder ETR Warnung einstellen.
6. Vor einem Entfernen der Motor- und Netzstecker
ist sicherzustellen, daß die Netzversorgung
unterbrochen ist.
German
MG.28.J1.62 - VLT is a registered Danfoss trademark
11
■Warnung vor unbeabsichtigtem Anlaufen
Der Motor kann mit einem digitalen Befe hl,
einem Busbefehl, einem Sollwert oder Ort
Stopp angehalten werden, obwohl der
Frequenzumrichter weiter unter Netzspannung steht.
Ist ein unbeabsichtigtes Anlaufen des Motors gemäß
den Bestimmungen zur Pers onensicherheit unzulässig,
so sind die o.g. Stoppfunktionen nicht ausreichend.
Während der Programmierung von Parametern
kann der M otor ohne Vorwarnung anlauf en. Daher
immer die Stopptaste [STOP/RESET ] betätigen,
bevor Datenwerte geändert werden.
Ein angehaltener Motor kann wieder anlaufen,
sofern die Elektronik des Frequenzumrichters defekt
ist, oder falls eine vorübergehende Belastung, ein
Fehler in der Versorgungsspannung oder ein Fehler
am Motoranschluß beseitigt wurde.
AKD 2800 Quick Setup
12
MG.28.J1.62 - VLT is a registered Danfoss trademark
Loading...
+ 26 hidden pages