Danfoss Air Units Installation guide

MAKING MODERN LIVING POSSIBLE
Installation Guide
Danfoss Air Units
www.heating.danfoss.com
Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service.
The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
© 2014 Copyright Danfoss A/S
Installation Guide Danfoss Air Units

Table of Contents

1 Safety Note .................................................................... 3
2 Before Start .................................................................... 3
3 Installation of Air Units ............................................................ 4
4 Installation of CCM Module and Air Dial ................................................. 5
4.1 Electrical connections .......................................................... 5
4.2 Wireless connection ........................................................... 5
4.3 Air Dial .................................................................... 5
4.4 Mounting and removing CCM module and Air Dial ........................................ 6
5 Connecting to Danfoss Link™ CC ...................................................... 6
5.1 Connecting the Air Unit to Danfoss Link™ CC, physical installation .............................. 6
5.2 Connecting the Air Unit to Danfoss Link™ CC, wireless inclusion ............................... 7
5.3 Performing a network test after adding a new device ...................................... 7
5.4 Setting basic steps in the Danfoss Link™ CC ............................................ 8
6 Balancing of the Main Air Volume ..................................................... 8
7 Service Menu ................................................................... 9
8 Technical Specifications ............................................................ 10
8.1 a² Unit .................................................................... 10
8.2 a³ Unit .................................................................... 12
8.3 w¹ Unit .................................................................... 14
8.4 w² Unit .................................................................... 16
9 Troubleshooting ................................................................. 17

1 Safety Note

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person respon­sible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Apart from the replacement of air filters and exterior cleaning of the system, any kind of maintenance will require the use of trained personnel.

2 Before Start

Check the Danfoss Air Unit packing list to ensure that the shipment is complete. If a complete Danfoss Air Solution is ordered, a packing list for the Air Flex duct system is included. Inspect to ensure that no parts or components have been damaged.
Standard delivery includes:
Danfoss Air Unit
Wall bracket (if w-model)
CCM
Cabels
Optional deliveries:
Air Dial
Danfoss LinkTM CC
Danfoss Heating Solutions VIEWB302
3
2
4
1
2
3
4
5
6
1
1 cm
2
3
5
75 mm
1
2
3
4
5
6
Installation Guide Danfoss Air Units

3 Installation of Air Units

Attic Units a² and a³
1. Pull out the spigots 1. Never lift the unit into the spigots, as it can damage the unit.*
2. Turn the spigots around and mount them using the included tapping screws (for power drill, use lowest torque setting).
3. Make a platform
4. Allow for 60 cm free space in front of unit, to assure service access.
5. Make sure the unit is mounted with a minor backward fall.
6. A siphon 5 must always be installed with the unit (to be ordered separately).
7. Mount the siphon on the joist
8. Connect the siphon to a drain 6.
9. The condensate line 3 must be insulated where risk of freezing occurs.
10. Connect the hose to the unit outlet condensate spigot. Lead the connected pipe to the out­let, allowing for a gradient of min. 1 cm/metre.
11. Remove the front panel and foam front, fill the condensate tray, check the outlet and reas­semble the front.
* If the unit is lifted into the spigots, it might cause leakage between the steel cabinet and the polystyr­ene core. The leakage can be fixed from the inside of the unit by sealing the spigots with an acrylic­based sealant.
for the unit of 16 mm plywood or MDF sheet around 50 mm wall batts.
below the unit or in the room below the attic.
Wall Units w¹ and w²
1. Place the mounting bracket 1 on the wall in desired position (75 mm from bracket bottom to unit top), mark up and drill holes. Use screws suitable for the wall surface (not included).
2. Make sure that the bracket is mounted absolutely horizontal.
3. Hang the unit onto the bracket.
4. Attach the self-adhesive rubber separators
to the lower rear back plate.
5. Allow for 60 cm free space in front of unit, to assure service access.
6. A siphon
must always be installed with the unit (to be ordered separately).
7. Mount the siphon on the wall below the unit.
8. Connect the siphon to the drain
at the unit bottom.
9. The condensate line 4 must be insulated where risk of freezing occurs.
10. Connect the hose to the unit outlet condensate spigot. Lead the connected pipe to the out­let, allowing for a gradient of min. 1 cm/metre.
11. Remove the front panel and foam front, fill the condensate tray, check the outlet and reas­semble the front.
Wall Unit w¹
In order to comply with safety standards and avoid the risk of malfunction, the supplied protec­tion shield must be mounted on top of the w¹-unit covering the connector plate.
4
VIEWB302 Danfoss Heating Solutions
1
2
3
4
5
6
1
2
3
4
!
Installation Guide Danfoss Air Units

4 Installation of CCM Module and Air Dial

4.1 Electrical connections

1. Connect power cable 4 to Air unit 3.
2. Plug in communication cable 2 between CCM module 1 and Air unit.
3. Check the signal. If it is too weak, the CCM module should be placed elsewhere, e.g. on the same floor as as the Air Dial (see Air Dial Link Test).
4. If possible, place the CCM module close to an ethernet connection for future connection to PC.
5. If accessories (electrical preheating, electrical afterheating, water heating surface or geo­thermal surface) are present, the pin on terminals 5 and 6 must be removed (also see the instructions included with the accessories).
Communication cable connections:
1. White/Orange, 2. Orange, 3. Black, 4. White/Blue, 5. Blue, 6. Black Note! The communication cable can be extended up to 200 m. Use shielded cable , 22 or 24 AWG with 2 x twisted pair.

4.2 Wireless connection

When powering up the CCM module a green LED will flash slowly, indicating the CCM module has yet to be connected to the Air Dial. To connect the Air Dial, insert the batteries. The Air Dial starts in installation mode and automat­ically guides through the set-up.
1. Set language.
2. Create network (press button on CCM module and then press Air Dial).
3. Set basic step (setting up the main air volume).
4. Finish.
Green LED lights continuously Connected established Red LED flashes slowly 5 times Connection attempt failed, see Troubleshooting.
Tab. 2: LED blink patterns on the CCM
4.3

Air Dial

The Air Dial has an integrated temperature sensor. To ensure best possible performance, place the Air Dial according to following guidelines:
Place the Air Dial 80-150 cm above floor level.
Place the Air Dial free of curtains etc.
Place the Air Dial where the temperature is representative.
Do not place the Air Dial in bathrooms.
Do not place the Air Dial in direct sunlight.
Do not place the Air Dial onto outer wall.
Do not place the Air Dial directly above heat source.
Danfoss Heating Solutions VIEWB302
5
2
1
2
1
1
1
2
1
2
1
2
3
4
5
6
1
2
3
4
Installation Guide Danfoss Air Units
Air Dial Link Test
Before mounting the Air Dial permanently, perform a link test to ensure that transmission conditions are sufficient for the required loca­tion:
1. Press the Air Dial button for 5 seconds to access the Service Menu (The Service Menu remains visible for one hour).
2. Select the Link Test function.
3. The function shows if the transmission conditions are sufficient or not.
4. If the link test fails, see Troubleshooting.

4.4 Mounting and removing CCM module and Air Dial

CCM module
Mounting:
1. Place the CCM on the wall bracket.
2. Press downwards to click the CCM into place.
Removing:
1. Press in the two latches on the side.
2. Pull the CCM upwards.
Air Dial
Mounting:
1. Place the Air Dial on the wall bracket.
Removing:
1. Lift the Air Dial.
2. Pull the Air Dial away.
2. Press downwards to click the Air Dial into place.

5 Connecting to Danfoss Link™ CC

5.1 Connecting the Air Unit to Danfoss Link™ CC, physical installation

1. Connect power cable 4 to Air unit 3.
2. Plug in communication cable 2 between CCM module 1 and Air unit.
3. If possible, place the CCM module close to an ethernet connection for future connection to PC.
4. If accessories (electrical preheating, electrical afterheating, water heating surface or geo­thermal surface) are present, the pin on terminals 5 and 6 must be removed (also see the instructions included with the accessories).
5. The Air Unit is now ready to be added to the Danfoss Link™ CC.
Communication cable connections:
1. White/Orange, 2. Orange, 3. Black, 4. White/Blue, 5. Blue, 6. Black Note! The communication cable can be extended up to 200 m. Use shielded cable , 22 or 24 AWG with 2 x twisted pair.
6
VIEWB302 Danfoss Heating Solutions
Loading...
+ 14 hidden pages