Controller tray for refrigeration
appliance control with TEV
AK-CT 200A + AK-CT 450A
ADAP-KOOL® Refrigeration control systems
AK-CT 450A
Introduction
Application
Complete refrigeration appliance control with great exibility to
adapt to all types of refrigeration appliances and cold storage
rooms.
• For refrigeration with brine
• For use with a thermostatic expansion valve (TEV)
Advantages
• Optimised for installation by manufacturer
• Electricity-controlled and voltage controlled relay connections
• Loads requiring electricity can be connected directly
• Overcurrent limitation
• Energy optimisation of the whole refrigeration appliance
• One controller for several dierent refrigeration appliances
• Quick set-up with predened settings
• Built-in data communication
• Built-in clock function with power reserve
Principle
The temperature in the appliance is registered by one or two
temperature sensors which are located in the air ow before the
evaporator (S3) or after the evaporator (S4) respectively.
A setting for thermostat, alarm thermostat and display reading
determines the inuence the two sensor values should have for
each individual function.
In addition product sensor S6, which can be optionally placed in
the appliance, can be used to register the temperature near the
required product in a certain place within the appliance.
The temperature of the evaporator is registered with the S5 sensor
which can be used as a defrosting sensor.
In addition to the output for the solenoid valve type EVR the controller has 9 relay outputs which are dened by the use selected –
the individual usage options are described in detail on page 12
Functions
• Day/night thermostat with ON/OFF or modulating principle
• Product sensor S6 with separate alarm limits
• Switch between thermostat settings via digital input
• Start of defrost via schedule, digital input or network
• Natural, electric, hot gas defrost or brine defrost
• Stop of defrost on time and/or temperature
• Coordination of defrosting among several controls
• Pulsing of fans when thermostat is satised
• Case cleaning function for documentation of HACCP procedure
• Rail heat control via day/night load or dew point
• Door function
• Control of two compressors
• Control of night blinds
• Light control
• Heat thermostat
• Integrated MODBUS communication with the option of
mounting a LonWorks communication card
Here is an overview of the controller’s usage options.
• Standard appliance or cooling room with one valve,
one evaporator and one cooling section.
• Refrigeration appliance with one valve, two evaporators
and two cooling sections (each with its own temperaturemeasuring function).
• Refrigeration device with one valve, one evaporator and
two cooling sections.
A setting will congure input and outputs so that the controller’s
operation interface is directed at the selected application.
The current settings for the respective uses can be found
on page 34.
Installation benets
The controller is designed to provide a number of advantages
when installed by the refrigeration appliance manufacturer,
such as:
High relay load
Load connection/disconnection is controlled by a voltage
measurement and a current measurement, so that the relay’s
switch function can operate under optimal conditions.
The controller can then connect loads of up to 16 A, without
the use of auxiliary relays.
Spring clamps
All cable connections are made using plugs with spring switches.
This allows for fast and easy installation.
Parallel power point
Several of the outlets have double or triple connections points,
so the use of external loop clips is not usually necessary.
Structure of the controller
The controller consists of hardware type AK-CT 200A and a
software identity code AK-CT 450A.
This software identity code is delivered in a separate plug
and must be placed in an RJ45 plug in the hardware. It is rst
necessary to mount the plug when conguring the controller.
Regulation can be performed on the basis of the following principles:
Direct expansion
The temperature is controlled either through the starting/stopping of a compressor or through the opening/closing of a solenoid valve in the liquid line.
Brine
Here, the temperature is controlled by opening/closing a solenoid
valve/motor valve in the brine supply.
Temperature control
The temperature in the appliance is registered by one or two
temperature sensors which are located in the air ow before the
evaporator (S3) or after the evaporator (S4) respectively. A setting
for the thermostat, alarm thermostat and display reading determines how much the two sensor values should inuence each
individual function, e.g. 50% will produce an equal value from
both sensors.
Various weightings can be set for day and night operation.
The actual temperature control can take place in two ways: as an
ordinary ON/OFF regulation with a dierential, or as a modulating control where the temperature variation will not be nearly as
great as in ON/OFF control. There is however a limit to the use of
a modulating control as it can only be used in DX central plant or
brine system.
In principle, regulation in this system is the same as described
above, but is now performed with a PI function. This results in
reduced uctuation of the regulated air temperature with stable
loads, giving a more constant air humidity.
The function gives a constant temperature regulation with a temperature value, which lies half-way between the on and o values
of the thermostat.
The operating parameters of the PI regulation are automatically
optimised via the preset on and o values and the degree of
opening of the valve.
The dierential aects the amplication of the regulator and can
therefore not be set to less than 2K in order to ensure regulation
stability.
In a decentralised plant the thermostat function with ON/OFF
control should be selected.
In a central plant the thermostat function may either be selected
for ON/OFF control or modulating control.
Temperature monitoring
Just as is possible for the thermostat, the alarm monitoring can
be set with a weighting between S3 and S4 so that you can decide
how much the two sensor values should inuence the alarm
monitoring. Minimum and maximum limits can be set for alarm
temperature and time delays. A longer time delay can be set
for high temperature alarms after defrosting, appliance cleaning
or start-up.
Thermostat bands can be used benecially for appliances where
dierent product types are stored which require dierent temperature conditions. It is possible to change between the two
dierent thermostat bands via a contact signal on a digital input.
Separate thermostat and alarm limits can be set for each thermostat band – also for the product sensor.
Night setback of thermostat value
In refrigeration appliances there may be big load dierences
between the shop’s opening and closing hours, especially if night
lids/blinds are used. The thermostat reference may be raised here
without it having any eect on the product temperature.
Change-over between day and night operation can take place,
as follows:
• via an external switch signal.
• via a signal from the data communication system.
Product sensor
A separate product sensor S6, which may be placed in the
appliance, can also be used and which can register and monitor
the temperature in the warmest part of the appliance. There are
separate alarm limits and time delays for the product sensor.
Appliance cleaning
This function makes it easy for the shop’s sta to carry out a
cleaning of the appliance according to a standard procedure.
Appliance cleaning is activated via a signal – as a rule via a key
switch placed on the appliance.
Appliance cleaning is carried out via three phases:
1 - at the rst activation the refrigeration is stopped, but the fans
keep on operating in order to defrost the evaporators. ”Fan” is
shown on the display.
2 - at the second activation the fans are also stopped and the
appliance can now be cleaned. ”OFF” is shown on the display.
3 - At the third activation refrigeration is recommenced.
The display will show the actual appliance temperature,
(o97 setting).
When appliance cleaning is activated a cleaning alarm is
transmitted to the normal alarm recipient. A later processing
of these alarms will document that the appliance has been
cleaned as often as planned.
Alarm monitoring
There are no temperature alarms during appliance cleaning.
Appliance shut-down
The function closes the solenoid valve and all outputs are
switched o.
The cooling appliance is stopped like the “Main switch”, but this
happens without an “A45 standby alarm”.
The function can be enabled by a switch on the DI input or via
a setting through data communication.
Depending on the application you may choose between the
following defrost methods:
Electric: The heating element is activated
Hotgas: Here the solenoid valves are controlled so that the hotgas can ow through the evaporator
Brine: Here, the solenoid/motor valve is opened on the supply
pipe, so that hot brine can be fed through.
Natural: Here the fans are kept operating during the defrost
Defrost sequence
1) Pump down
2) Defrost
3) Waiting position after defrost
4) Draining (drain delay. Hotgas only)
5) Drip o
6) Delay of fan
Hot gas defrost (application 7 only)
This type of connection can be used on systems with hotgas
defrost, but only in small systems in, say, supermarkets – the
functional content has not been adapted to systems with large
charges.
Must not be used together with PMLX and GPLX valves, unless
a time delay relay is installed, which ensures that the PMLX/GPLX
valve is closed completely before the hotgas is turned on.
Drip tray heating element
It is possible to control a heating element in the drip tray for
hot gas defrosting. When defrosting is commenced, the heating
element is activated. The heating element remains activated until
a set time after defrosting has ended by time or temperature.
Start of defrost
A defrost can be started in dierent ways
Interval: Defrost is started at xed time intervals, say, every
eighth hour. An interval must ALWAYS be set to
a "higher" value than the period set between two
defrostings when a schedule or network signal is used.
Refrigeration time: Defrost is started at xed refrigeration time
intervals, in other words, a low need for refrigeration will
”postpone” the defrost
Schedule: Here defrost can be started at xed times of the
day and night. However, max. 6 times
Contact: Defrost is started with a contact signal on a digital input
Network: The signal for defrost is received from a system unit
via the data communication
Manual: An extra defrost can be activated from the controller’s
lower-most button
All the mentioned methods can be used at random – if just of
them is activated a defrost will be started.
There are two ways in which coordinated defrost can be arranged.
Either with wire connections between the controllers or via data
communication
Wire connections
The digital input DI2 is connected between the current controllers.
When one controller starts a defrost all the other controllers will
follow suit and likewise start a defrost. After the defrost the individual controllers will move into waiting position. When all are in
waiting position there will be a change-over to refrigeration.
Coordination via data communication
Here the system unit handles the coordination.
The controllers are gathered in defrosting groups and the system
unit ensures that defrosting is started in the group according to a
weekly schedule.
When a controller has completed defrosting, it sends a message
to the system unit and then goes into a waiting position. When
every controller in the group is in a waiting position, refrigeration
is again permitted in all the individual controllers.
Defrost based on refrigeration time
When the aggregate refrigeration time has passed a xed time,
a defrost will be started.
Max. 10 pcs.
System manager
Min. time between defrosts
There is a 2 hours minimum time between defrosts.
This avoids that planned defrosts in accordance with the weekly
schedule are carried out immediately after a defrost on demand
has been carried out. The time applies from when a Defrost based
on refrigeration time has been completed to when a planned
defrost is again permitted. Defrost based on refrigeration time will
not start defrosting with a shorter interval than the 2 hours either.
Melting function
This function will stop the air ow in the evaporator from being reduced by frost created by uninterrupted operation for a long time.
The function is activated if the thermostat temperature has
remained in the range between -5°C and +10°C for a longer
period than the set melting interval. The refrigeration will then be
stopped during the set melting period. The frost will be melted
so that the air ow and hence the evaporator’s capacity will be
greatly improved.
Real-time clock
The controller has a built-in real-time clock which can be used
to start defrosts. This clock has a power reserve of more than 24
hours.
If the controller is equipped with data communication, the clock
will automatically be updated from the system unit.
Control of two compressors (application 8)
The two compressors must be of the same size.
When the controller demands refrigeration it will rst cut in
the compressor with the shortest operating time. After the time
delay the second compressor will be cut in.
When the temperature has dropped to ”the middle of the
dierential”, the compressor with the longest operation time
will be cut out.
The running compressor will continue until the temperature
has reached the cutout value. Then it will cut out. When the
temperature again reaches the middle of the dierential,
a compressor will again be started.
If one compressor cannot maintain the temperature within the
dierential, the second compressor will also be started.
If one of the compressors has run on its own for two hours,
the compressors will be changed over so that operational time
is balanced.
The two compressors must be of a type that can start up against
a high pressure.
The compressors’s settings for ”Min On time” and ”Min O time”
will always have top priority during normal regulation. But if one
of the override functions is activated, the ”Min On time” will be
disregarded.
Railheat
It is possible to pulse-control the power to the rail heat in order
to save energy. Pulse control can either be controlled according
to day/night load or dew point.
Pulse control according to day and night
Various ON periods can be set for day and night operation.
A period time is set as well as the percentage part of the period
in which the rail heat is ON.
Pulse control according to dew point
In order to use this function a system manager of the type AK-SM
is required which can measure dew point and distribute the
current dew point to the appliance controllers. For this the rail
heat’s ON period is controlled from the current dew point.
Two dew point values are set in the appliance control:
• One where the eect must be max. i.e.100%. (o87)
• One where the eect must be min. (o86).
At a dew point which is equal to or lower than the value in 086,
the eect will be the value indicated in o88.
In the area between the two dew point values the controller will
manage the power to be supplied to the rail heat.
During defrosting
The rail heating will be active during defrosting (as selected
in setting d27).
To obtain energy savings it is possible to pulse control the power
supply to the fans at the evaporators.
Pulse control can be accomplished in one of the following ways:
- during the thermostat’s cutout period (cold room)
- during night operation and during the thermostat’s cutout
period (appliance with night lid)
A period of time is set as well as the percentage of this period of
time where the fans have to be operating.
Cutout of fans during plant breakdowns
If the refrigeration in a breakdown situation stops, the
temperature in the cold room may rise quickly as a result of the
power supply from large fans. In order to prevent this situation the
controller can stop the fans if the temperature at S5 exceeds a set
limit value.
Fan pause
When the setting P65 is set to a value greater than 0, the fans will
stop while the night blind is rolling down.
Eco-mode
When the night blind is down, the fan speed can be reduced.
Eco-mode is not allowed if the heating function has been
activated.
When Eco-mode is enabled, relay DO8 will be activated.
Period time
Light function
The function can be used for controlling the light in a refrigeration
appliance or in a cold room. It can also be used for controlling
a motorised night blind.
The light function can be dened in more than one way:
- The light is controlled via a signal from a door contact.
The light will remain on for 2 minutes after the door has been
shut.
- The light is controlled via the day/night function.
- The light is controlled via the data communication from
a system unit.
Here there are two operational options if data communication
should fail:
- The light can go ON.
- The light can stay in its current mode.
• Two signals, both of which can be on before the light goes on.
One can be a DI contact signal at the appliance (fx DI3) and the
other can be via data communication or a voltage signal.
Voltage signal must be activated on DI7.
The light is switched o when "r12" (Main switch) is set to o
(see o98).
The light is switched o when the appliance cleaning function
is activated.
If an override of the light is desired, this can be done via pulse
pressure on a DI input + setting = 19.
Extra light (light 2)
Light 2 can also be activated by one DI input, e.g. DI4.
It can also be controlled with two signals. For two signals,
the second signal must be sent with a voltage signal on DI8.
Light 1
controlled by
DI7
and fx DI3.
Light 2
(extra light)
controlled by
DI8 and fx DI4.
Motorised night blind can be controlled automatically from
the controller. The night blinds will follow the status of the light
function. When the light is switched on, the night blinds opens
and when the light is switched o, the night blinds close again.
When the night blinds are closed, it is possible to open them
using a pulse signal on the digital input. If this input is activated,
the night blinds will open and the refrigeration appliance can
be lled with new products. If the input is activated again,
the blinds close again.
If the activation is omitted, the blind will close automatically
when the delay time expires. A setting is used to dene whether
the light is to be on or o when the night blind is up.
When the night blind function is used, the thermostat function
can control with dierent weighting between the S3 and S4
sensors. A weighting during day operation and another when
the blind is closed.
A night blind is open when the appliance cleaning function
is activated.
A setting can dene that the night blind is open when "r12"
(Main switch) is set to o (see o98).
Digital inputs
There are six digital inputs with contact function and two digital
inputs with high voltage signal.
They can be used for the following functions:
- Retransmission of contacts position via data communication
- Door contact function with alarm
- Starting or cancelling a defrost cycle
- Main switch - start/stop of cooling
- Night setback
- Thermostat bands switch
- General alarm monitoring
- Case cleaning
- Forced cooling
- Override of night blinds
- Coordinated defrost (DI2 only)
- Forced closing of valve
- Appliance shutdown
- Light, Extra light, Override light
Forced closing
The solenoid valve can be closed with an external signal
( "Forced closing").
If a defrost cycle is in progress, the forced closing status will not
be re-established until the defrost is completed. Otherwise,
the defrost cycle will be stopped immediately when the signal
is received. The function can be dened in o90. The signal can
be received from the DI3-input or via the data communication.
During a forced closing the fans can be dened to be stopped
or in operation.
Door contact
The door contact function can via the digital inputs be dened
for two dierent applications:
Alarm monitoring
The controller monitors the door contact and delivers an alarm
message if the door has been opened for a longer period than
the set alarm delay.
Alarm monitoring and stop of refrigeration
When the door is opened the refrigeration is stopped, i.e. the
injection, the compressor and the fan are stopped and light
switch on.
If the door remains open for a longer time than the set restart
time, refrigeration will be resumed. This will ensure that
refrigeration is maintained even if the door is left open or
if the door contact should be defective. If the door remains
open for a longer period than the set alarm delay an alarm
will also be triggered.
The heating function is used to prevent the temperature
becoming too low, e.g. in a cutting room, etc. The limit for
when the heating function cuts o is set as an oset value
under the current cutout limit for the refrigeration thermostat.
This ensures that refrigeration and heating do not occur
simultaneously. The dierence for the heating thermostat has
the same value as for the refrigeration thermostat. To prevent
that the heating thermostat cuts in during short-term drops
in air temperature a time delay can be set for when to change
from refrigeration to heating.
Data communication
The controller has xed built-in MODBUS data communication.
If there is a requirement for a dierent form of data
communication, a Lon RS 485 module can be inserted in the
controller.
The connection must then be to terminal RS 485.
(To use a Lon RS 485 module and gateway type AKA 245
the module must be Version 6.20 or higher.)
It is not possible, however, to show all parameters available
in AK-CT 450A).
Refrigeration
Neutral zone
Heat
Important
All connections to the data communication MODBUS and RS 485
must comply with the requirements for data communication
cables. See literature: RC8AC.
Display
The controller has two plugs for a display. Here display type
EKA 163B or EKA 164B (max. length 15m) can be connected.
EKA 163B is a display for readings.
EKA 164B is both for readings and operation.
(It is not possible to connect a display to the Modbus terminals,
as in the other AK-CC 450 controllers.)
If there are two cooling sections,
the bottom plug will be the A
section and the top plug will be
the B section.
If there is one cooling section,
the displays will be the same for
both plugs.
Override
The controller contains a number of functions which can be used together with the override function in the master gateway/system
manager.
Function via data communicationFunction in gateway/system managerUsed parameters in AK-CT 450A
Start of defrostingDefrost control / Time schedule / Defrost group--- Def start
Here is a survey of the controller’s eld of application.
The applications are all adapted for commercial refrigeration
systems in the form of either refrigeration appliances or cold
storage rooms.
A setting (o61) will dene the relay outputs so that the controller’s
interface will be targeted to the chosen application.
Control sensors and temperature monitoring function
S3 and S4 are temperature sensors. The application will determine
whether either one or the other or both sensors are to be used.
S3 is placed in the air ow before the evaporator. S4 after the
evaporator.
A percentage setting will determine how the control is to be
based.
If there are two cooling sections, S3b is used for section 2.
S5 is a defrost sensor and is placed on/in the ns of
the evaporator.
An S5B is also used when there are two evaporators, as well as
when there is a long, single evaporator.
S6 is a product sensor. S6B used when there are two sections.
Digital input
DI1 to DI6 is the on/o input that can be used, for example, for
one of the following functions: Door function, alarm function, defrost start, external main switch, nighttime operation, thermostat
reference switch, appliance cleaning, forced cooling, light, defrost
cancellation or defrost coordination.
DI7 and DI8 are 230 V inputs that can activate similar functions.
(For light function with two signals, the input is locked for
Light 1/Light 2.)
See the functions in the respective settings o02, o37, o84, etc.
Control of night blinds
Night blinds follow the status of the light function – when the
light is switched on, the night blinds are up and when the light is
switched o, the night blinds are down. In addition a digital input
provides the option of forced opening of the blinds so that the
appliance can be lled with products.
Heat thermostat
The heat thermostat is typically used if the temperature is to be
controlled within narrower limits, e.g. for cutting rooms, etc. The
heating thermostat can be set as a dierence in relation to the
cutout limit for the refrigeration thermostat so that simultaneous
refrigeration and heating are avoided.
Varmelegemet tilsluttes DO2 udgangen, og vil være aktiv under
The heating element is connected to the DO2 outlet and will be
active during regulation when the temperature becomes too low.
The outlet will also be active if electric defrost is required.
The function is dened by setting the delay time r63 lower than
the max. value.
The function cannot be used together with hot gas defrosting.
FunctionInput/Settings menuSetting
DI1DI2 DI3 DI4DI5 DI6DI7 DI8
o02 o37 o84 P55 P56 P57 P58 P59
Not used++++++++0
Follows DI’s status ++++++++1
Door contact function++++++++2
Door alarm++++++++3
Start defrost++++++++4
Main switch++++++++5
Nighttime operation++++++++6
Thermostat band++++++++7
DI alarm when closed++
No function++++++
DI alarm when open++
No function++++++
Appliance cleaning++++++++10
Forced cooling++++++++11
Night blind++++++++12
Coordinated defrost+
No function+++++++
Forced close++++++++14
Appliance shutdown++++++++15
Light++++++++16
Extra light++++++++17
No defrost++++++++18
Override light++++++++19
Example
If DI1 is used to start a defrost cycle, o02 must be set to 4.
Hot gas defrosting is adapted to commercial appliances/
rooms with limited system lling.
One relay controls the main valve in the suction line.
One relay controls the hot gas valve.
One relay controls the drain valve.
There is no time delay between stops of hot gas and start
of draining.
8
”Two-compressor” operation.
The two compressors must be of the same size. On start-up
(after defrosting, operational stop, etc.) both compressors are
started with a set time shift. One compressor starts at half the
dierential so that an optimum adaptation of compressor
capacity takes place for the current load in the appliance/
room. There is automatic runtime equalisation between the
compressors.
230 V, or 2 phases + neutral, or 3 phases + neutral. 50 Hz.
Neutral must be tted. If neutral is not in place, the controller can
be damaged. During assembly and disassembly, the power supply
must be interrupted).
DO1
Cooling or exhaust port valve
DO2
Defrost cycle or hot gas valve
DO3
Light
DO4
Light 2, compressor 2 or heating element in drip tray
DO5
Night blind or defrost cycle 2
DO6
Rail heat
DO7
Fan
AO1
Analogue output signal, 0-10 V
The signal will follow the EVR valve’s degree of opening
(OD=0% will display 0 V and OD=100% will display 10 V).
The output can be used to control one e.g. 6 minutes modulating
valve.DI1-DI6
Digital input signal.
The dened function is active when the input is closed/opened.
DI7-DI8
Digital input signal.
The dened function is active when the input receives 230 V.
(Forced closing is, however, active at 0 V)
Data communication
If data communication is used, it is important that the installation
of the data communication cable is performed correctly.
See separate literature No. RC8AC…
MODBUS
For data communication.
Terminal 133 = BTerminal 134 = A+
Terminal 135 = screen
RS485 (terminal 130, 131,132)
For data communication, but only if a data communication
module is inserted in the controller. The module can be a LON
RS485.
Terminal 130 = B (B-)
Terminal 131 = A (A+)
Terminal 132 = screen
DO8
Fan in economy mode or defrost 3 or drain valve
DO9
Alarm
There is a connection between terminal 100 and 101 in an alarm
situation, as well as when the controller is without voltage.
DOA
Connection of solenoid valve type EVR. The coil must be half wave
rectied.
S2
Not used
S3, S4, S5, S6
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of
the same type.
S3, air sensor, placed in the warm air before the evaporator
S3B can be used on appliances with two cooling sections
S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in
the conguration)
S5, defrost sensor, placed on the evaporator
S5B can be used on appliances with two evaporators,
or on models with long evaporators
S6, product sensor
S6B can be used on appliances with two cooling sections
Pressure transmitter
Not used
(For LON RS485 and gateway type AKA 245 the gateway must be
version 6.20 or higher.)
EKA Display
If there is be external reading/operation of the controller, display
type EKA 163B or EKA 164B can be connected.
Electric noise
Cables for sensors, DI inputs and data communication must be
kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided.
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could still
present problems. Electronic controls are no substitute for normal,
good engineering practice.
Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer's
responsibility to check the installation thoroughly, and to t the
necessary safety devices.
Special reference is made to the necessity of signals to the
controller when the compressor is stopped and to the need of
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further
advice, etc.
There are 3 holes on the base in which
a terminal strip (type Wago 862-8593)
can be mounted.
There are holes for 2 terminal strips.
Stripping wire
The following demands for stripping, so the insulation does not
enter the spring clip.
ID module AK-CT 450A
This module contains a code which, together
with the others, will enable regulation using
an solenoid valve.
The installation and removal of the module must always be
performed while the appliance is voltage-free.
When the module is inserted in the plug, the controller can be set.
The settings will be saved in both the controller and the module.
A module with settings will always overwrite the settings in
the controller. An overwrite will be nished 3 seconds after the
controller is turned on.
The module can be removed from the controller for a short period
of time in order to transfer the settings to another, corresponding
controller. Remember to disconnect the voltage to ensure the
system is voltage-free.
If the controller registers a missing module, an alarm will be
issued. This alarm will be regularly repeated until the module is
inserted in the controller again.
If the controller is without a module for a longer period of time
(several days), the regulation will stop and all outputs are reset.
If it becomes necessary to erase all settings from the module, it
can be inserted into the controller and setting P61 can then be activated. Then remove the module without restarting the controller.
Coordinated defrost via
cable connections
A factory-new or “empty” module can be used to retrieve settings
based on a corresponding controller.
Insert the module into the controller from which the settings are
to be retrieved.
Turn on voltage.
Wait 3 seconds. Turn o again.
The module now contains all settings — including the Modbus
address.
Remember to change the address when the module has been
inserted into the receiving apparatus.
Max. 10 pcs.
The following controllers can be connected
up in this way:
EKC 204A, AK-CC 210, AK-CC 250,
AK-CC 450, AK-CC 550
AK-CT 550A, AK-CT 450A,
Refrigeration is resumed when all
controllers have “released” the signal for
defrost.
Coordinated defrost via
data communication
The setting of controllers to coordinate
their defrosting takes place in the
gateway/system manager.
Refrigeration is resumed when all
controllers have “released” the signal for
defrost.
Normally the temperature value from one of the two thermostat sensors S3 or S4 or
a mixture of the two measurements is displayed.
In o17 the ratio is determined.
ThermostatThermostat control
Set point
Regulation is based on the set value plus a displacement, if applicable. The value is set
via a push on the centre button.
The set value can be locked or limited to a range with the settings in r02 and r 03.
The reference at any time can be seen in "u91 Cutout temp".
Dierential
When the temperature is higher than the reference + the set dierential, the
compressor relay will be cut in. It will cut out again when the temperature comes
down to the set reference.
Ref. Dif.
Setpoint limitation
The controller’s setting range for the setpoint may be narrowed down, so that much
too high or much too low values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. allowable reference value may
be lowered.
To avoid a too low setting of the setpoint, the min. allowable reference value may
be increased.
Correction of the display’s temperature
If the temperature at the products and the temperature received by the controller
are not identical, an oset adjustment of the display temperature can be carried out.
Temperature unit
Set here if the controller is to show temperature values in °C or in °F.
Correction of signal from S4
Compensation possibility due to long sensor cable
Correction of signal from S3 and S3B
Compensation possibility due to long sensor cable
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or a manual override of the
outputs can be allowed. (For manual control the value is set at -1. Then the EVR outlet
and the relay outlets can be force-controlled by the respective reading parameters
(u23, u58, etc.). Here the read value can be overwritten.) Refer also to the menu
overview on page 33
Start / stop of refrigeration can also be accomplished with the external switch
function connected to a DI input.
Stopped refrigeration will give a ”Standby alarm”.
Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller
changes over to night operation. (Select a negative value if there is to be cold
accumulation.)
Thermostat function
Here it is dened how the thermostat is to operate. Either as an ordinary ON/OFF
thermostat or as a modulating thermostat.
1: ON/OFF thermostat
2: Modulating
Parameter by operation via data
communication
Display air (u56)
Cutout °C
r01Dierential
r02Max cutout °C
r03Min cutout °C
r04Disp. Adj. K
r05Temp. unit
°C=0. / °F=1
(Only °C on AKM, whatever
the setting)
r09Adjust S4
r10Adjust S3
r12Main Switch
1: Start
0: Stop
-1: Manual control of outputs allowed
r13Night oset
r14Therm. mode
When operation is ”modulating” the EVR valve will limit the ow of refrigerant so
that the temperature variation will be less than for the ON/OFF thermostat.
The dierential (r01) must not be set lower than 2K for "modulating".
In a decentralised plant you must select the ON/OFF thermostat setting.
Selection of thermostat sensor
Here you dene the sensor the thermostat is to use for its control function. S3, S4, or
a combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
Only for control of refrigeration (-5 to +10°C). The function ensures that the
evaporator will not be blocked by frost. Here you set how often the function is
to stop the refrigeration and hence transform the frost to water (or ice if there is
too much frost).
Melt period
Here you set how long an on-going melt function is to last.
Set point 2
The thermostat’s cutout value when the thermostat band 2 is activated via a digital
input.
Correction of signal from S6
Compensation possibility due to long sensor cable
Correction of signal from S6B
Compensation possibility due to long sensor cable
Selection of thermostat sensor S4% during night operation or night blinds down
Here you dene the sensor the thermostat is to use for its control function. S3, S4, or
a combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
Heat function
Set the size of the Neutral Zone for changeover from cooling to heating
Time delay on transition from refrigeration phase to heating phase.
(there is not time delay on transition from heating phase to refrigeration phase).
The heating function is not active when the delay time is set to the max. value
(240 min.).
Product type
This function sets the temperature reference and associated alarm limits.
1=Vegetables, 8°C. 2=Milk, 0°C. 3=Meat/sh, -2°C. 4=Freeze, -20°C. 5=Ice, -24°C.
See overview on page 33.
AlarmAlarm settings
The controller can give alarm in dierent situations. When there is an alarm all the
light-emitting diodes (LED) will ash on the controller front panel, and the alarm
relay will cut in.
Alarm delay (short alarm delay on air temperature)
If the upper or the lower alarm limit values are exceeded, a timer function will
commence. The alarm will not become active until the set time delay has been
passed. The time delay is set in minutes.
Time delay for door alarm
The time delay is set in minutes.
The function is dened for a DI function, see o02, o37 or other DI.
Time delay for cooling (long alarm delay)
This time delay is used during start-up, during defrost, immediately after a defrost.
There will be change-over to the normal time delay (A03) when the temperature
has dropped below the set upper alarm limit.
The time delay is set in minutes.
Upper alarm limit
Here you set when the alarm for high temperature is to start. The limit value is set
in °C (absolute value).
The limit value will be raised during night operation. The value is the same as the one
set for night setback, but will only be raised if the value is positive.
In application 3 and 6, the setting is the same for S3 and S3B.
Lower alarm limit
Here you set when the alarm for low temperature is to start. The limit value is set in °C
(absolute value).
In application 3 and 6, the setting is the same for S3 and S3B.
Upper alarm limit for thermostat 2 (Thermostat band 2)
(Same function as for thermostat 1)
Lower alarm limit for thermostat 2 (Thermostat band 2)
(Same function as for thermostat 1)
Upper alarm limit for S6 temperature at thermostat 1A22HighLim1 S6
Lower alarm limit for S6 temperature at thermostat 1A23LowLim1 S6
Upper alarm limit for S6 temperature at thermostat 2 (Thermostat band 2)A24HighLim2 S6
Lower alarm limit for S6 temperature at thermostat 2 (Thermostat band 2)A25LowLim2 S6
S6 temperature alarm delay
The alarm is activated if one of the relevant alarm limits A22, A23, A24 or A25 is
exceeded. The time delay is set in minutes.
(Alarms will not activate when the setting is set to the maximum value. 240 min.)
r16MeltInterval
r17Melt period
r21Cutout2 temp
r59Adjust S6
r60Adjust S6B
r61Ther.S4% Ngt
r62Heat NZ
r63HeatStartDel
r89
Night setbck
(start of night signal. 0=Day, 1=Night)
With data communication the importance of the individual alarms can be
dened. Setting is carried out in the
“Alarm destinations” menu via AKM.
A cut-out/cut-in input will result in alarm when the time delay has been passed.
The function is dened in o02.
Delay of a DI2 alarm
A cut-out/cut-in input will result in alarm when the time delay has been passed.
The function is dened in o37
Signal to the alarm thermostat
Here you have to dene the ratio between the sensors which the alarm thermostat
has to use. S3, S4 or a combination of the two.
With setting 0% only S3 is used. With 100% only S4 is used.
(The setting also applies to a possible B section - S3B, S4)
Time delay on S6 (product sensor) for pull-down (long alarm delay)
This time delay is used for start-up, during defrosting, immediately after a defrost and
after an appliance clean.
A change is carried out to standard time delay (A26) when the temperature has
reached below the set upper alarm limit.
The time delay is set in minutes.
Alarm delay (short alarm delay on section B air temperature)
A timer function starts if the top or bottom alarm limit is exceeded. The alarm will rst
becomes active when the set delay time has been exceeded.
The time delay is set in minutes.
CompressorCompressor control
The compressor relay works in conjunction with the thermostat. When the
thermostat calls for refrigeration the compressor relay be operated.
Running times
To prevent irregular operation, values can be set for the time the compressor is to run
once it has been started. And for how long it at least has to be stopped.
The running times are not observed when defrosts start.
Min. ON-time (in minutes)c01Min. On time
Min. OFF-time (in minutes)c02Min. O time
Time delay for couplings of two compressors
Settings indicate the time that has to elapse from the rst relay cuts in and until
the next relay has to cut in.
DefrostDefrost control
The controller contains a timer function that is zeroset after each defrost start.
The timer function will start a defrost if/when the interval time is passed.
The timer function starts when voltage is connected to the controller, but it is
displaced the rst time by the setting in d05.
If there is power failure the timer value will be saved and continue from here when
the power returns.
This timer function can be used as a simple way of starting defrosts, but it will always
act as safety defrost if one of the subsequent defrost starts is not received.
The controller also contains a real-time clock. By means of settings of this clock and
times for the required defrost times, defrost can be started at xed times of the day.
Defrost start can also be accomplished via data communication, via contact signals or
manual start-up.
All starting methods will function in the controller. The dierent functions have to be
set, so that multiple defrosts are avoided..
Defrost can be performed using electricity, hot gas, naturally or brine.
The actual defrost will be stopped based on time or temperature with a signal from
a temperature sensor.
Defrost method
Here you set whether defrost is to be accomplished with electricity, gas, "air" or brine.
During defrost the defrost relay will be cut in.
A27AI.Delay DI1
A28AI.Delay DI2
A36Alarm S4%
A52PullD del.S6
A53AI.Delay S3B
Reset alarm
EKC error
c05Step delay
u58 comp1/LLSV
Here you can read the status of the
compressor relay.
d01Def. method
0 = non. 1 = El. 2 = Gas. 3 = Brine.
4 = Air.
Defrost stop temperature
The defrost is stopped at a given temperature which is measured with a sensor
(the sensor is dened in d10).
The function is zeroset and will start the timer function at each defrost start.
When the time has expired the function will start a defrost.
The function is used as a simple defrost start, or it may be used as a safeguard if
the normal signal fails to appear.
If master/slave defrost without clock function or without data communication is used,
the interval time will be used as max. time between defrosts.
If a defrost start via data communication does not take place, the interval time will be
used as max. time between defrosts.
When there is defrost with clock function or data communication, the interval time
must be set for a somewhat longer period of time than the planned one, as the
interval time will otherwise start a defrost which a little later will be followed by
the planned one.
In connection with power failure the interval time will be maintained, and when
the power returns the interval time will continue from the maintained value.
The interval time is not active when set to 0.
Max. defrost duration
This setting is a safety time so that the defrost will be stopped if there has not already
been a stop based on temperature or via coordinated defrost.
(The setting is the defrost time if d10 is set to 0.)
Time staggering for defrost cutins during start-up
The function is only relevant if you have several refrigeration appliances or groups
where you want the defrost to be staggered in relation to one another. The function is
furthermore only relevant if you have chosen defrost with interval start (d03).
The function delays the interval time d03 by the set number of minutes, but it only
does it once, and this at the very rst defrost taking place when voltage is connected
to the controller.
The function will be active after each and every power failure.
Drip-o time
Here you set the time that is to elapse from a defrost and until the compressor is to
start again. (The time when water drips o the evaporator).
d03Def Interval
(0=o)
d04Max Def. time
d05Time Stagg.
d06DripO time
Delay of fan start after defrost
Here you set the time that is to elapse from compressor start after a defrost and until
the fan may start again. (The time when water is “tied” to the evaporator).
Fan start temperature
The fan may also be started a little earlier than mentioned under “Delay of fan start
after defrost”, if the defrost sensor S5 registers a lower value than the one set here.
Fan cut in during defrost
Here you can set whether fan is to operate during defrost.
0: Stopped (Runs during pump down)
1: Running (stopped during "fan delay")
2: Running during pump down and defrost. After that stopped
Defrost sensor
Here you dene the defrost sensor.
0: None, defrost is based on time
1: S5
2: S4
3: S5+S5B (In application 3, there is an individual defrost stop at S5 and S5B. In the
other applications, the defrost cycle is stopped when both sensors register the
stop temperature.)
Pumpdown delay
Set the time where the evaporator is emptied of refrigerant prior to the defrost.
Drain delay (only in connection with hotgas)
Set the time where the evaporator is emptied of condensed refrigerant after
the defrost.
Defrost on demand – aggregate refrigeration time
Set here is the refrigeration time allowed without defrosts. If the time is passed,
a defrost will be started.
With setting = 0 the function is cut out.
Delay on stop of heating in the drip tray
The time applies from the time the defrost stops by time or temperature to the time
the heating element in the drip tray needs to be disconnected.
Postpone alarm info for timed stop
The defrost stop by temperature has failed. It has stopped by time, which will result
in an alarm notication. Wait to send an alarm until x consecutive alarms have
registered subsequent “timed stop alarms”. The counter is reset after each correct
stop by temperature.
Here you can set how the rail heat is to be regulated during a defrost cycle.
0: No rail heat
1: No change; continues as during regulation.
2: 100% on
If you wish to see the temperature at the defrost sensor, push the controller’s
lowermost button. (May be changed to another function in o92.)
If you wish to start an extra defrost, push the controller’s lowermost button for
four seconds.
You can stop an ongoing defrost in the same way
FanFan control
Fan stop temperature
The function stops the fans in an error situation, so that they will not provide power
to the appliance. If the defrost sensor S5 registers a higher temperature than the one
set here, the fans will be stopped. There will be re-start at 2 K below the setting.
The function is not active during a defrost or start-up after a defrost.
With setting +50°C (=max. value) the function is interrupted.
Pulse operation of fan
0: No pulse operation
1: Pulse operation when the thermostat does not call for refrigeration
2: Pulse operation when the thermostat does not call for refrigeration, but only
during night operation
Pulse operation period for fan
Here the overall pulse time is set. The sum of ON-to and OFF time.
ON time for fan
Here the % part of the period the fans are to be in operation is set.
Max. S4 temperature during defrost
Here the maximum S4 temperature during a defrost cycle can be set. If the value
is exceeded, the fans will be stopped. The function is not active when the themperature is set to max value (15°C).
Parameter for cooling function
Period time for the pulse width period (PWM)
Expert setting - The value should only be changed by specially trained sta.
Max. opening degree at PWMn64Pwm Max. OD
Min. opening degree at PWMn65Pwm Min. OD
Wind up factor at PWM
Expert setting - The value should only be changed by specially trained sta.
Amplication factor at PWM
Expert setting - The value should only be changed by specially trained sta.
Integration time at PWM
Expert setting - The value should only be changed by specially trained sta.
d27Railh. at def
Defrost temp.
Def Start
Here you can start a manual defrost
Hold After Def
Shows ON when the controller is
operating with coordinated defrost.
Disable def.
Defrost in progress can be stopped
Defrost State
Status on defrost
1= pump down / defrost
MC def. start
The system unit can start/prevent
a defrost cycle
F04FanStopTemp.
F05FanPulseMode
F06Fan cycle
F07Fan ON %
F22FanStopS4Def
u59 Fan Relay
Here you can read the fan relay status,
or force-control the relay in “Manual
control” mode.
(Not used if an external defrosting schedule is used via data communication.)
Up to six individual times can be set for the defrost start throughout the day.
When all t01 to t16 equal 0 the clock will not start defrosts.
Real-time clock::
In the event of a power failure of less than four hours, the clock function will be saved.
Clock: Hour settingt07
Clock: Minute settingt08
Clock: Date settingt45
Clock: Month settingt46
Clock: Year settingt47
Electricity monitoring
Current amount of electricity through relay 1L11DO1 Amp
Same for relays 2 to 8L12-18 DO2 Amp......DO8 Amp
Fuse status for relay circuit 1, O=interrupted, On=ok.
A broken fuse must be restored with the setting=”On”
Same for relays 2 to 8L22-28 DO2 Fuse...... DO8 Fuse
Set the electricity value at which the relay should cut out in the event of overcurrent
Recommended setting = measured consumption +25%. (In setting = 0 the current
monitor will be cancelled).
Same for relays 2 to 8L32-38 DO2 FuseSize...... DO8 FuseSize
Current voltage at phase F1L51L1 voltage
Current voltage at phase F2L52L2 voltage
Current voltage at phase F3L53L3 voltage
Alarm limit for low DO2 load. (Not application 7)
An alarm is issued if the electricity consumption becomes lower than the set value.
Alarm limit for low DO5 load (Application 2,4 and 6 only)L65DO5 Low Load
Alarm limit for low DO6 loadL66DO6 Low Load
Alarm limit for low DO8 load (Application 2, 3, 4 and 6 only)L68DO8 Low Load
MiscellaneousMiscellaneous
Delay of output signal after start-up
After start-up or a power failure the controller’s functions can be delayed so that
overloading of the electricity supply network is avoided.
Here you can set the time delay.
Digital input signal - DI1
The controller has a digital input 1 which can be used for one of the following
functions:
O: The input is not used
1) Status display of a contact function
2) Door function. When the input is open it signals that the door is open. The
refrigeration and the fans are stopped and light switched on. When the time
setting in “A04” is passed, an alarm will be given. The cooling will restart when
the time in o89 has passed
3) Door alarm. When the input is open it signals that the door is open. When the time
setting in “A04” is passed, there will be alarm.
4) Defrost. The function is started with a pulse signal. (see also o37)
5) Main switch. Regulation is carried out when the input is short-circuited, and
regulation is stopped when the input is put in pos. OFF.
6) Night operation. When the input is short-circuited, there will be regulation for
night operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when input is closed.
8) Separate alarm function. Alarm will be given when the input is short-circuited.
9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and
9 the time delay is set in A27)
10) Case cleaning. The function is started with a pulse signal. See also description on
page 5.
11) Forced cooling(used for hot gas defrosting) when input is closed.
12) Night cover. Pulse signal activates night blind.
13) Not used.
14) Forced close when input is interrupted.
15) Appliance shutdown when input is closed.
16) Light. DO3 pulls when the input is closed.
17) Extra light. DO4 pulls when the input is closed.
18) Cancel defrost cycle. All defrost cycles are cancelled when the input is closed.
19) Override light (pulse signal)
t11-t16
L21DO1 Fuse
L31DO1 FuseSize
L62DO2 Low Load
o01DelayOfOutp.
o02DI 1 Cong.
Denition takes place with the numerical value shown to the left.
(0 = o)
u10 DI1 state
(Measurement)
The DI input’s present status is shown
here. ON or OFF.
If the controller is built into a network with data communication, it must have an
address, and the master gateway of the data communication must then know this
address.
The address is set between 0 and 240, depending on the system unit and the selected
data communication. If the system unit is gateway type AKA 245, the version must be
6.20 or higher.
The address is sent to the gateway when the menu is set in pos. ON
IMPORTANT: Before you set o04, you MUST set o61. Otherwise you will be
transmitting incorrect data.
(The function is not used when the data communication is MODBUS)
Access code 1 (Access to all settings)
If the settings in the controller are to be protected with an access code you can set a
numerical value between 0 and 100. If not, you can cancel the function with setting 0.
(99 will always give you access).
Sensor type for S3, S4, S5, S6, S3B, S5B, S6B
Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use
a sensor with another signal accuracy. That may either be a PTC sensor (1000 ohm
at 25°C)
All the mounted sensors S3-S6 must be of the same type.
Max. standby time after coordinated defrost
When a controller has completed a defrost it will wait for a signal which tells that the
refrigeration may be resumed. If this signal fails to appear for one reason or another,
the controller will itself start the refrigeration when this standby time has elapsed.
Select signal for the display S4%
Here you dene the signal to be shown by the display.
S3, S4, or a combination of the two.
With setting 0% only S3 is used. With 100% only S4.
Digital input signal - D2
The controller has a digital input 2 which can be used for one of the following
functions:
O: The input is not used.
1) Status display of a contact function
2) Door function. When the input is open it signals that the door is open. The refrigeration and the fans are stopped and light turn on. When the time setting in “A04”
has passed, an alarm will be issued. The cooling is restarted when the time in o89
has passed.
3) Door alarm. When the input is open it signals that the door is open. When the time
setting in “A04” is passed an alarm will be given.
4) Defrost. The function is started with a pulse signal. The controller will register when
the DI input is activated. The controller will then start a defrost cycle. If the signal is
to be received by several controllers (coordinated defrost) it is important that ALL
connections are mounted the same way (DI to DI and GND to GND).
5) Main switch. Regulation is carried out when the input is short-circuited, and
regulation is stopped when the input is put in pos. OFF.
6) Night operation. When the input is short-circuited, there will be regulation for
night operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input is
closed.
8) Separate alarm function. Alarm will be given when the input is short-circuited.
9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and
9 delay time is set in A28)
10) Case cleaning. The function is started with a pulse signal. See also description on
page 5.
11) Forced refrigeration at hotgas defrost when the input is short-circuited.
12) Night blinds. Pulse signal activates night blind.
13) The input is used for coordinated defrost in conjunction with other controllers
of the same type.
14) Forced close when input is interrupted.
15) Appliance shutdown when input is closed.
16) Light. DO3 pulls when the input is closed.
17) Extra light. DO4 pulls when the input is closed.
18) Cancel defrost cycle. All defrost cycles are cancelled when the input is closed.
(If night blind selected, it will be synchronised with the light function)
1) Light is controlled via day/night status
2) Light is controlled via data communication and "Light remote o39"
3) Light is controlled by door contact, as dened via a DI input where the setting is
selected as either 2 or 3. When the door is opened the relay will cut in. When the
door is closed again there will be a time delay of two minutes before the light is
switched o.
4) As "2" but if there are any 15-minute network errors, the light will switch on and
the night blind will open.
5) Light controlled with local DI switch and a central signal from either data communication or a 230 V signal on DI7. Both must be on before the light is turned on.
6) Like “5”, but manual control of the night blind will also activate the light, which
means the light will switch on when the night blind is up.
Activation of light relay
Here the relay can be activated, but only if a setting of 2, 5 or 6 has been dened in
o38.
Rail heat during day operation
The ON period is set as a percentage of the time
Rail heat during night operation
The ON period is set as a percentage of the time
Rail heat cycle
The period of time for the aggregate ON time + OFF time is set in minutes
Case cleaning
The status of the function can be followed here or the function can be started
manually.
0 = Normal operation (no cleaning)
1 = Cleaning with fans operating. All other outputs are O.
2 = Cleaning with stopped fans. All outputs are O.
If the function is controlled by a signal at a DI-input, the relevant status can be seen
here in the menu.
Selection of application
The controller can be dened in various ways. Here you set which of the
8 applications is required. On page 13 to 16 you can see a survey of applications.
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
Access code 2 (Access to adjustments)
There is access to adjustments of values, but not to conguration settings. If the
settings in the controller are to be protected with an access code you can set a
numerical value between 0 and 100. If not, you can cancel the function with setting 0.
If the function is used, access code 1 (o05) must also be used.
Save as factory setting
With this setting you save the controller’s actual settings as a new basic setting
(the earlier factory settings are overwritten).
Digital input signal - DI3 Switch signal
The controller has a digital input 3 which can be used for one of the following
functions:
O: The input is not used.
1) Status display of the switch function
2) Door function. When the input is open it signals that the door is open. The refrigeration and the fans are stopped and light turn on. When the time setting in “A04”
has passed, an alarm will be issued. The cooling is restarted when the time in o89
has passed.
3) Door alarm. When the input is open it signals that the door is open. When the time
setting in “A04” is passed an alarm will be given.
4) Defrost. The function is started with a pulse signal. (see also o37)
5) Main switch. Regulation is carried out when the input is closed, and regulation is
stopped when the input is open.
6) Night operation. When the input closed, there will be regulation for night
operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input
is closed.
8) Not used.
9) Not used.
10) Case cleaning. The function is started with a pulse signal. See also description
on page 5.
11) Forced refrigeration at hotgas defrost when the input is closed.
12) Night cover. Pulse signal activates night blind
13) Not used
14) Forced closing when input is interrupted.
15) Appliance shutdown when input is closed.
16) Light. DO3 pulls when the input is closed.
17) Extra light. DO4 pulls when the input is closed.
18) Cancel defrost cycle. All defrost cycles are cancelled when the input is closed.
The rail heat can be controlled in several ways:
0: The function is not used
1: Pulse control is used with a timer function following the day/night operation
(o41 and o42)
2: Pulse control is used with a dew point function. This function requires that a signal
is received about the dew point value. The value is measured by a system manager
and sent to the controller via the data communication.
Dew point value where the rail heat is minimum
This function is discussed earlier in the manual.
Dew point value where the rail heat is maximum
This function is discussed earlier in the manual.
Lowest permitted rail heat eect
Here the % part of the eect to be achieved when the dew point value is minimum.
o85Railh. mode
o86DewP Min lim
o87DewP Max lim
o88Rail Min ON%
Start of refrigeration when door is open
If the door has been left open, refrigeration must be started after a set time. That time
can be set here.
Fan operation for forced closing
If “forced closing” is activated, it will aect the operation of the fan and the defrosting.
Select the desired settings:
0: The fans will stop. Defrosting permitted.
1: The fans will run. Defrosting permitted.
(For 0 and 1: If the “forced closing” signal comes during a defrosting cycle,
or if a new defrosting cycle begins, the fans will follow the setting in d09.)
2: The fans will stop. Defrosting not permitted.
3: The fans will run. Defrosting not permitted.
(For 2 and 3: If the “forced closing” signal interrupts a defrosting cycle
but disappears again within 10 minutes, the defrosting cycle will resume.)
Alternative display
A reading can be displayed by pressing the lower button on the controller. This
reading is set from the factory so that the defrosting stop temperature is displayed.
A dierent setting will give the following reading:
1: (Defrost stop temperature = factory setting)
2: S6 temperature
Display of temperature during normal operation
1: Air temperature. Weighted S3 + S4
2: Product temperature S6
Light and night blinds denition
0: Light is switched o and night blinds are open when the main switch is o
1: Light and night blinds are independent of main switch.
Conguration of alarm relay
The alarm relay will be activated upon an alarm signal from the following groups:
0 - No relay function
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
128 - Disconnected fuse
The groups that are to activate the alarm relay must be set by using a numerical value
which is the sum of the groups that must be activated.
(E.g.: a value of 5 will activate all high temperature alarms and all sensor error.
Digital input signal - DI4. Switch signal. See DI3 aboveP55DI4 cong.
Digital input signal - DI5. Switch signal. See DI3 aboveP56DI5 cong.
Digital input signal - DI6. Switch signal. See DI3 aboveP57DI6 cong.
Digital input signal - DI7. High voltage signal. Functions the same as those
for DI3, but signal is 0 V/230 V. See also the summary on page 12.
Digital input signal - DI8. High voltage signal. See DI7 aboveP59DI8 cong.
Max. opening time for night blind after manual DI activation
The delay time before the night blind automatically goes down again after being
manually opened for product stocking.
Reset settings on ID module
Reset all settings so that the ID module can receive settings from another controller.
o89DoorInjStart
o90Fan forcedCl
o92Displ menu 2
o97Disp. Ctrl.
o98Light MS = O
P41Al.Rel.Conf.
P58DI7 cong.
P60BlindOpenTim
P61ResetID Mem.
Conguration of night blind function
On= night blind function used. O=night blind function not used.
Here you can set the fan pause time, so the night blind can roll down unhindered
to the correct position.
Max. on time for light after manual DI activation
Delay time before light goes o again after light has been turn on manual due to
product stocking.
ServiceService
Temperature measured with S5 sensoru09S5 temp.
Status on DI1 input. on/1=closedu10DI1 status
Read the duration of the ongoing defrost or the duration of the last completed
defrost.
Temperature measured with S3 sensoru12S3 air temp
Status at the day-/night operation (night operation: on/o)u13Night Cond.
Temperature measured with S4 sensoru16S4 air temp
Thermostat temperatureu17Ther. air
Read the ongoing cutin time for the thermostat or the duration of the last
completed cutin
Read the valve’s actual opening degreeu23Valve OD %
Read the temperature at the S6 sensoru36S6 temp
Status on DI2 input. on/1=closedu37DI2 status
Air temperature. Weighted S3 + S4u56Display air
Measured temperature for alarm thermostatu57Alarm air
* Status on relay for coolingu58Comp1/LLSV
Status on relay for fanu59Fan relay
* Status on relay for defrostu60Def. relay
Status on relay for railheatu61Railh. relay
* Status on relay for alarm
Status on relay for lightu63Light relay
* Status on relay for hot gas valveu64SuctionValve
* Status on relay for compressor 2u67Comp2 relay
* Temperature measured with S5B sensor
* Temperature measured with S3B sensor
* Temperature measured with S6B sensor
* Status on relay for hot gas
* Status on relay for heating element in drip tray
* Status on relay for night blinds
* Status on relay for defrost 2
* Readout of the actual rail heat eect in %
Readout of which thermostat used for regulation: 1= Thermostat 1,
2= Thermostat 2
Status on input DI3 (closed / open)
Readout of the actual cutin value for the thermostat
Readout of the actual cut out value for the thermostat
* Measured temperature for alarm thermostat for B section
* Air temperature. Weighted S3 + S4 temp. for B section
* Status of relay for light 2U36Extra light
* Status of relay for ECO fanU37Fan Eco
* Status of relay for defrost 3U38Def. relay 3
Status of DI4 input. On=closedU39DI4 status
Status of DI5 input. On=closedU40DI5 status
Status of DI6 input. On=closedU41DI6 status
Status of high-voltage input DI7, 230 V = 1 = closedU42DI7 status
Status of high voltage input DI8, 230 V = 1 = closedU43DI8 status
0-10 V output indicates EVR valve’s degree of openingU44AO1 voltage
Modbus communication status, 0% = none; 100% = everything okU45Comm. status
Read usage of DI2 signal: 0 = see status in u37; 1 = output for coordinated defrostU54DI2 In/Out
Status of relay for drain valve, 1 = onU55Drain valve
ON indicates controller error
Dewpoint value received from system unit
*) Not all will be displayed. Only the function belonging to the selection application is displayed.
The controller goes through some regulating situations where it is just waiting for
the next point of the regulation. To make these “why is nothing happening” situations
Ctrl. state:
(Shown in all menu displays)
visible, you can see an operating status on the display. Push briey (1s) the upper button. The individual status codes have the following meanings:
Waiting for end of the coordinated defrostS11
When the compressor is operating it must run for at least x minutes.S22
When the compressor is stopped, it must remain stopped for at least x minutes.S33
The evaporator drips o and waits for the time to run outS44
Refrigeration stopped by main switch. Either with r12 or a DI-inputS1010
Refrigeration stopped by thermostatS1111
Defrost sequence. Defrost in progressS1414
Defrost sequence. Fan delay — water attaches to the evaporatorS1515
Forced closing.
S1616
Refrigeration stopped due to stopped injection function
Door is open. DI input is openS1717
Melt function in progress. Refrigeration is interruptedS1818
Modulating thermostat controlS1919
Emergency cooling due to sensor errorS2020
Normal controlS2323
Manual control of outputsS2525
Case cleaningS2929
Forced coolingS3030
Delay on outputs during start-upS3232
Heat function is activeS3333
Appliance shutdownS4545
Other displays:
The defrost temperature cannot be displayed. There is stop based on timenon
Defrost in progress / First cooling after defrost when temperature is still over
-d-
the thermostat band.
Password required. Set password PS
Regulation is stopped via main switchOFF
*) Emergency cooling will take eect when there is lack of signal from a dened S3 or S4 sensor. The regulation will continue with a registered average
cutin frequency. There are two registered values – one for day operation and one for night operation.
In an error situation the LED’s on the display will ash and the alarm relay will be activated. If you push the top button in this situation you can see
the alarm report in the display.
There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
Code / Alarm text via data
communication
A1/--- High t.alarm
A2/--- Low t. alarm
A4/--- Door alarm
A5/--- Max hold time
A13/--- High temp S6
A14/--- Low temp S6
A15/--- DI1 alarmDI1 alarm8
A16/--- DI2 alarmDI2 alarm8
A45/--- Standby mode
A59/--- Case clean
A70/--- High temp S3B
A71/--- Low temp S3B
A72/--- High temp S6B
A73/--- Low temp S6B
E1/--- Ctrl. errorFaults in the controller32
E6/--- RTC errorCheck clock32
E25/--- S3 errorError on S3 sensor4
E26/--- S4 errorError on S4 sensor4
E27/--- S5 errorError on S5 sensor4
E28/--- S6 errorError on S6 sensor4
E34/--- S3 error BError on S3B sensor4
E37/--- S5 error B
E38/--- S6 error B
E40/--- ID ModuleErr
E41/--- DO1 Fuse err.
E42........E48 / DO2....DO8
E52/--- DO2 Low LoadLow power consumption on DO2. Check the load128
E55/--- DO5 Low LoadLow power consumption on DO5. Check the load128
E56/--- DO6 Low LoadLow power consumption on DO6. Check the load128
E58/--- DO8 Low LoadLow power consumption on DO8. Check the load128
---/--- Max Def.TimeDefrost stopped on time instead of temperature16
Data communication
The importance of individual alarms can be dened with a setting. The setting must be carried out in the group "AKM Alarm destinations"
Settings from
System manager
High1XXXX
Middle2XXX
Low3XXX
Log onlyX
Disabled
DescriptionAlarm relay groups
High temperature alarm
Low temperature alarm
Door alarm
The ”o16” function is activated during a coordinated defrost
Temperature alarm. High S6
Temperature alarm. Low S6
Standby position (stopped refrigeration via r12 or DI input)
Case cleaning. Signal from DI input
High temperature alarm, B section
Low temperature alarm, B-section
High temperature alarm, B section
Low temperature alarm, B-section
Error on S5B sensor
Error on S6B sensor
Incorrect communication with ID module
Excess current on DO1. Fuse has cut out
As above; fuse has cut out on the respective relay(s)
The values will be shown with three digits, and with a setting
you can determine whether the temperature is to be shown in
°C or in °F.
Light-emitting diodes (LED) on front panel
The three lower bottom LEDs will light up when the relevant relay
is activated.
º
º = Refrigeration
º = Defrost
º = Fan running
The light-emitting diodes will ash when there is an alarm.
In this situation you can download the error code to
the display and cancel/sign for the alarm by giving the top
button a brief push.
The buttons
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the
column with parameter codes. Find the parameter code you
want to change and push the middle buttons until value for
the parameter is shown. When you have changed the value,
save the new value by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until conguration access cFg is shown.
2. Push the upper or the lower button and nd that parameter you
want to change.
3. Push the middle button to enter the group.
4. Push the upper or the lower button and nd that parameter you
want to change.
5. Push the middle button until the parameter value is shown.
6. Push the upper or the lower button and select the new value
7. Push the middle button again to freeze the value.
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan
the rolling stack.
Set temperature
1. Push the middle button until the temperature value is shown.
2. Push the upper or the lower button and select the new value.
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor,
if selected in o92.)
• A short press of the lower button.
Manuel start or stop of a defrost
• Push the lower button for four seconds.
Return to previous menu
1. Press the top or bottom button until ESc is shown.
Displacement of time on cutin of defrost at start-upd05111111110 min.240 min.0
Drip o timed06111111110 min.60 min.0
Delay for fan start after defrostd07111111110 min.60 min.0
Fan start temperatured0811111111-50 °C0 °C-5
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4, 3=S5 og S5B) d1011111111030
Pump down delayd16111111110 min.60 min.0
Drain delay (used at hot gas defrost only)d1710 min.60 min.0
Max. aggregate refrigeration time between two defrostsd18111111110 hrs48 hrs0/OFF
Heat in drip tray. Time from defrosting stops to heating in the
drip tray is switched o
Number of permissible extended defrost cycles before an alarm
is issued
Rail heat during defrost cycle:
0=inactive, 1=continues as set, 2=100% on
FanF-
Fan stop temperature (S5)F0411111111-50°C50°C50
Pulse operation on fans: 0=No pulse operation, 1=At thermostat
cuts out only, 2= Only at thermostat cut outs during night
operation
Period time for fan pulsation (on-time + o-time)F06111111111 min.30 min.5
On-time in % of period timeF07111111110 %100 %100
Max. permissible S4 temperature during defrost cycle. If the value
is exceeded, the fans will stop. (Setting = 15 = no function)
Electricity monitoringL-
Current measured electricity through relay 1 (DO1)L1111111111Ampere
Same for relays 2 to 8L12-
Fuse status for relay 1/Forced control of relay 1./ ReconnectionL21111111110/o1/on1/on
Same for relays 2 to 8L22-
Electrical current value at which relay cuts out; 0 = not used
Recommended setting = measured consumption + 25%
Same for relays 2 to 8L32-
Current measured voltage in phase L1L5111111111V
Current measured voltage in phase L2L5211111111V
Current measured voltage in phase L3L5311111111V
Alarm limit for low consumption on DO2L621111111 0 A10 A1
Alarm limit for low consumption on DO5L6511110 A10 A1
Alarm limit for low consumption on DO6 L66111111110 A10 A0
Alarm limit for low consumption on DO8 L681 1110 A10 A1
Parameters for refrigeration function
Period time for the pulse width period (PWM)n631111111130 sec.900 sec.300
Max. opening degree at PWMn641111111110%100%100
Min. opening degree at PWMn65111111110%90%0
Expert setting. Windup at PWMn66111111110.21.01.0
Expert setting. Kp at PWMn67111111110.510.04.0
Expert setting. Tn at PWMn681111111160 sec1800 sec300
Miscellaneouso-
Delay of output signals after start-upo01111111110 sec600 sec5
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-signal).
5=ext.main switch. 6=night operation 7=thermostat band
changeover (activate r21). 8=alarm function when closed.
9=alarm function when open. 10=case cleaning (pulse signal).
11=forced cooling at hot gas defrost, 12=night cover. . 13=not
used. 14=forced close. 15=appliance shutdown. 16=light.
17=extra light. 18=cancel defrost. 19=override light.
Network addresso031111111102400
On/O switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at LON 485 only)
Access code 1 (all settings)o051111111101000
Used sensor type : 0=Pt1000, 1=Ptc1000, o06111111110/Pt1/Ptc0/Pt
Max hold time after coordinated defrosto16111111110 min.360 min.20
Select signal for display view. S4% (100%=S4, 0%=S3)o17111111110 %100 %100
Input signal on DI2. Function:
0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start
(pulse signal). 5=ext. main switch. 6=night operation
7=thermostat band changeover (activate r21). 8=alarm function
when closed. 9=alarm function when open. 10=case cleaning
(pulse signal). 11=forced cooling at hot gas defrost, 12=night
cover.13=coordinated defrost). 14=forced close. 15=appliance
shutdown. 16=light. 17=extra light. 18=cancel defrost.
19=override light.
Conguration of light function: 1=Light follows day/night operation, 2=Light control via data communication via ‘o39’, 3=Light
control with a DI-input, 4=As with “2”, but light switch on and
night cover will open if the network cuts out for more than
15 minutes. 5=Light goes on when a signal is received from both
DI and central signal (DI7 or data communication). 6=Like “5”,
but light also goes on for manual activation of night blind.
Activation of light relay (only if o38=2, 5 or 6)
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + O time)
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output O.
Select application. See overview page 13 to 16*o6111111111181
Access code 2 (partial access)***o641111111101000
Replace the controllers factory settings with the present settings
Input signal on DI3. Function:
(0=not used. 1=status on DI3. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse-signal).
5=ext. main switch 6=night operation, 7=thermostat band
changeover (activate r21). 8=Not used. 9=Not used. 10=case
cleaning (pulse signal). 11=forced cooling at hot gas defrost,
12=night cover. 13=Not used. 14=Refrigeration stopped (forced
closing). 15=appliance shutdown. 16=light. 17=extra light.
18=cancel defrost. 19=override light.
Rail heat control
0=not used, 1=pulse control with timer function (o41 and o42),
2=pulse control with dew point function
Dew point value where the rail heat is minimum
Dew point value where the rail heat is 100% on
Lowest permitted rail heat eect in %
Time delay from "open door” refrigeration is started
Fan operation on stopped refrigeration (forced closing):
0: The fans will be stopped and defrosting will be permitted.
1: The fans will run and defrosting will be permitted.
2: The fans will be stopped and defrosting will not be permitted.
3: The fans will run and defrosting will not be permitted.
Denition of readings on lower button:
1=defrost stop temperature, 2=S6 product temperature,
Display of temperature
1= u56 Air temperature
2= u36 product temperature
Light and night blinds dened
0: Light is switch o and night blind is open when the main
switch is o
1: Light and night blind is independent of main switch
Conguration of alarm relay
The alarm relay will be activated upon an alarm signal from
the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
128 - Fuse cut out
The groups that are to activate the alarm relay must be set by
using a numerical value which is the sum of the groups that
must be activated.
(E.g.: a value of 5 will activate all high temperature alarms and
all sensor error.
Input signal on DI4. Switch signal. See DI3 aboveP55
Status of high-voltage input DI7, 230 V = 1 = closedU4211111111
Status of high voltage input DI8, 230 V = 1 = closedU4311111111
0-10 V output indicates EVR valve’s degree of opening**U4411111111
Modbus communication status, 0% = none; 100% = everything
ok
Read usage of DI2 signal: 0 = see status in u37; 1 = output for
coordinated defrost
Status of relay to drain valve: 1 = drawn**U551
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
Factory setting
Follow these steps if you need to return to the factory-set values:
- Connect a display with control buttons to the controller
- Activate setting P61 to reset the ID module
- Disconnect the supply voltage to the controller
- Remove the ID module from the controller
- Hold in the top and bottom buttons on the display while reconnecting the supply voltage
Main switchAutomated fuse, 4 terminals, 16 A, SIL-approved
Sensor S2Not used
Sensor S3, S3B,
S4, S5, S5B, S6,
S6B
Accuracy
Display2 plugs for connecting external display
External display EKA 163B or 164B
Digital inputs
DI1, DI2, DI3,
DI4, DI5, DI6
Digital inputs
DI7, DI8
Electrical connection cable
Relays
Solid state
output
Analogue
voltage outlet
Environments
EnclosureIP 20
Weight3.8 kg
Data
communication
Power reserve
for the clock
Approvals
*) Gold plating ensures make function with small contact loads.
400 V 3N a.c. / 400 V 2N a.c. / 230 V N a.c.
+10/-15%, 30 VA, 50 Hz
Pt 1000 or
PTC 1000 ohm / 25°C
(All must be of the same type)
Measuring range -60 to +120°C
±1 K below -35°C
Controller
± 0,5 K between -35 to +25°C;
±1 K above +25°C
Pt 1000 sensor
I-reading
L11 - L18
±0,3 K at 0°C
±0,005 K per degree
0-10 A: +/- 15%
min. +/- 1A
Signal from contact functions
Requirements to contacts: None
Cable length must be max. 15 m
Use auxiliary relays when the cable is longer
230 V a.c.
On: DI > 80 V a.c.
O: DI < 24 V a.c.
Max. 2.5 mm2
Max. 16 A (12) A
DO1-DO8
I max: (adjustable 4-16 A)
I max. = 0 = cut out cancelled
Alarm relay4 (3) A. Min. 100 mA*
Max. 240 V half wave rectied
Max. 0.5 A
DOA (for coil)
Leakage < 1 mA
Max. 1 coil
Electronic coil controller EEC may
not be used
AO1
0-10 V
R
Load
> 1 kΩ
0 to +55°C, During operations
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock inuence / vibrations
Fixed MODBUS
Extension optionsLON RS485
24 hours
EU Low Voltage Directive and EMC demands re
CE-marking complied with
LVD-tested acc. EN 60730-1, EN 60730-2-1 and
EN 60730-2-9
EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.