Danfoss ADAP-KOOL Installation guide

Design guide
Data communication
between ADAP-KOOL® Refrigeration Controls
ADAP-KOOL® Refrigeration control systems
Introduction
Within this guide descriptions and specifications will be shown that supports the data communication interface with Danfoss refrigeration controls systems.
Data communication
System unit
System operation
The guide describes:
- The various forms of communication
- Cable to be used
- Length of cable
- Termination of cable
- When to install a repeater and
- How do the individual controllers become visible on the network
- What happens if a controller has to be replaced
- What happens if the gateway has to be replaced
The recommendations mentioned in this document are intended as instructions for the market’s refrigeration engineers and electricians who install Danfoss refrigeration controls.
Controllers
Repeater
ADAP-KOOL® only
The above communication systems are used for internal communi­cation between ADAP-KOOL® refrigeration control systems. The devices are not designed to communicate with equipment manufactured by other manufacturers.
IP network
In the case of controllers and system units that can be connected to an IP network, installation should be carried out on the basis of the requirements that apply to an IP network, i.e. cables must be at least category 5.
Contents
Introduction .................................................................................2
A little about controllers and system units ...............................3
Communication survey ............................................................................... 3
System units .................................................................................................... 4
Addressing of controllers in the network ............................................. 6
Replacement of controllers in the network ......................................... 6
Replacement of system units in the network ..................................... 6
Requirements to installation ......................................................7
Important ......................................................................................................... 7
Lon RS 485 - bus ............................................................................................. 8
MOD - bus ...................................................................................................... 10
Lon TP 78 - bus .............................................................................................12
DANBUSS ........................................................................................................14
Combinations of net ..................................................................16
Bridge .............................................................................................................. 16
Repeater .........................................................................................................17
2 Design guide RC8AC902 © Danfoss 2017-06 Data communication
A little about controllers and system units
Communication survey
The table below shows which controllers can communicate with which system units and with what form of data communication. The summary is valid as of ultimo 2015, but the ADAP-KOOL® Refrigeration Control System is continually being extended.
System operation
AK-ST 500
AK-EM 100
AK-EM 800
1)
AKM
System unit Controller serie / type Lon
3)
AK-SM 800
2)
series
AK - controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH
EKC 3xx x
EKC 202, AK-CC 210 x x
EKC 302, AK-CC 250, 350, AK-PC, AK-CT x
AK-CC 450, 550 (x) x (x)
AK-PI 200 x x
AK-CM (communication module) + AK-XM x x
DGS, SLV, Wattnote, Power meter, light control (3. party) x
RS485
Mod-
bus
Lon
TP 78
DAN­BUSS
x x x
x
IP
AK-SM 350 AK-SM 720
AK - controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH
x x x
x
EKC 3xx x
EKC 202, AK-CC 210 x x
EKC 302, AK-CC 250, 350, AK-PC, AK-CT x
AK-CC 450, 550 (x) x (x)
AK-PI 200 x x
DGS, SLV x
AK-SC 255, 355 x
2)
x x
2)
AK-CM (communication module) + AK-XM x x
AK - controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH
x
AK-CC 750 (TP 78 version) x
EKC 302, AK-CC 250, 350, 450, 550, AK-CT x
EKC 202, 4xx, 5xx, AK-CC, AK-PC x
AKM
EM 100 AKA 245 x x
AKA, AKC, AKL x
AK - controllers with extension modules AK-CC, AK-PC, AK-LM, AK-CH
x
EKC 202, 302, 3xx, 4xx, 5xx, AK-CC 210 x
AK-CC 450, 550 x x
1) AKM can receive alarms and logs from an AK-SM 720 and AK-SM 350. The connec­tion is made via an analogue modem, a GPS modem or an IP network.
2) Can be delivered in two versions:
- Standard Lon-RS485
- Retro-fit Lon TP 78.
3) Together with AK-SM 350 and AK-SM 720 only.
x
Data communication Design guide RC8AC902 © Danfoss 2017-06 3
System units
A brief summary is presented here of the communication options for the various system devices:
AK-SM 820
Up to 32 controllers can be connected, which can communicate on:
- Lon
- Modbus
- External I/O modules via AK-CM 101C
- Ethernet communication for other AK-SM or AK-SC devices
- AK-PI 200 protocol interface with DANBUSS communication
AK-SM 850, AK-SM 880
Up to 120 controllers can be connected, which can communicate on:
- Lon
- Modbus
- External I/O modules via AK-CM 101C
- Ethernet communication for other AK-SM or AK-SC devices
- AK-PI 200 protocol interface with DANBUSS communication
AK-SM 880 it can be delivered in a version, which can communi­cate in 4 x TP 78 or AK-CM 101A.
AK-SM 720
There are three forms of data communication:
- A Lon RS485 bus, to which up to 199 devices can be connected.
- A Modbus, to which up to 120 devices can be connected.
- Ethernet communication for other AK-SM devices, to which up to 199 addresses can be connected.
The system device can communicate with:
- AK-CC, AK-PC controllers
- EKC with either Lon RS485 or Modbus communication
- AK-PI 200 protocol interface with DANBUSS communication
- AK-PI 300 protocol interface for Daikin devices
- Other AK-SM 720 devices
- AKM and AK-EM 800 via agent.
Lon RS485
Modbus
IP network
Lon RS485
Modbus
IP network
Lon RS485 (max. 199 devices)
Modbus (max. 120 devices)
Total on bus: Lon RS 485 + Modbus: max. 199 devices
IP network (max. 199 addresses) Total AK-SM 720 + AK-PI 200 + IP + bus: max. 200 devices.
A repeater must be added if there are more than 120 devices on the Lon RS485 communication.
Total up to 32 devices
Total up to 120 devices
AK-SM 350
This device can record up to 65 (99) readings. A reading could for example be a directly mounted temperature sensor or an external device with a temperature sensor, where the readings is loaded via data communication. There are four forms of data communication:
- A Lon RS485
- A Modbus
- RS485 TP (Third Party) To which gas detectors, type GD, can be
Lon RS485
Modbus
RS 485 TP
Total up to 65 (99) devices
connected
- Ethernet communication for other AK-SM 720 or AK-SC devices.
AK-SM 350 can communicate with:
IP network
- EKC with either Lon RS485 or Modbus communication
- AK-CC, AK-PC controllers
- Gas detectors type GD
- AK-PI 200 protocol interface with DANBUSS communication
- Ethernet communication for other AK-SM or AK-SC devices.
4 Design guide RC8AC902 © Danfoss 2017-06 Data communication
AK-SC 255 / AK-SC 355
AK-SC 255 and 355 are available in 2 versions:
- Modbus + Lon TP 78 communication
- Modbus + Lon RS485 communication
- Ethernet communication for other AK-SC or AK-SM devices.
The system device can communicate with:
- External I/O modules via AK-CM 101C or 101A (depending on model)
- All controllers where the communication is supported by:
Modbus, Lon, TP78).
Gateway type AKA 245
This system device is equipped with DANBUSS data communi­cation and Lon RS485 data communication. It can control the communication of up to 120 controllers. The controllers can be distributed between Lon and DANBUSS by setting a continuous Lon address range of up to 119 addresses. The system device can create communication for type AKM sys­tem software. The system device can communicate with:
- AKC controllers
- EKC controllers with a Lon RS 485 communication
- AK-CC, AK-PC controllers
- AK-EM 800 via Agent
Modbus Lon RS485 / TP 78
IP network
DANBUSS
Lon RS485
Total up to 120 devices
Data communication Design guide RC8AC902 © Danfoss 2017-06 5
Addressing of controllers in the network
1. Connect voltage
2. Set the address in the respective controllers If you should inadvertently give two or more controllers the same address, only the first controller will be visible from the system device.
3. The system device must know the controllers. The following will occur depending on the communication type:
Lon RS485
Or better: The system device can scan the network and find all connected controllers. This scan function must be started manu­ally in the system device.
Modbus, TP78
Replacement of controllers in the network
Settings
The system operation includes functions to copy a controller’s settings. This function can be used where a controller is to be replaced with the same software version. After swapping, the set­tings are copied back onto the controller.
Address
Remember to reset the address of the controller with the same address and get the controller to notify the system device again. (You should also do this yourself if you are retaining the existing LON module). Here, the controller can send a service PIN to the system device.
Here, the system device must scan the network. The service PIN function on each controller cannot send the ad­dress to the system device.
DANBUSS
On DANBUSS, the addresses must be set before the power is switched on. The system device will find the controllers on the network itself.
Modbus, TP78
The system device will scan the network and find the controllers that have been replaced. This scan function must be started manu­ally in the system device.
Lon RS485
• AK-SC 255, 355, SM 850
The system device will scan the network and find the control­lers that have been replaced. This scan function must be started manually in the system device.
• AK-SM 350, 720, AKA 245
Here, the controller will send a service PIN to the system device.
Replacement of system units in the network
If you replace the system device, all settings and data can be retrieved and reloaded with a backup function. See user Guide for the respective system device, so you can see how the setup and the collected data is retained.
• Terminate data communication inputs as previously
• Set the system device address
• Load the controller addresses up to the system device.
AK-SM 820, 850, 880
Set the address to the same value as on the previous system device. Then start the Rescan function.
AK-SM 350
No address needs to be set on AK-SM 350. Start the scan function to find all connected controllers.
DANBUSS
On DANBUSS the system device will find the controllers on the network itself.
AK-SM 720
Set the address to the same value as on the previous system device. The scan function can then be started to find all connected controllers.
AK-SC 255, 355
Set the address to the same value as on the previous system de­vice. Then start the Rescan function.
Gateway type AKA 245
Set the system address using the AKA 21 operating device. On the DANBUSS communication, the Gateway will find the con­trollers itself. On Lon RS485 the scan function can be activated from the AKA 21 operating module. This function is called “Press Enter to scan LON bus”. NB! When the scan function is used, all alarm priorities in all connected EKC controllers will be deleted and returned to their factory settings.
6 Design guide RC8AC902 © Danfoss 2017-06 Data communication
Loading...
+ 12 hidden pages